Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-06-05 Cont ID  
Sent By amorse Date 2007-06-05 Time 16:08 Rev Time 0.00
Received By amorse Date 2007-06-05 Time 16:08 Sent To PC
Notes
2007-06-05 16:09:37 
  
 PASSED
  
 *******NOTE**********
  
 TO EXPEDITE PLAN REVIEW ALL INFO AND PROCEDURES PER
 CITY OF WEST PALM MEMO MUST BE MET. 2 COPIES OF
 SCHEDULE COMPLETED AS REQUIRED, PRODUCT APPROVALS SHALL
 ONLY CIRCLE THE APPROPRIATE METHODS THAT WILL BE USED
 AND THE CORRECT TOP AND BOTTOM CONNECTION TYPES. IF
 THESE DO NOT MATCH REVIEW TAKES MUCH LONGER AS WE TRY
 TO ESTABLISH WHAT YOU ARE USING AND END UP FAILING THE
 REVIEW DUE TO CONFLICTING INFORMATION. PLEASE NOTE THAT
 USING THE WORST CASE DESIGN PRESSURES ESPECIALLY ON THE
 LARGER OPENINGS INSTEAD OF THE CORRECT PRESSURE COULD
 LEAD TO THE SHUTTER NOT BEING DESIGNED FOR USE
 REQUIRED. (SEE PAGE 7 OF 13, WIND DESIGN PSF OF - 65
 ALLOWS ONLY 11'-9" SHUTTER SPAN

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-05-12 Cont ID  
Sent By amorse Date 2007-05-12 Time 17:07 Rev Time 0.00
Received By amorse Date 2007-05-12 Time 17:07 Sent To PC
Notes
2007-05-12 17:12:18 
  
 DENIED
  
 1)DESIGN PRESSURE IN THE 2004 FBC HAVE BEEN UPDATED
 WITH THE 2006 AMENDMENTS, ANY BUILDING IN A NORMALLY
 EXPOSURE BCATEGORY THAT HAS OPEN TERRAIN (INCLUDES
 BODIES OF WATER, GOLF COURSES, ETC) IN ANY QUADRANT FOR
 A DISTANCE OF 600 FT WILL BE CONSIDERED EXPOSURE C.
  
 2)SHUTTER PERMIT APPLICATIONS REQUIRE A KEY PLAN,
 SHUTTER SCHEDULE CLEARLY MARKED WITH THE INFORMATION
 SPECIFIC TO THE SITE (TYPE OF CONSTRUCTION, MOUNTING
 CONNECTION TYPE, ANCHOR TYPE, ETC.) PLEASE SEE THE
 ATTACHED UPDATED SCHEDULE AND THE DRAWINGS THAT ARE
 PART OF THE PRODUCT APPROVALS TO CORRESPOND WITH THE
 SCHEDULE. ****** PLEASE SEE THAT THE DRAWINGS HAVE MANY
 ITEMS NOT ON SCHEDULE CIRCLED, INCREASES FOR EXPOSURE C
 WILL NOT REACH SPANS REQUIRED, CONNECTION TYPES CHOSEN
 DO NOT MATCH ANCHOR SPACING AND TAPCONS, EDGE DISTANCE
 CIRCLED DO NOT MATCH SCHEDULE. *******
  
 3)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-05-22 Cont ID  
Sent By adarroug Date 2007-05-22 Time 15:56 Rev Time 0.00
Received By adarroug Date 2007-05-22 Time 15:56 Sent To B
Notes
2007-05-22 15:56:35TO "AMORSE" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2007-05-12 Time   Rev Time 0.00
Received By adarroug Date 2007-04-25 Time 09:21 Sent To  
Notes
2007-04-25 09:21:36TO "MISC" BOX#1


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved