2007-05-02 13:19:15 | DENIED |
| REFERENCE: |
| ** FBC-2004 FUEL GAS. |
| ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION |
| REQUIREMENTS. |
| ** FBC-2004 CHAPTER 1, THE CITY OF |
| WEST PALM BEACH AMENDMENTS. |
| ** FLORIDA ADMINISTRATIVE CODE. |
| ** FLORIDA STATUTES. |
| |
| THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| GAS PLAN REVIEW TO MEET CODE COMPLIANCE: |
| |
| 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2004 |
| FUEL GAS CODE. |
| NOTE: THE SUBMITTED ISOMETRIC DOES NOT INDICATE THE |
| CORRESPONDING LENGTHS OF THE CUT SECTIONS OF PIPE OF |
| THE PROPOSED GENERATOR GAS PIPING. PLEASE DO THIS ON |
| THE RESUBMITTAL TO VERIFY THE INDICATED TOTAL DEVELOPED |
| LENGTH OF THIRTY SIX FEET (36'). IS THE TOTAL DEVELOPED |
| LENGTH OF THIRTY SIX FEET (36') FOR THE PROPOSED |
| GENERATOR OR FOR THE EXISTING SYSTEM. PLEASE CLARIFY ON |
| THE RESUBMITTAL. |
| |
| 2. SHOW TYPE OF PIPING MATERIAL BEING |
| INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| NUMBER OF CORRUGATED STAINLESS STEEL |
| TUBING FOR EACH PIPE SIZE BEING USED. |
| NOTE: NOT ALL PIPE SIZES ARE INDICATED ON THE |
| ISOMETRIC. THE PIPING OUT OF THE METER SHOULD BE SIZED |
| 1-1/4".PLEASE DO THIS ON THE RESUBMITTAL. |
| |
| 3. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| OF CAPACITY TABLES A.3.1(4). |
| NOTE: PLEASE CLEARLY INDICATE THE LONGEST LENGTH OF THE |
| EXISTING SYSTEM AND THE PROPOSED SYSTEM TO VERIFY HOW |
| SYSTEM IS TO BE SIZED. |
| |
| 4. PER FBC-2004 FUEL GAS, SECTION 404.13.3AN |
| INSULATED COPPER TRACER WIRE SHALL BE INSTALLED |
| ADJACENT TO UNDERGROUND NONMETALLIC GAS PIPING. THE |
| TRACER WIRE SIZE SHALL NOT BE LESS THAN 18 AWG AND THE |
| INSULATION TYPE SHALL BE SUITABLE FOR DIRECT BURIAL. |
| NOTE: PLEASE INDICATE THIS ON THE RESUBMITTAL FOR THE |
| UNDERGROUND PE. |
| |
| 5. PER FBC-2004 FUEL GAS SECTION 409.5 EQUIPMENT |
| SHUTOFF VALVE: EACH APPLIANCE SHALL BE PROVIDED WITH A |
| SHUTOFF VALVE SEPERATE FROM THE APPLIANCE. THE SHUTOFF |
| VALVE SHALL BE LOCATED IN THE SAME ROOM AS THE |
| APPLIANCE, NOT FURTHER THAN 6 FEET FROM THE APPLIANCE, |
| AND SHALL BE INSTALLED UPSTREAM FROM THE UNION, |
| CONNECTOR OR QUICK DISCONNECT DEVICE IT SERVES. SUCH |
| SHUTOFF VALVES SHALL BE PROVIDED WITH ACCESS. NOTE: |
| PLEASE INDICATE A SHUTOFF VALVE FOR THE PROPOSED |
| GENERATOR ON THE RESUBMITTAL. |
| |
| 6. A GAS PERMIT CAN NOT BE ISSUED UNTIL |
| A GEN/RES PERMIT APPLICATION HAS BEEN |
| APPLIED FOR AND APPROVED BY ZONING FOR |
| THE GENERATOR LOCATION. |
| |
| END OF COMMENTS: |
| |