Plan Review Details - Permit 07040808
Plan Review Stops For Permit 07040808
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2007-06-13 Cont ID  
Sent By shill Date 2007-06-13 Time 15:24 Rev Time 0.00
Received By shill Date 2007-06-13 Time 15:24 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-07-05 Cont ID  
Sent By btrobaug Date 2007-07-05 Time 16:21 Rev Time 0.00
Received By btrobaug Date 2007-07-05 Time 16:05 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-04-27 Cont ID  
Sent By btrobaug Date 2007-04-27 Time 14:23 Rev Time 0.50
Received By btrobaug Date 2007-04-27 Time 13:54 Sent To M
Notes
2007-04-27 14:23:05 
 DENIED/INCOMPLETE INFORMATION
  
 1} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN,
 METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT
 COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE REVIEWED.
 DO THIS ON A SITE PLAN, NOT ON THE SURVEY, 106.1.3FBC.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2007-07-13 Cont ID  
Sent By mperson Date 2007-07-13 Time 09:03 Rev Time 0.45
Received By mperson Date 2007-07-13 Time 09:03 Sent To PC
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-05-02 Cont ID  
Sent By mperson Date 2007-05-02 Time 10:22 Rev Time 0.45
Received By mperson Date 2007-05-02 Time 10:22 Sent To B
Notes
2007-05-02 13:19:15DENIED
 REFERENCE:
 ** FBC-2004 FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 NOTE: THE SUBMITTED ISOMETRIC DOES NOT INDICATE THE
 CORRESPONDING LENGTHS OF THE CUT SECTIONS OF PIPE OF
 THE PROPOSED GENERATOR GAS PIPING. PLEASE DO THIS ON
 THE RESUBMITTAL TO VERIFY THE INDICATED TOTAL DEVELOPED
 LENGTH OF THIRTY SIX FEET (36'). IS THE TOTAL DEVELOPED
 LENGTH OF THIRTY SIX FEET (36') FOR THE PROPOSED
 GENERATOR OR FOR THE EXISTING SYSTEM. PLEASE CLARIFY ON
 THE RESUBMITTAL.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 NOTE: NOT ALL PIPE SIZES ARE INDICATED ON THE
 ISOMETRIC. THE PIPING OUT OF THE METER SHOULD BE SIZED
 1-1/4".PLEASE DO THIS ON THE RESUBMITTAL.
  
 3. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 NOTE: PLEASE CLEARLY INDICATE THE LONGEST LENGTH OF THE
 EXISTING SYSTEM AND THE PROPOSED SYSTEM TO VERIFY HOW
 SYSTEM IS TO BE SIZED.
  
 4. PER FBC-2004 FUEL GAS, SECTION 404.13.3AN
 INSULATED COPPER TRACER WIRE SHALL BE INSTALLED
 ADJACENT TO UNDERGROUND NONMETALLIC GAS PIPING. THE
 TRACER WIRE SIZE SHALL NOT BE LESS THAN 18 AWG AND THE
 INSULATION TYPE SHALL BE SUITABLE FOR DIRECT BURIAL.
 NOTE: PLEASE INDICATE THIS ON THE RESUBMITTAL FOR THE
 UNDERGROUND PE.
  
 5. PER FBC-2004 FUEL GAS SECTION 409.5 EQUIPMENT
 SHUTOFF VALVE: EACH APPLIANCE SHALL BE PROVIDED WITH A
 SHUTOFF VALVE SEPERATE FROM THE APPLIANCE. THE SHUTOFF
 VALVE SHALL BE LOCATED IN THE SAME ROOM AS THE
 APPLIANCE, NOT FURTHER THAN 6 FEET FROM THE APPLIANCE,
 AND SHALL BE INSTALLED UPSTREAM FROM THE UNION,
 CONNECTOR OR QUICK DISCONNECT DEVICE IT SERVES. SUCH
 SHUTOFF VALVES SHALL BE PROVIDED WITH ACCESS. NOTE:
 PLEASE INDICATE A SHUTOFF VALVE FOR THE PROPOSED
 GENERATOR ON THE RESUBMITTAL.
  
 6. A GAS PERMIT CAN NOT BE ISSUED UNTIL
 A GEN/RES PERMIT APPLICATION HAS BEEN
 APPLIED FOR AND APPROVED BY ZONING FOR
 THE GENERATOR LOCATION.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-06-27 Cont ID  
Sent By adarroug Date 2007-06-27 Time 11:00 Rev Time 0.00
Received By adarroug Date 2007-06-27 Time 11:00 Sent To Z
Notes
2007-06-27 11:01:10TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-04-27 Cont ID  
Sent By adarroug Date 2007-04-27 Time 10:11 Rev Time 0.00
Received By adarroug Date 2007-04-27 Time 10:10 Sent To E
Notes
2007-04-27 10:11:21TO "GEN-RES" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-06-13 Cont ID  
Sent By shill Date 2007-06-13 Time 15:24 Rev Time 0.00
Received By shill Date 2007-04-24 Time 11:29 Sent To  
Notes
2007-04-24 11:29:37TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-07-06 Cont ID  
Sent By tgordon Date 2007-07-06 Time 08:10 Rev Time 0.20
Received By tgordon Date 2007-07-06 Time 08:10 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-04-27 Cont ID  
Sent By tgordon Date 2007-04-27 Time 15:53 Rev Time 0.15
Received By tgordon Date 2007-04-27 Time 15:53 Sent To G
Notes
2007-04-27 15:55:15*** DENIED ***
 1) SEE ZONING REVIEW NOTES, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  

Review Stop Z ZONING
Rev No 2 Status P Date 2007-06-28 Cont ID  
Sent By choops Date 2007-06-28 Time 14:26 Rev Time 0.00
Received By choops Date 2007-06-28 Time 14:26 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2007-04-26 Cont ID  
Sent By jroach Date 2007-04-26 Time 14:48 Rev Time 0.00
Received By jroach Date 2007-04-26 Time 14:48 Sent To I
Notes
2007-04-26 14:50:56***FAILED***
  
  
 1) PLEASE PROVIDE DISTANCE FROM FRONT PROPERTY LINE TO
 EDGE OF GENERATOR.
  
 2)PLEASE PROVIDE DISTANCE FROM SIDE PROPERTY LINE TO
 EDGE OF GENERATOR
  
  
 CHRIS HOOPS
 ZONING TECHNICIAN
 805-6720