Plan Review Details - Permit 07040753
Plan Review Stops For Permit 07040753
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-08-01 Cont ID  
Sent By mjacobs Date 2007-08-01 Time 17:50 Rev Time 0.00
Received By mjacobs Date 2007-08-01 Time 17:24 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-06-21 Cont ID  
Sent By mjacobs Date 2007-06-21 Time 08:52 Rev Time 0.00
Received By mjacobs Date 2007-06-21 Time 07:27 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-05-08 Cont ID  
Sent By mjacobs Date 2007-05-08 Time 08:16 Rev Time 0.00
Received By mjacobs Date 2007-05-07 Time 14:21 Sent To  
Notes
2007-05-07 15:57:50BUILDING PLAN REVIEW
 PERMIT: 07040753
 ADD: 1720 CENTREPARK DR. E
 CONT: THE WEITZ CO, LLC.
 TEL: (561)686-5511
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 2)110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PROJECT WAS DESIGNED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 ) NUMBER OF FLOORS
 ) NUMBER OF ROOMS
 ) SQ. FT. FOOTPRINT
 ) SQ. FT. UNDER ROOF (TOTAL)
 ) OCCUPANT LOAD
  
 3)FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE
 RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE:
 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT
 THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 4)THE DOOR ELEVATION ON SHEET A2.01 SHOWS A 3' X 7'
 DOOR, HOWEVER THE FLOOR PLAN SHOWS 3' X 8' DOORS.
 CLARIFY.
  
 5)WHERE IS THE FOURTH 8'-8" PARTITION WALL LOCATED?
 THERE ARE THREE SECTIONS SHOWN ON THE PLANS, INDICATE
 WHERE THE OTHER WALL IS.
  
 6)THE TITLE BLOCK IS MISSING THE PRINTED NAME AND
 LICENSE NUMBER OF THE ARCHITECT OF RECORD. THE DATE ON
 THE SEAL IS NOT LEGIBLE. SEE F.A.C.61G1-16.004.
  
 7)IF THERE IS A SOFFIT AT THE PERIMETER OF THE
 ACOUSTICAL TILE CEILING IN THE OPEN WORKSTATION AREA,
 PROVIDE THE WALL DETAIL FOR THAT SOFFIT. ALSO PROVIDE
 SOME ELEVATION DETAILS OF THE PROJECT. CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE
 THE LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED.
 FBC. 106.1.1.(SEE ALSO SEC. 106.3.5).
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2007-08-24 Cont ID  
Sent By dpalmer Date 2007-08-24 Time 07:40 Rev Time 0.00
Received By dpalmer Date 2007-08-24 Time 07:26 Sent To PC
Notes
2007-08-24 07:40:56STAMPED PLANS.

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2007-08-22 Cont ID  
Sent By dpalmer Date 2007-08-22 Time 17:29 Rev Time 0.00
Received By dpalmer Date 2007-08-22 Time 17:25 Sent To PC
Notes
2007-08-22 17:29:34*** DENIED 4TH REVIEW ***
  
  
 1) NOTE: PLEASE SEE THE TWO SETS NEED TO BE COMPLETE
 WITH ORIGINAL SIGNED, DATED AND SEALED PLANS.
 PLEASE SEE SHEET E1.02 IN ONE SET IS MISSING THE RAISED
 SEAL.
 PLEASE SEE SHEET E1.04 ON THE 2ND SET IS A PHOTO-COPY
 OF SIGNED AND SEALED PLANS.
 ** ALL MUST BE ORIGINAL, RAISED SEAL AND DATED PER FS
 481.221.
  
 ** CALLED MR. RICHARD WATSON OF THE WEITZ COMPANY TO
 HAVE NEW SHEETS BROUGHT IN FOR STAMPING.
  
 2) NOTE: PLEASE KNOW AS OF THIS REVIEW THE FEE ASSESSED
 PER THE FS 553.80(2)(B) STILL REMAINS AND IS A BALANCE
 OF $1800.00
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-07-27 Cont ID  
Sent By dpalmer Date 2007-07-27 Time 13:10 Rev Time 0.00
Received By dpalmer Date 2007-07-27 Time 12:37 Sent To  
Notes
2007-07-27 13:11:00*** UNSAT3RD REVIEW ***
  
 ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW STILL
 REMAIN.
  
 1) NOTE: PLEASE SEE AS REQUESTED ON THE PREVIOUS
 REVIEW, PLEASE COMPLY WITH FBC CHAPTER 13 FOR LIGHTING
 CONTROLS.ALL NEW BEING INSTALLED NEEDS TO COMPLY.
 THIS TENANT SPACE IS NOT DEFINED AS A BUILDING AND THIS
 SPACE IS LOCATED IN A BUILDING GREATER THAN 5K SQ FT.
 THE RESPONSE MENTIONS THIS IS 2400 + SQ FT AND DOES NOT
 NEED LIGHTING CONTROLS. THIS IS NOT THE CASE.PLEASE
 SEE THE DEFINITIONS OF A BUILDING IN BOTH CHAPTER 13
 AND FBC DEFINITIONS. TENANT OCCUPANCIES LOCATED IN A
 BUILDING OVER 5K SQ FT EVEN IF 200 SQ FT FOR EXAMPLE
 FOR THE INDIVIDUAL TENANT SPACE STILL REQUIRES LIGHTING
 CONTROLS FOR AUTOMATED SHUTTING OFF/TURNING OFF OF
 LIGHTS.
 THIS HAS BEEN CONFIRMED WITH THE STATE ON MANY
 OCCASIONS AND THE STATE TAC COMMITTEE WHEN THE CODE
 CHANGE WAS MADE ALMOST TWO EARS AGO.
 PLEASE SEE THE ENERGY CALCULATIONS CAN NOT BE CONFIRMED
 AND DO NOT CORRELATE FOR LIGHTING CONTROLS AND PLANS.
 13-415.1.ABC.1.1, .1.2, 13-415.1.A, 13-415.2
 13-101.
  
 2) NOTE: PLEASE SEE THE PREVIOUS REVIEW REQUESTED THE
 ADDRESS OF THE UNIT OR SUITE NUMBER TO BE ADDED TO THE
 PLANS, HOWEVER THE RESPONSE MENTIONS THIS ENTIRE
 BUILDING IS ONE TENANT.
 PLEASE SEE THE ENERGY CALCULATIONS WHICH WERE SUBMITTED
 BY THE ARCHITECT STATES A UNIT/SUITE OF #118?
 PLEASE CLARIFY HOW THIS IS POSSIBLE.
  
 3) NOTE: PLEASE SEE THE PREVIOUS REVIEW NOTES GAVE
 NOTICE TO FS 553.80(2)(B) WITH RESPECT TO REPEAT
 COMMENTS FOR CODE COMPLIANCE.
 PLEASE SEE A FEE HAS NOW BEEN ASSESSED TO THE DESIGN
 PROFESSIONAL AS REQUIRED PER THE ABOVE FLORIDA STATUTE.
 THIS FEE OF $1800.00 IS DUE BEFORE PLANS CAN BE
 RESUBMITTED.
 ONE COPY OF ELECTRICAL PLANS ALONG WITH ONE COPY OF
 ENERGY CALCULATIONS ARE BEING RETAINED BY THIS OFFICE.
 TO DATE NO ONE HAS CONTACTED THIS REVIEWER TO GO OVER
 ANY OF THE COMMENTS.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-06-18 Cont ID  
Sent By dpalmer Date 2007-06-18 Time 11:15 Rev Time 0.00
Received By dpalmer Date 2007-06-18 Time 09:05 Sent To  
Notes
2007-06-18 11:16:08 
  
 *** UNSAT 2ND REVIEW ***
  
 ** PLEASE SEE SOME COMMENTS FROM THE PREVIOUS ARE STILL
 IN NEED OF ADDRESSING.
 ** PLEASE KNOW AS NOT ALL INFORMATION NEEDED WAS
 SUBMITTED FOR A CODE COMPLIANT REVIEW THERE MAY BE NEW
 COMMENTS ON RE-SUBMITTAL OF PLANS.
  
 1) NOTE: PLEASE SEE COMPLIANCE WITH CHAPTER 13 OF THE
 FBC HAS NOT BEEN ADDRESSED. THE REQUIRED LIGHTING
 CONTROLS AS PREVIOUSLY NOTED HAVE NOT BEEN PLACED ON
 PLANS. PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED ARE
 NOT CORRECT. THE FIXTURES DO NOT CORRELATE, THE TYPES,
 THE CONTROLS ETC.
 PLEASE SEE ALL OF CHAPTER AND THE SECTIONS AS
 PREVIOUSLY GIVEN.
 13-415.1.ABC.1.1, .1.2, .1.3, 13-415.1.AB.1.1,
 13-415.2, 13-415.2.ABC.1.2
  
 2) NOTE: PLEASE SEE NOTE #3 FROM PREVIOUS REVIEW WHICH
 STATED THE MISSING REQUIRED INFORMATION ON TITLE BLOCKS
 PER 61G1-16.004. (STILL MISSING THE PRINTED LICENSE
 NUMBER OF THE ARCHITECT).
  
 3) NOTE: PLEASE SEE THE CIRCUITING MAY NOT ONLY USE
 LIGHTING, RECEPTACLES ETC. THESE NEED TO BE SPECIFIC TO
 ROOMS, AREAS, OR OTHER TYPE OF DESIGNATION. MAY USE A
 NUMERICAL DESIGNATION TO OFFICES OR OTHER LOCATIONS.
 PLEASE SEE 408.4
  
 4) NOTE: PLEASE SEE ADDRESS ONLY INDICATES THE
 LOCATION. THIS BUILDING CONTAINS MORE THAN ONE
 SUITE/UNIT NUMBER? IF SO PLEASE SEE THE PERMIT
 APPLICATION NEEDS TO STATE THE SUITE/UNIT ALONG WITH
 THE PLANS.
  
 5) NOTE: PLEASE SEE MISPRINT FOR NEW PANEL L1C, WHICH
 IS SHOWN AS LC1 ON PANEL AND L1C ON RISER.
 FBC 106.1.2
  
 6) NOTE: PLEASE SEE FS 553.802B WITH RESPECT TO REPEAT
 COMMENTS FOR CODE COMPLIANCE. THIS IS ONLY A NOTICE
 GIVEN AT THIS TIME.
  
 ** PLEASE SEE POSSIBLE COMMENTS FROM OTHER TRADES WHICH
 MAY AFFECT THE ELECTRICAL PLANS OR DESIGN OF PROJECT.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-04-30 Cont ID  
Sent By dpalmer Date 2007-04-30 Time 15:21 Rev Time 0.00
Received By dpalmer Date 2007-04-30 Time 13:18 Sent To  
Notes
2007-04-30 15:21:42** UNSAT **
  
 ** PLEASE SEE THAT ANY REFERENCES TO THE FBC CHAPTER 1
 ARE FROM THE ADMINISTRATIVE CODE ADOPTED BY THE CITY OF
 WEST PALM BEACH.
  
  
 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS
 WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES
 PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
  
 2) NOTE: PLEASE SEE 2004 FBC CHAPTER 13 W/ 2006
 REVISIONS.
 PLEASE SEE MISSING LIGHTING CONTROLS PER
 13-415.1.ABC.1.1, .1.2. A LIGHTING CONTACTOR IS
 INDICATED, HOWEVER NO TIMES SCHEDULING, NO TIME OVER
 RIDES, ETC ARE SHOWN.
 PLEASE SEE THE WRONG EDITION OF THE FLORIDA ENERGY CODE
 IS SHOWN AND CALCULATED.
 PLEASE CORRELATE THE LIGHTING AS SHOWN ON PLANS WITH
 THAT OF THE FIXTURES, WATTAGES ETC AS SHOWN ON
 CALCULATIONS.
 PLEASE SEE THE CONTROL FOR LIGHTING NEEDS TO COORDINATE
 WITH THE METHOD ON PLANS.
 PLEASE SEE 13-415.ABC.1.2
 PLEASE BE SURE THAT ANY OVER RIDE DEVICES ARE SHOWN ON
 PLANS AND SYMBOL LEGEND.
 PLEASE BE SURE THE ENERGY CALCULATIONS ARE SIGNED AND
 SEALED. THEY ARE ONLY SIGNED AS SUBMITTED.
 13-103.1.1.1
  
 3) NOTE: PLEASE SEE MISSING INFORMATION ON TITLE BLOCKS
 AS REQUIRED PER FAC 61G1-16.004.
 PLEASE SEE THE MISSING PRINTED NAME AND PRINTED LICENSE
 NUMBER FOR THE ARCHITECT OF RECORD.
  
 4) NOTE: PLEASE SEE 408.4 WHICH REQUIRE THE CIRCUITING
 TO BE SPECIFIC TO THE ROOMS AND AREAS IN WHICH THEY
 FEED.
 PLEASE KNOW THESE CAN BE DONE BY THE ROOM NAME OR
 NUMERICAL DESIGNATION.
 PLEASE SEE THE FOLLOWING TEXT WHICH IS TAKEN FROM THE
 CODE.
  
 *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE
 THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A
 PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE
 THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED.
 CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED
 AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE
 BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN,
 DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE
 CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT
 ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS
 ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR
 RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT
 OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE
 ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT
 PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS
 SECTION.*
 408.4, 310.16, 240.4 ETC
 FBC 106.3.5.4
  
 5) NOTE: PLEASE INCLUDE THE ADDRESS OF THE PROJECT ON
 TITLE BLOCKS.
 PLEASE SEE AS APPLIED IS 1720 E CENTREPARK DR.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-08-07 Cont ID  
Sent By mawillia Date 2007-08-07 Time 11:53 Rev Time 0.00
Received By mawillia Date 2007-08-07 Time 11:04 Sent To  
Notes
2007-08-07 11:53:07*****APPROVED W/REMINDER*****
  
  
 ALL COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE
 BEEN ADDRESSED;PLAN SHEETS A2.01, E1.01, AND FP 1.01
 WERE STAMPED, INITIALED, AND DATED.SINCE1 OF THE 2
 SUBMITTED PLAN SHEETSE1.02, E 1.03, AND E1.03 WERE
 RETAINED BY THE ELECTRICAL PLAN REVIEWER, FIRE STAMPING
 WILL BE REQUIRED FOR SHEET E1.02 AND E1.04.
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-06-20 Cont ID  
Sent By mawillia Date 2007-06-20 Time 11:58 Rev Time 0.00
Received By mawillia Date 2007-06-20 Time 11:45 Sent To  
Notes
2007-06-20 11:57:49*****UNSAT*****
  
 THE FOLLOWING COMMENTS FROM THE PREVIOUS FIRE PLAN
 REVIEW STILL NEED TO BE ADDRESSED:
  
  
 3.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.ADD
 TO THE APPROPIATE PLAN SHEET
  
 4.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE DAILY OR MORE FREQUENTLY AS
 NECESSARY FOR SAFE OPERATION.ADD TO THE APPROPIATE
 PLAN SHEET
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-05-14 Cont ID  
Sent By mawillia Date 2007-05-14 Time 11:19 Rev Time 0.00
Received By mawillia Date 2007-05-14 Time 10:47 Sent To  
Notes
2007-05-14 11:19:13*****DENIED*****
  
  
 1.THE COMPLETE ADDRESS OF WHERE THE SCOPE OF WORK IS
 TO BE CONDUCTED SHALL BE IN THE TITLE BLOCK OF EACH
 SUBMITTED PLAN SHEET.
  
 2.THE 2003 EDITION OF NFPA 101 - LIFE SAFETY CODE -
 SHALL BE REFERENCED.
  
 3.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 4.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE DAILY OR MORE FREQUENTLY AS
 NECESSARY FOR SAFE OPERATION.
  
 5.SPECIFY THE INTERIOR FINISH MATERIALS FOR WALLS AND
 CEILINGS AS CLASS A, CLASS B, OR CLASS C.
  
 6.ON DRAWING E1.04,AMEND FIRE ALARM SYSTEM NOTE #17
 TO INDICATE THAT DUCT SMOKE DETECTORS SHALL INITIATE A
 GENERAL FIRE ALARM.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-11-29 Cont ID  
Sent By adarroug Date 2007-11-29 Time 16:44 Rev Time 0.00
Received By adarroug Date 2007-11-29 Time 16:44 Sent To M
Notes
2007-11-29 16:44:44TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-10-17 Cont ID  
Sent By adarroug Date 2007-10-17 Time 11:50 Rev Time 0.00
Received By adarroug Date 2007-10-17 Time 11:50 Sent To M
Notes
2007-10-17 11:51:05TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-08-16 Cont ID  
Sent By adarroug Date 2007-08-16 Time 16:05 Rev Time 0.00
Received By adarroug Date 2007-08-16 Time 16:05 Sent To E
Notes
2007-08-16 16:05:21TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-07-18 Cont ID  
Sent By adarroug Date 2007-07-18 Time 10:17 Rev Time 0.00
Received By adarroug Date 2007-07-18 Time 10:17 Sent To  
Notes
2007-07-26 14:29:03TO "BOB"#10
2007-07-18 10:18:02WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-06-13 Cont ID  
Sent By adarroug Date 2007-06-13 Time 09:42 Rev Time 0.00
Received By adarroug Date 2007-06-13 Time 09:42 Sent To  
Notes
2007-06-14 14:27:15TO "BOB"#5
2007-06-13 09:42:47WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-05-14 Cont ID  
Sent By mawillia Date 2007-05-14 Time 10:47 Rev Time 0.00
Received By mawillia Date 2007-04-23 Time 15:09 Sent To  
Notes
2007-04-23 15:10:59TO "BOB"#16

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2007-12-04 Cont ID  
Sent By tgordon Date 2007-12-04 Time 11:57 Rev Time 0.25
Received By tgordon Date 2007-12-04 Time 11:56 Sent To  
Notes
2007-12-04 11:57:43REVISION TO MECH. PLAN PAGE M1.01.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-10-22 Cont ID  
Sent By tgordon Date 2007-10-22 Time 10:18 Rev Time 0.25
Received By tgordon Date 2007-10-22 Time 10:18 Sent To  
Notes
2007-10-22 10:19:38REVISION TO MECH. PLANS PAGE M1.01.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-06-15 Cont ID  
Sent By tgordon Date 2007-06-15 Time 11:14 Rev Time 0.45
Received By tgordon Date 2007-06-15 Time 11:14 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-04-25 Cont ID  
Sent By tgordon Date 2007-04-25 Time 14:03 Rev Time 0.45
Received By tgordon Date 2007-04-25 Time 14:03 Sent To  
Notes
2007-04-25 14:34:18*** DENIED ***
 1) ENERGY CALCULATIONS ARE CALLING FOR A 92,000 BTU A/C
 SYSTEM, MECHANICAL PLANS ARE CALLING FOR A 30,000 BTU
 A/C SYSTEM, THE TWO MUST COINCIDE, PLEASE CORRECT.
  
 2) COOLING LOAD CALCULATIONS ARE CALLING FOR 76,810
 TOTAL BTU'S, MECHANICAL PLANS ARE CALLING FOR 30,000
 TOTAL BTU'S. SEE 2004 FBC 13--407.1.ABC.1.1, PLEASE
 CORRECT.
  
 3) PLEASE SHOW OUTDOOR AIR CALCULATIONS ON MECHANICAL
 PLANS, SEE 2004 FBC/M 403.3.
  
 4) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-400.3.ABC.2.
  
 5) COULD NOT FIND THE A/C SYSTEM IN THE EQUIPMENT SPEC.
 LISTED ON THE ARI DIRECTORY WEB SITE. PLEASE SUBMIT
 DETAILED MANUFACTURER'S SPECIFICATION'S AND
 INSTALLATION INSTRUCTIONS FOR A/C SYSTEM BEING
 INSTALLED..
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop Z ZONING
Rev No 1 Status N Date 2007-07-30 Cont ID  
Sent By choops Date 2007-07-30 Time 17:33 Rev Time 0.00
Received By choops Date 2007-07-30 Time 17:33 Sent To PC
Notes
2007-07-30 17:34:24*VALUE OF PROPOSED WORK DOES NOT EXCEED 50% OF THE
 IMPROVEMENT VALUE.