Plan Review Details - Permit 07040733
Plan Review Stops For Permit 07040733
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-11-08 Cont ID  
Sent By jjohnsto Date 2007-11-08 Time 17:25 Rev Time 0.00
Received By jjohnsto Date 2007-11-08 Time 17:24 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-09-18 Cont ID  
Sent By jwitmer Date 2007-09-18 Time 08:13 Rev Time 1.55
Received By jwitmer Date 2007-09-18 Time 08:13 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-06-14 Cont ID  
Sent By jwitmer Date 2007-06-14 Time 17:07 Rev Time 1.33
Received By jwitmer Date 2007-06-14 Time 17:00 Sent To FIRE
Notes
2007-06-14 17:30:40BUILDING PLAN REVIEW
 PERMIT: 07040733
 ADD: 7750 OKEECHOBEE BLVD SUITE# 3
 CONT: ATLANTIDA CONSTRUCTION
 TEL: (561)313-2706
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE
 FILED WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF
 THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE
 RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE:
 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT
 THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) PLANS SUBMITTED AFTER DEC. 8,2006 SHALL BE DESIGNED
 TO THE 2006 FLORIDA BUILDING CODE- BUILDING AND THE
 2006 FLORIDA EXISTING BUILDING CODE . ALSO INDICATE TO
 WHAT LEVEL OF ALTERATION WORK WILL BE COMPLETED UNDER
 THIS PERMIT?
  
 4) IS THIS TENANT SPACE A CHANGE OF OCCUPANCY? IF SO
 PLANS WILL NEED TO BE REVIEWED BY PALM BEACH COUNTY
 IMPACT FEES OFFICE.BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH
 COUNTY. THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED
 BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED
 TO THE PERMIT APPLICATION. PLEASE CALL (561)233-5025
 FOR MORE INFORMATION.
  
 5) PLEASE REVIEW THE REFLECTED CEILING PLAN AND THE
 FLOOR PLAN THE DOOR LAYOUT CHANGESFOR THE DOORS
 LEADING TO THE RESTROOMS. THE SECOND ISSUE IS THE
 CORRECTION OF THE TWO DOORS LEADING TO THE RESTROOM .
 11-4.1.6(2) DUTY TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL TO ALTERED AREAS SHALL BE DEEMED
 DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE
 COST EXCEEDS 20 % OF THE COST OF THE ALTERATION TO THE
 PRIMARY FUNCTION AREA.
 (A)(I) AN ACCESSIBLE ENTRANCE
 (II) AN ACCESSIBLE ROUTE
 (III) AT LEAST ONE ACCESSIBLE REST-
 ROOM FOR EACH SEX OR A SINGLE
 UNISEX RESTROOM
 (IIII) ACCESSIBLE TELEPHONE
 (IV) ELEMENTS SUCH AS PARKING, STOR-
 AGE OR ALARMS.
 11-4.13.7 TWO DOORS IN SERIES.
 THE MINIMUM SPACE BETWEEN TWO HINGED OR PIVOTED DOORS
 IN SERIES SHALL BE 48 INCHES (1219 MM) PLUS THE WIDTH
 OF ANY DOOR SWINGING INTO THE SPACE. DOORS IN SERIES
 SHALL SWING EITHER IN THE SAME DIRECTION OR AWAY FROM
 THE SPACE BETWEEN THE DOORS [SEE FIGURE 26 (A)]. SEE
 ATTACHMENT.
  
 6) INDICATE COMPLIANCE WITH:11-4.32.1 MINIMUM NUMBER.
 FIXED OR BUILT-IN SEATING OR TABLES REQUIRED TO BE
 ACCESSIBLE BY SECTION 11-4.1 SHALL COMPLY WITH SECTION
 11-4.32 . 11-4.32.2 SEATING.
 IF SEATING SPACES FOR PEOPLE IN WHEELCHAIRS ARE
 PROVIDED AT FIXED TABLES OR COUNTERS, CLEAR FLOOR SPACE
 COMPLYING WITH SECTION 11-4.2.4 SHALL BE PROVIDED. SUCH
 CLEAR FLOOR SPACE SHALL NOT OVERLAP KNEE SPACE BY MORE
 THAN 19 INCHES (485 MM) (SEE FIGURE 45 ).
 ALL FIXED SEATING IN PUBLIC FOOD SERVICE
 ESTABLISHMENTS, IN ESTABLISHMENTS LICENSED UNDER THE
 BEVERAGE LAW FOR CONSUMPTION ON THE PREMISES, AND IN
 ALL OTHER FACILITIES GOVERNED BY REFERENCE SECTION
 11-4.1 SHALL BE DESIGNED AND CONSTRUCTED IN ACCORDANCE
 WITH THE FOLLOWING REQUIREMENTS:
 (1)ALL AISLES ADJACENT TO FIXED SEATING SHALL
 PROVIDE CLEAR FLOOR SPACE FOR WHEELCHAIRS.
 (2)WHERE THERE ARE OPEN POSITIONS ALONG BOTH SIDES
 OF SUCH AISLES, THE AISLES SHALL BE NOT LESS THAN 52
 INCHES (1321 MM) WIDE. 11-4.32.3 KNEE CLEARANCES.
 IF SEATING FOR PEOPLE IN WHEELCHAIRS IS PROVIDED AT
 TABLES OR COUNTERS, KNEE SPACES AT LEAST 27 INCHES (685
 MM) HIGH, 30 INCHES (760 MM) WIDE, AND 19 INCHES (485
 MM) DEEP SHALL BE PROVIDED (SEE FIGURE 45 ). 11-4.32.4
 HEIGHT OF TABLES OR COUNTERS. THE TOPS OF ACCESSIBLE
 TABLES AND COUNTERS SHALL BE FROM 28 INCHES TO 34
 INCHES (710 MM TO 865 MM) ABOVE THE FINISH FLOOR OR
 GROUND.
  
 7)INDICATE COMPLIANCE WITH: 11-5.1 GENERAL.
 EXCEPT AS SPECIFIED OR MODIFIED IN THIS SECTION,
 RESTAURANTS AND CAFETERIAS SHALL COMPLY WITH THE
 REQUIREMENTS OF SECTION 11-4.1 TO SECTION 11-4.35 .
 WHERE FIXED TABLES (OR DINING COUNTERS WHERE FOOD IS
 CONSUMED BUT THERE IS NO SERVICE) ARE PROVIDED, AT
 LEAST 5 PERCENT, BUT NOT LESS THAN ONE, OF THE FIXED
 TABLES (OR A PORTION OF THE DINING COUNTER) SHALL BE
 ACCESSIBLE AND SHALL COMPLY WITH SECTION 11-4.32 AS
 REQUIRED IN SECTION 11-4.1.3 (18). IN ESTABLISHMENTS
 WHERE SEPARATE AREAS ARE DESIGNATED FOR SMOKING AND
 NONSMOKING PATRONS, THE REQUIRED NUMBER OF ACCESSIBLE
 FIXED TABLES (OR COUNTERS) SHALL BE PROPORTIONALLY
 DISTRIBUTED BETWEEN THE SMOKING AND NONSMOKING AREAS.
 IN NEW CONSTRUCTION, AND WHERE PRACTICABLE IN
 ALTERATIONS, ACCESSIBLE FIXED TABLES (OR COUNTERS)
 SHALL BE DISTRIBUTED THROUGHOUT THE SPACE OR FACILITY.
  
  
 8)INDICATE COMPLIANCE WITH: 11-5.2 COUNTERS AND BARS.
  
 WHERE FOOD OR DRINK IS SERVED AT COUNTERS EXCEEDING 34
 INCHES (865 MM) IN HEIGHT FOR CONSUMPTION BY CUSTOMERS
 SEATED ON STOOLS OR STANDING AT THE COUNTER, A PORTION
 OF THE MAIN COUNTER WHICH IS 60 INCHES (1525 MM) IN
 LENGTH MINIMUM SHALL BE PROVIDED IN COMPLIANCE WITH
 SECTION 11-4.32 OR SERVICE SHALL BE AVAILABLE AT
 ACCESSIBLE TABLES WITHIN THE SAME AREA.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-11-05 Cont ID  
Sent By dpalmer Date 2007-11-05 Time 16:01 Rev Time 0.00
Received By dpalmer Date 2007-11-05 Time 16:01 Sent To  
Notes
2007-11-05 16:03:17NEW E-1, OK,STAMPED.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-09-05 Cont ID  
Sent By dpalmer Date 2007-09-05 Time 19:12 Rev Time 0.00
Received By dpalmer Date 2007-09-05 Time 18:36 Sent To  
Notes
2007-09-05 19:13:08** DENIED 2ND REVIEW **
  
  
 ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW ARE
 STILL IN NEED OF ADDRESSING.
  
 1) NOTE: PLEASE SEE THE VALUE FOR COMPLETE SCOPE OF
 WORK SHALL INCLUDE ALL LABOR, ALL MATERIALS, ALL
 PERMANENTLY INSTALLED EQUIPMENT, ARCHITECTURAL AND
 DESIGN FEES ETC.
 PLEASE SEE THE ELECTRICAL SCOPE OF WORK AS ORIGINALLY
 SHOWN HAS SUBSTANTIALLY INCREASED ALONE.
 PLEASE MAKE ADJUSTMENTS OR A VALUE WILL BE APPLIED
 USING GUIDES ADOPTED UNDER THE FBC AND ADOPTED
 REFERENCE BOOKS.
  
 2) NOTE: PLEASE SEE THE NEW ENERGY CALCULATIONS
 SUBMITTED ARE NOT COMPLETE. PLEASE SEE THE LIGHTING
 DENSITIES ARE SHOWN BLANK.
 PLEASE SEE THE SIGNATURE NOT THE TYPED NAME OF PERSON
 PREPARING DOCUMENT IS REQUIRED. 13-103.1.1.1
 PLEASE SEE THE ENGINEER OF RECORD AS LISTED IS NOT
 SIGN, DATED AND SEALED. FBC 13-103.1.1.1, FAC
 61G15-23.002, FS 471.025
 PLEASE SEE THE OWNER AGENT IS BLANK.
 FBC 13-415.1.C
  
 ** ELECTRICAL PLANS ARE IN GOOD SHAPE AS THE ENGINEER
 DID A GOOD JOB ADDRESSING THE ELECTRICAL COMMENTS. WELL
 DONE.
  
 ** PLEASE ADDRESS COMMENTS #1 AND #2. THE ELECTRICAL
 SHEETS WILL BE STAMPED AT THIS TIME.
  
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-04-27 Cont ID  
Sent By dpalmer Date 2007-04-27 Time 16:35 Rev Time 0.00
Received By dpalmer Date 2007-04-27 Time 15:28 Sent To  
Notes
2007-04-27 16:35:49** UNSAT **
  
 ** PLEASE SEE THAT ANY REFERENCES TO THE FBC CHAPTER 1
 ARE FROM THE ADMINISTRATIVE CODE ADOPTED BY THE CITY OF
 WEST PALM BEACH.
  
  
 1) NOTE:PLEASE SEE THE VALUE FOR SCOPE OF WORK SHALL
 INCLUDE ALL LABOR, EQUIPMENT AND MATERIALS EVEN IF ANY
 OF THESE ARE OWNER SUPPLIED.
 PLEASE SEE THE VALUE IS LOW AT THIS TIME AND WILL NEED
 TO BE ADJUSTED.
 PLEASE THAT A VALUE MAY BE ASSESSED BY USING GUIDES AS
 ADOPTED BY THE FBC. 108.3
  
 2) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH
 ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS
 UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 ** PLEASE SEE THE INCORRECT NEC IS NOTED.
  
 3) NOTE: PLEASE PROVIDE MORE DETAIL FOR LIGHTING
 CONTROLS BEING INSTALLED. PLEASE PROVIDE DETAIL ON
 OCCUPANCY DEVICE AND PLEASE SEE SOME AREAS LIKE THE
 KITCHEN IN WHICH THE SINGLE WALL WHICH AT LOCATION
 SHOWN MAY NOT PROVIDE THE NEEDED COVERAGE.
 PLEASE DETAIL THE CONNECTION IN BAR AREA AND ALL OTHER
 AREAS.
 PLEASE SEE THE EXISTING BATH ROOMS WILL REQUIRE
 DEVICES.
 PLEASE SEE NOT ALL AREAS INDICATE LIGHTING POWER
 DENSITIES.
 PLEASE SUBMIT ENERGY CALCULATIONS SHOWING COMPLIANCE.
 PLEASE BE SURE THE FIXTURE LEGEND IS COMPLETED WITH ALL
 FIXTURE TYPES, WATTAGES ETC. (THESE MAY BE REVISED AT A
 LATER DATE IF CHANGED).
 PLEASE SEE 13-415.1.ABC.1.1, .1.2, .1.3,
 13-415.1.AB.1.1, 13-415.2 ETC.
  
 4) NOTE: PLEASE INDICATE ALL RECEPTACLES SERVING
 KITCHEN AREAS AS GFI. MOST ARE DONE AND ONLY ONE IS
 MISSING IN THIS DESIGNATED AREA.
 PLEASE ALSO SEE ONLY MISPRINT FOR THE CODE SECTION AS
 NOTED IN GENERAL ELECTRICAL NOTES.
 PLEASE SEE 210.8B3.
  
 5) NOTE: PLEASE SEE ELECTRICAL SHEETS IN TWO OF THE
 SETS ARE INSERTED UPSIDE DOWN, BACKWARDS AND THERE ARE
 MORE SHEETS THAN SHOULD BE IN SETS.
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND INSERT NEW
 SHEETS INTO COMPLETE SETS FOR REVIEW AND STAMPING.
 PLEASE BE SURE TO CHECK THE SHEETS.
 PLEASE ONLY SUBMIT ONE COPY OF THE OLD/VOIDED REMOVED
 SHEETS.
 ** PLEASE BE CAREFUL NOT TO DISCARD ANY SHEETS STAMP BY
 THE DIVISION OF HOTELS ETC).
  
 6) NOTE: PLEASE INDICATE IF THE PANELS CONTAIN
 FEED-THRU LUGS OR IS THERE OVER CURRENT PROTECTION FROM
 ONE TO THE OTHER?
 FBC 106.1.2
  
 7) NOTE: PLEASE SEE THE LOADS AS SHOWN ON PANEL *A* IS
 LOWER THAN THE LOAD ON LOAD CALCULATIONS.THIS IS NOT
 POSSIBLE WHEN PANEL USUALLY SHOW THE CONNECTED LOAD OR
 THE SAME DE-RATED LOAD AS FIGURED IN THE LOAD
 CALCULATIONS.
 PLEASE COORDINATE THESE.
 FBC 106.1.2
 NEC 220
  
 8) NOTE: PLEASE SEE 422.13 AS THIS WAS REVISED IN THE
 2005 CODE TO REQUIRE ALL ELECTRIC WATER HEATER LOADS TO
 BE SHOWN AND DONE AT 125%.
  
 9) NOTE: PLEASE INDICATE THE EXISTING LIGHTING FIXTURES
 IN THE BATHROOMS.
  
 10) NOTE: PLEASE SEE THE TITLE COVER SHEET INDICATES
 PLANS SUBMITTED BY MARTEK, YET NO MECHANICAL PLANS WERE
 SUBMITTED FOR REVIEW? PLEASE VERIFY.
  
  
 IF THERE ARE ANY QUESTIONS, PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE OR REVIEWER.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-11-12 Cont ID  
Sent By mawillia Date 2007-11-12 Time 15:11 Rev Time 0.00
Received By mawillia Date 2007-11-12 Time 14:58 Sent To  
Notes
2007-11-12 15:09:51*****APPROVED*****
  
 PLAN SHEETSA-1 AND E-1 WERE STAMPED, INITIALED, AND
 DATED.
  
  
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-09-24 Cont ID  
Sent By mawillia Date 2007-09-24 Time 14:31 Rev Time 0.00
Received By mawillia Date 2007-09-24 Time 14:07 Sent To  
Notes
2007-09-24 14:26:06*****UNSAT*****
  
 ALL OF THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW
 HAVE BEEN ADDRESSED EXCEPT FOR THE FOLLOWING:
  
 8.SPECIFY THE INTERIOR FINISH MATERIAL FOR WALLS AND
 CEILINGS IN THE EXITS, EXIT AISLE CORRIDORS AND OTHER
 SPACES. SPECIFY IN TERMS OF CLASS "A", CLASS "B", OR
 CLASS "C"
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE (ON THE PLANS) EACH ITEM WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-06-25 Cont ID  
Sent By mawillia Date 2007-06-25 Time 16:16 Rev Time 0.00
Received By mawillia Date 2007-06-21 Time 13:02 Sent To  
Notes
2007-06-25 15:48:06*****DENIED*****
  
  
 1.ON THE COVER SHEET, REFERENCE THE 2003 EDITION OF
 NFPA 101.
  
 2.PLEASE INDICATE IF THIS IS A CHANGE OF OCCUPANCY.
  
 3.INDICATE IF THE BUILDING/TENANT SPACE IS FIRE
 SPRINKLERED AND/OR HAS A FIRE ALARM.IF THE SCOPE OF
 WORK HAS CAUSE FOR ANY OF THESE SYSTEMS TO BE
 REMODELED, SEPARATE PLANS AND PERMIT WILL BE REQUIRED.
  
 4.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 5.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR
 MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 6.THE REMOVAL AND/OR THE STOCKING OF BUILDING
 MATERIALS & SUPPLIES SHALL NOT INTERFERE OR HINDER
 EMERGENCY RESPONSE ACCESS TO THE PROPERTY OR VICINITY
 THEREOF (INCLUDING STREETS,ROADS, FIRE LANES).
  
 7.PROVIDE A T LEAST ONE 2A:10BC RATED FIRE
 EXTINGUISHER IN THE NON COOKING AREA.
  
 8.SPECIFY THE INTERIOR FINISH MATERIAL FOR WALLS AND
 CEILINGS IN THE EXITS, EXIT AISLE CORRIDORS AND OTHER
 SPACES.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE (ON THE PLANS) EACH ITEM WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
2007-06-25 15:15:30*****

Review Stop G GAS REVIEW
Rev No 3 Status N Date 2007-11-30 Cont ID  
Sent By mperson Date 2007-11-30 Time 11:22 Rev Time 0.00
Received By mperson Date 2007-11-30 Time 11:22 Sent To PC
Notes
2007-11-30 11:24:13NOTE: FLORIDA PUBLIC UTILITIES CO. HAS A SEPERATE GAS
 PERMIT FOR THE GAS SYSTEM, PERMIT #07080547.

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2007-09-21 Cont ID  
Sent By kstevens Date 2007-09-21 Time 10:21 Rev Time 0.00
Received By kstevens Date 2007-09-21 Time 10:21 Sent To  
Notes
2007-09-21 10:23:27DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 ****FROM PREVIOUS REVIEW:
  
 1. SHT A-2 KITCHEN EQUIPMENT INDICATES GAS APPLIANCES.
 A SEPARATE GAS PERMIT IS REQUIRED. PLEASE PROVIDE THE
 FOLLOWING INFORMATION FOR THE GAS PERMIT:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 C. TYPE OF GAS, (LP OR NATURAL).
  
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 F. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 H. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 I. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 J. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
  
 ****NO RESPONSE, GAS COMMENTS NOT ADDRESSED.
 INFORMATION NOW SHOWN ON SHEET E-1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-06-29 Cont ID  
Sent By kstevens Date 2007-06-06 Time 14:25 Rev Time 0.00
Received By kstevens Date 2007-06-06 Time 14:24 Sent To  
Notes
2007-06-29 14:26:58DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 1. SHT A-2 KITCHEN EQUIPMENT INDICATES GAS APPLIANCES.
 A SEPARATE GAS PERMIT IS REQUIRED. PLEASE PROVIDE THE
 FOLLOWING INFORMATION FOR THE GAS PERMIT:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 C. TYPE OF GAS, (LP OR NATURAL).
  
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 F. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 H. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 I. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 J. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-12-04 Cont ID  
Sent By adarroug Date 2007-12-04 Time 16:01 Rev Time 0.00
Received By adarroug Date 2007-12-04 Time 16:01 Sent To P
Notes
2007-12-04 16:01:47TO "P" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-12-04 Cont ID  
Sent By adarroug Date 2007-12-04 Time 15:50 Rev Time 0.00
Received By adarroug Date 2007-12-04 Time 15:50 Sent To P
Notes
2007-12-04 15:50:42TO "P" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-10-19 Cont ID  
Sent By adarroug Date 2007-10-19 Time 12:00 Rev Time 0.00
Received By adarroug Date 2007-10-19 Time 12:00 Sent To  
Notes
2007-11-05 11:35:49TO "COMM" BD#28
2007-10-19 12:01:13WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-08-08 Cont ID  
Sent By dpalmer Date 2007-08-08 Time 18:31 Rev Time 0.00
Received By dpalmer Date 2007-08-08 Time 18:31 Sent To  
Notes
2007-09-05 10:28:16TO "COMM" BD#11
2007-08-08 18:31:32WAITING FOR COMM BOARD.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-06-25 Cont ID  
Sent By mawillia Date 2007-06-21 Time 13:02 Rev Time 0.00
Received By mawillia Date 2007-04-23 Time 14:26 Sent To  
Notes
2007-04-23 14:26:32WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-11-06 Cont ID  
Sent By tgordon Date 2007-11-06 Time 08:48 Rev Time 0.25
Received By tgordon Date 2007-11-06 Time 08:48 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-09-07 Cont ID  
Sent By tgordon Date 2007-09-07 Time 13:58 Rev Time 0.30
Received By tgordon Date 2007-09-07 Time 13:58 Sent To  
Notes
2007-09-07 14:29:49PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (WPB), FLORIDA
 ADMINISTRATIVE CODE (FAC), AND FLORIDA STATUTES (FS).
  
 *** DENIED ***
 *** EXISTING RESTAURANT NEW OFFICE BEING INCLOSED AND
 NEW KITCHEN HOOD NOTES TO BE ADJUSTED. ***
  
 1) PLANS MUST SHOW THAT KITCHEN EXHAUST HOODS ARE BEING
 INSTALLED TO COMPLY WITH MECH. 507.2. SHOW LOCATION OF
 HOODS, TYPE OF HOODS, SIZE OF HOODS, EXHAUST AND
 MAKE-UP AIR CFM'S. (ENGINEERING FOR HOODS MAY BE
 SUBMITTED WHEN APPLYING FOR HOOD PERMIT).
  
 2) PROVIDE OUT-SIDE AIR CALCULATIONS, SEE MECH.401.2.
  
 3) PROVIDE AIR BALANCE CALCULATIONS TO SHOW COMPLIANCE
 WITH FBC 13-409.1.ABC.3.6.1.
  
 4) THE OFFICE WILL REQUIRE RETURN AIR, SEE MECH.
 601.4.
  
 5) THE RESPONSE LETTER SUBMITTED BY NELSON MARIN STATES
 (THESE FACTORS ARE CONSIDERED IN THE ENERGY
 CALCULATIONS SUBMITTED WITH THESE DRAWINGS). AS THE
 ENERGY CAL'S ARE ON FORM C THEY SHOW NO CALCULATIONS OR
 CONSIDERATIONS. PLEASE SUBMIT THE CALCULATIONS THAT YOU
 ARE REFERRING TO.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-05-09 Cont ID  
Sent By tgordon Date 2007-05-09 Time 09:45 Rev Time 0.30
Received By tgordon Date 2007-05-09 Time 09:44 Sent To  
Notes
2007-05-09 09:48:35*** DENIED ***
 1) NO MECHANICAL (A/C) PLANS WERE SUBMITTED FOR REVIEW,
 PLEASE SUBMIT MECHANICAL PLANS FOR REVIEW,SEE 2004
 FBC CITY OF WPB AMEND. 106.3.5.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 4 Status P Date 2007-12-17 Cont ID  
Sent By mperson Date 2007-12-17 Time 06:05 Rev Time 0.00
Received By mperson Date 2007-12-17 Time 06:04 Sent To  
Notes
2007-12-17 07:05:47NOTE: PER ROBERT BROWN SENT TO LUIS MARTINEZ FOR PERMIT
 PROCESSING.

Review Stop P PLUMBING
Rev No 3 Status F Date 2007-11-30 Cont ID  
Sent By mperson Date 2007-11-30 Time 10:35 Rev Time 0.00
Received By mperson Date 2007-11-30 Time 10:35 Sent To G
Notes
2007-11-30 11:21:53PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 05 & 06 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS
 TO CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED 3RD TIME:
  
 ***** FROM PREVIOUS REVIEW*****
  
 1. PLANS SHALL BE ROUTED TO THE STATE OF FLORIDA,
 DEPT. OF BUSINESS REGULATION, HOTEL & RESTAURANT FOOD
 SERVICE LICENSE FOR REVIEW PRIOR TO RESUBMITTING TO THE
 CITY FOR REVIEW. AMINIMUM OF TWO SETS OF PLANS WITH
 REVIEW STAMPS FROM DBPR WITH THE TWO PAGE "WORKSHEETS"
 ATTACHED TO THE STAMPED SHEET SHALL BE SUBMITTED FOR
 REVIEW. SECTION 102.2.1.
 *****RESPONSE NOTED: HOWEVER THE RESUBMITTED PLANS DO
 NOT HAVE THE TWO PAGE "WORKSHEETS" ATTACHED TO THE
 STAMPED DBPR PLAN SHEET. THESE TWO PAGE WORKSHEETS ARE
 REQUIRED.
  
 2. PER MUNICIPAL CODE ARTICLE III SECTION 90-124,
 THE EXISTING/PROPOSED GREASE INTERCEPTOR SHALL BE SIZED
 AND LOCATED BY ENVIRONMENTAL COMPLIANCE DIVISION OF THE
 UTILITY DEPARTMENT. PLEASE CONTACT RODNEY COMPO, PHONE:
 (561) 822-2272, E-MAIL: [email protected] OR CLAVIN
 WILLIAMS, PHONE: (561) 822-2284, E-MAIL:
 [email protected]. THEIR FAX NUMBER IS (561) 822-2287.
 NOTE: WRITTEN APPROVAL IS REQUIRED OF THE
 EXISTING/PROPOSED GREASE INTERCEPTOR FROM ENVIRONMENTAL
 COMPLIANCE BEFORE A PERMIT CAN BE ISSUED.
 *****REPONSE NOTED: HOWEVER APPROVAL OF THE INTERCEPTOR
 SIZE AND LOCATION IS REQUIRED FROM ENVIRONMENTAL
 COMPLIANCE. PLEASE SUBMIT APPROVAL SHEET FROM MR. COMPO
 OR MR. WILLIAMS. PERMIT WILL NOT BE ISSUED WITHOUT
 ENVIRONMENTAL COMPLIANCE APPROVAL SHEET.
  
 3. OK
  
 4. OK
  
 5. OK
  
 6. OK
  
 7. OK
  
 8. OK
  
 9. OK (REMOVED FROM NOTES) HOWEVER APPROVAL OF THE
 SIZE AND LOCATION STILL REQUIRED FROM EVIRONMENTAL
 COMPLIANCE, REFERENCE COMMENT #2.
  
 10. OK
  
 11. OK, NOTE: FLORIDA PUBLIC UTILITIES CO. HAS A
 SEPERATE PERMIT FOR THE GAS PIPING SYSTEM PERMIT
 #07080547.
  
 **********NEW COMMENTS**********
  
 1B & 2B. OK, WATER HEATER IS EXISTING.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-09-21 Cont ID  
Sent By kstevens Date 2007-09-21 Time 09:12 Rev Time 0.00
Received By kstevens Date 2007-09-21 Time 09:12 Sent To  
Notes
2007-09-21 10:20:23DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 CITY WPB MUNICIPAL CODE
  
 ****FROM PREVIOUS REVIEW:
  
 1. PLANS SHALL BE ROUTED TO THE STATE OF FLORIDA, DEPT.
 OF BUSINESS REGULATION, HOTEL & RESTAURANT FOOD SERVICE
 LICENSE FOR REVIEW PRIOR TO RESUBMITTING TO THE CITY
 FOR REVIEW. A MINIMUM OF TWO SETS OF PLANS WITH REVIEW
 STAMPS FROM DBPR WITH THE TWO PAGE "WORKSHEETS"
 ATTACHED TO THE STAMPED SHEET SHALL BE SUBMITTED FOR
 REVIEW. SECTION 102.2.1.
 ****NO RESPONSE, NOT ADDRESSED.
  
 2. THE GREASE INTERCEPTOR SHALL BE SIZED AND LOCATED BY
 ENVIRONMENTAL COMPLIANCE DIVISION OF THE UTILITY DEPT.
 PLEASE CONTACE RODNEY COMPO, (561) 822-2272 OR CALVIN
 WILLIAMS, (561) 822-2284. THEIR FAX NUMBER IS (561)
 822-2287 AND THEIR E-MAIL ADDRESSES ARE [email protected]
 AND [email protected]. MUNICIPAL CODE ARTICLE III
 SECTION 90-124.
 ****RESPONSE NOTED, BUT APPROVAL OF INTERCEPTOR SIZE
 SHALL BE FROM INDUSTRIAL PRETREATMENT, ENVIRONMENTAL
 COMPLIANCE. PLEASE SUBMIT APPROVAL SHEET FROM MR. COMPO
 OR MR. WILLIAMS.
  
 3. OK
  
 4. EQUIPMENT AND FIXTURES UTILIZED FOR THE STORAGE,
 PREPARATION AND HANDLING OF FOOD SHALL DISCHARGE
 THROUGH AN INDIRCET WASTE PIPE BY MEANS OF AN AIR GAP.
 SECTION 802.1. SEE THE THREE COMPARTMENT SINK AND THE
 TWO COMPARTMENT SINK. A FLOOR SINK SHALL BE REQUIRED.
 SECTION 802.3.
 ****RESPONSE NOTED, BUT THE TWO COMPARTMENT SINK SHOWS
 A FLOOR DRAIN AS THE INDIRECT WASTE RECEPTOR. FLOOR
 DRAINS ARE NOT APPROVED WASTE RECEPTORS PER SECTION
 802.3. A FLOOR SINK IS REQUIRED. PLEASE CHANGE FIXTURE
 ON PLANS & NOTES.
  
 5. SUBMIT A WATER RISER DIAGRAM SHOWING ALL PIPE SIZES,
 VALVES, AND WATER HAMMER ARRESTORS REQUIRED FOR QUICK
 CLOSING VALVES. WATER HAMMER ARRESTORS SHALL BE LOCATED
 NEAR THE FIXTURE IN AN "EFFECTIVE RANGE" NOT IN THE
 CEILING. PDI-WH 201 AND MANUF. INSTALLATION
 INSTRUCTIONS. SECTION 106.3.5.1.3(3)(10)(13).
 ****RESPONSE NOTE, BUT NO RISER DIAGRAMS WERE SUBMITTED
 SHOWING THE PIPING TO THE NEW FIXTURES.
  
 6. AN RPZV BACKFLOW IS REQUIRED ON THE WATER SUPPLY TO
 THE RESTAURANT. SECTION 608.13.2.
 ****NO RESPONSE, NOT ADDRESSED.
  
 7. THERMAL EXPANSION CONTROL IS REQUIRED PER SECTION
 607.3.1. PLEASE INDICATE METHOD.
 ****NO RESPONSE, NOT ADDRESSED.
  
 8. OK
  
 9. SHT A-1 CODE REVIEW NOTES CONCERNING GREASE
 INTERCEPTORS. THE WEST PALM BEACH MUNICIPAL CODE,
 ARTICLE III SECTION 90-124(7)(A THRU G) SHALL GOVERN
 THE INSTALLATION, TYPE, MANITENANCE ETC OF THE GREASE
 INTERCEPTOR. SEE ATTACHED SHEET FOR REQUIREMENTS.
 ****NO RESPONSE, NOT ADDRESSED.
  
 10. SHT A-2 PLUMBING GENERAL NOTES #4. SUBMIT A
 CONDENSATE RISER DIAGRAM SHOWING ALL PIPE SIZES, TRAPS,
 VENTS AND INDICATE THE TERMINATION POINT. SECTION
 106.3.5.1.3(13).--NOTE #6PVC PIPEIS NOT ALLOWED
 FOR DISTRIBUTION PIPE PER TABLE 605.4.--NOTE #8 AIR
 CHAMBERS ARE NOT APPROVED. PDI-WH 201 AND SECTION
 604.9. WATER HAMMER ARRESTORS ARE REQUIRED FOR ALL
 QUICK CLOSING VALVES.
 ****NO RESPONSE, NOT ADDRESSED FOR GENERAL NOTES #4 &
 #8. NOTE #6 IS OK.
  
 11. SHT A-2 KITCHEN EQUIPMENT INDICATES GAS APPLIANCES.
 A SEPARATE GAS PERMIT IS REQUIRED. PLEASE PROVIDE THE
 FOLLOWING INFORMATION FOR THE GAS PERMIT:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 C. TYPE OF GAS, (LP OR NATURAL).
  
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 F. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 H. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 I. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 J. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
  
 ****NO RESPONSE FOR ALL GAS REQUIREMENTS, COMMENTS NOT
 ADDRESSED. INFORMATION NOW SHOWN ON SHEET E-1.
  
 **********NEW COMMENTS**********
  
 1B. THE ENERGY CALCULATIONS ARE INCOMPLETE. PLEASE
 INDICATE THE SYSTEMS INFORMATION FOR THE WATER HEATER.
 SECTION 13-103.
  
 2B. SEE ATTACHED SHEET CONCERNING FS 553.80(2)(B) AND
 THE DESIGN PROFESSIONAL. THIS IS GIVEN AS A NOTICE ONLY
 AT THIS TIME.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-06-06 Cont ID  
Sent By kstevens Date 2007-06-06 Time 11:22 Rev Time 0.00
Received By kstevens Date 2007-06-06 Time 11:22 Sent To  
Notes
2007-06-06 12:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 CITY WPB MUNICIPAL CODE
  
 1. PLANS SHALL BE ROUTED TO THE STATE OF FLORIDA, DEPT.
 OF BUSINESS REGULATION, HOTEL & RESTAURANT FOOD SERVICE
 LICENSE FOR REVIEW PRIOR TO RESUBMITTING TO THE CITY
 FOR REVIEW. A MINIMUM OF TWO SETS OF PLANS WITH REVIEW
 STAMPS FROM DBPR WITH THE TWO PAGE "WORKSHEETS"
 ATTACHED TO THE STAMPED SHEET SHALL BE SUBMITTED FOR
 REVIEW. SECTION 102.2.1.
  
 2. THE GREASE INTERCEPTOR SHALL BE SIZED AND LOCATED BY
 ENVIRONMENTAL COMPLIANCE DIVISION OF THE UTILITY DEPT.
 PLEASE CONTACE RODNEY COMPO, (561) 822-2272 OR CALVIN
 WILLIAMS, (561) 822-2284. THEIR FAX NUMBER IS (561)
 822-2287 AND THEIR E-MAIL ADDRESSES ARE [email protected]
 AND [email protected]. MUNICIPAL CODE ARTICLE III
 SECTION 90-124.
  
 3. THE FLOOR DRAINS IN THE KITCHEN ANDBAKERY AREAS AS
 WELL AS THE MOP SINK SHALL DISCHARGE INTO THE GREASE
 WASTE SYSTEM, NOT THE SANITARY.SECTION 90-124(7)
  
 4. EQUIPMENT AND FIXTURES UTILIZED FOR THE STORAGE,
 PREPARATION AND HANDLING OF FOOD SHALL DISCHARGE
 THROUGH AN INDIRCET WASTE PIPE BY MEANS OF AN AIR GAP.
 SECTION 802.1. SEE THE THREE COMPARTMENT SINK AND THE
 TWO COMPARTMENT SINK. A FLOOR SINK SHALL BE REQUIRED.
 SECTION 802.3.
  
 5. SUBMIT A WATER RISER DIAGRAM SHOWING ALL PIPE SIZES,
 VALVES, AND WATER HAMMER ARRESTORS REQUIRED FOR QUICK
 CLOSING VALVES. WATER HAMMER ARRESTORS SHALL BE LOCATED
 NEAR THE FIXTURE IN AN "EFFECTIVE RANGE" NOT IN THE
 CEILING. PDI-WH 201 AND MANUF. INSTALLATION
 INSTRUCTIONS. SECTION 106.3.5.1.3(3)(10)(13).
  
 6. AN RPZV BACKFLOW IS REQUIRED ON THE WATER SUPPLY TO
 THE RESTAURANT. SECTION 608.13.2.
  
 7. THERMAL EXPANSION CONTROL IS REQUIRED PER SECTION
 607.3.1. PLEASE INDICATE METHOD.
  
 8. SHT A-1 SCHEMATIC RISER DIAGRAM, NEW HAND SINKS ARE
 NOT VENTED AS SHOWN. PLEASE SHOW COMPLIANCE WITH
 SECTION 901.2.1.--THE EXISING LINE BEING DEMO'D
 SHALL COMPLY WITH SECTION 704.5. NO DEAD ENDS.
  
 9. SHT A-1 CODE REVIEW NOTES CONCERNING GREASE
 INTERCEPTORS. THE WEST PALM BEACH MUNICIPAL CODE,
 ARTICLE III SECTION 90-124(7)(A THRU G) SHALL GOVERN
 THE INSTALLATION, TYPE, MANITENANCE ETC OF THE GREASE
 INTERCEPTOR. SEE ATTACHED SHEET FOR REQUIREMENTS.
  
 10. SHT A-2 PLUMBING GENERAL NOTES #4. SUBMIT A
 CONDENSATE RISER DIAGRAM SHOWING ALL PIPE SIZES, TRAPS,
 VENTS AND INDICATE THE TERMINATION POINT. SECTION
 106.3.5.1.3(13).--NOTE #6PVC PIPEIS NOT ALLOWED
 FOR DISTRIBUTION PIPE PER TABLE 605.4.--NOTE #8 AIR
 CHAMBERS ARE NOT APPROVED. PDI-WH 201 AND SECTION
 604.9. WATER HAMMER ARRESTORS ARE REQUIRED FOR ALL
 QUICK CLOSING VALVES.
  
 11. SHT A-2 KITCHEN EQUIPMENT INDICATES GAS APPLIANCES.
 A SEPARATE GAS PERMIT IS REQUIRED. PLEASE PROVIDE THE
 FOLLOWING INFORMATION FOR THE GAS PERMIT:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 C. TYPE OF GAS, (LP OR NATURAL).
  
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 F. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 H. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 I. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 J. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved