 |
Plan Review Details - Permit 07040733
Plan Review Stops For Permit 07040733 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2007-11-08 |
|
|
Cont ID |
|
Sent By |
jjohnsto |
Date |
2007-11-08 |
Time |
17:25 |
Rev Time |
0.00 |
Received By |
jjohnsto |
Date |
2007-11-08 |
Time |
17:24 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2007-09-18 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2007-09-18 |
Time |
08:13 |
Rev Time |
1.55 |
Received By |
jwitmer |
Date |
2007-09-18 |
Time |
08:13 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2007-06-14 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2007-06-14 |
Time |
17:07 |
Rev Time |
1.33 |
Received By |
jwitmer |
Date |
2007-06-14 |
Time |
17:00 |
Sent To |
FIRE |
|
Notes |
2007-06-14 17:30:40 | BUILDING PLAN REVIEW | | PERMIT: 07040733 | | ADD: 7750 OKEECHOBEE BLVD SUITE# 3 | | CONT: ATLANTIDA CONSTRUCTION | | TEL: (561)313-2706 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | W/ 2006 FBC REVISIONS | | * WEST PALM BEACH AMENDMENTS | | | | REVIEW | | ACTION: DENIED | | | | 1)--- VERY IMPORTANT STATEMENT --- | | PLEASE DO NOT IGNORE! | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | YOUR ANTICIPATED COOPERATION. | | | | 2)) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE | | FILED WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF | | THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS | | NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE | | RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: | | 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT | | THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. | | | | 3) PLANS SUBMITTED AFTER DEC. 8,2006 SHALL BE DESIGNED | | TO THE 2006 FLORIDA BUILDING CODE- BUILDING AND THE | | 2006 FLORIDA EXISTING BUILDING CODE . ALSO INDICATE TO | | WHAT LEVEL OF ALTERATION WORK WILL BE COMPLETED UNDER | | THIS PERMIT? | | | | 4) IS THIS TENANT SPACE A CHANGE OF OCCUPANCY? IF SO | | PLANS WILL NEED TO BE REVIEWED BY PALM BEACH COUNTY | | IMPACT FEES OFFICE.BEFORE A PERMIT TO CONSTRUCT, MAY | | BE ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH | | COUNTY. THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED | | BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED | | TO THE PERMIT APPLICATION. PLEASE CALL (561)233-5025 | | FOR MORE INFORMATION. | | | | 5) PLEASE REVIEW THE REFLECTED CEILING PLAN AND THE | | FLOOR PLAN THE DOOR LAYOUT CHANGESFOR THE DOORS | | LEADING TO THE RESTROOMS. THE SECOND ISSUE IS THE | | CORRECTION OF THE TWO DOORS LEADING TO THE RESTROOM . | | 11-4.1.6(2) DUTY TO PROVIDE AN ACCESSIBLE PATH OF | | TRAVEL TO ALTERED AREAS SHALL BE DEEMED | | DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE | | COST EXCEEDS 20 % OF THE COST OF THE ALTERATION TO THE | | PRIMARY FUNCTION AREA. | | (A)(I) AN ACCESSIBLE ENTRANCE | | (II) AN ACCESSIBLE ROUTE | | (III) AT LEAST ONE ACCESSIBLE REST- | | ROOM FOR EACH SEX OR A SINGLE | | UNISEX RESTROOM | | (IIII) ACCESSIBLE TELEPHONE | | (IV) ELEMENTS SUCH AS PARKING, STOR- | | AGE OR ALARMS. | | 11-4.13.7 TWO DOORS IN SERIES. | | THE MINIMUM SPACE BETWEEN TWO HINGED OR PIVOTED DOORS | | IN SERIES SHALL BE 48 INCHES (1219 MM) PLUS THE WIDTH | | OF ANY DOOR SWINGING INTO THE SPACE. DOORS IN SERIES | | SHALL SWING EITHER IN THE SAME DIRECTION OR AWAY FROM | | THE SPACE BETWEEN THE DOORS [SEE FIGURE 26 (A)]. SEE | | ATTACHMENT. | | | | 6) INDICATE COMPLIANCE WITH:11-4.32.1 MINIMUM NUMBER. | | FIXED OR BUILT-IN SEATING OR TABLES REQUIRED TO BE | | ACCESSIBLE BY SECTION 11-4.1 SHALL COMPLY WITH SECTION | | 11-4.32 . 11-4.32.2 SEATING. | | IF SEATING SPACES FOR PEOPLE IN WHEELCHAIRS ARE | | PROVIDED AT FIXED TABLES OR COUNTERS, CLEAR FLOOR SPACE | | COMPLYING WITH SECTION 11-4.2.4 SHALL BE PROVIDED. SUCH | | CLEAR FLOOR SPACE SHALL NOT OVERLAP KNEE SPACE BY MORE | | THAN 19 INCHES (485 MM) (SEE FIGURE 45 ). | | ALL FIXED SEATING IN PUBLIC FOOD SERVICE | | ESTABLISHMENTS, IN ESTABLISHMENTS LICENSED UNDER THE | | BEVERAGE LAW FOR CONSUMPTION ON THE PREMISES, AND IN | | ALL OTHER FACILITIES GOVERNED BY REFERENCE SECTION | | 11-4.1 SHALL BE DESIGNED AND CONSTRUCTED IN ACCORDANCE | | WITH THE FOLLOWING REQUIREMENTS: | | (1)ALL AISLES ADJACENT TO FIXED SEATING SHALL | | PROVIDE CLEAR FLOOR SPACE FOR WHEELCHAIRS. | | (2)WHERE THERE ARE OPEN POSITIONS ALONG BOTH SIDES | | OF SUCH AISLES, THE AISLES SHALL BE NOT LESS THAN 52 | | INCHES (1321 MM) WIDE. 11-4.32.3 KNEE CLEARANCES. | | IF SEATING FOR PEOPLE IN WHEELCHAIRS IS PROVIDED AT | | TABLES OR COUNTERS, KNEE SPACES AT LEAST 27 INCHES (685 | | MM) HIGH, 30 INCHES (760 MM) WIDE, AND 19 INCHES (485 | | MM) DEEP SHALL BE PROVIDED (SEE FIGURE 45 ). 11-4.32.4 | | HEIGHT OF TABLES OR COUNTERS. THE TOPS OF ACCESSIBLE | | TABLES AND COUNTERS SHALL BE FROM 28 INCHES TO 34 | | INCHES (710 MM TO 865 MM) ABOVE THE FINISH FLOOR OR | | GROUND. | | | | 7)INDICATE COMPLIANCE WITH: 11-5.1 GENERAL. | | EXCEPT AS SPECIFIED OR MODIFIED IN THIS SECTION, | | RESTAURANTS AND CAFETERIAS SHALL COMPLY WITH THE | | REQUIREMENTS OF SECTION 11-4.1 TO SECTION 11-4.35 . | | WHERE FIXED TABLES (OR DINING COUNTERS WHERE FOOD IS | | CONSUMED BUT THERE IS NO SERVICE) ARE PROVIDED, AT | | LEAST 5 PERCENT, BUT NOT LESS THAN ONE, OF THE FIXED | | TABLES (OR A PORTION OF THE DINING COUNTER) SHALL BE | | ACCESSIBLE AND SHALL COMPLY WITH SECTION 11-4.32 AS | | REQUIRED IN SECTION 11-4.1.3 (18). IN ESTABLISHMENTS | | WHERE SEPARATE AREAS ARE DESIGNATED FOR SMOKING AND | | NONSMOKING PATRONS, THE REQUIRED NUMBER OF ACCESSIBLE | | FIXED TABLES (OR COUNTERS) SHALL BE PROPORTIONALLY | | DISTRIBUTED BETWEEN THE SMOKING AND NONSMOKING AREAS. | | IN NEW CONSTRUCTION, AND WHERE PRACTICABLE IN | | ALTERATIONS, ACCESSIBLE FIXED TABLES (OR COUNTERS) | | SHALL BE DISTRIBUTED THROUGHOUT THE SPACE OR FACILITY. | | | | | | 8)INDICATE COMPLIANCE WITH: 11-5.2 COUNTERS AND BARS. | | | | WHERE FOOD OR DRINK IS SERVED AT COUNTERS EXCEEDING 34 | | INCHES (865 MM) IN HEIGHT FOR CONSUMPTION BY CUSTOMERS | | SEATED ON STOOLS OR STANDING AT THE COUNTER, A PORTION | | OF THE MAIN COUNTER WHICH IS 60 INCHES (1525 MM) IN | | LENGTH MINIMUM SHALL BE PROVIDED IN COMPLIANCE WITH | | SECTION 11-4.32 OR SERVICE SHALL BE AVAILABLE AT | | ACCESSIBLE TABLES WITHIN THE SAME AREA. | | | | BUILDING PLAN REVIEW | | JIM WITMER C. B. O. | | | | TEL: (561)805-6715 | | FAX: (561)659-8026 | | E-MAIL: [email protected] | | | | | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2007-11-05 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-11-05 |
Time |
16:01 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-11-05 |
Time |
16:01 |
Sent To |
|
|
Notes |
2007-11-05 16:03:17 | NEW E-1, OK,STAMPED. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2007-09-05 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-09-05 |
Time |
19:12 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-09-05 |
Time |
18:36 |
Sent To |
|
|
Notes |
2007-09-05 19:13:08 | ** DENIED 2ND REVIEW ** | | | | | | ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW ARE | | STILL IN NEED OF ADDRESSING. | | | | 1) NOTE: PLEASE SEE THE VALUE FOR COMPLETE SCOPE OF | | WORK SHALL INCLUDE ALL LABOR, ALL MATERIALS, ALL | | PERMANENTLY INSTALLED EQUIPMENT, ARCHITECTURAL AND | | DESIGN FEES ETC. | | PLEASE SEE THE ELECTRICAL SCOPE OF WORK AS ORIGINALLY | | SHOWN HAS SUBSTANTIALLY INCREASED ALONE. | | PLEASE MAKE ADJUSTMENTS OR A VALUE WILL BE APPLIED | | USING GUIDES ADOPTED UNDER THE FBC AND ADOPTED | | REFERENCE BOOKS. | | | | 2) NOTE: PLEASE SEE THE NEW ENERGY CALCULATIONS | | SUBMITTED ARE NOT COMPLETE. PLEASE SEE THE LIGHTING | | DENSITIES ARE SHOWN BLANK. | | PLEASE SEE THE SIGNATURE NOT THE TYPED NAME OF PERSON | | PREPARING DOCUMENT IS REQUIRED. 13-103.1.1.1 | | PLEASE SEE THE ENGINEER OF RECORD AS LISTED IS NOT | | SIGN, DATED AND SEALED. FBC 13-103.1.1.1, FAC | | 61G15-23.002, FS 471.025 | | PLEASE SEE THE OWNER AGENT IS BLANK. | | FBC 13-415.1.C | | | | ** ELECTRICAL PLANS ARE IN GOOD SHAPE AS THE ENGINEER | | DID A GOOD JOB ADDRESSING THE ELECTRICAL COMMENTS. WELL | | DONE. | | | | ** PLEASE ADDRESS COMMENTS #1 AND #2. THE ELECTRICAL | | SHEETS WILL BE STAMPED AT THIS TIME. | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | REVIEWER. | | | | ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES | | WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2007-04-27 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-04-27 |
Time |
16:35 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-04-27 |
Time |
15:28 |
Sent To |
|
|
Notes |
2007-04-27 16:35:49 | ** UNSAT ** | | | | ** PLEASE SEE THAT ANY REFERENCES TO THE FBC CHAPTER 1 | | ARE FROM THE ADMINISTRATIVE CODE ADOPTED BY THE CITY OF | | WEST PALM BEACH. | | | | | | 1) NOTE:PLEASE SEE THE VALUE FOR SCOPE OF WORK SHALL | | INCLUDE ALL LABOR, EQUIPMENT AND MATERIALS EVEN IF ANY | | OF THESE ARE OWNER SUPPLIED. | | PLEASE SEE THE VALUE IS LOW AT THIS TIME AND WILL NEED | | TO BE ADJUSTED. | | PLEASE THAT A VALUE MAY BE ASSESSED BY USING GUIDES AS | | ADOPTED BY THE FBC. 108.3 | | | | 2) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH | | ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS | | UNDER THE NEW CODES ADOPTED BY THE STATE. | | PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO | | THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. | | PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY | | AFFECT DESIGNS FOR ALL TRADES. | | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS | | REVIEWER AT A MINIMUM. | | 2004 FBC W/ 2006 REVISIONS | | 2005 NFPA-70 | | 2002 NFPA-72 | | ** PLEASE SEE THE INCORRECT NEC IS NOTED. | | | | 3) NOTE: PLEASE PROVIDE MORE DETAIL FOR LIGHTING | | CONTROLS BEING INSTALLED. PLEASE PROVIDE DETAIL ON | | OCCUPANCY DEVICE AND PLEASE SEE SOME AREAS LIKE THE | | KITCHEN IN WHICH THE SINGLE WALL WHICH AT LOCATION | | SHOWN MAY NOT PROVIDE THE NEEDED COVERAGE. | | PLEASE DETAIL THE CONNECTION IN BAR AREA AND ALL OTHER | | AREAS. | | PLEASE SEE THE EXISTING BATH ROOMS WILL REQUIRE | | DEVICES. | | PLEASE SEE NOT ALL AREAS INDICATE LIGHTING POWER | | DENSITIES. | | PLEASE SUBMIT ENERGY CALCULATIONS SHOWING COMPLIANCE. | | PLEASE BE SURE THE FIXTURE LEGEND IS COMPLETED WITH ALL | | FIXTURE TYPES, WATTAGES ETC. (THESE MAY BE REVISED AT A | | LATER DATE IF CHANGED). | | PLEASE SEE 13-415.1.ABC.1.1, .1.2, .1.3, | | 13-415.1.AB.1.1, 13-415.2 ETC. | | | | 4) NOTE: PLEASE INDICATE ALL RECEPTACLES SERVING | | KITCHEN AREAS AS GFI. MOST ARE DONE AND ONLY ONE IS | | MISSING IN THIS DESIGNATED AREA. | | PLEASE ALSO SEE ONLY MISPRINT FOR THE CODE SECTION AS | | NOTED IN GENERAL ELECTRICAL NOTES. | | PLEASE SEE 210.8B3. | | | | 5) NOTE: PLEASE SEE ELECTRICAL SHEETS IN TWO OF THE | | SETS ARE INSERTED UPSIDE DOWN, BACKWARDS AND THERE ARE | | MORE SHEETS THAN SHOULD BE IN SETS. | | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND INSERT NEW | | SHEETS INTO COMPLETE SETS FOR REVIEW AND STAMPING. | | PLEASE BE SURE TO CHECK THE SHEETS. | | PLEASE ONLY SUBMIT ONE COPY OF THE OLD/VOIDED REMOVED | | SHEETS. | | ** PLEASE BE CAREFUL NOT TO DISCARD ANY SHEETS STAMP BY | | THE DIVISION OF HOTELS ETC). | | | | 6) NOTE: PLEASE INDICATE IF THE PANELS CONTAIN | | FEED-THRU LUGS OR IS THERE OVER CURRENT PROTECTION FROM | | ONE TO THE OTHER? | | FBC 106.1.2 | | | | 7) NOTE: PLEASE SEE THE LOADS AS SHOWN ON PANEL *A* IS | | LOWER THAN THE LOAD ON LOAD CALCULATIONS.THIS IS NOT | | POSSIBLE WHEN PANEL USUALLY SHOW THE CONNECTED LOAD OR | | THE SAME DE-RATED LOAD AS FIGURED IN THE LOAD | | CALCULATIONS. | | PLEASE COORDINATE THESE. | | FBC 106.1.2 | | NEC 220 | | | | 8) NOTE: PLEASE SEE 422.13 AS THIS WAS REVISED IN THE | | 2005 CODE TO REQUIRE ALL ELECTRIC WATER HEATER LOADS TO | | BE SHOWN AND DONE AT 125%. | | | | 9) NOTE: PLEASE INDICATE THE EXISTING LIGHTING FIXTURES | | IN THE BATHROOMS. | | | | 10) NOTE: PLEASE SEE THE TITLE COVER SHEET INDICATES | | PLANS SUBMITTED BY MARTEK, YET NO MECHANICAL PLANS WERE | | SUBMITTED FOR REVIEW? PLEASE VERIFY. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE DO NOT HESITATE IN | | CONTACTING THIS OFFICE OR REVIEWER. | | | | ** IMPORTANT** | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | PICKED UP FOR CORRECTIONS, PLEASE BE | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | AND STAMPING. DO NOT LEAVE ANY | | OLD/VOIDED SHEETS IN SETS. | | PLEASE KNOW ONLY ONE SET OF THE | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | FOR REFERENCE. | | THIS WILL HELP IN THE REVIEW PROCESS AND | | AVOID ANY DELAYS. | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2007-11-12 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2007-11-12 |
Time |
15:11 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2007-11-12 |
Time |
14:58 |
Sent To |
|
|
Notes |
2007-11-12 15:09:51 | *****APPROVED***** | | | | PLAN SHEETSA-1 AND E-1 WERE STAMPED, INITIALED, AND | | DATED. | | | | | | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
F |
Date |
2007-09-24 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2007-09-24 |
Time |
14:31 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2007-09-24 |
Time |
14:07 |
Sent To |
|
|
Notes |
2007-09-24 14:26:06 | *****UNSAT***** | | | | ALL OF THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW | | HAVE BEEN ADDRESSED EXCEPT FOR THE FOLLOWING: | | | | 8.SPECIFY THE INTERIOR FINISH MATERIAL FOR WALLS AND | | CEILINGS IN THE EXITS, EXIT AISLE CORRIDORS AND OTHER | | SPACES. SPECIFY IN TERMS OF CLASS "A", CLASS "B", OR | | CLASS "C" | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | LETTER INDICATING WHERE (ON THE PLANS) EACH ITEM WAS | | ADDRESSED | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2007-06-25 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2007-06-25 |
Time |
16:16 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2007-06-21 |
Time |
13:02 |
Sent To |
|
|
Notes |
2007-06-25 15:48:06 | *****DENIED***** | | | | | | 1.ON THE COVER SHEET, REFERENCE THE 2003 EDITION OF | | NFPA 101. | | | | 2.PLEASE INDICATE IF THIS IS A CHANGE OF OCCUPANCY. | | | | 3.INDICATE IF THE BUILDING/TENANT SPACE IS FIRE | | SPRINKLERED AND/OR HAS A FIRE ALARM.IF THE SCOPE OF | | WORK HAS CAUSE FOR ANY OF THESE SYSTEMS TO BE | | REMODELED, SEPARATE PLANS AND PERMIT WILL BE REQUIRED. | | | | 4.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | 5.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL | | BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR | | MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION. | | | | 6.THE REMOVAL AND/OR THE STOCKING OF BUILDING | | MATERIALS & SUPPLIES SHALL NOT INTERFERE OR HINDER | | EMERGENCY RESPONSE ACCESS TO THE PROPERTY OR VICINITY | | THEREOF (INCLUDING STREETS,ROADS, FIRE LANES). | | | | 7.PROVIDE A T LEAST ONE 2A:10BC RATED FIRE | | EXTINGUISHER IN THE NON COOKING AREA. | | | | 8.SPECIFY THE INTERIOR FINISH MATERIAL FOR WALLS AND | | CEILINGS IN THE EXITS, EXIT AISLE CORRIDORS AND OTHER | | SPACES. | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | LETTER INDICATING WHERE (ON THE PLANS) EACH ITEM WAS | | ADDRESSED | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 | 2007-06-25 15:15:30 | ***** |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
3 |
Status |
N |
Date |
2007-11-30 |
|
|
Cont ID |
|
Sent By |
mperson |
Date |
2007-11-30 |
Time |
11:22 |
Rev Time |
0.00 |
Received By |
mperson |
Date |
2007-11-30 |
Time |
11:22 |
Sent To |
PC |
|
Notes |
2007-11-30 11:24:13 | NOTE: FLORIDA PUBLIC UTILITIES CO. HAS A SEPERATE GAS | | PERMIT FOR THE GAS SYSTEM, PERMIT #07080547. |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
2 |
Status |
F |
Date |
2007-09-21 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2007-09-21 |
Time |
10:21 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2007-09-21 |
Time |
10:21 |
Sent To |
|
|
Notes |
2007-09-21 10:23:27 | DENIED | | REFERENCE: FBC-2004 FUEL GAS | | | | ****FROM PREVIOUS REVIEW: | | | | 1. SHT A-2 KITCHEN EQUIPMENT INDICATES GAS APPLIANCES. | | A SEPARATE GAS PERMIT IS REQUIRED. PLEASE PROVIDE THE | | FOLLOWING INFORMATION FOR THE GAS PERMIT: | | | | A. SUBMIT AN ISOMETRIC DRAWING THAT | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | AND CORRESPONDING LENGTHS PER FBC-2004 | | FUEL GAS CODE. | | | | B. SHOW TYPE OF PIPING MATERIAL BEING | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | NUMBER OF CORRUGATED STAINLESS STEEL | | TUBING FOR EACH PIPE SIZE IF BEING USED. | | | | C. TYPE OF GAS, (LP OR NATURAL). | | | | D. BTU LOAD OF EACH APPLIANCE AND THE | | TOTAL BTU LOAD ON THE SYSTEM. REFER TO | | THE FBC-2004 FUEL GAS CODE SECS. 401.8 | | THRU 402.6.1 AND TABLES 402.4(1) THRU | | 402.4(33). | | | | E. SHOW THE DISTANCE FROM THE POINT OF | | DELIVERY, (METER), TO THE MOST REMOTE | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | FBC-2004 FUEL GAS CODE APPENDIX A - USE | | OF CAPACITY TABLES A.3.1(4). | | | | F. INDICATE THE DELIVERY PRESSURE (PSI) | | PER FBC-2004 FUEL GAS CODE SEC. 402.2. | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. | | | | G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | STANDARDS NFPA 54, NFPA 58, AND THE | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | | H. CLEARLY SHOW THE LOCATION AND CAP- | | ACITY OF LP TANK(S), TYPE OF TANK (DOT | | OR ASME), THE DISTANCE OF THE TANK FROM | | THE BUILDING AND ADJACENT PROPERTY LINES | | THE DISTANCE OF THE TANK FROM ALL SOUR- | | CES OF IGNITION, OTHER CONTAINERS, BUILD | | INGS, AND THE LOCATION OF ANY BUILDING | | OPENINGS BELOW THE RELIEF VALVE OF THE | | TANK PER NFPA 58, TABLE 3-2.2.2. | | | | I. CLEARLY INDICATE ON THE PLAN IF THE | | LP TANK IS ABOVE OR BELOW GROUND, AND | | SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES | | PER NFPA 58. IF THE TANK | | IS BELOW GROUND THE CONTAINER SHALL BE | | SECURILY ANCHORED PER NFPA 58 SECTION | | 3-2.2.7(H). | | | | J. EMERGENCY HOOD SHUT DOWN SHUT OFF | | VALVE TO BE BELOW CEILING. MANUAL SHUT | | OFF VALVE TO BE UPSTREAM. UNION TO BE | | DOWN STREAM OF MANUAL VALVE. | | | | ****NO RESPONSE, GAS COMMENTS NOT ADDRESSED. | | INFORMATION NOW SHOWN ON SHEET E-1. | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | WITH A DESCRIPTION OF THE REVISION | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID | | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY | | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU | | FOR YOUR ANTICIPATED COOPERATION. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
F |
Date |
2007-06-29 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2007-06-06 |
Time |
14:25 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2007-06-06 |
Time |
14:24 |
Sent To |
|
|
Notes |
2007-06-29 14:26:58 | DENIED | | REFERENCE: FBC-2004 FUEL GAS | | | | 1. SHT A-2 KITCHEN EQUIPMENT INDICATES GAS APPLIANCES. | | A SEPARATE GAS PERMIT IS REQUIRED. PLEASE PROVIDE THE | | FOLLOWING INFORMATION FOR THE GAS PERMIT: | | | | A. SUBMIT AN ISOMETRIC DRAWING THAT | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | AND CORRESPONDING LENGTHS PER FBC-2004 | | FUEL GAS CODE. | | | | B. SHOW TYPE OF PIPING MATERIAL BEING | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | NUMBER OF CORRUGATED STAINLESS STEEL | | TUBING FOR EACH PIPE SIZE IF BEING USED. | | | | C. TYPE OF GAS, (LP OR NATURAL). | | | | D. BTU LOAD OF EACH APPLIANCE AND THE | | TOTAL BTU LOAD ON THE SYSTEM. REFER TO | | THE FBC-2004 FUEL GAS CODE SECS. 401.8 | | THRU 402.6.1 AND TABLES 402.4(1) THRU | | 402.4(33). | | | | E. SHOW THE DISTANCE FROM THE POINT OF | | DELIVERY, (METER), TO THE MOST REMOTE | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | FBC-2004 FUEL GAS CODE APPENDIX A - USE | | OF CAPACITY TABLES A.3.1(4). | | | | F. INDICATE THE DELIVERY PRESSURE (PSI) | | PER FBC-2004 FUEL GAS CODE SEC. 402.2. | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. | | | | G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | STANDARDS NFPA 54, NFPA 58, AND THE | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | | H. CLEARLY SHOW THE LOCATION AND CAP- | | ACITY OF LP TANK(S), TYPE OF TANK (DOT | | OR ASME), THE DISTANCE OF THE TANK FROM | | THE BUILDING AND ADJACENT PROPERTY LINES | | THE DISTANCE OF THE TANK FROM ALL SOUR- | | CES OF IGNITION, OTHER CONTAINERS, BUILD | | INGS, AND THE LOCATION OF ANY BUILDING | | OPENINGS BELOW THE RELIEF VALVE OF THE | | TANK PER NFPA 58, TABLE 3-2.2.2. | | | | I. CLEARLY INDICATE ON THE PLAN IF THE | | LP TANK IS ABOVE OR BELOW GROUND, AND | | SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES | | PER NFPA 58. IF THE TANK | | IS BELOW GROUND THE CONTAINER SHALL BE | | SECURILY ANCHORED PER NFPA 58 SECTION | | 3-2.2.7(H). | | | | J. EMERGENCY HOOD SHUT DOWN SHUT OFF | | VALVE TO BE BELOW CEILING. MANUAL SHUT | | OFF VALVE TO BE UPSTREAM. UNION TO BE | | DOWN STREAM OF MANUAL VALVE. | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | WITH A DESCRIPTION OF THE REVISION | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID | | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY | | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU | | FOR YOUR ANTICIPATED COOPERATION. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2007-12-04 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-12-04 |
Time |
16:01 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-12-04 |
Time |
16:01 |
Sent To |
P |
|
Notes |
2007-12-04 16:01:47 | TO "P" BOX/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2007-12-04 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-12-04 |
Time |
15:50 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-12-04 |
Time |
15:50 |
Sent To |
P |
|
Notes |
2007-12-04 15:50:42 | TO "P" BOX/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2007-10-19 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-10-19 |
Time |
12:00 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-10-19 |
Time |
12:00 |
Sent To |
|
|
Notes |
2007-11-05 11:35:49 | TO "COMM" BD#28 | 2007-10-19 12:01:13 | WAITING FOR "COMM" BD |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2007-08-08 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-08-08 |
Time |
18:31 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-08-08 |
Time |
18:31 |
Sent To |
|
|
Notes |
2007-09-05 10:28:16 | TO "COMM" BD#11 | 2007-08-08 18:31:32 | WAITING FOR COMM BOARD. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2007-06-25 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2007-06-21 |
Time |
13:02 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2007-04-23 |
Time |
14:26 |
Sent To |
|
|
Notes |
2007-04-23 14:26:32 | WAITING FOR "COMM" BD |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2007-11-06 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2007-11-06 |
Time |
08:48 |
Rev Time |
0.25 |
Received By |
tgordon |
Date |
2007-11-06 |
Time |
08:48 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2007-09-07 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2007-09-07 |
Time |
13:58 |
Rev Time |
0.30 |
Received By |
tgordon |
Date |
2007-09-07 |
Time |
13:58 |
Sent To |
|
|
Notes |
2007-09-07 14:29:49 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST | | PALM BEACH AMENDMENTS TO CHAPTER 1 (WPB), FLORIDA | | ADMINISTRATIVE CODE (FAC), AND FLORIDA STATUTES (FS). | | | | *** DENIED *** | | *** EXISTING RESTAURANT NEW OFFICE BEING INCLOSED AND | | NEW KITCHEN HOOD NOTES TO BE ADJUSTED. *** | | | | 1) PLANS MUST SHOW THAT KITCHEN EXHAUST HOODS ARE BEING | | INSTALLED TO COMPLY WITH MECH. 507.2. SHOW LOCATION OF | | HOODS, TYPE OF HOODS, SIZE OF HOODS, EXHAUST AND | | MAKE-UP AIR CFM'S. (ENGINEERING FOR HOODS MAY BE | | SUBMITTED WHEN APPLYING FOR HOOD PERMIT). | | | | 2) PROVIDE OUT-SIDE AIR CALCULATIONS, SEE MECH.401.2. | | | | 3) PROVIDE AIR BALANCE CALCULATIONS TO SHOW COMPLIANCE | | WITH FBC 13-409.1.ABC.3.6.1. | | | | 4) THE OFFICE WILL REQUIRE RETURN AIR, SEE MECH. | | 601.4. | | | | 5) THE RESPONSE LETTER SUBMITTED BY NELSON MARIN STATES | | (THESE FACTORS ARE CONSIDERED IN THE ENERGY | | CALCULATIONS SUBMITTED WITH THESE DRAWINGS). AS THE | | ENERGY CAL'S ARE ON FORM C THEY SHOW NO CALCULATIONS OR | | CONSIDERATIONS. PLEASE SUBMIT THE CALCULATIONS THAT YOU | | ARE REFERRING TO. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729 | | E-MAIL; [email protected] |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2007-05-09 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2007-05-09 |
Time |
09:45 |
Rev Time |
0.30 |
Received By |
tgordon |
Date |
2007-05-09 |
Time |
09:44 |
Sent To |
|
|
Notes |
2007-05-09 09:48:35 | *** DENIED *** | | 1) NO MECHANICAL (A/C) PLANS WERE SUBMITTED FOR REVIEW, | | PLEASE SUBMIT MECHANICAL PLANS FOR REVIEW,SEE 2004 | | FBC CITY OF WPB AMEND. 106.3.5. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
4 |
Status |
P |
Date |
2007-12-17 |
|
|
Cont ID |
|
Sent By |
mperson |
Date |
2007-12-17 |
Time |
06:05 |
Rev Time |
0.00 |
Received By |
mperson |
Date |
2007-12-17 |
Time |
06:04 |
Sent To |
|
|
Notes |
2007-12-17 07:05:47 | NOTE: PER ROBERT BROWN SENT TO LUIS MARTINEZ FOR PERMIT | | PROCESSING. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
F |
Date |
2007-11-30 |
|
|
Cont ID |
|
Sent By |
mperson |
Date |
2007-11-30 |
Time |
10:35 |
Rev Time |
0.00 |
Received By |
mperson |
Date |
2007-11-30 |
Time |
10:35 |
Sent To |
G |
|
Notes |
2007-11-30 11:21:53 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH | | 05 & 06 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS | | TO CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE | | (F.A.C.), AND FLORIDA STATUTES (F.S.). | | | | PLUMBING PLAN REVIEW: | | DENIED 3RD TIME: | | | | ***** FROM PREVIOUS REVIEW***** | | | | 1. PLANS SHALL BE ROUTED TO THE STATE OF FLORIDA, | | DEPT. OF BUSINESS REGULATION, HOTEL & RESTAURANT FOOD | | SERVICE LICENSE FOR REVIEW PRIOR TO RESUBMITTING TO THE | | CITY FOR REVIEW. AMINIMUM OF TWO SETS OF PLANS WITH | | REVIEW STAMPS FROM DBPR WITH THE TWO PAGE "WORKSHEETS" | | ATTACHED TO THE STAMPED SHEET SHALL BE SUBMITTED FOR | | REVIEW. SECTION 102.2.1. | | *****RESPONSE NOTED: HOWEVER THE RESUBMITTED PLANS DO | | NOT HAVE THE TWO PAGE "WORKSHEETS" ATTACHED TO THE | | STAMPED DBPR PLAN SHEET. THESE TWO PAGE WORKSHEETS ARE | | REQUIRED. | | | | 2. PER MUNICIPAL CODE ARTICLE III SECTION 90-124, | | THE EXISTING/PROPOSED GREASE INTERCEPTOR SHALL BE SIZED | | AND LOCATED BY ENVIRONMENTAL COMPLIANCE DIVISION OF THE | | UTILITY DEPARTMENT. PLEASE CONTACT RODNEY COMPO, PHONE: | | (561) 822-2272, E-MAIL: [email protected] OR CLAVIN | | WILLIAMS, PHONE: (561) 822-2284, E-MAIL: | | [email protected]. THEIR FAX NUMBER IS (561) 822-2287. | | NOTE: WRITTEN APPROVAL IS REQUIRED OF THE | | EXISTING/PROPOSED GREASE INTERCEPTOR FROM ENVIRONMENTAL | | COMPLIANCE BEFORE A PERMIT CAN BE ISSUED. | | *****REPONSE NOTED: HOWEVER APPROVAL OF THE INTERCEPTOR | | SIZE AND LOCATION IS REQUIRED FROM ENVIRONMENTAL | | COMPLIANCE. PLEASE SUBMIT APPROVAL SHEET FROM MR. COMPO | | OR MR. WILLIAMS. PERMIT WILL NOT BE ISSUED WITHOUT | | ENVIRONMENTAL COMPLIANCE APPROVAL SHEET. | | | | 3. OK | | | | 4. OK | | | | 5. OK | | | | 6. OK | | | | 7. OK | | | | 8. OK | | | | 9. OK (REMOVED FROM NOTES) HOWEVER APPROVAL OF THE | | SIZE AND LOCATION STILL REQUIRED FROM EVIRONMENTAL | | COMPLIANCE, REFERENCE COMMENT #2. | | | | 10. OK | | | | 11. OK, NOTE: FLORIDA PUBLIC UTILITIES CO. HAS A | | SEPERATE PERMIT FOR THE GAS PIPING SYSTEM PERMIT | | #07080547. | | | | **********NEW COMMENTS********** | | | | 1B & 2B. OK, WATER HEATER IS EXISTING. | | | | ********IMPORTANT INFORMATION******** | | IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, | | PLEASE REPLACE ONLY SHEETS | | WHICH HAVE CHANGED, PLEASE INCLUDE A | | TRANSMITTAL LETTER INDICATING HOW EACH | | ITEM WAS ADDRESSED AND PROVIDE ONE COPY | | OF ALL OLD/VOIDED SHEETS FOR REFERENCE | | ONLY. | | NOTE: THERE IS ONLY ONE CORRECTED DRAWING | | IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS | | EXAMINER FOR REFERENCE FOR THE | | RESUBMITTAL. | | | | END OF COMMENTS: | | | | REVIEW BY: MIKE PERSON | | PLUMBING PLANS EXAMINER | | (561) 805-6730 | | FAX (561) 805-6731 | | E-MAIL: [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2007-09-21 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2007-09-21 |
Time |
09:12 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2007-09-21 |
Time |
09:12 |
Sent To |
|
|
Notes |
2007-09-21 10:20:23 | DENIED | | REFERENCE: FBC-2004 PLUMBING | | FBC-2004 FUEL GAS | | FBC-2004 CHAPTER 1 | | CITY WPB MUNICIPAL CODE | | | | ****FROM PREVIOUS REVIEW: | | | | 1. PLANS SHALL BE ROUTED TO THE STATE OF FLORIDA, DEPT. | | OF BUSINESS REGULATION, HOTEL & RESTAURANT FOOD SERVICE | | LICENSE FOR REVIEW PRIOR TO RESUBMITTING TO THE CITY | | FOR REVIEW. A MINIMUM OF TWO SETS OF PLANS WITH REVIEW | | STAMPS FROM DBPR WITH THE TWO PAGE "WORKSHEETS" | | ATTACHED TO THE STAMPED SHEET SHALL BE SUBMITTED FOR | | REVIEW. SECTION 102.2.1. | | ****NO RESPONSE, NOT ADDRESSED. | | | | 2. THE GREASE INTERCEPTOR SHALL BE SIZED AND LOCATED BY | | ENVIRONMENTAL COMPLIANCE DIVISION OF THE UTILITY DEPT. | | PLEASE CONTACE RODNEY COMPO, (561) 822-2272 OR CALVIN | | WILLIAMS, (561) 822-2284. THEIR FAX NUMBER IS (561) | | 822-2287 AND THEIR E-MAIL ADDRESSES ARE [email protected] | | AND [email protected]. MUNICIPAL CODE ARTICLE III | | SECTION 90-124. | | ****RESPONSE NOTED, BUT APPROVAL OF INTERCEPTOR SIZE | | SHALL BE FROM INDUSTRIAL PRETREATMENT, ENVIRONMENTAL | | COMPLIANCE. PLEASE SUBMIT APPROVAL SHEET FROM MR. COMPO | | OR MR. WILLIAMS. | | | | 3. OK | | | | 4. EQUIPMENT AND FIXTURES UTILIZED FOR THE STORAGE, | | PREPARATION AND HANDLING OF FOOD SHALL DISCHARGE | | THROUGH AN INDIRCET WASTE PIPE BY MEANS OF AN AIR GAP. | | SECTION 802.1. SEE THE THREE COMPARTMENT SINK AND THE | | TWO COMPARTMENT SINK. A FLOOR SINK SHALL BE REQUIRED. | | SECTION 802.3. | | ****RESPONSE NOTED, BUT THE TWO COMPARTMENT SINK SHOWS | | A FLOOR DRAIN AS THE INDIRECT WASTE RECEPTOR. FLOOR | | DRAINS ARE NOT APPROVED WASTE RECEPTORS PER SECTION | | 802.3. A FLOOR SINK IS REQUIRED. PLEASE CHANGE FIXTURE | | ON PLANS & NOTES. | | | | 5. SUBMIT A WATER RISER DIAGRAM SHOWING ALL PIPE SIZES, | | VALVES, AND WATER HAMMER ARRESTORS REQUIRED FOR QUICK | | CLOSING VALVES. WATER HAMMER ARRESTORS SHALL BE LOCATED | | NEAR THE FIXTURE IN AN "EFFECTIVE RANGE" NOT IN THE | | CEILING. PDI-WH 201 AND MANUF. INSTALLATION | | INSTRUCTIONS. SECTION 106.3.5.1.3(3)(10)(13). | | ****RESPONSE NOTE, BUT NO RISER DIAGRAMS WERE SUBMITTED | | SHOWING THE PIPING TO THE NEW FIXTURES. | | | | 6. AN RPZV BACKFLOW IS REQUIRED ON THE WATER SUPPLY TO | | THE RESTAURANT. SECTION 608.13.2. | | ****NO RESPONSE, NOT ADDRESSED. | | | | 7. THERMAL EXPANSION CONTROL IS REQUIRED PER SECTION | | 607.3.1. PLEASE INDICATE METHOD. | | ****NO RESPONSE, NOT ADDRESSED. | | | | 8. OK | | | | 9. SHT A-1 CODE REVIEW NOTES CONCERNING GREASE | | INTERCEPTORS. THE WEST PALM BEACH MUNICIPAL CODE, | | ARTICLE III SECTION 90-124(7)(A THRU G) SHALL GOVERN | | THE INSTALLATION, TYPE, MANITENANCE ETC OF THE GREASE | | INTERCEPTOR. SEE ATTACHED SHEET FOR REQUIREMENTS. | | ****NO RESPONSE, NOT ADDRESSED. | | | | 10. SHT A-2 PLUMBING GENERAL NOTES #4. SUBMIT A | | CONDENSATE RISER DIAGRAM SHOWING ALL PIPE SIZES, TRAPS, | | VENTS AND INDICATE THE TERMINATION POINT. SECTION | | 106.3.5.1.3(13).--NOTE #6PVC PIPEIS NOT ALLOWED | | FOR DISTRIBUTION PIPE PER TABLE 605.4.--NOTE #8 AIR | | CHAMBERS ARE NOT APPROVED. PDI-WH 201 AND SECTION | | 604.9. WATER HAMMER ARRESTORS ARE REQUIRED FOR ALL | | QUICK CLOSING VALVES. | | ****NO RESPONSE, NOT ADDRESSED FOR GENERAL NOTES #4 & | | #8. NOTE #6 IS OK. | | | | 11. SHT A-2 KITCHEN EQUIPMENT INDICATES GAS APPLIANCES. | | A SEPARATE GAS PERMIT IS REQUIRED. PLEASE PROVIDE THE | | FOLLOWING INFORMATION FOR THE GAS PERMIT: | | | | A. SUBMIT AN ISOMETRIC DRAWING THAT | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | AND CORRESPONDING LENGTHS PER FBC-2004 | | FUEL GAS CODE. | | | | B. SHOW TYPE OF PIPING MATERIAL BEING | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | NUMBER OF CORRUGATED STAINLESS STEEL | | TUBING FOR EACH PIPE SIZE IF BEING USED. | | | | C. TYPE OF GAS, (LP OR NATURAL). | | | | D. BTU LOAD OF EACH APPLIANCE AND THE | | TOTAL BTU LOAD ON THE SYSTEM. REFER TO | | THE FBC-2004 FUEL GAS CODE SECS. 401.8 | | THRU 402.6.1 AND TABLES 402.4(1) THRU | | 402.4(33). | | | | E. SHOW THE DISTANCE FROM THE POINT OF | | DELIVERY, (METER), TO THE MOST REMOTE | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | FBC-2004 FUEL GAS CODE APPENDIX A - USE | | OF CAPACITY TABLES A.3.1(4). | | | | F. INDICATE THE DELIVERY PRESSURE (PSI) | | PER FBC-2004 FUEL GAS CODE SEC. 402.2. | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. | | | | G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | STANDARDS NFPA 54, NFPA 58, AND THE | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | | H. CLEARLY SHOW THE LOCATION AND CAP- | | ACITY OF LP TANK(S), TYPE OF TANK (DOT | | OR ASME), THE DISTANCE OF THE TANK FROM | | THE BUILDING AND ADJACENT PROPERTY LINES | | THE DISTANCE OF THE TANK FROM ALL SOUR- | | CES OF IGNITION, OTHER CONTAINERS, BUILD | | INGS, AND THE LOCATION OF ANY BUILDING | | OPENINGS BELOW THE RELIEF VALVE OF THE | | TANK PER NFPA 58, TABLE 3-2.2.2. | | | | I. CLEARLY INDICATE ON THE PLAN IF THE | | LP TANK IS ABOVE OR BELOW GROUND, AND | | SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES | | PER NFPA 58. IF THE TANK | | IS BELOW GROUND THE CONTAINER SHALL BE | | SECURILY ANCHORED PER NFPA 58 SECTION | | 3-2.2.7(H). | | | | J. EMERGENCY HOOD SHUT DOWN SHUT OFF | | VALVE TO BE BELOW CEILING. MANUAL SHUT | | OFF VALVE TO BE UPSTREAM. UNION TO BE | | DOWN STREAM OF MANUAL VALVE. | | | | ****NO RESPONSE FOR ALL GAS REQUIREMENTS, COMMENTS NOT | | ADDRESSED. INFORMATION NOW SHOWN ON SHEET E-1. | | | | **********NEW COMMENTS********** | | | | 1B. THE ENERGY CALCULATIONS ARE INCOMPLETE. PLEASE | | INDICATE THE SYSTEMS INFORMATION FOR THE WATER HEATER. | | SECTION 13-103. | | | | 2B. SEE ATTACHED SHEET CONCERNING FS 553.80(2)(B) AND | | THE DESIGN PROFESSIONAL. THIS IS GIVEN AS A NOTICE ONLY | | AT THIS TIME. | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | WITH A DESCRIPTION OF THE REVISION | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID | | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY | | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU | | FOR YOUR ANTICIPATED COOPERATION. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2007-06-06 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2007-06-06 |
Time |
11:22 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2007-06-06 |
Time |
11:22 |
Sent To |
|
|
Notes |
2007-06-06 12:00:00 | DENIED | | REFERENCE: FBC-2004 PLUMBING | | FBC-2004 FUEL GAS | | FBC-2004 CHAPTER 1 | | CITY WPB MUNICIPAL CODE | | | | 1. PLANS SHALL BE ROUTED TO THE STATE OF FLORIDA, DEPT. | | OF BUSINESS REGULATION, HOTEL & RESTAURANT FOOD SERVICE | | LICENSE FOR REVIEW PRIOR TO RESUBMITTING TO THE CITY | | FOR REVIEW. A MINIMUM OF TWO SETS OF PLANS WITH REVIEW | | STAMPS FROM DBPR WITH THE TWO PAGE "WORKSHEETS" | | ATTACHED TO THE STAMPED SHEET SHALL BE SUBMITTED FOR | | REVIEW. SECTION 102.2.1. | | | | 2. THE GREASE INTERCEPTOR SHALL BE SIZED AND LOCATED BY | | ENVIRONMENTAL COMPLIANCE DIVISION OF THE UTILITY DEPT. | | PLEASE CONTACE RODNEY COMPO, (561) 822-2272 OR CALVIN | | WILLIAMS, (561) 822-2284. THEIR FAX NUMBER IS (561) | | 822-2287 AND THEIR E-MAIL ADDRESSES ARE [email protected] | | AND [email protected]. MUNICIPAL CODE ARTICLE III | | SECTION 90-124. | | | | 3. THE FLOOR DRAINS IN THE KITCHEN ANDBAKERY AREAS AS | | WELL AS THE MOP SINK SHALL DISCHARGE INTO THE GREASE | | WASTE SYSTEM, NOT THE SANITARY.SECTION 90-124(7) | | | | 4. EQUIPMENT AND FIXTURES UTILIZED FOR THE STORAGE, | | PREPARATION AND HANDLING OF FOOD SHALL DISCHARGE | | THROUGH AN INDIRCET WASTE PIPE BY MEANS OF AN AIR GAP. | | SECTION 802.1. SEE THE THREE COMPARTMENT SINK AND THE | | TWO COMPARTMENT SINK. A FLOOR SINK SHALL BE REQUIRED. | | SECTION 802.3. | | | | 5. SUBMIT A WATER RISER DIAGRAM SHOWING ALL PIPE SIZES, | | VALVES, AND WATER HAMMER ARRESTORS REQUIRED FOR QUICK | | CLOSING VALVES. WATER HAMMER ARRESTORS SHALL BE LOCATED | | NEAR THE FIXTURE IN AN "EFFECTIVE RANGE" NOT IN THE | | CEILING. PDI-WH 201 AND MANUF. INSTALLATION | | INSTRUCTIONS. SECTION 106.3.5.1.3(3)(10)(13). | | | | 6. AN RPZV BACKFLOW IS REQUIRED ON THE WATER SUPPLY TO | | THE RESTAURANT. SECTION 608.13.2. | | | | 7. THERMAL EXPANSION CONTROL IS REQUIRED PER SECTION | | 607.3.1. PLEASE INDICATE METHOD. | | | | 8. SHT A-1 SCHEMATIC RISER DIAGRAM, NEW HAND SINKS ARE | | NOT VENTED AS SHOWN. PLEASE SHOW COMPLIANCE WITH | | SECTION 901.2.1.--THE EXISING LINE BEING DEMO'D | | SHALL COMPLY WITH SECTION 704.5. NO DEAD ENDS. | | | | 9. SHT A-1 CODE REVIEW NOTES CONCERNING GREASE | | INTERCEPTORS. THE WEST PALM BEACH MUNICIPAL CODE, | | ARTICLE III SECTION 90-124(7)(A THRU G) SHALL GOVERN | | THE INSTALLATION, TYPE, MANITENANCE ETC OF THE GREASE | | INTERCEPTOR. SEE ATTACHED SHEET FOR REQUIREMENTS. | | | | 10. SHT A-2 PLUMBING GENERAL NOTES #4. SUBMIT A | | CONDENSATE RISER DIAGRAM SHOWING ALL PIPE SIZES, TRAPS, | | VENTS AND INDICATE THE TERMINATION POINT. SECTION | | 106.3.5.1.3(13).--NOTE #6PVC PIPEIS NOT ALLOWED | | FOR DISTRIBUTION PIPE PER TABLE 605.4.--NOTE #8 AIR | | CHAMBERS ARE NOT APPROVED. PDI-WH 201 AND SECTION | | 604.9. WATER HAMMER ARRESTORS ARE REQUIRED FOR ALL | | QUICK CLOSING VALVES. | | | | 11. SHT A-2 KITCHEN EQUIPMENT INDICATES GAS APPLIANCES. | | A SEPARATE GAS PERMIT IS REQUIRED. PLEASE PROVIDE THE | | FOLLOWING INFORMATION FOR THE GAS PERMIT: | | | | A. SUBMIT AN ISOMETRIC DRAWING THAT | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | AND CORRESPONDING LENGTHS PER FBC-2004 | | FUEL GAS CODE. | | | | B. SHOW TYPE OF PIPING MATERIAL BEING | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | NUMBER OF CORRUGATED STAINLESS STEEL | | TUBING FOR EACH PIPE SIZE IF BEING USED. | | | | C. TYPE OF GAS, (LP OR NATURAL). | | | | D. BTU LOAD OF EACH APPLIANCE AND THE | | TOTAL BTU LOAD ON THE SYSTEM. REFER TO | | THE FBC-2004 FUEL GAS CODE SECS. 401.8 | | THRU 402.6.1 AND TABLES 402.4(1) THRU | | 402.4(33). | | | | E. SHOW THE DISTANCE FROM THE POINT OF | | DELIVERY, (METER), TO THE MOST REMOTE | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | FBC-2004 FUEL GAS CODE APPENDIX A - USE | | OF CAPACITY TABLES A.3.1(4). | | | | F. INDICATE THE DELIVERY PRESSURE (PSI) | | PER FBC-2004 FUEL GAS CODE SEC. 402.2. | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. | | | | G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | STANDARDS NFPA 54, NFPA 58, AND THE | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | | H. CLEARLY SHOW THE LOCATION AND CAP- | | ACITY OF LP TANK(S), TYPE OF TANK (DOT | | OR ASME), THE DISTANCE OF THE TANK FROM | | THE BUILDING AND ADJACENT PROPERTY LINES | | THE DISTANCE OF THE TANK FROM ALL SOUR- | | CES OF IGNITION, OTHER CONTAINERS, BUILD | | INGS, AND THE LOCATION OF ANY BUILDING | | OPENINGS BELOW THE RELIEF VALVE OF THE | | TANK PER NFPA 58, TABLE 3-2.2.2. | | | | I. CLEARLY INDICATE ON THE PLAN IF THE | | LP TANK IS ABOVE OR BELOW GROUND, AND | | SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES | | PER NFPA 58. IF THE TANK | | IS BELOW GROUND THE CONTAINER SHALL BE | | SECURILY ANCHORED PER NFPA 58 SECTION | | 3-2.2.7(H). | | | | J. EMERGENCY HOOD SHUT DOWN SHUT OFF | | VALVE TO BE BELOW CEILING. MANUAL SHUT | | OFF VALVE TO BE UPSTREAM. UNION TO BE | | DOWN STREAM OF MANUAL VALVE. | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | WITH A DESCRIPTION OF THE REVISION | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID | | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY | | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU | | FOR YOUR ANTICIPATED COOPERATION. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |