Plan Review Stops For Permit 07040689 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2007-08-30 |
|
|
Cont ID |
|
Sent By |
mjacobs |
Date |
2007-08-30 |
Time |
07:52 |
Rev Time |
0.00 |
Received By |
mjacobs |
Date |
2007-08-30 |
Time |
07:17 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2007-07-19 |
|
|
Cont ID |
|
Sent By |
mjacobs |
Date |
2007-07-19 |
Time |
15:19 |
Rev Time |
0.00 |
Received By |
mjacobs |
Date |
2007-07-19 |
Time |
12:29 |
Sent To |
PC |
|
Notes |
2007-07-19 14:39:53 | BUILDING PLAN REVIEW | | PERMIT: 07040689 | | ADD:2235 OKEECHOBEE BLVD | | CONT: BENCHMARK III CORP | | TEL: (561)744-8686 | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | W/ 2006 FBC REVISIONS | | * WEST PALM BEACH AMENDMENTS | | | | REVIEW 2ND | | ACTION: DENIED | | | | 1)OK | | | | 2)11-4.26.1ALL HANDRAILS, GRAB BARS, AND TUB AND | | SHOWER SEATS REQUIRED TO BE ACCESSIBLE BY SECTION | | 11-4.1 , 11-4.8 , 11-4.9 , 11-4.16 , 11-4.17 , 11-4.20 | | OR 11-4.21 SHALL COMPLY WITH SECTION 11-4.26 . INDICATE | | THE TYPE OF BACKING WHICH WILL MEET THE 250LB BENDING | | MOMENT REQUIREMENT STATED IN SECTION(11-4.26.3). | | | | 3) THE CERTIFICATE OF AUTHORIZATION NUMBER OF ARCHITECT | | AND ASSOCIATES, P.A.SHALL BE INDICATED IN THE TITLE | | BLOCK ON EACH PAGE. | | 61G1-16.004 TITLE BLOCK. | | A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR | | INTERIOR DESIGN DRAWINGS AND SPECIFICATION | | IDENTIFICATION SHEETS. THE TITLE BLOCK MUST, AT A | | MINIMUM, CONTAIN THE FOLLOWING INFORMATION: | | (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER. | | (2) FIRM LICENSE NUMBER. | | (3) NAME OR IDENTIFICATION OF PROJECT. | | (4) DATE PREPARED. | | (5) A SPACE FOR THE SIGNATURE AND DATED SEAL. | | (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING | | THE DOCUMENT. | | | | 4 ) FL S S 713.13 | | NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF | | THE COURT. | | NOTE: 713.13(2) | | IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS | | NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE | | RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: | | 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT | | THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. | | | | 5)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS | | LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS | | AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST | | EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC | | (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES | | PER 108.3 FBC* | | | | NEW***** | | 6)FBC 1210.2 WALLS WITHIN 2 FEET OF UNIRALS AND | | WATER CLOSETS SHALL HAVE A SMOOTH, HARD, NONABSORBENT | | SURFACE, TO A HEIGHT OF 4 FEET ABOVE THE FLOOR, AND | | EXCEPT FOR STRUCTUREAL ELEMENTS, THE MATERIALS USED IN | | SUCH WALLS SHALL BE OF A TYPE THAT IS NOT ADVERSELY | | AFFECTED BY MOISTURE. INDICATE CLEARLY ON THE PLANS THE | | FINISH FOR THE BATHROOM WALLS MEETING THE REQUIREMENTS | | OF THIS SECTION. | | | | MYRON JACOBS | | BUILDING PLAN REVIEWER | | 805-6726 | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2007-04-25 |
|
|
Cont ID |
|
Sent By |
mjacobs |
Date |
2007-04-25 |
Time |
06:26 |
Rev Time |
0.00 |
Received By |
mjacobs |
Date |
2007-04-25 |
Time |
05:35 |
Sent To |
|
|
Notes |
2007-04-25 06:26:26 | BUILDING PLAN REVIEW | | PERMIT: 07040689 | | ADD: 2235 OKEECHOBEE BLVD | | CONT: BENCHMARK III CORP | | TEL: (561)744-8686 | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | W/ 2006 FBC REVISIONS | | * WEST PALM BEACH AMENDMENTS | | | | REVIEW 1ST | | ACTION: DENIED | | | | 1)THE DRAWINGS SHALL SHOW COMPLIANCE WITH SECTIONS | | 11-4.22.2 DOORS.(1)ALL DOORS TO ACCESSIBLE TOILET | | ROOMS SHALL COMPLY WITH SECTION 11-4.13 . DOORS SHALL | | NOT SWING INTO THE CLEAR FLOOR SPACE REQUIRED FOR ANY | | FIXTURE. SEE SECTIONS 11-422.3 -11-4.22.7. | | | | 2)11-4.26.1ALL HANDRAILS, GRAB BARS, AND TUB AND | | SHOWER SEATS REQUIRED TO BE ACCESSIBLE BY SECTION | | 11-4.1 , 11-4.8 , 11-4.9 , 11-4.16 , 11-4.17 , 11-4.20 | | OR 11-4.21 SHALL COMPLY WITH SECTION 11-4.26 . INDICATE | | THE TYPE OF BACKING WHICH WILL MEET THE 250LB BENDING | | MOMENT REQUIREMENT STATED IN SECTION(11-4.26.3). | | | | 3) THE CERTIFICATE OF AUTHORIZATION NUMBER OF ARCHITECT | | AND ASSOCIATES, P.A.SHALL BE INDICATED IN THE TITLE | | BLOCK ON EACH PAGE. | | 61G1-16.004 TITLE BLOCK. | | A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR | | INTERIOR DESIGN DRAWINGS AND SPECIFICATION | | IDENTIFICATION SHEETS. THE TITLE BLOCK MUST, AT A | | MINIMUM, CONTAIN THE FOLLOWING INFORMATION: | | (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER. | | (2) FIRM LICENSE NUMBER. | | (3) NAME OR IDENTIFICATION OF PROJECT. | | (4) DATE PREPARED. | | (5) A SPACE FOR THE SIGNATURE AND DATED SEAL. | | (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING | | THE DOCUMENT. | | | | 4 ) FL S S 713.13 | | NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF | | THE COURT. | | NOTE: 713.13(2) | | IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS | | NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE | | RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: | | 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT | | THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. | | | | 5)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS | | LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS | | AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST | | EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC | | (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES | | PER 108.3 FBC* | | | | MYRON JACOBS | | BUILDING PLAN REVIEWER | | 805-6726 | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
5 |
Status |
P |
Date |
2007-09-11 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-09-11 |
Time |
09:55 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-09-11 |
Time |
09:55 |
Sent To |
PC |
|
Notes |
2007-09-11 09:56:45 | NEW SHEET SUBMITTED TO COMPLETE SECOND SET. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
F |
Date |
2007-09-07 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-09-07 |
Time |
16:58 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-09-07 |
Time |
16:22 |
Sent To |
PC |
|
Notes |
2007-09-07 17:04:00 | *** PLANS IN TEMP FAILED STATUS AS ONLY ONE REVISED | | SHEET A-3 WAS SUBMITTED. CALLED AND SPOKE WITH THE | | ARCHITECT AND GREG FROM BENCHMARK. WILL BRING IN NEW | | SHEET ON MONDAY 9/10. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
F |
Date |
2007-08-23 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-08-23 |
Time |
18:02 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-08-23 |
Time |
17:17 |
Sent To |
|
|
Notes |
2007-08-23 18:02:20 | | | *** DENIED 3RD REVIEW *** | | | | ** PLEASE SEE THERE ARE SUBSTANTIAL NEW COMMENTS. THIS | | IS THE FIRST REVIEW OF MANY ITEMS WHICH ARE NOW ON | | PLANS WHICH WERE NOT ON PLANS PREVIOUSLY SUBMITTED. | | PLEASE SEE THIS IS THE FIRST TIME THAT A PANEL | | SCHEDULE, LOAD CALCULATIONS AND RISER HAVE BEEN | | SUBMITTED FOR REVIEW CREATING SEVERAL NEW COMMENTS. | | | | 1) NOTE: PLEASE SEE THE NEW PANEL WHICH SEEMS TO BE | | REPLACING THE EXISTING PANEL DOES NOT CORRELATE WITH | | RISER OR LOAD CALCULATIONS. | | PLEASE SEE MANY OF THE FOLLOWING ITEMS WHICH ARE NOT | | CODE COMPLIANT. | | A) PLEASE SEE THE RISER SHOWS THIS AS AN EXISTING | | 3-PHASE PANEL AND FEEDERS YET THE NEW PANEL IS SHOWN AS | | A 1-PHASE PANEL? | | B) PLEASE SEE NO OVER CURRENT PROTECTION IN THE | | EXISTING MAIN IS BEING SHOWN ON THE RISER FOR NEW | | PANEL. THIS WAS REQUESTED ON THE TWO PREVIOUS REVIEWS | | AND THE INFORMATION SUBMITTED IS NOT COMPLETE. ONLY | | SHOWS 2/0 FOR FEEDERS AND BEING 3-PHASE YET AGAIN NEW | | PANEL IS 1-PHASE. | | C) PLEASE SEE THE VOLTAGE OF THE PANEL IS BEING SHOWN | | AS 120/240 YET THE LOAD CALCULATIONS INDICATES THIS | | SERVICE AND CALCULATIONS AS 120/208V? | | D) PLEASE SEE THERE A NUMEROUS BREAKERS ON THE PANEL | | SCHEDULE WHICH ARE SHOWN AS 2-POLE BREAKERS FEEDING | | SINGLE POLE CIRCUITS WHICH CAN NOT BE POSSIBLE. PLEASE | | SEE THERE ARE 2-POLE CIRCUITS SHOWN FOR THREE POLE | | SPACES. PLEASE SEE THERE ARE THREE POLE SPACES WITH TWO | | POLES CIRCUIT BREAKERS. | | *** NONE OF THESE THINGS CORRELATE AND IT IS NOT | | POSSIBLE. PLEASE CORRELATE ALL BREAKERS AND CIRCUITS. | | PLEASE BE SURE TO CORRECTLY INDICATE IF THESE ARE | | 1-POLE, 2-POLEPR 3-POLE DEPENDING ON THE CIRCUIT AND | | WHETHER OR NOT PANEL IS SINGLE PHASE OR THREE PHASE. | | PLEASE BE SURE ALL SPACES IN PANEL CORRELATE WITH THE | | PHASES AND SPACE EACH BREAKER WILL TAKE. | | 408.4. | | E) PLEASE SEE RISER INDICATES PANEL AS 150AMP YET PANEL | | IS BEING SHOWN AS 225AMP. IS THE EXISTING 150AMP AND | | THE NEW ONE WILL BE 225AMP? | | F) PLEASE SEE 110.14 AND 310.16 AS 2/0 CONDUCTORS ARE | | NOT RATED FOR 200 OR 225AMP OCP. PLEASE KNOW YOU MAY | | ONLY USE THE 75 DEGREE COLUMN IN THE NEC UNLESS LUGS | | ARE 90 DEGREE RATED. (MOST EQUIPMENT IS 75, SPECIAL | | ORDER FOR 90 ONLY) | | | | 2) NOTE: PLEASE SUBMIT LOAD CALCULATIONS WHICH MEET THE | | MINIMUM AS REQUIRED PER THE NEC 220. | | PLEASE SEE THE LOADS SHOWN FOR THE A/C EXCEED THE | | BRANCH CIRCUIT RATING OF THE BREAKERS AND | | CONDUCTORS.240.4, 310.16 ( THIS IS BASED ON THESE BEING | | SHOWN IN A SINGLE PHASE PANEL. THIS MAY BE OK, IF | | INDEED THIS IS A THREE PHASE PANEL AND SERVICE. | | PLEASE SHOW ALL CONTINUOUS LOADS AT 125% AS REQUIRED | | PER 215.3, 230.42 ETC. (LIGHTING). | | PLEASE SEE 422.13 AS THE MINIMUM LOAD FOR WATER HEATERS | | ARE REQUIRED TO BE FIGURED AND SHOWN AT 125%. | | PLEASE SEE 220.87 | | | | 3) NOTE: PLEASE SEE NOW THAT PANEL HAS MOVED WHICH IT | | WAS SHOWN ON PREVIOUS PLANS IN CLOSET, THE PLANS ARE | | NOW MISSING THE REQUIRED WATER HEATER DISCONNECT PER | | 422.31. | | | | 4) NOTE: GFI REQUIRED FOR BATH ROOM RECEPTACLES | | 210.8B1 | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2007-07-11 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-07-11 |
Time |
16:15 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-07-11 |
Time |
15:26 |
Sent To |
|
|
Notes |
2007-07-11 16:16:15 | | | | | **** UNSAT 2ND REVIEW **** | | | | ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL | | IN NEED OF ADDRESSING ALONG WITH SOME NEW NOTES BASED | | ON PLANS AND INFORMATION SHOWN. | | | | 1) NOTE: PLEASE SEE TITLE BLOCKS ARE MISSING THE FIRM | | LICENSE NUMBER ALSO KNOWN AS THE CERTIFICATE OF | | AUTHORIZATION NUMBER. | | FAC 61G1-16.002, FS 481.219. | | | | 2) NOTE:PLEASE SEE NOT ALL CIRCUITING IS SHOWN ON | | PLANS AS PREVIOUSLY REQUESTED. PLEASE SEE THERE NOW AN | | INDICATION OF A NEW PANEL WITH NUMEROUS CIRCUITS WHICH | | ARE NOT ON PLANS? | | PLEASE SEE 700.12F FOR CIRCUITING OF EMERGENCY AND EXIT | | LIGHTS. | | FBC 106.1.2, 106.3.5.1.2 | | NEC 408.4, 240.4, 310.16 | | | | 3) NOTE: PLEASE SEE NO CONTROLS FOR LIGHTING WAS | | SUBMITTED WITH COMPLIANCE TO THE FBC CHAPTER 13 AS | | PREVIOUSLY GIVEN. | | REVIEW OF THESE CAN NOT BE DONE AT THIS TIME AS NONE | | ARE SHOWN. | | PLEASE SEE 13-415.1.ABC.1.1, .1.2, AND .1.3. PLEASE SEE | | 13-415.2 | | PLEASE INDICATE DEVICES, TYPES FOR COVERAGE, MAXIMUM | | TIMES ON DEVICES ETC. | | | | 4) NOTE: PLEASE SEE THE LOCATION OF THE PANEL AS SHOWN | | IS NOT PERMITTED. 408.7, 110.26, 240.24 ETC. | | | | 5) NOTE: PLEASE SEE NO INFORMATION FOR THIS NEW PANEL | | WAS SHOWN ON HOW AND WHERE THIS PANEL IS FED. | | PLEASE SEE NO RISER DIAGRAM, WIRING, CONDUCTORS ETC ON | | WHERE THIS NEW PANEL IS FED. | | PLEASE SEE NO LOAD CALCULATIONS WERE SUBMITTED | | INDICATING ANY NEW LOADS FOR THIS PANEL WHICH IS BEING | | ADDED TO THE EXISTING ELECTRICAL SERVICE? | | PLEASE SEE 215.5, 220, 240, 310.16, 240.4 ETC. | | | | | | ** IMPORTANT** | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | PICKED UP FOR CORRECTIONS, PLEASE BE | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | AND STAMPING. DO NOT LEAVE ANY | | OLD/VOIDED SHEETS IN SETS. | | PLEASE KNOW ONLY ONE SET OF THE | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | FOR REFERENCE. | | THIS WILL HELP IN THE REVIEW PROCESS AND | | AVOID ANY DELAYS. | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | REVIEWER. | | | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2007-04-27 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-04-27 |
Time |
09:24 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-04-27 |
Time |
08:56 |
Sent To |
|
|
Notes |
2007-04-27 09:24:18 | ** UNSAT ** | | | | ** PLEASE SEE THAT ANY REFERENCES TO THE FBC CHAPTER 1 | | ARE FROM THE ADMINISTRATIVE CODE ADOPTED BY THE CITY OF | | WEST PALM BEACH. | | | | | | 1) NOTE: PLEASE SEE MISSING CIRCUITING FOR NEW | | ELECTRICAL WHICH IS TO BE SHOWN. PLEASE CORRELATE WITH | | A PANEL SCHEDULE TO BE SUBMITTED. | | PLEASE INCLUDE CONDUCTOR SIZES ALONG WITH OVER CURRENT | | PROTECTION DEVICES. | | FBC 106.3.5.1.2 | | 408.4, 310.16, 240.4 | | | | 2) NOTE: PLEASE SEE THE LOCATION OF THE NEW ELECTRICAL | | PANEL DOES NOT MEET 110.26, 408.7, 240.24 OF THE NEC | | FOR MINIMUM CLEARANCES, VICINITY OF EASILY IGNITABLE | | MATERIALS ETC. | | PLEASE RELOCATE. | | | | 3) NOTE: PLEASE KNOW DEPENDING ON THE LOCATION OF THE | | NEW PANEL, A DISCONNECT MAY BE REQUIRED FOR THE WATER | | HEATER. | | 422.31 | | | | 4) NOTE: PLEASE PROVIDE LIGHTING ON PLANS AND | | CONTROLS. | | PLEASE SEE LS 101 7.8, AND 7.9 AS AN EMERGENCY BATTERY | | BACK UP LIGHT OF SOME KIND WILL BE REQUIRED. | | | | 5) NOTE: PLEASE SEE 13-415.1.ABC.1.1, .1.2,OF THE | | 2004 FBC W/2006 REVISIONS. | | | | | | 6) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS | | WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES | | PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE. | | PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO | | THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. | | PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY | | AFFECT DESIGNS FOR ALL TRADES. | | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS | | REVIEWER AT A MINIMUM. | | 2004 FBC W/ 2006 REVISIONS | | 2005 NFPA-70 | | 2002 NFPA-72 | | 2003 NFPA-101 | | | | ** IMPORTANT** | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | PICKED UP FOR CORRECTIONS, PLEASE BE | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | AND STAMPING. DO NOT LEAVE ANY | | OLD/VOIDED SHEETS IN SETS. | | PLEASE KNOW ONLY ONE SET OF THE | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | FOR REFERENCE. | | THIS WILL HELP IN THE REVIEW PROCESS AND | | AVOID ANY DELAYS. | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2007-08-28 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2007-08-28 |
Time |
21:35 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2007-08-28 |
Time |
18:40 |
Sent To |
|
|
Notes |
2007-08-28 22:10:50 | *****APPROVED***** | | | | | | ALL COMMENTS FROM THE PREVIOUS PLAN REVIEW HAVE BEEN | | ADDRESSED;THE APPROPIATE PLAN SHEET(S) TO BE | | FIRE-STAMPED WHEN ALL REVIEWERS HAVE BEEN SATISFIED. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
F |
Date |
2007-07-25 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2007-07-25 |
Time |
12:10 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2007-07-25 |
Time |
11:41 |
Sent To |
|
|
Notes |
2007-07-25 12:08:20 | *****UNSAT***** | | THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE | | PLAN REVIEW STILL NEED TO BE ADDRESSED.THE COMBINED | | RESPONSE AS NOTED ON SHEET A-1 IS INCORRECT.PLEASE BE | | ADVISED THAT ITEM #3 IS ALIFE SAFETY CODE (NFPA 101) | | OR A UNIFORM FIRE CODE (NFPA 1) NOT PER NFPA 241. | | | | | | 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | 3.ALL EXIT COMPONENTS SHALL BE MAINTAINED BEFORE, | | DURING, AND AFTER THE SCOPE OF WORK. | | | | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2007-05-07 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2007-05-07 |
Time |
12:56 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2007-05-07 |
Time |
12:43 |
Sent To |
|
|
Notes |
2007-05-07 12:55:50 | *****UNSAT***** | | | | | | 1.THE COMPLETE ADDRESS OF WHERE THE SCOPE OF WORK IS | | TO BE CONDUCTED SHALL BE IN THE TITLE BLOCK OF EACH | | SUBMITTED PLAN SHEET. | | | | 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | 3.ALL EXIT COMPONENTS SHALL BE MAINTAINED BEFORE, | | DURING, AND AFTER THE SCOPE OF WORK. | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2007-09-24 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-09-24 |
Time |
14:10 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-09-24 |
Time |
14:10 |
Sent To |
P |
|
Notes |
2007-09-24 14:10:43 | TO "JLEECH" DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2007-09-06 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-09-06 |
Time |
16:31 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-09-06 |
Time |
16:31 |
Sent To |
E |
|
Notes |
2007-09-06 16:31:50 | TO "DPALMER" DESK/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2007-08-13 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-08-13 |
Time |
10:43 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-08-13 |
Time |
10:43 |
Sent To |
|
|
Notes |
2007-08-23 13:27:12 | TO "BOB"#15 | 2007-08-13 10:43:20 | WAITING FOR "BOB" |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2007-07-05 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-07-05 |
Time |
10:36 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-07-05 |
Time |
10:36 |
Sent To |
|
|
Notes |
2007-07-10 14:04:44 | TO "BOB"#7 | 2007-07-05 10:38:55 | WAITING FOR "BOB" |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2007-05-07 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2007-05-07 |
Time |
12:43 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2007-04-20 |
Time |
10:30 |
Sent To |
|
|
Notes |
2007-04-20 10:32:41 | TO "BOB"#2 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2007-08-24 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2007-08-24 |
Time |
10:02 |
Rev Time |
0.20 |
Received By |
tgordon |
Date |
2007-08-24 |
Time |
10:02 |
Sent To |
|
|
Notes |
2007-08-24 10:02:51 | THREE BATHROOM EXHAUST FANS ONLY. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2007-07-11 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2007-07-11 |
Time |
13:40 |
Rev Time |
0.25 |
Received By |
tgordon |
Date |
2007-07-11 |
Time |
13:40 |
Sent To |
|
|
Notes |
2007-07-11 13:54:26 | *** DENIED *** | | 1) AS NOTED IN LAST REVIEW 4-30-07 NOTE #2.ARCHITECT | | BUSINESS LICENSE NUMBER AAC001630 MUST APPEAR IN THE | | TITLE BLOCK, SEE FAC 61G1-16.003 (2). | | | | 2) WOMEN EMPLOYEES RESTROOM REQUIRES THE EXHAUST FAN TO | | BE 100 CFM'S, THE MEN'S ROOM TO BE 150 CFM'S, AND THE | | WOMEN CUSTOMERS TO BE 100 CFM'S. SEE 2004 FBC/M TABLE | | 403.3. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2007-04-30 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2007-04-30 |
Time |
13:54 |
Rev Time |
0.20 |
Received By |
tgordon |
Date |
2007-04-30 |
Time |
13:54 |
Sent To |
|
|
Notes |
2007-04-30 14:04:27 | *** DENIED *** | | 1) PLEASE SHOW ON PAGE THREE, CFM'S OF EXHAUST FANS AND | | IF NEW OR EXISTING. | | | | 2) INFORMATION MISSING IN TITLE BLOCK FOR ARCHITECT, | | FIRM'S LICENSE NUMBER,SEE FAC 61G1-16.004 TITLE | | BLOCK. | | A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR | | INTERIOR DESIGN DRAWINGS AND SPECIFICATION | | IDENTIFICATION SHEETS. THE TITLE BLOCK MUST, AT A | | MINIMUM, CONTAIN THE FOLLOWING INFORMATION: | | (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER. | | (2) FIRM LICENSE NUMBER. | | (3) NAME OR IDENTIFICATION OF PROJECT. ("JOB | | ADDRESS" SEE CITY WPB AMEND. 106.1.1). | | (4) DATE PREPARED. | | (5) A SPACE FOR THE SIGNATURE AND DATED SEAL. | | (6) A SPACE FOR THE PRINTED NAME OF THE PERSON | | SEALING THE DOCUMENT. | | | | 3) PLEASE SHOW JOB ADDRESS "2235" IN TITLE BLOCK SEE | | (3) ABOVE. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
4 |
Status |
P |
Date |
2007-10-25 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2007-10-25 |
Time |
07:46 |
Rev Time |
0.00 |
Received By |
jleech |
Date |
2007-10-25 |
Time |
07:46 |
Sent To |
|
|
Notes |
2007-10-25 07:48:26 | PLUMBING AS-BUILT SANITARY RISER DIAGRAM |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2007-09-04 |
|
|
Cont ID |
|
Sent By |
mperson |
Date |
2007-09-04 |
Time |
11:00 |
Rev Time |
0.00 |
Received By |
mperson |
Date |
2007-09-04 |
Time |
11:00 |
Sent To |
PC |
|
Notes |
2007-09-04 11:08:20 | ****************PROVISO**************** | | PER FBC-2004 CHAPTER 11, FLORIDA ACCESSIBILITY CODE | | SECTION 11-4.18.4, FLUSH CONTROLS SHALL BE HAND | | OPERATED OR AUTOMATIC, AND SHALL COMPLY WITH SECTION | | 11-4.27.4 AND SHALL BE MOUNTED NO MORE THAN 44 INCHES | | ABOVE THE FINNISH FLOOR. | | | | REVIEW BY MIKE PERSON | | PLUMBING PLANS EXAMINER | | (561) 805-6730 | | FAX (561) 805-6731 | | E-MAIL= [email protected] | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2007-07-24 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2007-07-24 |
Time |
10:17 |
Rev Time |
0.00 |
Received By |
jleech |
Date |
2007-07-24 |
Time |
10:15 |
Sent To |
|
|
Notes |
2007-07-24 10:28:32 | DENIED; | | 1.( SECOND REQUEST) WATER AND SANITARY DIAGRAM | | REQUIRED. SEE FBC-2004 WPB AMENDMENTS TO CHAPTER 1, | | ADMINISTRATION CODE SECTION 106.3.5.1.3(13). | | 2. ONE URINAL IS REQUIRED TO BE HANDICAP COMPLIANT SHOW | | DETAIL ON PLANS. | | 3. LIST PLUMBING FIXTURES TO BE USED ON A FIXTURE | | SCHEDULE. ( SECOND REQUEST) | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 805-6695 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2007-05-01 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2007-05-01 |
Time |
07:14 |
Rev Time |
0.00 |
Received By |
jleech |
Date |
2007-05-01 |
Time |
07:10 |
Sent To |
|
|
Notes |
2007-05-01 07:29:13 | DENIED; | | 1. SHOW TURNING RADIUS IN HANDICAP STALL AND CLEAR | | FLOOR SPACE, (LAV IN WOMANS CUSTOMERS BATHROOM BY | | DOOR). | | 2. SANITARY AND WATER RISER REQUIRED. SEE FBC-2004 WPB | | AMENDMENTS TO CHAPTER 1, ADMINISTRATION CODE SECTION | | 106.3.5.1.3. | | 3. PAGE A-2 SHOWS 3 DIFFERENT TYPE OF TOILETS, PLEASE | | SPEC OUT THE TOILETS TO BE USED. SHOW A FIXTURE | | SCHEDULE ON PLANS. | | PLUMBING PLAN REVIEW BY | | JOHN LEECH | | 805-6695 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
N |
Date |
2007-07-23 |
|
|
Cont ID |
|
Sent By |
choops |
Date |
2007-07-23 |
Time |
17:37 |
Rev Time |
0.00 |
Received By |
choops |
Date |
2007-07-23 |
Time |
17:37 |
Sent To |
|
|
Notes |
2007-07-23 17:37:32 | *VALUE OF PROPOSED WORK DOES NOT EXCEED 50% OF THE | | IMPROVEMENT VALUE. |
|
|