Plan Review Details - Permit 07040689
Plan Review Stops For Permit 07040689
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-08-30 Cont ID  
Sent By mjacobs Date 2007-08-30 Time 07:52 Rev Time 0.00
Received By mjacobs Date 2007-08-30 Time 07:17 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-07-19 Cont ID  
Sent By mjacobs Date 2007-07-19 Time 15:19 Rev Time 0.00
Received By mjacobs Date 2007-07-19 Time 12:29 Sent To PC
Notes
2007-07-19 14:39:53BUILDING PLAN REVIEW
 PERMIT: 07040689
 ADD:2235 OKEECHOBEE BLVD
 CONT: BENCHMARK III CORP
 TEL: (561)744-8686
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 2ND
 ACTION: DENIED
  
 1)OK
  
 2)11-4.26.1ALL HANDRAILS, GRAB BARS, AND TUB AND
 SHOWER SEATS REQUIRED TO BE ACCESSIBLE BY SECTION
 11-4.1 , 11-4.8 , 11-4.9 , 11-4.16 , 11-4.17 , 11-4.20
 OR 11-4.21 SHALL COMPLY WITH SECTION 11-4.26 . INDICATE
 THE TYPE OF BACKING WHICH WILL MEET THE 250LB BENDING
 MOMENT REQUIREMENT STATED IN SECTION(11-4.26.3).
  
 3) THE CERTIFICATE OF AUTHORIZATION NUMBER OF ARCHITECT
 AND ASSOCIATES, P.A.SHALL BE INDICATED IN THE TITLE
 BLOCK ON EACH PAGE.
 61G1-16.004 TITLE BLOCK.
 A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR
 INTERIOR DESIGN DRAWINGS AND SPECIFICATION
 IDENTIFICATION SHEETS. THE TITLE BLOCK MUST, AT A
 MINIMUM, CONTAIN THE FOLLOWING INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER.
 (2) FIRM LICENSE NUMBER.
 (3) NAME OR IDENTIFICATION OF PROJECT.
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED SEAL.
 (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING
 THE DOCUMENT.
  
 4 ) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE
 RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE:
 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT
 THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 5)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC
 (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 PER 108.3 FBC*
  
 NEW*****
 6)FBC 1210.2 WALLS WITHIN 2 FEET OF UNIRALS AND
 WATER CLOSETS SHALL HAVE A SMOOTH, HARD, NONABSORBENT
 SURFACE, TO A HEIGHT OF 4 FEET ABOVE THE FLOOR, AND
 EXCEPT FOR STRUCTUREAL ELEMENTS, THE MATERIALS USED IN
 SUCH WALLS SHALL BE OF A TYPE THAT IS NOT ADVERSELY
 AFFECTED BY MOISTURE. INDICATE CLEARLY ON THE PLANS THE
 FINISH FOR THE BATHROOM WALLS MEETING THE REQUIREMENTS
 OF THIS SECTION.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-04-25 Cont ID  
Sent By mjacobs Date 2007-04-25 Time 06:26 Rev Time 0.00
Received By mjacobs Date 2007-04-25 Time 05:35 Sent To  
Notes
2007-04-25 06:26:26BUILDING PLAN REVIEW
 PERMIT: 07040689
 ADD: 2235 OKEECHOBEE BLVD
 CONT: BENCHMARK III CORP
 TEL: (561)744-8686
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST
 ACTION: DENIED
  
 1)THE DRAWINGS SHALL SHOW COMPLIANCE WITH SECTIONS
 11-4.22.2 DOORS.(1)ALL DOORS TO ACCESSIBLE TOILET
 ROOMS SHALL COMPLY WITH SECTION 11-4.13 . DOORS SHALL
 NOT SWING INTO THE CLEAR FLOOR SPACE REQUIRED FOR ANY
 FIXTURE. SEE SECTIONS 11-422.3 -11-4.22.7.
  
 2)11-4.26.1ALL HANDRAILS, GRAB BARS, AND TUB AND
 SHOWER SEATS REQUIRED TO BE ACCESSIBLE BY SECTION
 11-4.1 , 11-4.8 , 11-4.9 , 11-4.16 , 11-4.17 , 11-4.20
 OR 11-4.21 SHALL COMPLY WITH SECTION 11-4.26 . INDICATE
 THE TYPE OF BACKING WHICH WILL MEET THE 250LB BENDING
 MOMENT REQUIREMENT STATED IN SECTION(11-4.26.3).
  
 3) THE CERTIFICATE OF AUTHORIZATION NUMBER OF ARCHITECT
 AND ASSOCIATES, P.A.SHALL BE INDICATED IN THE TITLE
 BLOCK ON EACH PAGE.
 61G1-16.004 TITLE BLOCK.
 A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR
 INTERIOR DESIGN DRAWINGS AND SPECIFICATION
 IDENTIFICATION SHEETS. THE TITLE BLOCK MUST, AT A
 MINIMUM, CONTAIN THE FOLLOWING INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER.
 (2) FIRM LICENSE NUMBER.
 (3) NAME OR IDENTIFICATION OF PROJECT.
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED SEAL.
 (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING
 THE DOCUMENT.
  
 4 ) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE
 RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE:
 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT
 THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 5)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC
 (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 PER 108.3 FBC*
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2007-09-11 Cont ID  
Sent By dpalmer Date 2007-09-11 Time 09:55 Rev Time 0.00
Received By dpalmer Date 2007-09-11 Time 09:55 Sent To PC
Notes
2007-09-11 09:56:45NEW SHEET SUBMITTED TO COMPLETE SECOND SET.

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2007-09-07 Cont ID  
Sent By dpalmer Date 2007-09-07 Time 16:58 Rev Time 0.00
Received By dpalmer Date 2007-09-07 Time 16:22 Sent To PC
Notes
2007-09-07 17:04:00*** PLANS IN TEMP FAILED STATUS AS ONLY ONE REVISED
 SHEET A-3 WAS SUBMITTED. CALLED AND SPOKE WITH THE
 ARCHITECT AND GREG FROM BENCHMARK. WILL BRING IN NEW
 SHEET ON MONDAY 9/10.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-08-23 Cont ID  
Sent By dpalmer Date 2007-08-23 Time 18:02 Rev Time 0.00
Received By dpalmer Date 2007-08-23 Time 17:17 Sent To  
Notes
2007-08-23 18:02:20 
 *** DENIED 3RD REVIEW ***
  
 ** PLEASE SEE THERE ARE SUBSTANTIAL NEW COMMENTS. THIS
 IS THE FIRST REVIEW OF MANY ITEMS WHICH ARE NOW ON
 PLANS WHICH WERE NOT ON PLANS PREVIOUSLY SUBMITTED.
 PLEASE SEE THIS IS THE FIRST TIME THAT A PANEL
 SCHEDULE, LOAD CALCULATIONS AND RISER HAVE BEEN
 SUBMITTED FOR REVIEW CREATING SEVERAL NEW COMMENTS.
  
 1) NOTE: PLEASE SEE THE NEW PANEL WHICH SEEMS TO BE
 REPLACING THE EXISTING PANEL DOES NOT CORRELATE WITH
 RISER OR LOAD CALCULATIONS.
 PLEASE SEE MANY OF THE FOLLOWING ITEMS WHICH ARE NOT
 CODE COMPLIANT.
 A) PLEASE SEE THE RISER SHOWS THIS AS AN EXISTING
 3-PHASE PANEL AND FEEDERS YET THE NEW PANEL IS SHOWN AS
 A 1-PHASE PANEL?
 B) PLEASE SEE NO OVER CURRENT PROTECTION IN THE
 EXISTING MAIN IS BEING SHOWN ON THE RISER FOR NEW
 PANEL. THIS WAS REQUESTED ON THE TWO PREVIOUS REVIEWS
 AND THE INFORMATION SUBMITTED IS NOT COMPLETE. ONLY
 SHOWS 2/0 FOR FEEDERS AND BEING 3-PHASE YET AGAIN NEW
 PANEL IS 1-PHASE.
 C) PLEASE SEE THE VOLTAGE OF THE PANEL IS BEING SHOWN
 AS 120/240 YET THE LOAD CALCULATIONS INDICATES THIS
 SERVICE AND CALCULATIONS AS 120/208V?
 D) PLEASE SEE THERE A NUMEROUS BREAKERS ON THE PANEL
 SCHEDULE WHICH ARE SHOWN AS 2-POLE BREAKERS FEEDING
 SINGLE POLE CIRCUITS WHICH CAN NOT BE POSSIBLE. PLEASE
 SEE THERE ARE 2-POLE CIRCUITS SHOWN FOR THREE POLE
 SPACES. PLEASE SEE THERE ARE THREE POLE SPACES WITH TWO
 POLES CIRCUIT BREAKERS.
 *** NONE OF THESE THINGS CORRELATE AND IT IS NOT
 POSSIBLE. PLEASE CORRELATE ALL BREAKERS AND CIRCUITS.
 PLEASE BE SURE TO CORRECTLY INDICATE IF THESE ARE
 1-POLE, 2-POLEPR 3-POLE DEPENDING ON THE CIRCUIT AND
 WHETHER OR NOT PANEL IS SINGLE PHASE OR THREE PHASE.
 PLEASE BE SURE ALL SPACES IN PANEL CORRELATE WITH THE
 PHASES AND SPACE EACH BREAKER WILL TAKE.
 408.4.
 E) PLEASE SEE RISER INDICATES PANEL AS 150AMP YET PANEL
 IS BEING SHOWN AS 225AMP. IS THE EXISTING 150AMP AND
 THE NEW ONE WILL BE 225AMP?
 F) PLEASE SEE 110.14 AND 310.16 AS 2/0 CONDUCTORS ARE
 NOT RATED FOR 200 OR 225AMP OCP. PLEASE KNOW YOU MAY
 ONLY USE THE 75 DEGREE COLUMN IN THE NEC UNLESS LUGS
 ARE 90 DEGREE RATED. (MOST EQUIPMENT IS 75, SPECIAL
 ORDER FOR 90 ONLY)
  
 2) NOTE: PLEASE SUBMIT LOAD CALCULATIONS WHICH MEET THE
 MINIMUM AS REQUIRED PER THE NEC 220.
 PLEASE SEE THE LOADS SHOWN FOR THE A/C EXCEED THE
 BRANCH CIRCUIT RATING OF THE BREAKERS AND
 CONDUCTORS.240.4, 310.16 ( THIS IS BASED ON THESE BEING
 SHOWN IN A SINGLE PHASE PANEL. THIS MAY BE OK, IF
 INDEED THIS IS A THREE PHASE PANEL AND SERVICE.
 PLEASE SHOW ALL CONTINUOUS LOADS AT 125% AS REQUIRED
 PER 215.3, 230.42 ETC. (LIGHTING).
 PLEASE SEE 422.13 AS THE MINIMUM LOAD FOR WATER HEATERS
 ARE REQUIRED TO BE FIGURED AND SHOWN AT 125%.
 PLEASE SEE 220.87
  
 3) NOTE: PLEASE SEE NOW THAT PANEL HAS MOVED WHICH IT
 WAS SHOWN ON PREVIOUS PLANS IN CLOSET, THE PLANS ARE
 NOW MISSING THE REQUIRED WATER HEATER DISCONNECT PER
 422.31.
  
 4) NOTE: GFI REQUIRED FOR BATH ROOM RECEPTACLES
 210.8B1
  
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-07-11 Cont ID  
Sent By dpalmer Date 2007-07-11 Time 16:15 Rev Time 0.00
Received By dpalmer Date 2007-07-11 Time 15:26 Sent To  
Notes
2007-07-11 16:16:15 
  
 **** UNSAT 2ND REVIEW ****
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING ALONG WITH SOME NEW NOTES BASED
 ON PLANS AND INFORMATION SHOWN.
  
 1) NOTE: PLEASE SEE TITLE BLOCKS ARE MISSING THE FIRM
 LICENSE NUMBER ALSO KNOWN AS THE CERTIFICATE OF
 AUTHORIZATION NUMBER.
 FAC 61G1-16.002, FS 481.219.
  
 2) NOTE:PLEASE SEE NOT ALL CIRCUITING IS SHOWN ON
 PLANS AS PREVIOUSLY REQUESTED. PLEASE SEE THERE NOW AN
 INDICATION OF A NEW PANEL WITH NUMEROUS CIRCUITS WHICH
 ARE NOT ON PLANS?
 PLEASE SEE 700.12F FOR CIRCUITING OF EMERGENCY AND EXIT
 LIGHTS.
 FBC 106.1.2, 106.3.5.1.2
 NEC 408.4, 240.4, 310.16
  
 3) NOTE: PLEASE SEE NO CONTROLS FOR LIGHTING WAS
 SUBMITTED WITH COMPLIANCE TO THE FBC CHAPTER 13 AS
 PREVIOUSLY GIVEN.
 REVIEW OF THESE CAN NOT BE DONE AT THIS TIME AS NONE
 ARE SHOWN.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2, AND .1.3. PLEASE SEE
 13-415.2
 PLEASE INDICATE DEVICES, TYPES FOR COVERAGE, MAXIMUM
 TIMES ON DEVICES ETC.
  
 4) NOTE: PLEASE SEE THE LOCATION OF THE PANEL AS SHOWN
 IS NOT PERMITTED. 408.7, 110.26, 240.24 ETC.
  
 5) NOTE: PLEASE SEE NO INFORMATION FOR THIS NEW PANEL
 WAS SHOWN ON HOW AND WHERE THIS PANEL IS FED.
 PLEASE SEE NO RISER DIAGRAM, WIRING, CONDUCTORS ETC ON
 WHERE THIS NEW PANEL IS FED.
 PLEASE SEE NO LOAD CALCULATIONS WERE SUBMITTED
 INDICATING ANY NEW LOADS FOR THIS PANEL WHICH IS BEING
 ADDED TO THE EXISTING ELECTRICAL SERVICE?
 PLEASE SEE 215.5, 220, 240, 310.16, 240.4 ETC.
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-04-27 Cont ID  
Sent By dpalmer Date 2007-04-27 Time 09:24 Rev Time 0.00
Received By dpalmer Date 2007-04-27 Time 08:56 Sent To  
Notes
2007-04-27 09:24:18** UNSAT **
  
 ** PLEASE SEE THAT ANY REFERENCES TO THE FBC CHAPTER 1
 ARE FROM THE ADMINISTRATIVE CODE ADOPTED BY THE CITY OF
 WEST PALM BEACH.
  
  
 1) NOTE: PLEASE SEE MISSING CIRCUITING FOR NEW
 ELECTRICAL WHICH IS TO BE SHOWN. PLEASE CORRELATE WITH
 A PANEL SCHEDULE TO BE SUBMITTED.
 PLEASE INCLUDE CONDUCTOR SIZES ALONG WITH OVER CURRENT
 PROTECTION DEVICES.
 FBC 106.3.5.1.2
 408.4, 310.16, 240.4
  
 2) NOTE: PLEASE SEE THE LOCATION OF THE NEW ELECTRICAL
 PANEL DOES NOT MEET 110.26, 408.7, 240.24 OF THE NEC
 FOR MINIMUM CLEARANCES, VICINITY OF EASILY IGNITABLE
 MATERIALS ETC.
 PLEASE RELOCATE.
  
 3) NOTE: PLEASE KNOW DEPENDING ON THE LOCATION OF THE
 NEW PANEL, A DISCONNECT MAY BE REQUIRED FOR THE WATER
 HEATER.
 422.31
  
 4) NOTE: PLEASE PROVIDE LIGHTING ON PLANS AND
 CONTROLS.
 PLEASE SEE LS 101 7.8, AND 7.9 AS AN EMERGENCY BATTERY
 BACK UP LIGHT OF SOME KIND WILL BE REQUIRED.
  
 5) NOTE: PLEASE SEE 13-415.1.ABC.1.1, .1.2,OF THE
 2004 FBC W/2006 REVISIONS.
  
  
 6) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS
 WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES
 PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-08-28 Cont ID  
Sent By mawillia Date 2007-08-28 Time 21:35 Rev Time 0.00
Received By mawillia Date 2007-08-28 Time 18:40 Sent To  
Notes
2007-08-28 22:10:50*****APPROVED*****
  
  
 ALL COMMENTS FROM THE PREVIOUS PLAN REVIEW HAVE BEEN
 ADDRESSED;THE APPROPIATE PLAN SHEET(S) TO BE
 FIRE-STAMPED WHEN ALL REVIEWERS HAVE BEEN SATISFIED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-07-25 Cont ID  
Sent By mawillia Date 2007-07-25 Time 12:10 Rev Time 0.00
Received By mawillia Date 2007-07-25 Time 11:41 Sent To  
Notes
2007-07-25 12:08:20*****UNSAT*****
 THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE
 PLAN REVIEW STILL NEED TO BE ADDRESSED.THE COMBINED
 RESPONSE AS NOTED ON SHEET A-1 IS INCORRECT.PLEASE BE
 ADVISED THAT ITEM #3 IS ALIFE SAFETY CODE (NFPA 101)
 OR A UNIFORM FIRE CODE (NFPA 1) NOT PER NFPA 241.
  
  
 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3.ALL EXIT COMPONENTS SHALL BE MAINTAINED BEFORE,
 DURING, AND AFTER THE SCOPE OF WORK.
  
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-05-07 Cont ID  
Sent By mawillia Date 2007-05-07 Time 12:56 Rev Time 0.00
Received By mawillia Date 2007-05-07 Time 12:43 Sent To  
Notes
2007-05-07 12:55:50*****UNSAT*****
  
  
 1.THE COMPLETE ADDRESS OF WHERE THE SCOPE OF WORK IS
 TO BE CONDUCTED SHALL BE IN THE TITLE BLOCK OF EACH
 SUBMITTED PLAN SHEET.
  
 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3.ALL EXIT COMPONENTS SHALL BE MAINTAINED BEFORE,
 DURING, AND AFTER THE SCOPE OF WORK.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-09-24 Cont ID  
Sent By adarroug Date 2007-09-24 Time 14:10 Rev Time 0.00
Received By adarroug Date 2007-09-24 Time 14:10 Sent To P
Notes
2007-09-24 14:10:43TO "JLEECH" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-09-06 Cont ID  
Sent By adarroug Date 2007-09-06 Time 16:31 Rev Time 0.00
Received By adarroug Date 2007-09-06 Time 16:31 Sent To E
Notes
2007-09-06 16:31:50TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-08-13 Cont ID  
Sent By adarroug Date 2007-08-13 Time 10:43 Rev Time 0.00
Received By adarroug Date 2007-08-13 Time 10:43 Sent To  
Notes
2007-08-23 13:27:12TO "BOB"#15
2007-08-13 10:43:20WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-07-05 Cont ID  
Sent By adarroug Date 2007-07-05 Time 10:36 Rev Time 0.00
Received By adarroug Date 2007-07-05 Time 10:36 Sent To  
Notes
2007-07-10 14:04:44TO "BOB"#7
2007-07-05 10:38:55WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-05-07 Cont ID  
Sent By mawillia Date 2007-05-07 Time 12:43 Rev Time 0.00
Received By mawillia Date 2007-04-20 Time 10:30 Sent To  
Notes
2007-04-20 10:32:41TO "BOB"#2

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-08-24 Cont ID  
Sent By tgordon Date 2007-08-24 Time 10:02 Rev Time 0.20
Received By tgordon Date 2007-08-24 Time 10:02 Sent To  
Notes
2007-08-24 10:02:51THREE BATHROOM EXHAUST FANS ONLY.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-07-11 Cont ID  
Sent By tgordon Date 2007-07-11 Time 13:40 Rev Time 0.25
Received By tgordon Date 2007-07-11 Time 13:40 Sent To  
Notes
2007-07-11 13:54:26*** DENIED ***
 1) AS NOTED IN LAST REVIEW 4-30-07 NOTE #2.ARCHITECT
 BUSINESS LICENSE NUMBER AAC001630 MUST APPEAR IN THE
 TITLE BLOCK, SEE FAC 61G1-16.003 (2).
  
 2) WOMEN EMPLOYEES RESTROOM REQUIRES THE EXHAUST FAN TO
 BE 100 CFM'S, THE MEN'S ROOM TO BE 150 CFM'S, AND THE
 WOMEN CUSTOMERS TO BE 100 CFM'S. SEE 2004 FBC/M TABLE
 403.3.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-04-30 Cont ID  
Sent By tgordon Date 2007-04-30 Time 13:54 Rev Time 0.20
Received By tgordon Date 2007-04-30 Time 13:54 Sent To  
Notes
2007-04-30 14:04:27*** DENIED ***
 1) PLEASE SHOW ON PAGE THREE, CFM'S OF EXHAUST FANS AND
 IF NEW OR EXISTING.
  
 2) INFORMATION MISSING IN TITLE BLOCK FOR ARCHITECT,
 FIRM'S LICENSE NUMBER,SEE FAC 61G1-16.004 TITLE
 BLOCK.
 A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR
 INTERIOR DESIGN DRAWINGS AND SPECIFICATION
 IDENTIFICATION SHEETS. THE TITLE BLOCK MUST, AT A
 MINIMUM, CONTAIN THE FOLLOWING INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER.
 (2) FIRM LICENSE NUMBER.
 (3) NAME OR IDENTIFICATION OF PROJECT. ("JOB
 ADDRESS" SEE CITY WPB AMEND. 106.1.1).
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED SEAL.
 (6) A SPACE FOR THE PRINTED NAME OF THE PERSON
 SEALING THE DOCUMENT.
  
 3) PLEASE SHOW JOB ADDRESS "2235" IN TITLE BLOCK SEE
 (3) ABOVE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 4 Status P Date 2007-10-25 Cont ID  
Sent By jleech Date 2007-10-25 Time 07:46 Rev Time 0.00
Received By jleech Date 2007-10-25 Time 07:46 Sent To  
Notes
2007-10-25 07:48:26PLUMBING AS-BUILT SANITARY RISER DIAGRAM

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-09-04 Cont ID  
Sent By mperson Date 2007-09-04 Time 11:00 Rev Time 0.00
Received By mperson Date 2007-09-04 Time 11:00 Sent To PC
Notes
2007-09-04 11:08:20****************PROVISO****************
 PER FBC-2004 CHAPTER 11, FLORIDA ACCESSIBILITY CODE
 SECTION 11-4.18.4, FLUSH CONTROLS SHALL BE HAND
 OPERATED OR AUTOMATIC, AND SHALL COMPLY WITH SECTION
 11-4.27.4 AND SHALL BE MOUNTED NO MORE THAN 44 INCHES
 ABOVE THE FINNISH FLOOR.
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL= [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-07-24 Cont ID  
Sent By jleech Date 2007-07-24 Time 10:17 Rev Time 0.00
Received By jleech Date 2007-07-24 Time 10:15 Sent To  
Notes
2007-07-24 10:28:32DENIED;
 1.( SECOND REQUEST) WATER AND SANITARY DIAGRAM
 REQUIRED. SEE FBC-2004 WPB AMENDMENTS TO CHAPTER 1,
 ADMINISTRATION CODE SECTION 106.3.5.1.3(13).
 2. ONE URINAL IS REQUIRED TO BE HANDICAP COMPLIANT SHOW
 DETAIL ON PLANS.
 3. LIST PLUMBING FIXTURES TO BE USED ON A FIXTURE
 SCHEDULE. ( SECOND REQUEST)
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-05-01 Cont ID  
Sent By jleech Date 2007-05-01 Time 07:14 Rev Time 0.00
Received By jleech Date 2007-05-01 Time 07:10 Sent To  
Notes
2007-05-01 07:29:13DENIED;
 1. SHOW TURNING RADIUS IN HANDICAP STALL AND CLEAR
 FLOOR SPACE, (LAV IN WOMANS CUSTOMERS BATHROOM BY
 DOOR).
 2. SANITARY AND WATER RISER REQUIRED. SEE FBC-2004 WPB
 AMENDMENTS TO CHAPTER 1, ADMINISTRATION CODE SECTION
 106.3.5.1.3.
 3. PAGE A-2 SHOWS 3 DIFFERENT TYPE OF TOILETS, PLEASE
 SPEC OUT THE TOILETS TO BE USED. SHOW A FIXTURE
 SCHEDULE ON PLANS.
 PLUMBING PLAN REVIEW BY
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status N Date 2007-07-23 Cont ID  
Sent By choops Date 2007-07-23 Time 17:37 Rev Time 0.00
Received By choops Date 2007-07-23 Time 17:37 Sent To  
Notes
2007-07-23 17:37:32*VALUE OF PROPOSED WORK DOES NOT EXCEED 50% OF THE
 IMPROVEMENT VALUE.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved