Plan Review Details - Permit 07040663
Plan Review Stops For Permit 07040663
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-05-07 Cont ID  
Sent By btrobaug Date 2007-05-07 Time 15:29 Rev Time 0.50
Received By btrobaug Date 2007-05-07 Time 15:29 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-04-26 Cont ID  
Sent By btrobaug Date 2007-04-26 Time 12:15 Rev Time 0.00
Received By btrobaug Date 2007-04-26 Time 12:14 Sent To I
Notes
2007-04-26 12:15:02 
 DENIED/INCOMPLETE INFORMATION.
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} PROVIDE FEEDER CONDUIT AND CONDUCTOR SIZES,TYPES
 AND OCP. INDICATE THE LOCATION OF THE HOUE PANEL AND
 FEEDER ROUTE ON THE SITE PLAN.
  
 2} PROVIDE A CALCULATION FOR THE FOR THE LOAD(S)
 SERVED. SEE ARTICLE 555.12 NEC.
  
 3} A DISCONNECTING MEANS PER 225.31 SHALL BE LOCATED
 PER 555.7.PLEASE INDICATE INTENDED LOCATION ON THE
 PLAN.
  
 4} PLEASE PROVIDE SPECIFICATIONS FOR THE SHORE POWER
 RECEPTACLE EQUIPMENT TO BE INSTALLED ON THE DOCK.
  
 5} THE ENGINEER WHOSE NAME APPEARS ON THE TITLE BLOCK
 MUST SIGN, DATE AND SEAL THE DOCUMENT. 61G15-23.002
 FAC.
  
 6} THE VALUE ON THE APPLICATION MUST
 INCLUDE THE TOTAL COST OF LABOR AND
 MATERIAL. VALUATION REFERENCES MAY
 INCLUDE THE LATEST PUBLISHED DATA OF
 NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES PER 108.3 FBC AS
 AMENDED. INCREASE THE VALUE AT THE
 COUNTER WHEN RESUBMITTING.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-05-07 Cont ID  
Sent By adarroug Date 2007-05-07 Time 14:09 Rev Time 0.00
Received By adarroug Date 2007-05-07 Time 14:09 Sent To E
Notes
2007-05-07 14:09:52TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-04-26 Cont ID  
Sent By btrobaug Date 2007-04-26 Time 12:17 Rev Time 0.00
Received By btrobaug Date 2007-04-20 Time 15:23 Sent To PC
Notes
2007-04-26 12:06:47 
  
 DENIED/INCOMPLETE INFORMATION.
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} PROVIDE FEEDER CONDUIT AND CONDUCTOR SIZES,TYPES
 AND OCP. INDICATE THE LOCATION OF THE HOUE PANEL AND
 FEEDER ROUTE ON THE SITE PLAN.
  
 2} PROVIDE A CALCULATION FOR THE FOR THE LOAD(S)
 SERVED. SEE ARTICLE 555.12 NEC.
  
 3} A DISCONNECTING MEANS PER 225.31 SHALL BE LOCATED
 PER 555.7.PLEASE INDICATE INTENDED LOCATION ON THE
 PLAN.
  
 4} PLEASE PROVIDE SPECIFICATIONS FOR THE SHORE POWER
 RECEPTACLE EQUIPMENT TO BE INSTALLED ON THE DOCK.
  
 5} THE ENGINEER WHOSE NAME APPEARS ON THE TITLE BLOCK
 MUST SIGN, DATE AND SEAL THE DOCUMENT. 61G15-23.002
 FAC.
  
 6} THE VALUE ON THE APPLICATION MUST
 INCLUDE THE TOTAL COST OF LABOR AND
 MATERIAL. VALUATION REFERENCES MAY
 INCLUDE THE LATEST PUBLISHED DATA OF
 NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES PER 108.3 FBC AS
 AMENDED. INCREASE THE VALUE AT THE
 COUNTER WHEN RESUBMITTING.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
2007-04-20 15:24:11TO "E" BOX