2007-04-26 12:15:02 | | | DENIED/INCOMPLETE INFORMATION. | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | 1} PROVIDE FEEDER CONDUIT AND CONDUCTOR SIZES,TYPES | | AND OCP. INDICATE THE LOCATION OF THE HOUE PANEL AND | | FEEDER ROUTE ON THE SITE PLAN. | | | | 2} PROVIDE A CALCULATION FOR THE FOR THE LOAD(S) | | SERVED. SEE ARTICLE 555.12 NEC. | | | | 3} A DISCONNECTING MEANS PER 225.31 SHALL BE LOCATED | | PER 555.7.PLEASE INDICATE INTENDED LOCATION ON THE | | PLAN. | | | | 4} PLEASE PROVIDE SPECIFICATIONS FOR THE SHORE POWER | | RECEPTACLE EQUIPMENT TO BE INSTALLED ON THE DOCK. | | | | 5} THE ENGINEER WHOSE NAME APPEARS ON THE TITLE BLOCK | | MUST SIGN, DATE AND SEAL THE DOCUMENT. 61G15-23.002 | | FAC. | | | | 6} THE VALUE ON THE APPLICATION MUST | | INCLUDE THE TOTAL COST OF LABOR AND | | MATERIAL. VALUATION REFERENCES MAY | | INCLUDE THE LATEST PUBLISHED DATA OF | | NATIONAL CONSTRUCTION COST ANALYSIS | | SERVICES PER 108.3 FBC AS | | AMENDED. INCREASE THE VALUE AT THE | | COUNTER WHEN RESUBMITTING. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 | | [email protected] |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2007-05-07 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-05-07 |
Time |
14:09 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-05-07 |
Time |
14:09 |
Sent To |
E |
|
Notes |
2007-05-07 14:09:52 | TO "BTROBAUG" DESK/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2007-04-26 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2007-04-26 |
Time |
12:17 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2007-04-20 |
Time |
15:23 |
Sent To |
PC |
|
Notes |
2007-04-26 12:06:47 | | | | | DENIED/INCOMPLETE INFORMATION. | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | 1} PROVIDE FEEDER CONDUIT AND CONDUCTOR SIZES,TYPES | | AND OCP. INDICATE THE LOCATION OF THE HOUE PANEL AND | | FEEDER ROUTE ON THE SITE PLAN. | | | | 2} PROVIDE A CALCULATION FOR THE FOR THE LOAD(S) | | SERVED. SEE ARTICLE 555.12 NEC. | | | | 3} A DISCONNECTING MEANS PER 225.31 SHALL BE LOCATED | | PER 555.7.PLEASE INDICATE INTENDED LOCATION ON THE | | PLAN. | | | | 4} PLEASE PROVIDE SPECIFICATIONS FOR THE SHORE POWER | | RECEPTACLE EQUIPMENT TO BE INSTALLED ON THE DOCK. | | | | 5} THE ENGINEER WHOSE NAME APPEARS ON THE TITLE BLOCK | | MUST SIGN, DATE AND SEAL THE DOCUMENT. 61G15-23.002 | | FAC. | | | | 6} THE VALUE ON THE APPLICATION MUST | | INCLUDE THE TOTAL COST OF LABOR AND | | MATERIAL. VALUATION REFERENCES MAY | | INCLUDE THE LATEST PUBLISHED DATA OF | | NATIONAL CONSTRUCTION COST ANALYSIS | | SERVICES PER 108.3 FBC AS | | AMENDED. INCREASE THE VALUE AT THE | | COUNTER WHEN RESUBMITTING. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 | | [email protected] | 2007-04-20 15:24:11 | TO "E" BOX |
|
|
|