Plan Review Details - Permit 07040638
Plan Review Stops For Permit 07040638
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-04-30 Cont ID  
Sent By mawillia Date 2007-04-30 Time 12:27 Rev Time 0.00
Received By mawillia Date 2007-04-30 Time 12:17 Sent To  
Notes
2007-04-30 12:24:01*****APPROVED*****
  
  
 PLAN SHEET 1 OF 2 STAMPED, INTIALED, AND DATED;READY
 FOR PERMIT ISSUANCE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-04-20 Cont ID  
Sent By mwennerg Date 2007-04-20 Time 13:11 Rev Time 0.00
Received By mwennerg Date 2007-04-20 Time 13:11 Sent To  
Notes
2007-04-20 13:22:26***DENIED***
  
 1) PLEASE PROVIDE MORE INFORMATION/DETAILS FOR HOOD.
 SEE MECHANICAL COMMENT #1.
  
 2) IN ADDITION TO HOOD, SEPARATE SHOP DRAWINGS AND
 PERMIT REQUIRED FOR FIRE SUPPRESSION SYSTEM THAT SHALL
 BE IN COMPLIANCE WITH UL 300.
  
 3) PLEASE SHOW MINIMAL CLEARANCES TO COMBUSTIBLE
 SURFACES.
  
 4) SYSTEM SHALL BE TIED INTO FIRE ALARM IF PROVIDED. IF
 NO FIRE ALARM, A/V DEVICE(S) ARE STILL REQUIRED FOR
 OCCUPANT NOTIFICATION.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-04-20 Cont ID  
Sent By mwennerg Date 2007-04-20 Time 13:23 Rev Time 0.00
Received By mwennerg Date 2007-04-20 Time 09:40 Sent To  
Notes
2007-04-20 09:40:45TO "TGORDON" DESK

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-04-27 Cont ID  
Sent By tgordon Date 2007-04-27 Time 08:39 Rev Time 0.30
Received By tgordon Date 2007-04-27 Time 08:39 Sent To FIRE
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-04-20 Cont ID  
Sent By tgordon Date 2007-04-20 Time 11:04 Rev Time 1.00
Received By tgordon Date 2007-04-20 Time 11:04 Sent To FIRE
Notes
2007-04-20 11:43:05*** DENIED ***
 1) NO INFORMATION GIVEN ON HOOD TO DO PROPER REVIEW
 (IE. IF USED OR NEW,IF UL APPROVED, TYPE OF HOOD,
 MATERIALS MADE OF, SIZE OF HOOD ETC.), PLEASE CORRECT.
  
 2) PLEASE SHOW WHAT MATERIAL THE 12" SUPPLY AIR DUCT IS
 MADE OF, SEE 2004 FBC/M 506.3.1.2.
  
 3) PLEASE SHOW HOW EXHAUST AND SUPPLY FANS ARE TO BE
 SECURED TO THE CURBS TO WITH STAND 140 MPH WINDS AND
 COMPLY WITH 2004 FBC 1609.
  
 4) SEE PLANS PAGE 1, SECTION, PLEASE SHOW WHAT SIZE
 UNISTRUT IS TO BE USED.
  
 5) PLEASE NOTE ON PLANS SF1 CURB TO BE SECURED SAME AS
 EF1, IF NOT THEN SHOW DETAIL.
  
 6) PLEASE SHOW ON PLANS THAT A GUARD WILL BE INSTALLED
 ON ROOF TOP NEAR EDGE OF WALL, SEE 2004 FBC/M 304.10.
  
 *** 2004 FBC/M 304.10 GUARDS.
 GUARDS SHALL BE PROVIDED WHERE APPLIANCES, EQUIPMENT,
 FANS OR OTHER COMPONENTS THAT REQUIRE SERVICE ARE
 LOCATED WITHIN 10 FEET (3048 MM) OF A ROOF EDGE OR OPEN
 SIDE OF A WALKING SURFACE AND SUCH EDGE OR OPEN SIDE IS
 LOCATED MORE THAN 30 INCHES (762 MM) ABOVE THE FLOOR,
 ROOF OR GRADE BELOW. THE GUARD SHALL EXTEND NOT LESS
 THAN 30 INCHES (762 MM) BEYOND EACH END OF SUCH
 APPLIANCE, EQUIPMENT, FAN OR COMPONENT AND THE TOP OF
 THE GUARD SHALL BE LOCATED NOT LESS THAN 42 INCHES
 (1067 MM) ABOVE THE ELEVATED SURFACE ADJACENT TO THE
 GUARD. THE GUARD SHALL BE CONSTRUCTED SO AS TO PREVENT
 THE PASSAGE OF A 21-INCH-DIAMETER (533 MM) SPHERE AND
 SHALL COMPLY WITH THE LOADING REQUIREMENTS FOR GUARDS
 SPECIFIED IN THE FLORIDA BUILDING CODE, BUILDING .
  
 7) PLEASE SUBMIT TWO SETS OF PLANS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.