Plan Review Details - Permit 07040621
Plan Review Stops For Permit 07040621 |
Review Stop |
AD |
ADDRESSING |
Rev No |
2 |
Status |
P |
Date |
2007-09-11 |
|
|
Cont ID |
|
Sent By |
lursu |
Date |
2007-09-11 |
Time |
09:27 |
Rev Time |
0.00 |
Received By |
lursu |
Date |
2007-09-11 |
Time |
09:27 |
Sent To |
|
|
Notes |
2007-09-11 09:27:40 | SITE ADDRESS AND PCN ARE CORRECT. | | | | LACRAMIOARA URSU | | MIS - GIS SUPPORT SPECIALIST | | CITY OF WEST PALM BEACH | | OFFICE:822-1239 | | FAX: 822-1249 | | E-MAIL:[email protected] |
|
|
Review Stop |
AD |
ADDRESSING |
Rev No |
1 |
Status |
F |
Date |
2007-08-30 |
|
|
Cont ID |
|
Sent By |
lursu |
Date |
2007-08-30 |
Time |
15:06 |
Rev Time |
0.00 |
Received By |
lursu |
Date |
2007-08-30 |
Time |
15:06 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
13 |
Status |
P |
Date |
2008-07-25 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2008-07-25 |
Time |
16:29 |
Rev Time |
0.77 |
Received By |
jwitmer |
Date |
2008-07-25 |
Time |
16:29 |
Sent To |
|
|
Notes |
2008-07-25 16:30:22 | GV-102 REVISION # 5 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
12 |
Status |
P |
Date |
2008-07-25 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2008-07-25 |
Time |
16:16 |
Rev Time |
0.77 |
Received By |
jwitmer |
Date |
2008-07-25 |
Time |
16:16 |
Sent To |
|
|
Notes |
2008-07-25 16:17:08 | SHEET GV-102 REVISION# 5 OK |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
11 |
Status |
P |
Date |
2008-07-16 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2008-07-16 |
Time |
10:43 |
Rev Time |
0.77 |
Received By |
jwitmer |
Date |
2008-07-16 |
Time |
10:43 |
Sent To |
FIRE |
|
Notes |
2008-07-16 10:44:46 | BUILDING PLAN REVIEW | | PERMIT: 07040621 | | ADD: 5205 GREENWOOD | | CONT: HEDRICK BROTHERS | | TEL: (561)689-8880 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | W/ 2006 FBC REVISIONS | | * WEST PALM BEACH AMENDMENTS | | | | REVISIONREVIEW | | ACTION: REVIEWED | | | | REVISONAF-321 NEW SHEET WALL PENETRATION DETAILS | | JIM WITMER C. B. O. | | BUILDING PLAN REVIEW II | | | | TEL: (561)805-6715 | | FAX: (561)659-8026 | | E-MAIL: [email protected] | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
10 |
Status |
F |
Date |
2008-07-16 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2008-07-16 |
Time |
10:21 |
Rev Time |
0.55 |
Received By |
jwitmer |
Date |
2008-07-16 |
Time |
10:21 |
Sent To |
|
|
Notes |
2008-07-16 10:27:02 | BUILDING PLAN REVIEW | | PERMIT: 07040621 | | ADD: 5205 GREENWOOD | | CONT: HEDRICK BROTHERS | | TEL: (561)689-8880 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | W/ 2006 FBC REVISIONS | | * WEST PALM BEACH AMENDMENTS | | | | REVISIONREVIEW | | ACTION: DENIED | | | | REVISON TO CS-101 REVISION 5 PR#10 IS A REVISION TO | | STAIRS AND HANDRAIL, DETAIL 7/ CS501 THERE IS NO | | NARATIVE NOR DETAIL INDICATING WHAT HAS CHANGED, ONLY | | THERE IS A CHANGE. 106.1.2 ADDITIONAL INFORMATION | | REQUIRED. | | | | JIM WITMER C. B. O. | | BUILDING PLAN REVIEW II | | | | TEL: (561)805-6715 | | FAX: (561)659-8026 | | E-MAIL: [email protected] | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
9 |
Status |
F |
Date |
2008-06-30 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2008-06-30 |
Time |
10:10 |
Rev Time |
1.77 |
Received By |
jwitmer |
Date |
2008-06-30 |
Time |
10:10 |
Sent To |
PC |
|
Notes |
2008-06-30 10:53:06 | BUILDING PLAN REVIEW | | PERMIT: 07040621 | | ADD: 5205 GREENWOOD | | CONT: HEDRICK BROTHERS | | TEL: (561)689-8880 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | W/ 2006 FBC REVISIONS | | * WEST PALM BEACH AMENDMENTS | | | | REVISIONREVIEW | | ACTION: DENIED | | | | SHEET GV-102 THE REVISION INDICATES THE REMOVAL OF | | RATED SMOKE PARTITIONS FOR THE INCIDENTIAL MECHANICAL | | CHASE AND ELECTRICAL ROOM ON THE SECOND FLOOR LEVEL. | | INCIDENTIAL USE AREAS AS PER TABLE | | 302.1.1.1REQUIRES A 1 HOUR SEPERATION WITH THE | | EXCEPTION FOR FULLY SPRINKLED BUILDINGS WHICH THIS HAS. | | IN 302.1.1.1 WHERE TABLE 302.1.1 PERMITS AN AUTOMATIC | | FIRE -EXTINGUISHING SYSTEM WITHOUT A FIRE-BARRIER, THE | | INCIDENTIAL USE AREA SHALL BE SEPERATED BY CONSTRUCTION | | CAPABLE OF RESISTING THE PASSAGE OF SMOKE. | | | | JIM WITMER C. B. O. | | BUILDING PLAN REVIEW II | | | | TEL: (561)805-6715 | | FAX: (561)659-8026 | | E-MAIL: [email protected] | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
8 |
Status |
P |
Date |
2008-05-05 |
|
|
Cont ID |
|
Sent By |
lmartine |
Date |
2008-05-05 |
Time |
13:16 |
Rev Time |
0.00 |
Received By |
lmartine |
Date |
2008-05-05 |
Time |
13:16 |
Sent To |
|
|
Notes |
2008-05-05 13:18:37 | RESTAMP BUILDING PAGES ONLY LM |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
7 |
Status |
P |
Date |
2008-02-26 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2008-02-26 |
Time |
11:02 |
Rev Time |
1.11 |
Received By |
jwitmer |
Date |
2008-02-26 |
Time |
11:01 |
Sent To |
|
|
Notes |
2008-02-26 11:03:08 | REV# PR# 7 DATED 01-03-08 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
6 |
Status |
P |
Date |
2008-01-25 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2008-01-25 |
Time |
16:17 |
Rev Time |
0.77 |
Received By |
jwitmer |
Date |
2008-01-25 |
Time |
16:17 |
Sent To |
|
|
Notes |
2008-01-25 16:18:38 | MISSING SHEETS FROM THE APPROVED SET OF PLANS IN-101, | | IN-102 & AF-102 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
5 |
Status |
P |
Date |
2008-01-15 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2008-01-15 |
Time |
17:20 |
Rev Time |
2.22 |
Received By |
jwitmer |
Date |
2008-01-15 |
Time |
17:20 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2007-11-02 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2007-11-02 |
Time |
13:36 |
Rev Time |
4.44 |
Received By |
jwitmer |
Date |
2007-11-02 |
Time |
13:36 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2007-11-02 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2007-11-02 |
Time |
09:04 |
Rev Time |
4.44 |
Received By |
jwitmer |
Date |
2007-11-02 |
Time |
08:33 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2007-08-31 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2007-08-31 |
Time |
12:13 |
Rev Time |
4.44 |
Received By |
jwitmer |
Date |
2007-08-30 |
Time |
17:37 |
Sent To |
|
|
Notes |
2007-08-31 12:14:41 | 5205 GREENWOOD AVE | | BUILD-OUT3RD REVIEW | | | | | | | | | | BUILDING PLAN REVIEW | | PERMIT: 07040621 | | ADD: 5205 GREENWOOD | | CONT: HEDRICK BROTHERS | | TEL: (561)689-8880 | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | W/ 2006 FBC REVISIONS | | * WEST PALM BEACH AMENDMENTS | | 3RDREVIEW | | ACTION: DENIED | | | | NOTE! THIS PROJECT HAS BEEN SUBMITTED AS A PHASED | | PROJECT, THERE HAS BEEN A REMODEL ELEMENT, AND AN | | ADDITION TO THIS STRUCTURE. | | PLEASE NOTE THAT THESE PLANS WILL BE REVIEWED UNDER THE | | 2004 EXISTING BUILDING CODE 2006 EDITION , ALTERATIONS | | : LEVEL 3 AND CHAP 9 FOR ADDITIONS | | AS WELL AS 2006 FBC BUILDING.. | | | | 1)--- VERY IMPORTANT STATEMENT --- | | PLEASE DO NOT IGNORE! | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | A DESCRIPTION OF THE REVISION | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR | | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | 2 ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED | | WITH THE CLERK OF THE COURT. | | NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF | | COMMENCEMENT IS NOT ACTUALLY | | COMMENCED WITHIN 90 DAYS AFTER THE RECORDING THEREOF, | | SUCH NOTICE IS NULL & VOID. | | NOTE: 713.13(6)THE POSTING OF THE NOTICE OF | | COMMENCEMENT AT THE CONSTRUCTION | | SITE BEFORE THE FIRST INSPECTION. | | | | 3-4) COMPLIED. | | | | 5) SEMI-COMPLIED.SHEET GV-101 DOOR 174A IS MISSING | | THE 18? ON THE PULL SIDE OF DOOR AT LATCH SIDE OF DOOR. | | 11-4.13.6 MANEUVERING CLEARENCES AT DOORS. MINIMUM | | MANEUVERING CLEARANCES AT DOORS THAT ARE NOT AUTOMATIC | | OR POWER-ASSISTED SHALL BE AS SHOWN IN FIG. 25. THE | | FLOOR OR GROUND AREA WITH IN THE REQUIRED CLEARANCES | | SHALL BE CLEAR & LEVEL. | | 6-7A) COMPLIED. | | | | 7B) PROVIDE HOW THIS DOOR WILL CLOSE IF THE FIRE ALARMS | | OR FIRE SPRINKLERS ARE ACTIVATED? | | | | 7C)2ND REQUEST. SEMI-COMPLIED, THE DETAIL# 03 ON | | AF-402 IS TO BE 1HR RATED WALL PLEASE PROVIDE THE UL | | NUMBER OR US GYPSUM NUMBER THAT ALLOWS DRYWALL ON ONLY | | ONE SIDE OF THE ASSEMBLY? PLEASE PROVIDE THE COMPLETE | | UL LISTING NUMBER, PROVIDE A DETAIL OF THE UL LISTING | | AND PROVIDE A SECTION OF THE L HOUR RATED WALL.706.3 | | FIRE RESISTANCE RATINGS. | | | | 7D-9) COMPLIED. | | | | 10) 2ND REQUEST,GV-102 ELEVATOR LOBBY 200 INDICATES A | | PAIR OF DOORS AND THE OPPOSITE END OF THIS AREA THERE | | APPEARS TO BE GLASS, IT IS NOT CLEAR IF THIS IS A WALL | | OR IF IT IS A GLASS HANDRAIL, PLEASE PROVIDE A CUT | | THROUGH THIS SECTION. SEE ATRIUM REQUIREMENTS 404.5 SEE | | EXCEPTION (1).THE PLAN ACTUALLY INDICATES THE 1 HR | | RATED WALL TO FALL IN LINE WITH DOOR LINE. SHEET AF-601 | | INDICATES DOORS AND FRAMES BUT NO DOOR SCHEDULE. PLEASE | | PROVIDE THIS INFORMATION FOR THESE DOORS AND THE RATED | | DOORS FOR THE FIRST FLOOR. | | SHEET EA101 & EA 102 INDICATE SYMBOLS THAT | | POSSIBLY TIE TO THE ALARM PANEL BUT SHEET | | EC-001 WHICH IS THE FIRE ALARM SYMBOLS AND NOTES IS | | MISSING PLEASE PROVIDE. ADDITIONAL INFORMATION REQUIRED | | 106.1.2*. | | | | 11) NOTE, BY DEFINITION, THIS AREA (LOBBY 100) IS AN | | ATRIUM. ATRIUM . AN OPENING CONNECTING TWO OR MORE | | STORIES OTHER THAN ENCLOSED STAIRWAYS, ELEVATORS, | | HOISTWAY, ESCALATORS, PLUMBING, ELECTRICAL, | | AIR-CONDITIONING OR OTHER EQUIPMENT, WHICH IS CLOSED AT | | THE TOP AND NOT DEFINED AS A MALL. STORIES, AS USED IN | | THIS DEFINITION, DO NOT INCLUDE BALCONIES WITHIN | | ASSEMBLY GROUPS OR MEZZANINES THAT COMPLY WITH SECTION | | 505 . | | | | 11A-11B) COMPLIED. SMOKE CONTROL NOT REQUIRED SECTION | | 404 EXCEPTIONS. | | | | 12-17) COMPLIED. | | | | 18)SEMI-COMPLIED, THE FRONTS AND INTERIOR OF THE | | CABINETS ARE TO BE REMOVED FOR FRONTAL APPROACH | | 11-4.24.3 KNEE CLEARANCE THAT IS AT LEAST 27" HIGH 30" | | WIDE, AND 19" DEEP SHALL BE PROVIDED UNDERNEATH SINKS. | | 11-4.24.5 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE AT | | LEAST 30 INCHES BY 48 INCHES (760 MM BY 1219 MM) | | COMPLYING WITH SECTION 11-4.2.4 SHALL BE PROVIDED IN | | FRONT OF A SINK TO ALLOW FORWARD APPROACH. THE CLEAR | | FLOOR SPACE SHALL BE ON AN ACCESSIBLE ROUTE AND SHALL | | EXTEND A MAXIMUM OF 19 INCHES (485 MM) UNDERNEATH THE | | SINK. | | | | 19-20) COMPLIED. | | | | 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS | | OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF | | CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST | | RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT | | BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC | | REQUIREMENT, THE SPECIFIC | | REQUIREMENT SHALL BE APPLICABLE. | | | | BUILDING PLAN REVIEW | | JIM WITMER C. B. O. | | BUILDING PLAN REVIEW II | | | | | | TEL: (561)805-6715 | | FAX: (561)659-8026 | | E-MAIL: [email protected] |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2007-05-30 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2007-05-30 |
Time |
13:01 |
Rev Time |
3.33 |
Received By |
jwitmer |
Date |
2007-05-30 |
Time |
13:01 |
Sent To |
|
|
Notes |
2007-05-30 16:57:08 | BUILDING PLAN REVIEW | | PERMIT: 07040621 | | ADD: 5205 GREENWOOD | | CONT: HEDRICK BROTHERS | | TEL: (561)689-8880 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | W/ 2006 FBC REVISIONS | | * WEST PALM BEACH AMENDMENTS | | | | REVIEW | | ACTION: DENIED | | | | | | NOTE! THIS PROJECT HAS BEEN SUBMITTED AS A PHASED | | PROJECT, THERE HAS BEEN A REMODEL ELEMENT, AND AN | | ADDITION TO THIS STRUCTURE. | | PLEASE NOTE THAT THESE PLANS WILL BE REVIEWED UNDER THE | | 2004 EXISTING BUILDING CODE 2006 EDITION , ALTERATIONS | | : LEVEL 3 AND CHAP 9 FOR ADDITIONS | | AS WELL AS 2006 FBC BUILDING.. | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | PLEASE DO NOT IGNORE! | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | BER, WITH A DESCRIPTION OF THE REVISION | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | 2 ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED | | WITH THE CLERK OF THE COURT. | | NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF | | COMMENCEMENT IS NOT ACTUALLY | | COMMENCED WITHIN 90 DAYS AFTER THE RECORDING THEREOF, | | SUCH NOTICE IS NULL & VOID. | | NOTE: 713.13(6)THE POSTING OF THE NOTICE OF | | COMMENCEMENT AT THE CONSTRUCTION | | SITE BEFORE THE FIRST INSPECTION. | | | | 3A) SHEET GV-101 TYPE OF CONSTRUCTION: IV HEAVY TIMBER | | PLEASE LOOK AT | | SECTION 602 FOR BUILDING CONSTRUCTION CLASSIFICATIONS | | AND TABLE 503.THIS BUILDING IS NOT | | A HEAVY TIMBER DESIGN. NOTE IF IT IS AN "A OR B" | | CLASSIFICATION. | | | | 3B) GV-101 INDICATES 9006 SQ FT FIRST FLOOR WHILE THE | | 2ND FLOOR HAS 9170, THE FOOTPRINT ON THE FIRST FLOOR IS | | LARGER HAVING MORE ARERA, PLEASE RECALCULATE PLUS | | COVERED WALKWAY! | | | | 3C) NOTE INCREASES THAT CAN BE TAKEN FOR A FULLY | | SPRINKLERED BUILDING(AREA INCREASES)! | | | | 4) PLANS ALSO INDICATE THE BUILDING DESIGN IS THE 2004 | | FBC, PLANS SUBMITTED | | AFTER DEC 12,2006 FALL IN UNDER THE 2006 FBC. | | | | 5)SHEET GV-101 INDICATES DOORWAYS IN THE CORRIDOR | | THAT DO NOT HAVE IDENTIFYING TAGS, THE FIRST DOOR ISUE | | | | IS LOCATED BETWEEN ROOM 167 AND ROOM 171, THE SECOND | | DOOR IS LOCATED BETWEEN | | ROOMS 193 AND 125B. IN BOTH CASES IT APPEARS THERE IS | | NOT 18" ON THE LATCH SIDE OF THE DOORWAY. 11-4.13.6 | | MANEUVERING CLEARENCES AT DOORS. MINIMUM MANEUVERING | | CLEARANCES | | AT DOORS THAT ARE NOT AUTOMATIC OR POWER-ASSISTED SHALL | | BE AS SHOWN IN FIG. 25. THE FLOOR OR | | GROUND AREA WITH IN THE REQUIRED CLEARANCES SHALL BE | | CLEAR & LEVEL. | | | | 6)PLANS INDICATE THIS IS A BUSINESS OCCUPANCY, THE | | PLANS DO NOT IDENTIFY IF IT IS A SINGLE TENANT? THE | | FIRST FLOOR DOES HAVE TWO | | WAITING ROOMS 110 AND 150? 106.1.2* ADD INFO REQUIRED | | AND708.1(5). | | | | 7) GV-102 THE PLANS INDICATE ON THE MAIN ENTRY STAIR | | WITH ACOILING FIRE RATED DOOR AT THE HEAD OF THE | | SECOND STORY LANDING AND WHAT APPEARS TO BE A 1 HOUR | | RATED WALL. | | SHEET AF-402 DETAIL 03 INDICATES A HORIZONTAL COILING | | FIRE DOOR. | | 7A) PLEASE SUBMIT PRODUCT INFORMATION FOR A 1 HR RATED | | ASSEMBLY. | | 7B) PROVIDE HOW THIS DOOR WILL CLOSE IF THE FIRE ALARMS | | OR FIRE SPRINKLERS ARE ACTIVATED? | | 7C) THE DETAIL# 03 ON AF-402 IS TO BE 1HR RATED WALL | | PLEASE PROVIDE THE UL NUMBER OR US GYPSUM NUMBER THAT | | ALLOWS DRYWALL ON ONLY ONE SIDE OF THE ASSEMBLY? 7D) | | PLEASE INDICATE HOW ONE WOULD GAIN ACCESS TO DO | | MAINTENCE WORK ON THE COILED FIRE DOOR ? ADDITIONAL | | COMMENTS MAY APPEAR ON THESE ITEMS ONCE THE RESPONCES | | ARE REVIEWED. | | | | 8)GV-102 PLANS APPEAR TO HAVE A SLEEP STUDY AREA WITH | | A CONTROL ROOM. PLEASE PROVIDE ADDITIONAL INFORMATION | | AS TOTHE FUCTION OF THIS AREA? WILL THE PATIENTS BE | | THERE OVER 24 HRS? | | WILL THE PATIENTS BE MEDICATED? AND WILL THERE BE MORE | | THAN ONE PATEINT THERE SLEEPING? | | | | 9)GV-102 ROOM 210 CONFERENCE PRESENTATION THERE | | APPEARS TO BE A SEPERATE ROOM IN THE UPPER RIGHT CORNER | | WITH NO IDENTIFICATION? PLEASE PROVIDE ADDITIONAL | | INFORMATION. 106.1.2* | | | | 10) GV-102 ELEVATOR LOBBY 200 INDICATES A PAIR OF DOORS | | AND THE OPPOSITE END OF THIS AREA THERE APPEARS TO BE | | GLASS, IT IS NOT CLEAR IF THIS IS A WALL OR IF IT IS A | | GLASS HANDRAIL, PLEASE PROVIDE A CUT THROUGH THIS | | SECTION. SEE ATRUIM REQUIREMENTS 404.5 SEE EXCEPTION | | (1).THE PLAN ACTUALLY INDICATES THE 1 HR RATED WALL | | TO FALL IN LINE WITH DOOR LINE. SHEET AF-601 INDICATES | | DOORS AND FRAMES BUT NO DOOR SCHEDULE. PLEASE PROVIDE | | THIS INFORMATION FOR THESE DOORS AND THE RATED DOORS | | FOR THE FIRST FLOOR. | | | | 11) NOTE, BY DEFINITION, THIS AREA (LOBBY 100) IS AN | | ATRIUM. ATRIUM . AN OPENING CONNECTING TWO OR MORE | | STORIES OTHER THAN ENCLOSED STAIRWAYS, ELEVATORS, | | HOISTWAY, ESCALATORS, PLUMBING, ELECTRICAL, | | AIR-CONDITIONING OR OTHER EQUIPMENT, WHICH IS CLOSED AT | | THE TOP AND NOT DEFINED AS A MALL. STORIES, AS USED IN | | THIS DEFINITION, DO NOT INCLUDE BALCONIES WITHIN | | ASSEMBLY GROUPS OR MEZZANINES THAT COMPLY WITH SECTION | | 505 . | | | | 11A)404.4 SMOKE CONTROL. A SMOKE CONTROL SYSTEM SHALL | | BE INSTALLED IN ACCORDANCE WITH SECTION 909 . | | 11B)404.6 STANDBY POWER. EQUIPMENT REQUIRED TO | | PROVIDE SMOKE CONTROL SHALL BE CONNECTED TO A STANDBY | | POWER SYSTEM IN ACCORDANCE WITH SECTION 909.11 . | | | | 12) GV-102ROOM 223 PLEASE SHOW THE CLEAR FLOOR SPACE | | REQUIRED FOR PLUMBING FIXTURES, IT APPEARS THAT THE | | DOORWAY MAY SWING INTO THE LAV CLEAR FLOOR SPACE. | | 11-4.19.3 CLEAR FLOOR SPACE . | | A CLEAR FLOOR SPACE 30 INCHES BY 48 INCHES (760 MM BY | | 1219 MM) COMPLYING WITH SECTION 11-4.2.4 SHALL BE | | PROVIDED IN FRONT OF A LAVATORY TO ALLOW FORWARD | | APPROACH. SUCH CLEAR FLOOR SPACE SHALL ADJOIN OR | | OVERLAP AN ACCESSIBLE ROUTE AND SHALL EXTEND A MAXIMUM | | OF 19 INCHES (485 MM) UNDERNEATH THE LAVATORY (SEE | | FIGURE 32 ). | | | | 13) GV-102 ROOM XXX SHELL IS THIS THE SAME TENANT | | SPACE? | | | | 14)PLEASE DEVELOP A DOOR IDENIFICATION SYSTEM NO | | DOORS ARE IDENTIFIED ON EITHER FLOOR. | | | | 15) GV-102 CONFERENCE ROOM 210 HAS AN OCCUPANT LOAD OF | | APPROX 114 PEOPLE PLEASE SEE TABLE 1016.1 FOR ASSEMBLY | | OCCUPANCIES, OCCUPANT LOADS SERVED BY CORRIDORS, TABLE | | 1016.1WITH SPRINKLERS SYSTEMS AND OCCUPANT LOADS >30 | | REQUIRING 1 HR RATED CORRIDORS. | | | | 16) GV-102 ROOM 211 ELEVATOR MACHINE ROOM. 3006.4 | | MACHINE ROOMS AND MACHINERY SPACES. | | ELEVATOR MACHINE ROOMS AND MACHINERY SPACES SHALL BE | | ENCLOSED WITH CONSTRUCTION HAVING A FIRE-RESISTANCE | | RATING NOT LESS THAN THE REQUIRED RATING OF THE | | HOISTWAY ENCLOSURE SERVED BY THE MACHINERY. OPENINGS | | SHALL BE PROTECTED WITH ASSEMBLIES HAVING A | | FIRE-RESISTANCE RATING NOT LESS THAN THAT REQUIRED FOR | | THE HOISTWAY ENCLOSURE DOORS. | | | | 17) GV-102 ROOM 211 3006.1 ACCESS.AN APPROVED MEANS | | OF ACCESS SHALL BE PROVIDED TO ELEVATOR MACHINE ROOMS . | | AN APPROVED ACCESS DOES NOT HAVE MEANS OF EGRESS | | THROUGH TENANT SPACES. | | | | 18)AF-210 LOUNGE SINK IS CABINET ELEVATION INDICATES | | A 3'-0" ELEVATION. SINKS:11-4.24.2 SINKS, HEIGHT. | | SINKS SHALL BE MOUNTED WITH THE COUNTER NO HIGHER THAN | | 34" ABOVE THE FINISH FLOOR. | | 11-4.24.3 KNEE CLEARANCE THAT IS AT LEAST 27" HIGH | | 30" WIDE, AND 19" DEEP SHALL BE PROVIDED UNDERNEATH | | SINKS. 11-4.24.5 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE | | AT LEAST 30 INCHES BY 48 INCHES (760 MM BY 1219 MM) | | COMPLYING WITH SECTION 11-4.2.4 SHALL BE PROVIDED IN | | FRONT OF A SINK TO ALLOW FORWARD APPROACH. THE CLEAR | | FLOOR SPACE SHALL BE ON AN ACCESSIBLE ROUTE AND SHALL | | EXTEND A MAXIMUM OF 19 INCHES (485 MM) UNDERNEATH THE | | SINK. | | | | 19) AF-320 VARIOUS WALLS INDICATE THAT SOME MAY REQUIRE | | FIRE RATINGS, PLEASE PROVIDEINFORMATION ON THE FLOOR | | TO FLOOR ORFLOOR TO ROOF/ CEILING ASSEMBLIES. 713.1 | | GENERAL. JOINTS INSTALLED IN OR BETWEEN | | FIRE-RESISTANCE-RATED WALLS, FLOOR OR FLOOR/CEILING | | ASSEMBLIES AND ROOFS OR ROOF/CEILING ASSEMBLIES SHALL | | BE PROTECTED BY AN APPROVED FIRE-RESISTANT JOINT SYSTEM | | DESIGNED TO RESIST THE PASSAGE OF FIRE FOR A TIME | | PERIOD NOT LESS THAN THE REQUIRED FIRE-RESISTANCE | | RATING OF THE WALL, FLOOR OR ROOF IN OR BETWEEN WHICH | | IT IS INSTALLED. FIRE-RESISTANT JOINT SYSTEMS SHALL BE | | TESTED IN ACCORDANCE WITH SECTION 713.3 . THE VOID | | CREATED AT THE INTERSECTION OF A FLOOR/CEILING ASSEMBLY | | AND AN EXTERIOR CURTAIN WALL ASSEMBLY SHALL BE | | PROTECTED IN ACCORDANCE WITH SECTION 713.4 . | | | | 20) AF-401 GRAND STAIR SECTION AT THE TOP OF THE | | STAIRCASE THE HORIZONTAL PROJECTION OFTHE HANDRAIL IS | | TO BE A MINIMUM OF 1'-0" LONG. 11-4.9.4 | | | | | | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A | | RESULT OF THE ADDITIONAL INFORMATION REQUESTED | | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF | | THIS REVIEW. | | | | BUILDING PLAN REVIEW | | JIM WITMER C. B. O. | | | | TEL: (561)805-6715 | | FAX: (561)659-8026 | | E-MAIL: [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
9 |
Status |
P |
Date |
2008-05-04 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-05-04 |
Time |
10:42 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-05-04 |
Time |
10:00 |
Sent To |
|
|
Notes |
2008-05-04 10:43:04 | ** DENIED/PASSED REVIEW ** | | | | | | 1) NOTE: PLEASE SEE SOME OF THE REVISED SHEETS | | SUBMITTED ARE STAMPED OK FOR ELECTRICAL HOWEVER SOME | | ARE *FAILED*. | | PLEASE SEE THE FOLLOWING SHEETS LISTED ARE OK. | | EL-101, EL-102, EL-103, EE-301, EL-104, EE-310, EE-311, | | EE-401. THESE SHEETS ARE OK AND ONCE FIRE MARSHAL | | REVIEW IS DONE THESE CAN BE RELEASED. | | | | ** PLEASE SEE THE FOLLOWING SHEETS ARE FAILED BASED ON | | THE FACT THESE SHEETS ARE ALREADY IN FILE AS BEING | | REVISED PREVIOUSLY. THEY HAVE BEEN STAMPED WITH A VOID | | STAMP AS NOT TO GET CONFUSED WITH ACTUAL SHEETS WHICH | | ARE OK. | | | | ** PLEASE KNOW ONCE FIRE REVIEW IS DONE AND IS OK, ONE | | SET OF ELECTRICAL PLANS AND FIRE ALARM REVISIONS NEED | | TO BE RETAINED FOR RECORD SET. | | FIRE ALARM SHEETS HAVE BEEN REVISED FROM FILE SET | | PLANS. THESE ARE NOT RE-STAMPS. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE DO NOT HESITATE IN | | CONTACTING THIS REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
8 |
Status |
F |
Date |
2008-02-15 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-02-15 |
Time |
08:51 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-02-14 |
Time |
19:27 |
Sent To |
|
|
Notes |
2008-02-15 08:52:09 | 2008-02-15 08:52:09 | | | | *** DENIEDREVISIONS*** | | | | 1) NOTE: PLEASE SEE AS REQUESTED ON ALL PREVIOUS | | REVIEWS. PLEASE SUBMIT AND SHOW THE LIGHTING LEVELS FOR | | EGRESS PATHS FOR STAIRS UNDER NORMAL AND EMERGENCY | | CONDITIONS PER LS 1017.8.1.3 AND 7.9.2.2. | | THE ONLY SUBMITTED LEVELS ARE THE LEVELS UNDER | | EMERGENCY WHICH ARE OK, HOWEVER NO LEVELS UNDER NORMAL. | | THE NORMAL LIGHTING LEVELS FOR STAIRS IS TEN FOLD WHAT | | IS REQUIRED AS A MINIMUM UNDER EMERGENCY. | | ONCE AGAIN, PLEASE SEE 7.8.1.3 WHICH REQUIRES * 10FT | | CANDLES MINIMUM. THE FOLLOWING IS TEXT WHICH HAS BEEN | | CUT AND PASTED DIRECTLY FROM NFPA-101 2003. | | *** | | 7.8.1.3* THE FLOORS AND OTHER WALKING SURFACES WITHIN | | AN EXIT AND WITHIN THE PORTIONS OF THE EXIT ACCESS AND | | EXIT DISCHARGE DESIGNATED IN 7.8.1.1 SHALL BE | | ILLUMINATED AS FOLLOWS: | | (1)DURING CONDITIONS OF STAIR USE, THE MINIMUM | | ILLUMINATION FOR NEW STAIRS SHALL BE AT LEAST 108 LUX | | (10 FT-CANDLE), MEASURED AT THE WALKING SURFACES. | | | | PLEASE SUBMIT | | | | 2) NOTE: PLEASE SEE 700.12F FOR CIRCUITING OF EMERGENCY | | OR EXIT LIGHTS. THERE ARE EXCEPTIONS HOWEVER BASED ON | | THE LIGHTING AND CIRCUITING ON PLANS THE EXIT LIGHTS IN | | MAIN ENTRANCE AREA NEED TO BE CIRCUITED AHEAD OF ANY | | SWITCHING OR CONTROL DEVICES AND TO LOCAL BRANCH | | CIRCUIT. | | PLEASE THERE IS THE OCTAGONAL NOTE #1 ON THE NHP-8 | | CIRCUIT IN MAIN LOBBY, HOWEVER OCTAGONAL NOTE #1 SHOWS | | THIS AS *NOT USED*. | | PLEASE COORDINATE. | | | | | | PLEASE SUBMIT THE ABOVE. SHEETS EE-001, EP-101, EP-102 | | AND EC-102 APPEAR TO BE OK AT THIS TIME. THE OTHER | | SHEETS SUCH AS RISER SHEET WHICH SHOWS LOADS AND PANEL | | SCHEDULES WILL BE GETTING REVISED BASED ON NOTES | | ABOVE. | | REDLINED NEC 517.1 AS THIS APPLIES TO OCCUPANCY AND | | SCOPE OF WORK. | | ONLY SHEETS NOTED AS EE-001, EP-101, EP-102 AND EC-102 | | ARE BEING STAMPED. ONE COPY OF THESE SHEETS ARE REMOVED | | FROM ONE SET AND KEPT FOR FILE SET OF PLANS. ONE SET OF | | SHEETS ARE GIVEN BACK FOR THE CONTRACTORS ON-SITE SET. | | | | ** IF THERE ARE QUESTIONS, PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | 2008-02-14 19:38:48 | 2008-02-14 19:38:49 | | | | NOTES TO FOLLOW ONCE COMPLETED. SOME SHEETS ARE OK, | | SOME REMAIN WITH COMMENTS. | 2008-02-14 19:27:50 | 2008-02-14 19:27:50 | | | | IN ELEC FOR REVIEW, PLANS CONTAINS REVISIONS FOR FIRE, | | MECH, BLDG ALSO NOT ONLY ELECTRICAL AS INDICATED ON | | COVER SHEET. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
7 |
Status |
P |
Date |
2008-01-24 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-01-24 |
Time |
12:28 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-01-24 |
Time |
12:28 |
Sent To |
B |
|
Notes |
2008-01-24 12:29:14 | STAMPED THREE SHEETS LEFT FROM PREVIOUS SETS. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
6 |
Status |
P |
Date |
2008-01-09 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-01-09 |
Time |
13:38 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-01-09 |
Time |
13:37 |
Sent To |
|
|
Notes |
2008-01-09 13:38:12 | | | ** THE FOLLOWING WILL BE ATTACHED AS PROVISO. | | | | 1) NOTE: PLEASE SEE THE LIGHTING LEVELS IN STAIRS WILL | | BE REQUIRED TO SHOW 10FT CANDLES UNDER NORMAL FOR A | | MINIMUM AND IS PERMITTED DOWN TO 1FT CANDLE UNDER | | EMERGENCY. | | PLEASE SEE 7.8.1.3, 7.9.2.2. | | PLANS SHOWS LEVELS ABOVE 10FT CANDLES FOR BOTH. THIS | | INCLUDES A NEW UPS/IPS SYSTEM WHICH IS NOT REQUIRED. | | ENGINEERS MENTIONED SYSTEM WILL BE REMOVED. | | | | 2) NOTE: PLEASE SEE THE CIRCUITING FOR REAR STAIRS AND | | NOTES FOR LIGHTING AS NOTED FOR NHP-6 AND NHP-8 WILL BE | | REQUIRED TO BE UPDATED. | | | | 3) NOTE: MAXIMUM TIMES NOT SHOWN ON SYMBOL LEGEND FOR | | OC DEVICE. | | MAXIMUM TIME TO BE 30MINS PER 13-415.1.ABC.1.1. | | | | 4) NOTE: MISSING OC DEVICE IN ROOM 159, RED-LINED PER | | 13-415.1.ABC.1.1 AND .1.2. | | | | IF THERE ARE ANY QUESTIONS, PLEASE ONCE AGAIN CONTACT | | THIS OFFICE/REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
5 |
Status |
F |
Date |
2008-01-07 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-01-07 |
Time |
16:25 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-01-07 |
Time |
16:25 |
Sent To |
|
|
Notes |
2008-01-07 16:26:15 | *** TEMP FAILED STATUS*** | | | | 1) NOTE: 2ND SET OF PLANS MISSING SHEET EP101 AND | | EP102. CALLED ARCHITECT AND WILL FED-EX NEW SHEETS TO | | OFFICE. | | | | | | | | ** THE FOLLOWING WILL BE ATTACHED AS PROVISO. | | | | 1) NOTE: PLEASE SEE THE LIGHTING LEVELS IN STAIRS WILL | | BE REQUIRED TO SHOW 10FT CANDLES UNDER NORMAL FOR A | | MINIMUM AND IS PERMITTED DOWN TO 1FT CANDLE UNDER | | EMERGENCY. | | PLEASE SEE 7.8.1.3, 7.9.2.2. | | PLANS SHOWS LEVELS ABOVE 10FT CANDLES FOR BOTH. THIS | | INCLUDES A NEW UPS/IPS SYSTEM WHICH IS NOT REQUIRED. | | ENGINEERS MENTIONED SYSTEM WILL BE REMOVED. | | | | 2) NOTE: PLEASE SEE THE CIRCUITING FOR REAR STAIRS AND | | NOTES FOR LIGHTING AS NOTED FOR NHP-6 AND NHP-8 WILL BE | | REQUIRED TO BE UPDATED. | | | | 3) NOTE: MAXIMUM TIMES NOT SHOWN ON SYMBOL LEGEND FOR | | OC DEVICE. | | MAXIMUM TIME TO BE 30MINS PER 13-415.1.ABC.1.1. | | | | 4) NOTE: MISSING OC DEVICE IN ROOM 159, RED-LINED PER | | 13-415.1.ABC.1.1 AND .1.2. | | | | IF THERE ARE ANY QUESTIONS, PLEASE ONCE AGAIN CONTACT | | THIS OFFICE/REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
F |
Date |
2007-12-23 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-12-23 |
Time |
11:37 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-12-22 |
Time |
17:04 |
Sent To |
|
|
Notes |
2007-12-23 11:37:35 | 2007-12-23 11:37:35 | | ** DENIED4TH ** | | | | ** PLANS CONTAIN SOME ITEMS WHICH MAY BE REDLINED AND | | WILL NEED TO BE REVISED BEFORE ROUGH HOWEVER PLEASE SEE | | SOME ITEMS BELOW WHICH MUST BE DONE AT THIS TIME. THE | | NOTES WITH ** MUST BE ADDRESSED AT THIS TIME. THE NOTES | | WITHOUT ** WILL STILL NEED TO BE ADDRESSED, HOWEVER MAY | | BE DONE AT THIS TIME OR BEFORE ROUGH. | | | | | | ** 1) NOTE: PLEASE SEE THE RESPONSE LETTER MENTIONS | | LIGHTING PERFORMANCE DONE UNDER TABLE *B* FOR SPACE BY | | SPACE HOWEVER THERE ARE ALSO SHEETS FOR FORM 400C? | | PLEASE KNOW THAT IN EITHER CASE, THE SEPARATE LIGHTING | | PERFORMANCE CALCULATIONS SUBMITTED EACH MUST CONTAIN A | | COMPLETED TITLE BLOCK FROM THE DESIGN FIRM/ENGINEER OF | | RECORD ALONG WITH EACH SHEET SIGNED, DATED AND SEALED. | | PLEASE SEE FAC 61G15-23.002, FS 471.023. | | PLEASE KNOW THESE MAY BE SENT AND PLACED WITH PLANS AS | | THE CALCULATIONS ARE OK. | | AS NEW FORM 400C IS NOW BEING SUBMITTED FOR THE FIRST | | TIME, MECHANICAL REVIEW WILL BE REQUIRED EVEN AS THIS | | WAS PREVIOUSLY PASSED. | | | | 2) NOTE: PLEASE CLARIFY WHERE THE MAXIMUM TIMES ON | | OCCUPANCY SENSORS ARE? | | PLEASE CLARIFY TYPE OF OCCUPANCY DEVICE. IR? ETC | | 13-415.1.ABC.1.1, .1.2 | | PLEASE SEE MISSING DEVICE FROM ROOM 159. | | | | ** 3) NOTE: PLEASE CLARIFY THE NEW UPS WHICH HAS NOW | | BEEN ADDED TO PLANS WHICH WAS NOT ON PREVIOUS PLANS. | | THE RESPONSE LETTER MENTIONS THE FIXTURES WOULD NOT | | PROVIDE THE OUTPUT FOR MINIMUM LIGHTING LEVELS, HOWEVER | | AS MENTIONED ON ALL PREVIOUS REVIEWS THE LIGHTING | | LEVELS UNDER NORMAL FOR STAIRS IS 10FT CANDLES PER | | 7.8.1.3 AND IS PERMITTED TO GO DOWN TO 1FT CANDLE UNDER | | EMERGENCY CONDITIONS PER 7.9.2.2. THE AVERAGE FT CANDLE | | LEVELS UNDER EMERGENCY ARE NOT SHOWN HOWEVER BASED ON | | THE NUMBER OF POINTS AND THE LEVELS SHOWN IT SEEMS | | PERHAPS PREVIOUS NOTES WERE NOT TYPED IN A MANOR WHICH | | WAS UNDERSTOOD. | | PLEASE CLARIFY RESPONSE AND LIGHTING LEVELS BEING | | SHOWN. PLEASE SEE THE | | REAR STAIR ON PLANS CONTAIN A NOTE WHICH MENTIONS TO | | PLACE ON LOBBY 100 NHP-6 CIRCUIT YET THIS SAME REAR | | STAIR HAS A NOTE TO CIRCUIT LIGHTS TO NHP-8. HOW WILL | | THIS WORK AS THIS PLACES 220/240V ON FIXTURES. THIS | | MUST BE A MISPRINT. | | PLEASE SEE THE PANEL SCHEDULE DOES NOT INDICATE ANY | | CIRCUITING TO THE UPS AND SHOWS CIRCUITS TO FIXTURE | | UNITS. | | PLEASE CALL TO GO OVER THIS FOR LIGHTING. | | | | | | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY | | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE | | DO NOT HESITATE IN CONTACTING THIS OFFICE. | | PLEASE SEE BELOW FOR CONTACT INFORMATION. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | 2007-12-23 11:37:07 | 2007-12-23 09:57:07 | | REVIEW COMMENCED. | 2007-12-22 17:04:41 | 2007-12-22 17:04:41 | | | | IN ELECTRICAL FOR REVIEW. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
F |
Date |
2007-10-29 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-10-29 |
Time |
15:24 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-10-27 |
Time |
12:23 |
Sent To |
|
|
Notes |
2007-10-29 15:25:04 | | | ** DENIED 3RD REVIEW ** | | | | ** PLEASE SEE NOTES FROM PREVIOUS TWO REVIEWS WHICH | | STILL NEED TO BE ADDRESSED. | | PLEASE SEE AS STATED ON PREVIOUS REVIEWS, REVIEW NOTES | | CAN ONLY BE GIVEN ON PLANS AND DOCUMENTATION SUBMITTED. | | AS NOTED THERE MAY ALSO BE NEW NOTES FOR ITEMS WHICH | | COULD NOT BE REVIEWED PREVIOUSLY. | | | | 1) NOTE: PLEASE SEE AS NOTED ON PREVIOUS REVIEW, PLEASE | | INDICATE AREAS WHICH WIRING METHODS FOR NEC 517 WILL BE | | REQUIRED. PLEASE SEE THE RESPONSE IN LETTER AND MEETING | | HELD BEFORE PLANS WERE SUBMITTED WAS THAT THE BUILDING | | WAS ONLY GOING TO BE BUSINESS AND ADMINISTRATIVE | | OFFICES. | | PLEASE KNOW THAT IT HAS COME TO OUR ATTENTION AND PER | | PLANS SUBMITTED THERE WILL BE ROOMS IN WHICH DOCTORS | | WILL BE DOING EXAMS ALONG WITH EQUIPMENT. THE OCCUPANCY | | DOES NEED TO BE DESIGNATED AS A HEALTH CARE FACILITY IN | | ORDER FOR WIRING METHODS IN 517 TO BE REQUIRED IN SOME | | ROOMS. PLEASE SEE AREAS SUCH AS THE DOCTOR'S ADMIN | | OFFICES, RECEPTION, HALLWAYS, ETC ARE NOT AREAS WHICH | | FALL UNDER 517, HOWEVER EXAM ROOMS AND THE LIKE ARE. | | PLEASE ADJUST NOTES AND WIRING METHODS PER 517. PLEASE | | SEE 517.1, 517.10 AND 517.13. | | PLEASE SEE THE FOLLOWING WHICH IS TAKEN DIRECTLY FROM | | THE NEC COMMENTARY. | | | | *THE REQUIREMENTS OF ARTICLE 517 ARE INTENDED TO APPLY | | TO ALL TYPES OF HEALTH CARE FACILITIES. THE | | REQUIREMENTS FOR EACH TYPE OF HEALTH CARE FACILITY ARE | | NEVERTHELESS INTENDED TO BE APPLIED IN A VERY SPECIFIC | | MANNER. FOR EXAMPLE, IN A SUITE OF DOCTORS' OFFICES | | WITHIN AN OFFICE BUILDING, A DOCTOR'S BUSINESS OFFICE | | WOULD BE TREATED AS AN ORDINARY OCCUPANCY AND WOULD BE | | REQUIRED TO MEET ONLY THE APPLICABLE PORTIONS OF OTHER | | PARTS OF THIS CODE. HOWEVER, THE EXAMINING ROOMS | | ATTACHED TO THE DOCTOR'S BUSINESS OFFICE WOULD BE | | REQUIRED TO MEET THE PROVISIONS OF PART II AND 517.45 | | IN ARTICLE 517.* | | | | THIS IS ONLY ONE PART OF THE NEC PROVIDED. PLEASE KNOW | | THAT ANY WORK DONE UNDER SHELL/ADDITION PHASE II PERMIT | | MAY BE AFFECTED. | | | | 2) NOTE: PLEASE SEE FBC CHAPTER 13 (ALL). PLEASE SEE | | THAT THE TWO PREVIOUS REVIEWS MENTIONED THERE WERE | | SEVERAL SECTIONS OF THIS CHAPTER WHICH NEEDED TO BE | | ADDRESSED AS DESIGN FOR CHAPTER 13 LIGHTING CONTROLS | | HAD NOT BEEN SHOWN. | | PLEASE SEE THERE ARE STILL ITEMS FOR SEVERAL LOCATIONS | | WHICH HAVE NOT HAD THE COMMENTS ADDRESSED. | | | | A) PLEASE SEE THERE ARE SEVERAL SEPARATE SPACES WHERE | | NO LIGHTING CONTROLS FOR OVER RIDES ARE SHOWN. PLEASE | | SEE PREVIOUS TWO REVIEWS SECTION 13-415.1.ABC.1.2. | | PLEASE SEE FOR EXAMPLE SOME OF THESE LOCATIONS ARE THE | | SAME IN WHICH WAS REDLINED ON PREVIOUS PLANS. PLEASE | | SEE 123, 183, 161, 162, 159, 131, 110, 112, 209, 208 | | ETC. THESE ARE NOTED FOR SOME OF THESE LOCATIONS WHICH | | CONTAIN THE FLOOR TO CEILING HEIGHT PARTITIONS AS | | STATED IN THE CODE; HOWEVER NO OVER RIDE DEVICES ARE | | SHOWN. | | | | B) PLEASE SEE AREAS IN WHICH THE OCCUPANT MUST SEE THE | | LIGHTING IN WHICH IS BEING OVER RIDDEN OR CONTROLLED. | | PLEASE SEE THERE IS AN EXCEPTION HOWEVER NO DETAILS FOR | | THE EXCEPTION FOR INDICATOR/PILOT LIGHTS ARE SHOWN. | | PLEASE SEE 13-415.1.ABC.1.1, .1.2. PLEASE SEE FOR | | EXAMPLE THE FIRST FLOOR FOR CIRCUITS 60, 30 AND 32 | | WHICH ARE LV SWITCHES SHOWN AS THE LOBBY AREA HOWEVER | | FROM THIS LOCATION THE OCCUPANT CAN NOT SEE THE | | LIGHTING THEY ARE CONTROLLING. | | PLEASE SEE TENANT SPACES ALSO FOR EXAMPLE AS THE COMMON | | AREA LIGHTING DOES NOT INDICATE ANY OVER RIDE | | CONTROL(S). THE OCCUPANT ENTERING INTO THE SPACE/AREA | | NEEDS TO HAVE AN OVER RIDE OF THE TIMED SCHEDULED | | SYSTEM. | | PLEASE SEE FOR EXAMPLE THE OCTAGONAL NOTE #4 ON SHEET | | EL-101 AS THIS MENTIONS CIRCUIT NHP-11 YET THIS CIRCUIT | | ON PANEL SCHEDULE IS FOR THE 2ND FLOOR AND FOR A | | RECEPTACLE CIRCUIT AND NOTED FOR SHELL. HOW IS THIS | | POSSIBLE? | | PLEASE ALSO SEE FOR EXAMPLE THE LIGHTING WHICH IS SHOWN | | FOR HOUSE FOR SHELL FOR SECOND FLOOR WHICH DOES NOT | | SHOW ANY OVER RIDE DEVICES. | | PLEASE ALSO SEE FOR EXAMPLE THE LOBBY AREA WHICH IS | | BEING ILLUMINATED BY LIGHTING IN THE CEILING FROM THE | | 2ND FLOOR LIGHTING CONTROL PANEL. WHERE ARE THE OVER | | RIDE DEVICES FOR THE FRONT ENTRANCE AREA? THIS IS AN | | OPEN AREA FOR THE FIRST FLOOR. | | PLEASE CLARIFY CIRCUITING FOR FOUNDATION ROOM, | | CONFERENCE ROOM ON SECOND FLOOR AS THESE ARE SHOWN TO | | CIRCUIT 42 AND ALSO A 42A AND 42B? THIS IS UNCLEAR HOW | | THESE ARE CIRCUITED AS PANEL SCHEDULE IS BEING ASSUMED | | TO BE NHP2. THIS PANEL SCHEDULE ONLY INDICATES ONE #42 | | CIRCUIT. *LIGHTING*. | | THE FLOORS ARE REQUIRED TO BE SEPARATED. | | THESE ARE SOME EXAMPLES, AND IN NO WAY NOTES ALL | | POSSIBLE SCENERIOS. | | ** PLEASE SEE THAT THERE ARE SEVERAL AREAS IN WHICH | | LIGHTING CONTROLS ARE NOT YET COMPLETE FOR CHAPTER 13 | | AS NOTED. | | | | C) PLEASE SEE THE METHOD OF CALCULATIONS SUBMITTED AS | | *WHOLE BUILDING * METHOD *A* MAY NOT BE USED. THIS IS | | AN EXISTING BUILDING WHICH IS CURRENTLY BEING REMODELED | | UNDER METHOD *B*. | | THIS ALSO FALLS UNDER RENOVATED BUILDINGS PER | | 13-101.1.3. PLEASE SEE AS STATED ON PREVIOUS REVIEW THE | | METHOD CALCULATION WOULD DEPEND ON KNOWN FACTORS AND AS | | THERE ARE STILL PORTIONS OF THIS BUILDING NOT | | COMPLETED, METHOD *A* COULD NOT BE USED EITHER PER | | 13-101.6. | | PLEASE SUBMIT THE CORRECT METHOD WHICH AS STATED IN THE | | TWO SECTIONS GIVEN COULD BE *B* OR *C*.13-415.1.B.1 | | PLEASE SEE LIGHTING PERFORMANCE CALCULATIONS SHALL MEET | | 13-415. | | ** PLEASE SEE MECHANICAL COMMENTS AS THIS MAY ALSO BE | | PART OF THEIR REVIEW NOTES. | | | | D) PLEASE SUBMIT COMPLETE INFORMATION FOR LIGHTING | | CONTROL PANELS/SYSTEM BEING PROPOSED. PLEASE SEE THE | | PLANS ONLY FOR A *LIGHTING CONTROL PANEL* WHICH DOES | | NOT PROVIDE THE INFORMATION AS NEEDED FOR COMPLIANCE | | WITH SECTIONS A AND B OF THIS SAME NOTE #2 | | | | E) PLEASE PROVIDE NOTE ON PLANS FOR 13-413.1.ABC.2 | | WHICH CONTAINS SUB SECTIONS 2.1 AND 2.2. | | THIS WAS RECENTLY CONFIRMED WITH THE FLORIDA BUILDING | | COMMISSION. | | | | 3) NOTE: PLANS NOW INDICATE THE PHOTO-METRICS FOR | | EGRESS PATHS FOR NORMAL CONDITIONS, HOWEVER COULD NOT | | LOCATE LEVELS FOR EMERGENCY CONDITIONS. THIS COMMENT IS | | NOT FOR STAIRS AS THE SAME FIXTURES ARE FOR BOTH | | CONDITIONS. | | PLEASE CLARIFY THE EGRESS PATHS FOR CORRIDORS AS THE | | LEVELS ARE DONE SHOWING GENERAL FIXTURES AS WELL AS | | EMERGENCY. | | LS 101 7.8 AND 7.9. | | FAC 61G15-33.004 | | | | 4) NOTE: PLEASE SEE THE ENLARGED ELECTRICAL ROOMS WHICH | | ARE ON EE-401. PLEASE CLARIFY THE DESIGNATIONS AS ROOM | | #216 IS BEING NOTED FOR 2ND FLOOR HOWEVER 216 ON THE | | SECOND FLOOR IS A CORRIDOR. PLEASE SEE THE ROOM FOR THE | | ELECTRICAL CLOSET IS SHOWN AS 203 ON EL-102. THIS IS A | | MINOR COMMENT HOWEVER AS PLANS ARE COMING BACK FOR | | OTHER COMMENTS, PLEASE CORRECT AT THIS TIME. | | | | 5) NOTE: PLEASE SEE THE PREVIOUS REVIEW GAVE NOTICE TO | | FLORIDA STATUTES 553.80(2)(B). THERE ARE CODES WHICH | | WERE REPEATED ONCE AGAIN WHICH WERE NOTED THREE TIMES. | | THERE WILL BE A FEE ASSESSED AS REQUIRED BY THE | | STATUTES. THE FEE AMOUNT IS DUE BEFORE PLANS MAY BE | | RESUBMITTED. IT IS RECOMMENDED THAT THE COMMENTS ARE | | GONE OVER BEFORE PLANS ARE RESUBMITTED. ONE COPY OF THE | | ELECTRICAL SHEETS IS BEING RETAINED BY THIS OFFICE. | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | REVIEWER. | | | | ** IMPORTANT** | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR | | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL | | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS | | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT | | LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | SHOULD BE SUBMITTED FOR REFERENCE. | | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY | | DELAYS. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | 2007-10-29 10:17:40 | | | | | REVIEW COMMENCED. | 2007-10-27 12:23:51 | 2007-10-27 12:23:51 | | | | IN ELEC FOR REVIEW |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2007-08-25 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-08-25 |
Time |
16:54 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-08-25 |
Time |
14:23 |
Sent To |
|
|
Notes |
2007-08-25 16:54:22 | 2007-08-25 16:54:22 | | | | *** DENIED 2ND REVIEW *** | | | | PALM HEALTH CARE | | PHASE 3 INTERIOR BUILD OUT. | | | | | | ** PLEASE SEE THERE NOTES FROM PREVIOUS REVIEW ARE | | STILL IN NEED OF ADDRESSING ALONG WITH SOME NEW | | COMMENTS BASED ON INFORMATION NOW PLACED ON PLANS OR | | INFORMATION NOW SUBMITTED WHICH WAS NOT ON PREVIOUS | | PLANS. | | | | ** THERE ARE STILL ITEMS WHICH WERE NOT SUBMITTED; | | THEREFORE A REVIEW FOR CODE COMPLIANCE CAN NOT BE DONE. | | WHEN INFORMATION PREVIOUSLY REQUESTED IS NOT SUBMITTED | | AND A REVIEW OF THOSE ITEMS CAN NOT BE DONE, THEN MORE | | OFTEN THAN NOT THERE ARE NEW COMMENTS TWO, THREE OR | | FOUR REVIEWS LATER AS THE INFORMATION WAS NEVER | | SUBMITTED FOR REVIEW. PLEASE SEE NOTES BELOW. (#3) | | | | | | 1) NOTE:THIS NOTE WILL REMAIN FROM PREVIOUS REVIEW AS | | THE SHELL PLANS HAVE NOT YET BEEN PERMITTED AND CHANGES | | WILL BE FORTH COMING BASED ON COMMENTS FROM THIS REVIEW | | AND PREVIOUS REVIEW ON SHELL PERMIT REVIEW. | | PLEASE KNOW THAT IT IS MOST IMPORTANT TO COORDINATE | | PLANS WITH THE PLANS WHICH WERE SUBMITTED FOR SHELL | | BUILDING AND ADDITION. | | FBC 106.3.5.1.2, 106.1.2 | | | | 2) NOTE:PLEASE SEE THIS IS THE 2ND REQUEST: PLEASE | | SEE THE ENERGY CALCULATIONS SUBMITTED FOR THE BUILD OUT | | OF SPACE. | | PLEASE SEE THAT THE RESPONSE LETTER MENTIONS THESE WILL | | BE SUBMITTED AND DONE HOWEVER PLEASE SUBMIT *TWO* | | COMPLETE SETS OF ENERGY CALCULATIONS, SIGNED DATED AND | | SEALED BY THE RESPONSIBLE DESIGNER(S) OF RECORD AS | | REQUIRED PER FBC 13-103.1.1.1 , FAC 61G15-23.002, FS | | 471.025, 481.221. | | | | PLEASE KNOW THAT BASED ON THE BUILD OUT BEING SUBMITTED | | FOR PERMIT, THE KNOWN ENERGY CONSUMPTION ETC AND METHOD | | FOR SHELL PERMIT WOULD CHANGE. | | PLEASE BE SURE TO COORDINATE ALL FIXTURES, FIXTURE | | WATTAGES, TYPE OF FIXTURES, CONTROLS AND NUMBER OF | | FIXTURES BETWEEN PLANS AND ENERGY CALCULATIONS. AS THE | | CONTROLS AND AREAS ON THE PLANS MAY CHANGE THIS MAY | | AFFECT THE CALCULATIONS. . | | PLEASE SEE ELECTRIC TYPE WATER HEATERS FOR EXAMPLE ARE | | BEING SHOWN ON THE IDR, YET THE PLANS DO NOT SHOW | | THIS? | | PLEASE SUBMIT AND SHOW DETAILED CODE COMPLIANCE FOR | | LIGHTING CONTROLS AS REQUIRED PER CHAPTER 13 OF THE | | 2004 FBC. PLEASE SEE THAT SOME REFERENCES TO A LIGHTING | | CONTROL PANEL IS BEING NOTED HOWEVER THERE ARE TOO MANY | | AREAS WHICH ARE MISSING THE REQUIRED OVER RIDES FOR | | SPACES AND ZONES. PLEASE KNOW THAT ONE LIGHTING CONTROL | | PANEL MAY NOT FEED TWO FLOORS AS THE LCP SUBMITTED | | INDICATES. | | | | PLEASE SEE THE ELECTRICAL LIGHTING PLANS SUBMITTED ARE | | NOT COMPLETE WITH LIGHTING CONTROLS NOT ONLY REQUIRED | | PER CHAPTER 13, BUT MANY ROOMS AND AREAS DO NOT | | INDICATE ANY CONTROL FOR LIGHTING AT ALL. SOME | | LOCATIONS SHOWS A SYMBOL FOR A SWITCH HOWEVER MOST DO | | NOT SHOW ANY DEVICES | | PLEASE KNOW THAT STATING ONE NOTE (#5) WHICH MENTIONS | | OCCUPANCY DEVICE REQUIRED, DOES NOT SHOW CODE | | COMPLIANCE. | | PLEASE SHOW SCHEDULE IF A SYSTEM IS DESIGNED, OR | | INSTALLED. PLEASE INDICATE ALL MAXIMUM TIMES ON OVER | | RIDE DEVICES; PLEASE SHOW ALL DEVICES ON PLANS SO THAT | | COVERAGE FOR CODE COMPLIANCE AND SPACE CONTROLS CAN BE | | REVIEWED. | | 13-415.1.ABC.1.1, .1.2, .1.3. 13-415.1.AB.1.1, | | 13-415.2 | | PLEASE PROVIDE WORST CASE VOLTAGE DROP FOR | | BRANCH/CIRCUITS AND FEEDERS PER 13-413.1ABC.1.1, .1.2. | | THE VD FOR FEEDERS WERE LOCATED ON THE RISER HOWEVER | | PLEASE CLARIFY WHERE THE WORST CASE FOR BRANCH | | CIRCUIT(S) ARE SHOWN. | | THIS INFORMATION IS REQUIRED TO BE SIGNED, DATED AND | | SEALED BY THE RESPONSIBLE DESIGN PROFESSIONAL ALONG | | WITH TITLE BLOCK INFORMATION ON PLANS AND SHEETS. | | 13-103.1.1.1 | | | | ** PLEASE KNOW AT THIS TIME PLANS DO NOT INDICATE | | COMPLIANCE WITH THE 2004 FBC CHAPTER 13 AND MANY ITEMS | | REQUIRED FOR REVIEW ARE MISSING. PLEASE KNOW THERE MAY | | BE NEW COMMENTS ON THE FOLLOWING REVIEW AS INFORMATION | | WAS NOT SUBMITTED. | | PLEASE SEE CHAPTER 13 IN THE 2004 FBC . | | | | 3) NOTE: PLEASE SEE THE PREVIOUS REVIEW REQUESTED | | PHOTO-METRICS. SOME OF THESE WERE ADDED HOWEVER NEED | | LEVELS UNDER NORMAL AND EMERGENCY CONDITIONS. FLORIDA | | ADMINISTRATIVE CODE 61G15-33.004 | | ** PREVIOUS REVIEW NOTE: PLEASE SEE THAT THE PLANS ARE | | MISSING THE REQUIRED EGRESS PHOTO-METRICS AS PREVIOUSLY | | REQUESTED ON SHELL/ADDITION PLANS. AS THE | | SHELL/ADDITION PLANS ARE NOT ISSUED AT THIS TIME AND DO | | NOT INDICATE COMPLIANCE, PLEASE SUBMIT THE REQUIRED PER | | NFPA-101 7.8.1.3, 7.9.2.2 | | PLEASE ALSO SEE THE MULTI-USE BATHROOMS WILL BE | | REQUIRED TO CONTAIN A BATTERY BACK UP FIXTURE OF SOME | | TYPE. | | PLEASE SEE NOTES UNDER MAIN BUILDING SHELL/ADDITION | | PERMIT. | | | | 4) NOTE:PLEASE SEE THE RISER HAS NOW BEEN COMPLETELY | | CHANGED AND REVISED AND HAD CREATED SOME NEW COMMENTS. | | THERE ARE ALSO SOME COMMENTS WHICH STILL REMAIN FROM | | PREVIOUS REVIEW. | | PLEASE SEE THE RISER NOW SHOWS TWO NEW 400AMP MAINS | | FROM THE SUPPOSED EXISTING GUTTER FEEDING A NEW GUTTER. | | NO INFORMATION FOR THESE MAINS WAS SUBMITTED. NO TAP | | CONDUCTOR SIZES FROM THE EXISTING GUTTER, NOT | | CONDUCTORS FROM THE MAINS TO THE NEW GUTTER. (240.21, | | 240.4, 310.16) PLEASE VERIFY THE RISER AS THIS SHOWS NO | | METERING DEVICES ON THESE TWO MAINS. PLEASE OBTAIN | | INFORMATION FROM FPL. | | PREVIOUS NOTE # 5 REQUESTED THE RISER TO BE COMPLETE | | FOR ALL INFORMATION. | | | | 5) NOTE: PLEASE SEE AIC RATINGS ARE NOT SUBMITTED FOR | | ALL EQUIPMENT AS REQUESTED ON THE PREVIOUS REVIEW. | | STATING THE AVAILABLE FAULT CURRENT AT MOST LOCATIONS | | ON THE RISER IS FINE HOWEVER THIS DOES NOT GIVE THE | | INFORMATION FOR THE REQUIRED MINIMUM RATINGS FOR | | EQUIPMENT. | | 110.9 | | FBC 106.3.5.1.2 | | **REQUESTED ON PREVIOUS REVIEW NOTE # 5 | | | | 6) NOTE: PLEASE SEE THE RISER NOW SHOWS THE *GROUNDING | | ELECTRODE CONDUCTOR* AFTER THE FIRST MEANS OF | | DISCONNECT WHICH IS NOT PERMITTED AND NOT INSTALLED AS | | THE CODE REQUIRES PER 250.6, 250.24, 250.50 ETC. PLEASE | | SEE THIS WAS REQUESTED ON THE PREVIOUS REVIEW NOTE #5 | | | | 7) NOTE: PLEASE SEE MISSING *EQUIPMENT GROUNDING | | CONDUCTORS AFTER THE FIRST MEANS OF DISCONNECT AS | | REQUIRED PER 250.110, 250.24, 250.122. | | | | 8) NOTE: PLEASE SEE THE RISER IS STILL IN QUESTION AS | | SHOWN AS THE RISER NOW CONTAINS TWO 400AMP MAINS AND A | | 800AMP MAIN ON SERVICE ENTRANCE CONDUCTORS RATED AT | | 950AMPS. | | THE SERVICE CALCULATIONS SUBMITTED ARE BASED ON SOME | | AREAS AS SHELL AND NOT CLEAR ON THE COMPLETE SCOPE AND | | LOADS AND WHY 1600AMPS WORTH OF MAINS ARE BEING PLACED | | ON A SERVICE ONLY RATED AT 975AMPS BASED ON THE | | CONDUCTORS. | | THE RISER IS ALSO STILL IN QUESTION AS BASED ON THE | | TOTAL AMOUNT OF METER AND MAIN DISCONNECTS SHOWN. THE | | RISER LENDS TO TWO TENANTS ON THE FIRST FLOOR HOWEVER | | THE BUILD OUT PLANS ONLY INDICATE ONE TENANT. IF THIS | | IS INDEED ONE TENANT AND OCCUPANT, ONLY ONE METER IS | | PERMITTED. | | PLEASE ALSO SEE THE RISER LENDS TO THREE POSSIBLE | | TENANTS UPSTAIRS, YET THE PLANS ONLY LEND TO TWO. THE | | AMOUNT OF METERS PERMITTED TO EACH TENANT IS ONE. | | (HOUSE IS NIC) | | THIS INFORMATION WILL BE SENT TO ZONING AND BUILDING | | BASED ON OCCUPANCY AND TENANT SEPARATIONS ETC. PLEASE | | CLEAR UP RISER AND PROVIDE INFORMATION FOR THIS AS | | SHOWN. | | 215.5, 230.70, 230 ETC | | 90.4 | | FBC 106.1.2, 106.3.5.1.2 FOR ADDITIONAL INFORMATION | | NEEDED. | | | | 9) NOTE:THIS IS FROM PREVIOUS REVIEW NOTE #9. PLEASE | | SEE FBC 2004 11-4.28.1, .2 AND .3(4) AND STATE THE | | MINIMUM HORN, STROBE LEVELS ON PLANS FOR ADA REQUIRED | | AREAS. DEVICES ARE BEING SHOWN ON PLANS/LEGEND. PLEASE | | CORRELATE WITH PLANS, AND FA SHEETS SUBMITTED. | | ** PLEASE KNOW THAT THE FIRE ALARM WILL BE UNDER A | | SEPARATE PERMIT HOWEVER THE BASE LIFE SAFETY SYSTEM IS | | REQUIRED ON BASE PLANS AS SHOWN. DO NOT REMOVE FROM | | SETS. | | FBC 106.3.5.1.2 | | ** THE RESPONSE MENTIONS TO SEE THE HORNS ARE SET AT | | 1WATT AND CD LEVELS AT 15CD. THE RESPONSE LETTER | | SPECIFICALLY STATES TO SEE *EC 001* HOWEVER PLEASE SEE | | THE PLANS SUBMITTED CONTAIN A EE-001 AND EC-301 HOWEVER | | NO EC-001. IN EITHER CASE THESE MINIMUM LEVELS COULD | | NOT BE LOCATED ON THESE SHEETS. | | THE LEVELS ARE SUBSTANTIALLY HIGHER THAN THAT OF | | NFPA-72 | | | | 10) NOTE:SAME AS PREVIOUS REVIEW NOTE #10: PLEASE | | KNOW THAT THE LOW VOLTAGE SECURITY PLANS FOR CAMERAS | | ETC ARE TO BE UNDER SEPARATE PERMITS. | | THE RESPONSE LETTER SPECIFICALLY STATES THAT THIS IS | | NOT PART OF THE PACKAGE, HOWEVER PLEASE CLARIFY HOW AND | | WHY THESE PLANS ARE STILL BEING SUBMITTED. | | | | 11) NOTE: PREVIOUS NOTE #11: | | PLEASE COMPETE ALL CIRCUITING ON PLANS AND CORRELATE | | WITH THE SUBMITTED PANEL SCHEDULES. PLEASE BE SURE TO | | SEE PREVIOUS PLANS FOR SHELL BUILDING AND CIRCUITING | | PER 700.12F FOR ALL EMERGENCY AND EXIT LIGHTS. | | 106.1.2, | | 408.4 NEC.THE FOLLOWING TEXT IS TAKEN DIRECTLY FROM | | THE NEC. PLEASE BE SURE ALL AREAS, ROOMS DESIGNATIONS | | ETC COORDINATE WITH THE CIRCUITS ON PANEL SCHEDULES | | SPECIFIC. | | | | **SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO | | REQUIRE THAT THE IDENTIFICATION FOR EVERY CIRCUIT | | SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND | | CLEARLY STATE THE SPECIFIC PURPOSE FOR WHICH THE | | CIRCUIT IS USED. CIRCUITS USED FOR THE SAME PURPOSE | | MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR EXAMPLE, | | SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY OUTLETS IN | | THE KITCHEN, DINING ROOM, AND KITCHEN COUNTERTOPS. | | IDENTIFYING THE CIRCUITS AS SMALL APPLIANCE BRANCH | | CIRCUITS IS NOT ACCEPTABLE; INSTEAD, THEY SHOULD BE | | IDENTIFIED AS ``KITCHEN WALL RECEPTACLES,'' ``DINING | | ROOM FLOOR RECEPTACLE,'' OR ``KITCHEN COUNTERTOP | | RECEPTACLES LEFT OF SINK.'' CIRCUIT DIRECTORIES | | CONTAINING MULTIPLE ENTRIES WITH ONLY ``LIGHTS'' OR | | ``OUTLETS'' DO NOT PROVIDE THE SUFFICIENT DETAIL | | REQUIRED BY THIS SECTION.* | | 408.4, 310.16, 240.4 ETC | | FBC 106.3.5.4 | | | | ** PLEASE SEE THE SECTION OF THE COMMENTARY WAS ADDED | | TO POWER AND LIGHTING SHEETS WHICH IS NOT WHAT COMMENT | | WAS REQUESTING. PLEASE SEE THIS COMMENT WAS STATING THE | | CIRCUITS WHICH ARE ALREADY SHOWN ON THE SUBMITTED PANEL | | SCHEDULE WERE TO BE MORE SPECIFIC AND NOT TO ONLY STATE | | *OUTLET* OR *LIGHTING*. MAY USE ALPHA OR NUMERIC | | DESIGNATIONS OF CIRCUITS. | | PLEASE SEE THE PLANS WHICH HAD THIS NOT STATE ON PLANS | | ALSO IS QUOTING THE INCORRECT CODE SECTION. | | THIS APPEARS TO HAVE BEEN A MISPRINT. | | | | 12) NOTE:PLEASE SEE 517 OF THE NEC AND EXPAND ON ANY | | LOCATIONS PER 517 AND 517.13(A) AND (B) | | PLEASE EXPAND ON THE GROUNDING REQUIRED. | | THIS JURISDICTION HAS HAD SEVERAL INSTANCES WHERE | | CORRECT GROUNDING METHODS ARE NOT BEING DONE IN THE | | FIELD. WE ARE REQUIRING ADDITIONAL NOTES ON PLANS TO | | HELP ALLEVIATE POSSIBLE DELAYS IN PROJECTS. MANY TIMES | | THESE LOCATIONS HAVE TO BE COMPLETELY RE-WIRED DUE TO | | IMPROPER GROUNDING WHICH ONLY DELAYS AND HOLDS UP ALL | | INVOLVED. | | **MANY CONTRACTORS ARE AWARE OF CORRECT INSTALLATIONS | | IN MEDICAL OFFICES/PATIENT CARE AREAS, AND MANY ARE | | NOT. | | | | 13) NOTE: PLEASE COORDINATE PLANS WITH THE ELECTRICAL | | RISER DIAGRAM. | | PLEASE SEE THE MAIN ELECTRICAL ROOM LAYOUT DOES NOT | | CONTAIN ALL THE EQUIPMENT AS SHOWN ON RISER. PLEASE | | ALSO PROVIDE THE SIZES FOR THE GUTTER AS SHOWN. PLEASE | | SEE 110.26, 366. | | PLEASE SEE THE FOLLOWING EXTRACTED FROM THE NEC FOR USE | | OF READING AS THE GUTTER SHALL NOT EXTEND INTO THE | | WORKING CLEARANCE AREA BY MORE THAN 6 INCHES. | | | | *110.26(A)(3) | | (3) HEIGHT OF WORKING SPACE THE WORK SPACE SHALL BE | | CLEAR AND EXTEND FROM THE GRADE, FLOOR, OR PLATFORM TO | | THE HEIGHT REQUIRED BY 110.26(E). WITHIN THE HEIGHT | | REQUIREMENTS OF THIS SECTION, OTHER EQUIPMENT THAT IS | | ASSOCIATED WITH THE ELECTRICAL INSTALLATION AND IS | | LOCATED ABOVE OR BELOW THE ELECTRICAL EQUIPMENT SHALL | | BE PERMITTED TO EXTEND NOT MORE THAN 150 MM (6 IN.) | | BEYOND THE FRONT OF THE ELECTRICAL EQUIPMENT. | | ** COMMENTARY** | | IN ADDITION TO REQUIRING A WORKING SPACE TO BE CLEAR | | FROM THE FLOOR TO A HEIGHT OF 61/2 FT OR TO THE HEIGHT | | OF THE EQUIPMENT, WHICHEVER IS GREATER, 110.26(A)(3) | | PERMITS ELECTRICAL EQUIPMENT LOCATED ABOVE OR BELOW | | OTHER ELECTRICAL EQUIPMENT TO EXTEND INTO THE WORKING | | SPACE NOT MORE THAN 6 IN. THIS REQUIREMENT ALLOWS THE | | PLACEMENT OF A 12 IN. ? 12 IN. WIRE-WAY ON THE WALL | | DIRECTLY ABOVE OR BELOW A 6 IN. DEEP PANEL-BOARD | | WITHOUT IMPINGING ON THE WORKING SPACE OR COMPROMISING | | PRACTICAL WORKING CLEARANCES. THE REQUIREMENT CONTINUES | | TO PROHIBIT LARGE DIFFERENCES IN DEPTH OF EQUIPMENT | | BELOW OR ABOVE OTHER EQUIPMENT THAT SPECIFICALLY | | REQUIRES WORKING SPACE.** | | | | PLEASE SIZE GUTTERS ACCORDINGLY WHICH ARE BEING SHOWN | | DIRECTLY IN FRONT OF MAINS, EQUIPMENT AND METERS WHICH | | COULD BE A SAFETY HAZARD. | | | | 14) NOTE: PLEASE BE SURE TO GO OVER LOAD CALCULATIONS. | | PLEASE BE SURE TO SEE THE PREVIOUS REVIEW COMMENTS FOR | | ALL LOADS TO BE SHOWN. | | PLEASE SEE THE 2005 NEC FOR REQUIRED METHODS. 220.12, | | 220.14, 220.42, 220.44 AND ALL PREVIOUS SECTIONS AS | | PREVIOUSLY NOTED. | | PLEASE SUBMIT COMPLETE LOAD CALCULATIONS FOR SERVICE | | AND EACH OF THE PANELS AS BEING SHOWN EVEN THOSE BEING | | SET ASIDE FOR FUTURE USE. | | PLEASE SEE THE ENERGY CALCULATIONS INDICATE TWO | | ELECTRIC WATER HEATERS YET THE CALCULATIONS DO NOT | | INCLUDE THESE, PANEL SCHEDULES? PLEASE SEE 422.13 AS | | THESE ARE REQUIRED TO BE SHOWN AT 125%. | | PLEASE SEE ALL OF 220. | | PLEASE ALSO SEE 215.3, 230.42 ETC FOR ALL CONTINUOUS | | LOADS AND LARGEST MOTORS LOADS AT 125%. | | FBC ADMIN SECTION 106.3.5.1.2, 106.1.2 | | | | 15) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO | | REPEAT COMMENTS. | | THIS IS ONLY A NOTICE GIVEN AT THIS TIME. | | ONE COPY OF PLANS MAY BE RETAINED BY THIS OFFICE. | | | | AS STATED ON PREVIOUS REVIEW: | | PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2007-04-26 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-04-26 |
Time |
15:59 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-04-26 |
Time |
14:05 |
Sent To |
|
|
Notes |
2007-04-26 15:59:54 | ** UNSAT ** | | | | ** PLEASE SEE THAT ANY REFERENCES TO THE FBC CHAPTER 1 | | ARE FROM THE ADMINISTRATIVE CODE ADOPTED BY THE CITY OF | | WEST PALM BEACH. | | | | | | 1) NOTE: PLEASE SEE CODES REFLECTED ON PLANS ARE NOT | | CORRECT. | | PLEASE SEE THAT MANY OF THE CODES REFLECTED WENT OUT IN | | OCT 1ST OF 2005. PLEASE SEEMOST OF THE CODES ARE | | STILL FROM THE 2001 CODE AND ADOPTED STANDARDS AND | | CODES FROM THAT TIME. THERE ARE SEVERAL CODES WHICH ARE | | STILL BEING REFLECTED FROM THE *2001 FBC* , THE 2000 | | FLORIDA ACCESSIBILITY CODE ETC? | | PLEASE ALSO SEE THAT AS OF DECEMBER 8TH, 2006 THE | | CODES CHANGED TO THE 2006 REVISIONS TO THE 2004 FBC. | | PLEASE SEE THIS INCLUDES ALL MECHANICAL, PLUMBING | | BUILDING ETC. | | PLEASE SEE THAT AS OF THAT SAME DATE THE STATE ALSO | | ADOPTED THE NEW 2005 NFPA-70 (NEC). | | PLEASE SEE THE INCORRECT NFPA-101, 1 AND 72 ARE | | REFLECTED ALONG WITH THE INCORRECT NFPA-70 WHICH IS | | SHOWN AS THE 2002. | | PLEASE LIST THE FOLLOWING AT A MINIMUM ON ARCHITECTURAL | | COVER SHEET AND ELECTRICAL PLANS AT A MINIMUM. 2005 | | NFPA-70, 2002 NFPA-72, 2003 NFPA-101, 2003 NFPA-1. | | | | ** PLEASE KNOW THAT OTHER CODES FROM OTHER TRADES MAY | | ALSO BE STATED TO BE DONE. THIS IS FOR ELECTRICAL | | REVIEW ONLY HOWEVER ALL CORRECTED CODES MUST BE STATED | | FOR DESIGN WHETHER OR NOT COMMENTS ARE MADE BY ANY OF | | THE OTHER TRADES. | | | | 2) NOTE: PLEASE KNOW THAT IT IS MOST IMPORTANT TO | | COORDINATE PLANS WITH THE PLANS WHICH WERE SUBMITTED | | FOR SHELL BUILDING AND ADDITION. | | FBC 106.3.5.1.2, 106.1.2 | | | | 3) NOTE: PLEASE SEE THAT NO ENERGY CALCULATIONS WERE | | SUBMITTED FOR THE BUILD OUT OF SPACE. | | PLEASE KNOW THAT BASED ON THE BUILD OUT BEING SUBMITTED | | FOR PERMIT, THE KNOWN ENERGY CONSUMPTION ETC AND METHOD | | FOR SHELL PERMIT WOULD CHANGE. | | PLEASE SEE THAT NO REVIEW OF CODE COMPLIANCE CAN BE | | DONE AT THIS TIME. PLEASE BE SURE TO COORDINATE ALL | | FIXTURES, FIXTURE WATTAGES, TYPE OF FIXTURES, CONTROLS | | AND NUMBER OF FIXTURES BETWEEN PLANS AND ENERGY | | CALCULATIONS. | | PLEASE SUBMIT AND SHOW DETAILED CODE COMPLIANCE FOR | | LIGHTING CONTROLS AS REQUIRED PER CHAPTER 13 OF THE | | 2004 FBC. | | PLEASE SEE THE ELECTRICAL LIGHTING PLANS SUBMITTED ARE | | NOT COMPLETE WITH LIGHTING CONTROLS NOT ONLY REQUIRED | | PER CHAPTER 13, BUT MANY ROOMS AND AREAS DO NOT | | INDICATE ANY CONTROL FOR LIGHTING AT ALL. | | PLEASE KNOW THAT STATING ONE NOTE (#5) WHICH MENTIONS | | OCCUPANCY DEVICE REQUIRED, DOES NOT SHOW CODE | | COMPLIANCE. | | PLEASE SHOW SCHEDULE IF A SYSTEM IS DESIGNED, OR | | INSTALLED. PLEASE INDICATE ALL MAXIMUM TIMES ON OVER | | RIDE DEVICES; PLEASE SHOW ALL DEVICES ON PLANS SO THAT | | COVERAGE FOR CODE COMPLIANCE AND SPACE CONTROLS CAN BE | | REVIEWED. | | 13-415.1.ABC.1.1, .1.2, .1.3. 13-415.1.AB.1.1, | | 13-415.2 | | PLEASE PROVIDE WORST CASE VOLTAGE DROP FOR | | BRANCH/CIRCUITS AND FEEDERS PER 13-413.1ABC.1.1, .1.2. | | THIS INFORMATION IS REQUIRED TO BE SIGNED, DATED AND | | SEALED BY THE RESPONSIBLE DESIGN PROFESSIONAL ALONG | | WITH TITLE BLOCK INFORMATION ON PLANS AND SHEETS. THESE | | WOULD BE INCORPORATED IN PLAN SETS NOT SUBMITTED AS | | LOOSE SHEETS.13-103.1.1.1 | | | | ** PLEASE KNOW AT THIS TIME PLANS DO NOT INDICATE | | COMPLIANCE WITH THE 2004 FBC CHAPTER 13 AND MOST ITEMS | | REQUIRED FOR REVIEW ARE MISSING. PLEASE KNOW THERE MAY | | BE NEW COMMENTS ON THE FOLLOWING REVIEW AS INFORMATION | | WAS NOT SUBMITTED. | | PLEASE SEE CHAPTER 13 IN THE 2004 FBC . | | | | 4) NOTE: PLEASE SEE THAT THE PLANS ARE MISSING THE | | REQUIRED EGRESS PHOTO-METRICS AS PREVIOUSLY REQUESTED | | ON SHELL/ADDITION PLANS. AS THE SHELL/ADDITION PLANS | | ARE NOT ISSUED AT THIS TIME AND DO NOT INDICATE | | COMPLIANCE, PLEASE SUBMIT THE REQUIRED PER NFPA-101 | | 7.8.1.3, 7.9.2.2 | | PLEASE SEE NOTES UNDER MAIN BUILDING SHELL/ADDITION | | PERMIT. | | | | 5) NOTE: PLEASE SEE THAT THE RISER ON SHELL/ADDITION | | PERMIT HAS NOTES WHICH REQUIRES CHANGES. | | PLEASE SEE THERE IS MORE INFORMATION TO BE SUBMITTED | | WITH MORE COMPLETEDINFORMATION FOR CONDUCTORS, | | CONDUITS ETC, HOWEVER THERE ARE STILL SOME ITEMS WHICH | | NEED TO BE INCLUDED FOR CODE COMPLIANCE AS PREVIOUSLY | | NOTED. | | PLEASE SEE THE RISER AS SUBMITTED IS STILL NOT COMPLETE | | AT THIS TIME AND THERE ARE SEVERAL ITEMS WHICH CAN NOT | | BE REVIEWED FOR CODE COMPLIANCE. | | PLEASE SUBMIT A COMPLETE ELECTRICAL RISER DIAGRAM WITH | | ALL SERVICE ENTRANCE CONDUCTORS, FEEDERS, GROUNDING, | | SIZES OF ALL EQUIPMENT, LOCATIONS OF ALL EQUIPMENT, AIC | | RATINGS FOR ALL SERVICE EQUIPMENT ETC. | | ** PLEASE SEE SOME OF THE ITEMS WHICH ARE STILL | | MISSING. | | A) NO GROUNDING ELECTRODE SYSTEM. | | B) NO AIC RATINGS FOR ALL SERVICE EQUIPMENT. | | C) AN EQUIPMENT GROUNDING CONDUCTOR MAY NOT BE | | INSTALLED BEFORE THE FIRST MEANS OF DISCONNECT AS NOW | | SHOWN ON RISER. (250.6, 250.24) | | D) LOADS CAN NOT BE VERIFIED FOR SERVICE RISER AS SHOWN | | WHICH WILL BE NOTED BELOW TO VERIFY IF THE CONDUCTORS | | ETC SHOWN ARE OF ADEQUATE SIZE ETC. | | SECTIONS AS GIVEN IN PREVIOUS REVIEW. | | ** PLEASE SEE 110.9, 215.5, 240.4, 310.16, 230.70, | | 230.76, 230.79,250.50, 250.54, 250.56, 250.66, 240.24, | | 110.26 ETC. | | PLEASE SEE THAT THESE ARE ALL FROM THE 2005 NEC. | | | | 6) NOTE: PLEASE SEE PLANS MENTION A LOCK OFF/ON DEVICE | | IS TO BE INSTALLED HOWEVER NO NOTES COULD BE LOCATED | | FOR TYPE OF DEVICE WHICH IS REQUIRED TO BE INSTALLED AS | | NOTED ON PREVIOUS REVIEW. | | ** PLEASE KNOW THAT ANY LOCK-OFF DEVICES SHALL INCLUDE | | SUCH A DEVICE WHICH INCLUDES THE DEVICE AS AN INTEGRAL | | PART OF THE BREAKER. A *SNAP ON/CLIP ON* TYPE DEVICE IS | | NOT ACCEPTABLE TO THIS AHJ. | | 110.3, 90.4. | | | | 7) NOTE:PLEASE SEE NOTE UNDER SHELL/ADDITION PERMIT | | WITH RESPECT TO LOAD CALCULATIONS. | | PLEASE SEE THE SEPARATE SHEETS SUBMITTED FOR PANEL NHP | | DOES NOT PROVIDE THE REQUIRED AND REQUESTED INFORMATION | | FOR COMPLETE LOAD CALCULATIONS FOR SERVICE AND ALL | | EQUIPMENT BY THE DESIGNER OF RECORD.ALL INFORMATION | | SHALL BE INCLUDED IN RECORD SETS OF PLANS AND NOT | | SUBMITTED ON LOOSE SHEETS WHICH DO NOT CONTAIN THE | | COMPLETED INFORMATION OR DONE BY THE DESIGNER OR | | RECORD. | | PLEASE SEE THE 2005 NEC FOR REQUIRED METHODS. 220.12, | | 220.14, 220.42, 220.44 AND ALL PREVIOUS SECTIONS AS | | PREVIOUSLY NOTED. | | PLEASE SUBMIT COMPLETE LOAD CALCULATIONS FOR SERVICE | | AND EACH OF THE PANELS AS BEING SHOWN EVEN THOSE BEING | | SET ASIDE FOR FUTURE USE. PLEASE SEE THE ONLY PANEL | | SHOWN WHICH IS THE NHP AND THIS DOES NOT INCLUDE A LOAD | | SUMMARY OR HOW THE SERVICE WAS SIZED OR CORRECT LOAD | | CALCULATIONS FOR THIS PANEL OR SERVICE. | | PLEASE SEE NOTE #9 ABOVE AS THE SERVICE SIZE OR | | CONDUCTORS ARE NOT COMPLETE THE SIZE OF THE SERVICE CAN | | NOT BE DETERMINED AT THIS TIME. | | PLEASE SEE ALL OF 220. | | PLEASE ALSO SEE 215.3, 230.42 ETC FOR ALL CONTINUOUS | | LOADS AND LARGEST MOTORS LOADS AT 125%. | | FBC ADMIN SECTION 106.3.5.1.2, 106.1.2 | | | | 8) NOTE:THIS IS ONE OF THE SAME NOTES UNDER BASE | | BUILDING/SHELL PLANS. | | PLEASE SEE THIS SAME COMMENT FROM PREVIOUS REVIEW WHICH | | REMAINS AS NOT INFORMATION WAS SUBMITTED. PLEASE SEE | | NOTE ABOVE (#13) WHICH REQUEST THE AIC RATINGS FOR ALL | | EQUIPMENT. PLEASE BE SURE THESE CORRELATE WITH THE | | DIVISION SPEC SUBMITTED. 106.1.2. NEC 110.9 | | | | 9) NOTE: PLEASE SEE FBC 2004 11-4.28.1, .2 AND .3(4) | | AND STATE THE MINIMUM HORN, STROBE LEVELS ON PLANS FOR | | ADA REQUIRED AREAS. DEVICES ARE BEING SHOWN ON | | PLANS/LEGEND. PLEASE CORRELATE WITH PLANS, AND FA | | SHEETS SUBMITTED. | | ** PLEASE KNOW THAT THE FIRE ALARM WILL BE UNDER A | | SEPARATE PERMIT HOWEVER THE BASE LIFE SAFETY SYSTEM IS | | REQUIRED ON BASE PLANS AS SHOWN. DO NOT REMOVE FROM | | SETS. | | FBC 106.3.5.1.2 | | | | 10) NOTE: PLEASE KNOW THAT THE LOW VOLTAGE SECURITY | | PLANS FOR CAMERAS ETC ARE TO BE UNDER SEPARATE | | PERMITS. | | | | 11) NOTE: PLEASE COMPETE ALL CIRCUITING ON PLANS AND | | CORRELATE WITH THE SUBMITTED PANEL SCHEDULES. PLEASE BE | | SURE TO SEE PREVIOUS PLANS FOR SHELL BUILDING AND | | CIRCUITING PER 700.12E FOR ALL EMERGENCY AND EXIT | | LIGHTS. | | 106.1.2, | | 408.4 NEC.THE FOLLOWING TEXT IS TAKEN DIRECTLY FROM | | THE NEC. PLEASE BE SURE ALL AREAS, ROOMS DESIGNATIONS | | ETC COORDINATE WITH THE CIRCUITS ON PANEL SCHEDULES | | SPECIFIC. | | | | **SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO | | REQUIRE THAT THE IDENTIFICATION FOR EVERY CIRCUIT | | SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND | | CLEARLY STATE THE SPECIFIC PURPOSE FOR WHICH THE | | CIRCUIT IS USED. CIRCUITS USED FOR THE SAME PURPOSE | | MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR EXAMPLE, | | SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY OUTLETS IN | | THE KITCHEN, DINING ROOM, AND KITCHEN COUNTERTOPS. | | IDENTIFYING THE CIRCUITS AS SMALL APPLIANCE BRANCH | | CIRCUITS IS NOT ACCEPTABLE; INSTEAD, THEY SHOULD BE | | IDENTIFIED AS ``KITCHEN WALL RECEPTACLES,'' ``DINING | | ROOM FLOOR RECEPTACLE,'' OR ``KITCHEN COUNTERTOP | | RECEPTACLES LEFT OF SINK.'' CIRCUIT DIRECTORIES | | CONTAINING MULTIPLE ENTRIES WITH ONLY ``LIGHTS'' OR | | ``OUTLETS'' DO NOT PROVIDE THE SUFFICIENT DETAIL | | REQUIRED BY THIS SECTION.* | | 408.4, 310.16, 240.4 ETC | | FBC 106.3.5.4 | | | | ** IMPORTANT** | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | PICKED UP FOR CORRECTIONS, PLEASE BE | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | AND STAMPING. DO NOT LEAVE ANY | | OLD/VOIDED SHEETS IN SETS. | | PLEASE KNOW ONLY ONE SET OF THE | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | FOR REFERENCE. | | THIS WILL HELP IN THE REVIEW PROCESS AND | | AVOID ANY DELAYS. | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
8 |
Status |
N |
Date |
2008-07-22 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2008-07-22 |
Time |
10:31 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2008-07-22 |
Time |
10:17 |
Sent To |
B |
|
Notes |
2008-07-22 10:25:24 | *****NOT NEEDED***** | | | | | | NO FIRE-STAMPEING NEEDED TO THE COVER SHEET OR AF-321 | | SHEET. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
7 |
Status |
P |
Date |
2008-06-24 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2008-06-24 |
Time |
11:46 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2008-06-24 |
Time |
11:37 |
Sent To |
B |
|
Notes |
2008-06-24 11:46:08 | *****REVISION 4, DATED 6/11/08, APPROVED***** | | | | | | REVISED PLAN SHEET GV-102 STAMPED, INTIALED, AND DATED. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
6 |
Status |
P |
Date |
2008-05-09 |
|
|
Cont ID |
|
Sent By |
mwennerg |
Date |
2008-05-09 |
Time |
10:44 |
Rev Time |
0.00 |
Received By |
mwennerg |
Date |
2008-05-09 |
Time |
10:44 |
Sent To |
|
|
Notes |
2008-05-09 10:45:41 | SHEETS EL-101 - EL-104 WERE STAMPED, SIGNED AND DATED. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
5 |
Status |
F |
Date |
2008-02-26 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2008-02-26 |
Time |
17:48 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2008-02-26 |
Time |
16:55 |
Sent To |
|
|
Notes |
2008-02-26 17:40:19 | *****REVISION, DATED 01/21/08, PARTIAL APPROVAL***** | | | | REVISED PLAN SHEETS GV-102, AR-102, AND EA-102 WERE | | STAMPED, INITIALED, AND DATED;HOWEVER SHEETS EL-101 | | THRU EL-104 TO BE FIRE-STAMPED WHEN THE ELECTRICAL | | REVIEW IS SATISFIED. | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
4 |
Status |
P |
Date |
2008-01-14 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2008-01-14 |
Time |
13:04 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2008-01-14 |
Time |
12:05 |
Sent To |
|
|
Notes |
2008-01-14 12:46:43 | *****APPROVED***** | | | | PLAN SHEETS GV-101&102, AF-201, AR-101&102, IF-101&102, | | FS-101, FD-101&102, FK-101&102, EA-101&102, EC-301, AND | | EL-101&102WERE STAMPED, INITIALED, AND DATED. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2007-11-26 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2007-11-26 |
Time |
11:27 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2007-11-26 |
Time |
09:39 |
Sent To |
|
|
Notes |
2007-11-26 11:16:21 | *****PROVISO***** | | | | | | THE APPROPIATE PLAN SHEET(S) TO BE FIRE-STAMPED WHEN | | THE FOLLOWING COMMENT TAKEN FROM THE PREVIOUS FIRE PLAN | | REVIEWS HAS BEEN ADDRESSED: | | | | | | 09.INTERIOR FLOOR FINISH SHALL COMPLY WITH SECTION | | 10.2 OF NFPA 101;INTERIOR FLOOR FINISH IN EXIT | | ENCLOSURES SHALL BE CLASS I OR CLASS II.BE SPECIFIC | | PLEASE ADDRESS/INDICATE COMMENT IN THE PLANS AND/OR | | SPECIFICATIONS | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | LETTER INDICATING HOW/WHERE THE ITEMS WERE ADDRESSED | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
F |
Date |
2007-09-24 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2007-09-24 |
Time |
12:28 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2007-09-24 |
Time |
11:10 |
Sent To |
|
|
Notes |
2007-09-24 12:28:45 | *****DENIED***** | | THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE | | PLAN REVIEW STILL NEED TO BE ADDRESSED: | | | | | | 08.PLEASE CLARIFY/INDICATE SYMBOL FOR THE EMERGENCY | | LIGTS ON SHEETS AR-101, AR-102, EL-101, AND EL102. YOUR | | RESPONSE STILL DOES NOT CLARIFY/IDENTIFY TO DETERMINE | | EMERGENCY LIGHTING | | | | 09.INTERIOR FLOOR FINISH SHALL COMPLY WITH SECTION | | 10.2 OF NFPA 101;INTERIOR FLOOR FINISH IN EXIT | | ENCLOSURES SHALL BE CLASS I OR CLASS II.BE SPECIFIC | | PLEASE ADDRESS/INDICATE COMMENT IN THE PLANS AND/OR | | SPECIFICATIONS | | | | 18.ELEVATORS SHALL COMPLY WITH THE REQUIREMENTS OF | | ASME A17.1 (NEW ELEVATORS) OR ASME A17.3 (EXISTING | | ELEVATORS). COULD NOT LOCATE ON SHEET EP-101 AND EC-101 | | AS PER YOUR RESPONSE LETTER INDICATES | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | LETTER INDICATING HOW/WHERE THE ITEMS WERE ADDRESSED | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2007-06-28 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2007-06-27 |
Time |
07:40 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2007-06-26 |
Time |
10:25 |
Sent To |
|
|
Notes |
2007-06-27 12:56:21 | *****DENIED***** | | | | | | 01.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | 02.AS PERTAINS TO THE PROJECT CODE DATA ON GV-101, | | REFERENCE THE FOLLOWING:NFPA 1 (2003 EDITION),NFPA | | 101 (2003 EDITION),ANDFLORIDA FIRE PREVENTION CODE | | (2004 EDITION). | | | | 03.ON SHEET GV-101, EXPLAIN THE DIFFERENCE BETWEEN FE | | AND FHV LEGEND SYMBOLS.BOTH INDICATE FIRE | | EXTINGUISHER. | | | | 04.ON THE APPROPIATE EXTERIOR ELEVATION WHICH FRONTS | | GREENWOOD AVENUE, SHOW/DISPLAY THE NUMERICAL ADDRESS ON | | THE BUILDING.PLEASE BE REMINDED EVEN A MARKEE OR | | MONUMENT SIGN IS USED AT GREENWOOD AVENUE, THE | | NUMERICAL ADDRESS SHALL BE ON THE STRUCTURE AS PER WEST | | PALM BEACH ADDRESSING CODE. | | | | 05.PLANS INDICATE THAT THIS BUILDING WILL BE FIRE | | SPRINKLERED IN CONJUNCTION WITH A FIRE ALARM SYSTEM. | | SHOW THE LOCATION OF THE REQUIRED PREMISES ACCESS/KNOX | | BOX AT THE APPROPIATE EXTERIOR ELEVATION.FOR | | APPLICATIONS, CONTACT THE WPB FIRE PREVENTION AT | | 561-804-4724. | | | | 06.ON SHEET GV-102,EXPLAIN THE USE OF THE SLEEP | | ROOM (226). | | | | 07.ON SHEET GV-102, EXPLAIN THE AREA LOCATED IN THE | | TOP RIGTH CORNER IN THE CONFERENCE PRESENTATION ROOM | | (210).HOW IS ACESS GAINED? | | | | 08.PLEASE CLARIFY/INDICATE SYMBOL FOR THE EMERGENCY | | LIGTS ON SHEETS AR-101, AR-102, EL-101, AND EL102. | | | | 09.INTERIOR FLOOR FINISH SHALL COMPLY WITH SECTION | | 10.2 OF NFPA 101;INTERIOR FLOOR FINISH IN EXIT | | ENCLOSURES SHALL BE CLASS I OR CLASS II.BE SPECIFIC | | | | 10.INTERIOR WALL AND CEILING FINISH MATERIALS SHALL | | BE CLASS A OR CLASS B IN EXITS AND EXIT ACCESS | | CORRIDORS;SHALL BE CLASS A, CLASS B, OR CLASS C IN | | ALL OTHER AREAS. | | | | 11.ON SHEET FS-101, INDICATE FROM WHOM THE FIRE FLOW | | DATA WAS OBTAINED. | | | | 12.SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE | | FIRE SPRINKLER REMODEL AND FIRE ALARM SYSTEMS SCOPE OF | | WORK. | | | | 13.FIRE ALARM SYSTEM TO BE CLASS A OR FULLY | | ADDRESSABLE. | | | | 14.FIRE ALARM SYSTEM SHALL BE UL CERTIFIED FOR | | CENTRAL STATION SERVICE. | | | | 15.DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE | | ALARM IN ACCORDANCE WITH LOCAL REQUIREMENTS. | | | | 16.DOORS AS A MEANS OF EGRESS COMPONENT SHALL COMPLY | | WITH SECTION 7.2.1 OF NFPA 101. | | | | 17.ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM AN | | AREA HAVING AN OCCUPANT LOAD OF 100 OR MORE PERSONS | | SHALL BE PERMITTED TO BE PROVIDED WITH A LATCH OR LOCK | | ONLY IF THE LOCK OR LATCH IS PANIC HARDWARE OR FIRE | | EXIT HARDWARE. | | | | 18.ELEVATORS SHALL COMPLY WITH THE REQUIREMENTS OF | | ASME A17.1 (NEW ELEVATORS) OR ASME A17.3 (EXISTING | | ELEVATORS). | | | | 19.WARNING SIGNS (DO NOT USE IN THE EVENT OF A FIRE) | | ARE REQUIRED IN THE ELEVATOR LOBBIES. | | | | 20.ALL FIRE DOORS AND WINDOWS TO COMPLY WITH NFPA 80, | | FIRE DOORS AND WINDOWS. | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | LETTER INDICATING HOW/WHERE THE ITEMS WERE ADDRESSED | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
13 |
Status |
N |
Date |
2008-07-24 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-07-24 |
Time |
11:49 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-07-24 |
Time |
11:49 |
Sent To |
B |
|
Notes |
2008-07-24 11:49:39 | TO "JWITMER" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
12 |
Status |
N |
Date |
2008-07-03 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-07-03 |
Time |
10:06 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-07-03 |
Time |
10:06 |
Sent To |
|
|
Notes |
2008-07-03 10:06:38 | TO "COMM" BD#52 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
11 |
Status |
N |
Date |
2008-07-03 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-07-03 |
Time |
09:50 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-07-03 |
Time |
09:50 |
Sent To |
|
|
Notes |
2008-07-03 09:53:28 | TO "COMM" BD#55 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
10 |
Status |
N |
Date |
2008-06-24 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-06-24 |
Time |
15:59 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-06-24 |
Time |
15:59 |
Sent To |
B |
|
Notes |
2008-06-24 15:59:54 | TO "JWITMER" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
9 |
Status |
N |
Date |
2008-06-13 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-06-13 |
Time |
11:09 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-06-13 |
Time |
11:09 |
Sent To |
FIRE |
|
Notes |
2008-06-13 11:09:49 | TO "F" BOX/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
8 |
Status |
N |
Date |
2008-05-02 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-05-02 |
Time |
09:22 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-05-02 |
Time |
09:22 |
Sent To |
P |
|
Notes |
2008-05-02 09:23:02 | TO "P" BOX/RESTAMP |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
7 |
Status |
N |
Date |
2008-04-22 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-04-22 |
Time |
11:23 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-04-22 |
Time |
11:23 |
Sent To |
|
|
Notes |
2008-04-22 11:28:24 | TO "COMM" BD#36 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
6 |
Status |
N |
Date |
2008-02-11 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-02-11 |
Time |
11:53 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-02-11 |
Time |
11:53 |
Sent To |
|
|
Notes |
2008-02-12 10:21:58 | TO "COMM" BD#15 | 2008-02-11 11:55:18 | WAITING FOR "COMM" BD |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2008-01-22 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-01-22 |
Time |
13:44 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-01-22 |
Time |
13:44 |
Sent To |
E |
|
Notes |
2008-01-22 13:44:45 | TO "DPALMER" DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2007-12-20 |
|
|
Cont ID |
|
Sent By |
mmiller |
Date |
2007-12-20 |
Time |
18:06 |
Rev Time |
0.00 |
Received By |
mmiller |
Date |
2007-12-20 |
Time |
18:06 |
Sent To |
|
|
Notes |
2007-12-20 18:06:58 | SENT TO COMMERICAL BOARD # 38 MMILLER |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2007-10-04 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-10-04 |
Time |
08:52 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-10-04 |
Time |
08:52 |
Sent To |
|
|
Notes |
2007-10-25 15:43:10 | TO "COMM" BD#58--PLANS ON RACK/4 ROLLS AND BOOKS | 2007-10-04 08:53:30 | WAITING FOR "COMM" BD |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2007-08-07 |
|
|
Cont ID |
|
Sent By |
lmartine |
Date |
2007-08-07 |
Time |
15:41 |
Rev Time |
0.00 |
Received By |
lmartine |
Date |
2007-07-24 |
Time |
15:43 |
Sent To |
|
|
Notes |
2007-08-07 18:43:48 | TO COMM BOARD #43. | 2007-08-07 15:41:57 | WAITING FOR COMM. BOARD |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2007-06-27 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2007-06-27 |
Time |
11:56 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2007-06-27 |
Time |
11:57 |
Sent To |
|
|
Notes |
2007-04-20 14:47:17 | TO "COMM" BD#43 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
7 |
Status |
P |
Date |
2008-07-29 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2008-07-29 |
Time |
14:21 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2008-07-29 |
Time |
14:19 |
Sent To |
|
|
Notes |
2008-07-29 14:20:55 | 7/29/08 | | TEST AND BALANCE REPORT OK HM. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
6 |
Status |
P |
Date |
2008-04-28 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2008-04-28 |
Time |
10:52 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2008-04-28 |
Time |
10:52 |
Sent To |
|
|
Notes |
2008-04-28 10:52:50 | RESTAMP PAGE MH-102 ORIGINALLY REVIEWED 2/26/08. | | REVISION #3 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
5 |
Status |
P |
Date |
2008-02-26 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2008-02-26 |
Time |
14:27 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2008-02-26 |
Time |
14:23 |
Sent To |
|
|
Notes |
2008-02-26 14:24:21 | REVISED MH-102 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
4 |
Status |
P |
Date |
2008-01-17 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2008-01-17 |
Time |
15:12 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2008-01-17 |
Time |
15:12 |
Sent To |
PC |
|
Notes |
2008-01-17 15:12:34 | RESTAMP |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2007-11-15 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2007-11-15 |
Time |
15:35 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2007-11-15 |
Time |
14:31 |
Sent To |
|
|
Notes |
2007-11-15 15:36:06 | PASSED PENDING ACCEPTANCE OF ENERGY CALCULATIONS BY ALL | | OTHER INTERESTED TRADES. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2007-08-14 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2007-08-14 |
Time |
16:33 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2007-08-14 |
Time |
16:11 |
Sent To |
|
|
Notes |
2007-08-14 16:33:48 | REVIEW #: 2ND | | ACTION: DENIED | | | | FBC 2004 CODE FAMILY W/ 2005 AND 2006 AMENDMENTS | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH | | PREVIOUS EVIEW COMMENTS FOR THE PURPOSE OF CONTINUITY. | | | | 1. OK | | | | 2. BUILDING RELIEF SHOULD ONLY BE USED IF A BUILDING IS | | UNDER AN UNUSUALLY HIGH POSITIVE PRESSURE. THIS SYSTEM | | IS NOT BALANCED AS SUCH. THE AIR BALANCE ON FIRST FLOOR | | IS NOW AT -1365 CFM. AN OVERALL NEGATIVE PRESSURE IN | | THE BUILDING IS NOT ALLOWED. THE MECHANICAL SYSTEM | | SHALL BE DESIGNED TO ASSURE THAT THE BUILDING IS | | PRESSURIZED WITH RESPECT TO THE OUTDOORS IN ACCORDANCE | | WITH FBC 13-409.1.ABC.2. PROVIDE AN OVERALL AIR BALANCE | | SCHEDULE FOR THE BUILDING SHOWING COMPLIANCE WITH THIS | | SECTION. | | | | 3. OK | | | | 4. OK | | | | 5. PLEASE SHOW HOW ONE 600 CFM TRANSFER (TD-5 ON | | SCHEDULE) WILL ALLOW FOR 950 CFM OF MAKE-UP AIR. ALSO, | | WHEN THIS COMMENT IS ADDRESSED, PLEASE TAKE INTO | | ACCOUNT THE ISSUE RAISED BY THE LATEST COMMENT #2. | | | | 6. OK | | | | 7. OK | | | | 8. SOME REVISIONS HAVE TAKEN PLACE IN THIS AREA ON | | ARCHITECTURAL PLANS. IT APPEARS THAT A FIRE DAMPER HAS | | BEEN UNNECESSARILY ADDED TO THE OA DUCT THROUGH THE | | WALL BETWEEN ROOMS 150 AND 103. ALSO, A FIRE DAMPER IS | | MISSING IN THE 6X6 SUPPLY DUCT WHICH TERMINATES AT THE | | WALL BETWEEN ROOMS 101 AND 110. AS FOR BALANCED RETURN, | | THERE IS NO EXCEPTION IN FBC,M 601.4 FOR DOORS WITH | | HOLD-OPEN DEVICES. PROVIDE BALANCED RETURN. | | | | 9. OK | | | | 10. SEE COMMENT #2. | | | | 11. THERE ARE DOORS BETWEEN ROOMS 200 AND 201. PROVIDE | | BALANCED RETURN PER FBC,M 601.4. | | | | 12. OK | | | | 13. OK | | | | 14. OK | | | | 15. SEE COMMENT #11. | | | | 16. OK | | | | 17. OK | | | | 18. PRODUCT APPROVAL WITH INSTALLATION INSTRUCTIONS | | SHALL BE ON SITE FOR INSPECTION. | | | | 19. OK | | | | 20. A) PROVIDE TWO SETS OF ENERGY CALCULATIONS, EACH | | WITH THE ORIGINAL SIGNATURE AND SEAL OF THE DESIGNER | | PER FBC 13-103.1.1.1. NO PHOTOCOPIED SIGNATURES OR | | SEALS WILL BE ACCEPTED. | | B) BUILDING OWNER OR OWNER'S ARCHITECT SHALL CERTIFY | | THAT THE BUILDING IS IN COMPLIANCE WITH CHAPTER 13 OF | | THE FBC PER FBC 13-400.3.ABC.2. | | C) VERIFY THAT THE TYPES OF BUILDING COMPONENTS USED IN | | THE INPUT DATA REPORT MATCHES THE TYPES SHOWN ON THE | | PLANS AND/OR THE BUILDING. EXAMPLE: THIS IS NOT A METAL | | BUILDING WITH R-19 BATTS AS IS SHOWN ON ENERGY | | CALCULATIONS. IS THE EXTERIOR OF THIS BUILDING 6" METAL | | STUDS WITH R-13 BATTS? | | | | 21. OK | | | | 22. PG MC-702 DETAIL 1: NOTE #9, FCU'S SHALL BE SHUT | | DOWN BY DUCT SMOKE DETECTOR OR AREA SMOKE DETECTOR PER | | FBC,M 606.2.1. | | | | 23. OK | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | RONALD J REGUEIRO | | 561.805.6719 | | [email protected] |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2007-05-08 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2007-05-08 |
Time |
10:05 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2007-05-07 |
Time |
07:40 |
Sent To |
|
|
Notes |
2007-05-08 10:05:23 | --------------DENIED---------------- | | | | FBC 2004 CODE FAMILY W/2006 REVISIONS | | FBC CH 1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | ASHRAE 15-01 | | ASHRAE 62.1-04 | | | | 1. MH-101: THERE ARE MANY AREAS THROUGHOUT THIS FLOOR | | WHERE TRANSFER DUCTS ABOVE CEILING ARE TOO SMALL TO | | RETURN THE REQUIRED CFM BASED ON TD SCHEDULE ON MM-501. | | THERE ARE ALSO MANY ROOMS WHICH DO NOT HAVE ANY | | TRANSFER DUCT ABOVE CEILING TO ALLOW RETURN AIR FROM | | SPACE EVEN THOUGH THE SPACE IS SEPARATED FROM THE FCU | | BY A PARTITION. THERE ARE TOO MANY TO LIST, BUT HERE | | ARE SOME EXAMPLES: ROOMS 169,175,129,126,117,100. | | BALANCED RETURN IS REQUIRED FROM ALL HABITABLE ROOMS | | PER FBC,M 601.4. | | | | 2. MH-101: ROOM AIR DATA SCHEDULE DOES NOT ACCOUNT FOR | | 1510 CFM OF EXHAUST FROM OED'S (KEY NOTES 3&4). THE | | AMOUNT OF SUPPLY IS TO BE APPROXIMATELY EQUAL TO RETURN | | AND EXHAUST AIR PER FBC,M 403.1. SCHEDULE SHOWS 9080 | | CFM SUPPLY WITH 8220 R/A + 715 CFM EA +1510 EA. THERE | | IS A TOTAL OF 10445 CFM R/A AND EA VS 9080 CFM SUPPLY. | | BALANCE IS OFF BY 1365 CFM. PLEASE SHOW COMPLIANCE WITH | | THIS SECTION WHILE MAINTAINING MIN. REQUIRED | | VENTILATION RATES IN ACCORDANCE WITH FBC,M 403.3. | | | | 3. ERV-1 IS RATED FOR 2200 CFM ON SCHEDULE. TOTAL OA | | REQUIRED BY ALL FCU'S FED BY ERV-1 AS STATED ON FCU | | SCHEDULE IS 2510. PLEASE COORDINATE EQUIPMENT,SCHEDULES | | AND VENTILATION RATES IN CUNJUNCTION WITH REVIEW | | COMMENT #2. | | | | 4. MH-101: THE FOLLOWING FCU'S ARE MISSING A SIZE FOR | | OA DUCT: 1-6, 1-7, 1-9, 1-14. FCU 1-5 SHOWS 10X12 OA | | DUCT FOR 140 CFM. IS THIS CORRECT? PLEASE CLARIFY. FBC | | 106.1.1. | | | | 5. MH-101: 18X14 OED IS LOCATED IN CEILING SPACE ABOVE | | ROOM 182. THIS SPACE IS ISOLATED FROM OTHER CEILING | | SPACES EXCEPT FOR TD-3. IS TD-3 FOR THE PURPOSE OF | | RETURN BACK TO FCU OR IS IT TO ALLOW EXHAUST TO REACH | | OED? A) TD-3 IS TOO SMALL TO TRANSFER 950 CFM OF | | EXHAUST AND B) IT CANNOT BOTH ALLOW EXHAUST IN AND | | RETURN AIR OUT OF SPACE SIMULTANEOUSLY. PERHAPS THE OED | | CAN BE RELOCATED TO A LARGER OPEN PLENUM AREA TO ALLOW | | PROPER EXHAUST FLOW AND RETURN AIR FLOW FROM ROOM 182. | | BALANCED RETURN IS REQUIRED PER FBC,M 601.4. | | | | 6. MH-101: WHAT IS THE SIZE OF 2ND SUPPLY DROP IN | | WAITING 110? WHAT IS THE SIZE OF DUCT/GRILL AT | | ELECTRICAL CLOSET 101? FBC 106.1.1. | | | | 7. MH-101: THE FOLLOWING FCU'S SHOW CFM'S ON ROOM AIR | | DATA SCHEDULE WHICH DIFFER FROM THOSE SHOWN ON FCU | | SCHEDULE (MM-603): 1-2,1-3,1-4,1-6,1-8,1-10. WHICH IS | | CORRECT? PLEASE CLARIFY PER FBC 106.1.1. | | | | 8. MH-101: DUCTS ARE SHOWN PENETRATING 1-HOUR RATED | | WALLS FROM FCU-10 INTO LOBBY 100 AND ELECTRICAL ROOM | | 104. ALSO THE RETURN OPENING FROM LOBBY 100 INTO | | WAITING 110. | | A) WHAT SIZE IS RETURN OPENING? | | B) PLEASE SHOW THESE OPENINGS IN RATED ASSEMBLIES TO BE | | PROTECTED PER FBC,M 607.5. | | | | 9. MH-102: THE FOLLOWING FCU'S HAVE CFM VALUES ON ROOM | | AIR DATA SCHEDULE WHICH DIFFER FROM THOSE SHOWN ON FCU | | SCHEDULE: 2-1, 2-2. WHICH IS CORRECT? FBC 106.1.1. | | | | 10. MH-102: PLEASE SEE REVIEW COMMENT #2: SUPPLY IS NOT | | BALANCED WITH RETURN AND EXHAUST. 6990 CFM SUPPLY VS | | 5575 R/A+ 1920 CFM EA FOR A TOTAL OF 7495 CFM R/A AND | | EA.SYSTEM IS OUT OF BALANCE BY 505 CFM. FBC,M 403.1. | | | | 11. MH-102: DUCT AND TRANSFER OPENING IN RATED WALL AT | | ELEV. VESTIBULE 200. PLEASE SHOW OPENING PROTECTIVES | | PER FBC,M 607.5. | | | | 12. MH-102: ROOM AIR DATA SCHEDULE SHOWS EXEC. | | CONFERENCE ROOM AS 205A, FLOOR PLAN SHOWS CONFERENCE | | 206. PLEASE COORDINATE SCHEDULE AND FLOOR PLAN. | | | | 13. MH-102: PLEASE SHOW SIZES OF ALL EXHAUST BRANCH | | DUCTS SUCH AS IN LAVATORY 218 AND WC 223. | | | | 14. MH-102: CONFERENCE ROOM 206 SHOWS 570 CFM SUPPLY | | WITH ONE TD-2 TRANSFER DUCT WHICH IS RATED FOR MAX. 250 | | CFM ON PG MM-501. PLEASE SHOW BALANCED RETURN IN THIS | | AREA PER FBC,M 601.4. | | | | 15. MH-102: VESTIBULE 200 IS SHOWN TO HAVE ONE SUPPLY | | DROP AT 200 CFM WITH ONE TD-1 FOR TRANSFER WHICH HAS A | | MAX. OF 175 CFM PER MM-501. PLEASE SHOW BALANCED RETURN | | PER FBC,M 601.4. ALSO, PLAN SHOWS SOME TYPE OF | | RECTANGLE INTAKE GRILL IN CEILING. PLEASE CLARIFY. | | | | 16. MM-501 DETAIL #6: | | A) PLEASE SHOW MEANS OF ATTACHMENT OF SUPPORTS TO | | STRUCTURE AS WELL AS TYPE/SIZE OF SUPPORTS TO STRUCTURE | | AS WELL AS TYPE/SIZE OF SUPPORTS TO BE USED. | | B) PLEASE SHOW MEANS OF CONDENSATE SECONDARY/AUXILIARY | | DRAIN PROTECTION PER FBC,M 307.2.3. | | | | 17. MM-502 DETAIL #1: CONDENSATE DRAINS SHALL BE | | TRAPPED AS REQUIRED BY THE EQUIPMENT OR APPLIANCE | | MANUFACTURER. FBC,M 307.2.4 | | | | 18. MM-502 DETAIL #5: ROOF MOUNTED MECHANICAL UNITS | | SHALL BE MOUNTED ON CURBS RAISED A MINIMUM OF 8 INCHES | | (203 MM) ABOVE THE ROOF SURFACE, OR WHERE ROOFING | | MATERIALS EXTEND BENEATH THE UNIT, ON RAISED EQUIPMENT | | SUPPORTS PROVIDING A MINIMUM CLEARANCE HEIGHT IN | | ACCORDANCE WITH TABLE 1509.7. ALSO, PRE-ENGINNERED A/C | | STANDS ARE STRUCTURAL ELEMENTS AS DEFINED BY FAC 9B-72. | | THEREFORE, PRODUCT APPLROVAL IS REQUIRED. | | | | 19. PLEASE SHOW OUTDOOR AIR CALCULATIONS. FBC,M 403.3 | | AND FBC 106.1.2. | | | | 20. ENERGY CALCULATIONS SHALL BE MADE A PART OF THE | | PLANS AND SPECIFICATIONS OF THE BUILDING PER FBC | | 13-103.2. DESIGN PROFESSIONALS RESPONSIBLE UNDER | | FLORIDA LAW FOR THE DESIGN OF LIGHTING, ELECTRICAL, | | MECHANICAL, AND PLUMBING SYSTEMS AND THE BUILDING | | SHELL, SHALL CERTIFY COMPLIANCE OF THOSE BUILDING | | SYSTEMS WITH THE CODE BY SIGNING AND PROVIDING THEIR | | PROFESSIONAL REGISTRATION NUMBER ON THE ENERGY CODE | | FORM PROVIDED AS PART OF THE PLANS AND SPECIFICATIONS | | TO THE BUILDING DEPARTMENT. FBC 13-103.1.1.1. | | | | 21. MM-601: PLEASE PROVIDE SIZES ON CHILLED WATER | | SCHEMATIC AND DUCT RISER DIAGRAMS. ALSO, PLEASE SHOW | | PUMP LOCATION AND REMOVE THE NOTE STATING "OPTIONAL". | | FBC 106.1.1. | | | | 22. FAN SHUT-DOWN BY SMOKE DETECTOR IS REQUIRED FOR ALL | | SUPPLY FANS IN THE A/C SYSTEM, INCLUDING ERV'S PER | | FBC,M 607.2.2. EXCEPTIONS: AC-1 AND EMU-1. | | | | 23. ABOVE CEILING AREAS ARE USED AS PLENUMS. PLEASE | | ENSURE THAT ALL AMTERIALS EXPOSED IN PLENUMS ARE IN | | COMPLIANCE WITH FBC,M 602.2.1, INCLUDING TAGS, | | EQUIPMENT LABELS AND PIPE MARKERS AS LISTED IN | | SPECIFICATIONS BOOK SEC. 15075. ALSO SEE SEC. 15181-7 | | REGARDING CONDENSATE PIPING. PVC CANNOT BE USED IN A | | PLENUM AS IT DOES NOT MEET THE REQUIREMENTS OF | | 602.2.1. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT: | | | | RONALD J REGUEIRO | | 561.805.6719 | | [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
4 |
Status |
P |
Date |
2008-01-11 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2008-01-11 |
Time |
15:01 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2008-01-11 |
Time |
15:01 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
F |
Date |
2007-12-04 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2007-12-04 |
Time |
11:17 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2007-12-04 |
Time |
11:17 |
Sent To |
|
|
Notes |
2007-12-04 11:17:49 | DENIED | | REFERENCE: FBC-2004 PLUMBING | | FBC-2004 CHAPTER 1 | | FBC-2004 CHAPTER 11 | | FBC-2004 BUILDING | | | | ****FROM PREVIOUS REVIEW: | | ******FROM PREVIOUS REVIEWS: | | | | 1. SHT AF-210 DETAILS 6 & 9 LOUNGE (RMS 130 & 159) | | SINKS SHALL BE ACCESSIBLE. PLEASE SUBMIT A DETAIL | | SHOWING COMPLIANCE WITH SECTION 11-4.24 AND ALL | | SUBSECTIONS. | | ****RESPONSE NOTED, BUT SHOW COMPLIANCE WITH THE | | FOLLOWING: | | A. OK | | B. OK | | C. 11-4.24.5 CLEAR FLOOR SPACE - FORWARD APPROACH | | REQUIRED - CABINET DOORS UNDER SINK NOT APPROVED IN | | CLEAR FLOOR SPACE. PLEASE REMOVE. | | ******RESPONSE NOTED, BUT THE CLEAR FLOOR SPACE IS NOT | | SHOWN ON THE FLOOR PLAN. SEE FIG. 32 IN CHAPTER 11. | | D. OK | | C. OK | | | | 2. OK | | 3. OK | | 4. OK | | 5. OK | | | | 6. TOILET ROOMS 112, 131, 152, 161 & 183. PLEASE | | INDICATE FINISH FOR THE FLOORS AND WALLS PER SECTIONS | | 1210.1 & 1210.2. BE MINDFULL THAT THE WALLS WITHIN 2' | | OF ALL URINALS AND WATER CLOSETS SHALL HAVE A "SMOOTH, | | HARD, NONABSORBENT SURFACE" UP TO 4' ABOVE THE FLOOR. | | (PAINTED SURFACES OR WALL PAPER DO NOT MEET THE "HARD" | | REQUIREMENT OF THE CODE SECTION. | | ****RESPONSE NOTED, BUT THE SPECIFICATION APPENDIX A | | FINISH SCHEDULE DOES NOT REFLECT THE INFORMATION SHOWN | | ON SHT AF-211 DETAIL (2). PLEASE SUBMIT THE INFORMATION | | FOR ROOMS 208 & 209 AS WELL. ALSO THE PERSONAL SEAL, | | SIGNATURE AND DATE OF THE ARCHITECT SHALL APPEAR ON ALL | | ARCHITECTURAL DOCUMENTS TO BE FILED FOR PUBLIC RECORD | | PER FAC 61G1-16.003. THE TITLE BLOCK WITH ALL REQUIRED | | INFORMATION IS ALSO REQUIRED ON EACH SPECIFICATION | | APPENDIX A SHEET. THIS IS REQUIRED FOR ALL SHEETS | | SUBMITTED FOR PUBLIC RECORD SUCH AS THE DOOR SCHEDULE | | AND OTHER 8-1/2" BY 11" SHEETS SUBMITTED WITH | | SPECIFICATION INFORMATION. | | ******RESPONSE NOTED, BUT THE TITLE BLOCK INFORMATION | | REQUIRED IN NOT ON THE SHEETS AS REQUESTED. | | (SPOKE TO MR. ERNIEPALMER AND HE INDICATED THE INDEX | | FOR THE SPECIFICATION SHEETS HAS THE APPROPRIATE TITLE | | BLOCK INFORMATION) KSTEVENS | | | | 7. OK | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | WITH A DESCRIPTION OF THE REVISION | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID | | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY | | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU | | FOR YOUR ANTICIPATED COOPERATION. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2007-09-08 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2007-09-08 |
Time |
07:22 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2007-09-08 |
Time |
07:21 |
Sent To |
|
|
Notes |
2007-09-08 10:12:01 | DENIED | | REFERENCE: FBC-2004 PLUMBING | | FBC-2004 CHAPTER 1 | | FBC-2004 CHAPTER 11 | | FBC-2004 BUILDING | | | | ****FROM PREVIOUS REVIEW: | | | | 1. SHT AF-210 DETAILS 6 & 9 LOUNGE (RMS 130 & 159) | | SINKS SHALL BE ACCESSIBLE. PLEASE SUBMIT A DETAIL | | SHOWING COMPLIANCE WITH SECTION 11-4.24 AND ALL | | SUBSECTIONS. | | ****RESPONSE NOTED, BUT SHOW COMPLIANCE WITH THE | | FOLLOWING: | | A. 11-4.24.3 KNEE CLEARANCE | | B. 11-4.24.4 SINK DEPTH | | C. 11-4.24.5 CLEAR FLOOR SPACE - FORWARD APPROACH | | REQUIRED - CABINET DOORS UNDER SINK NOT APPROVED IN | | CLEAR FLOOR SPACE. PLEASE REMOVE. | | D. 11-4.24.6 EXPOSED PIPES & SURFACES | | C. 11-4.24.7 FAUCETS | | | | 2. SHT AF-212 DETAIL 5 KITCHEN SINK SHALL BE | | ACCESSIBLE. PLEASE SUBMIT A DETAIL SHOWING COMPLIANCE | | WITH SECTION 11-4.24 AND ALL SUBSECTIONS. ****RESPONSE | | STATES SINK HEIGHTS REVISED, BUT DETAIL DELETED. PLEASE | | CLARIFY. SECTION 106.1.1. | | | | 3. OK | | 4. OK | | 5. OK | | | | 6. TOILET ROOMS 112, 131, 152, 161 & 183. PLEASE | | INDICATE FINISH FOR THE FLOORS AND WALLS PER SECTIONS | | 1210.1 & 1210.2. BE MINDFULL THAT THE WALLS WITHIN 2' | | OF ALL URINALS AND WATER CLOSETS SHALL HAVE A "SMOOTH, | | HARD, NONABSORBENT SURFACE" UP TO 4' ABOVE THE FLOOR. | | (PAINTED SURFACES OR WALL PAPER DO NOT MEET THE "HARD" | | REQUIREMENT OF THE CODE SECTION. | | ****RESPONSE NOTED, BUT THE SPECIFICATION APPENDIX A | | FINISH SCHEDULE DOES NOT REFLECT THE INFORMATION SHOWN | | ON SHT AF-211 DETAIL (2). PLEASE SUBMIT THE INFORMATION | | FOR ROOMS 208 & 209 AS WELL. ALSO THE PERSONAL SEAL, | | SIGNATURE AND DATE OF THE ARCHITECT SHALL APPEAR ON ALL | | ARCHITECTURAL DOCUMENTS TO BE FILED FOR PUBLIC RECORD | | PER FAC 61G1-16.003. THE TITLE BLOCK WITH ALL REQUIRED | | INFORMATION IS ALSO REQUIRED ON EACH SPECIFICATION | | APPENDIX A SHEET. THIS IS REQUIRED FOR ALL SHEETS | | SUBMITTED FOR PUBLIC RECORD SUCH AS THE DOOR SCHEDULE | | AND OTHER 8-1/2" BY 11" SHEETS SUBMITTED WITH | | SPECIFICATION INFORMATION. | | | | 7. PLEASE SUBMIT SANITARY PIPING PLAN VIEW THAT REFLECT | | THE RISER DIAGRAM FOR THE FIRST AND SECOND FLOOR. | | SECTION 106.3.5.1.3(4). | | ****RESPONSE NOTED, AND I WILL VERIFY INFORMATION ON | | PERMIT #07010472. | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | WITH A DESCRIPTION OF THE REVISION | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID | | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY | | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU | | FOR YOUR ANTICIPATED COOPERATION. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2007-06-02 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2007-06-02 |
Time |
14:35 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2007-06-02 |
Time |
14:35 |
Sent To |
|
|
Notes |
2007-06-02 14:54:15 | DENIED | | REFERENCE: FBC-2004 PLUMBING | | FBC-2004 CHAPTER 1 | | FBC-2004 CHAPTER 11 | | FBC-2004 BUILDING | | | | 1. SHT AF-210 DETAILS 6 & 9 LOUNGE (RMS 130 & 159) | | SINKS SHALL BE ACCESSIBLE. PLEASE SUBMIT A DETAIL | | SHOWING COMPLIANCE WITH SECTION 11-4.24 AND ALL | | SUBSECTIONS. | | | | 2. SHT AF-212 DETAIL 5 KITCHEN SINK SHALL BE | | ACCESSIBLE. PLEASE SUBMIT A DETAIL SHOWING COMPLIANCE | | WITH SECTION 11-4.24 AND ALL SUBSECTIONS. | | | | 3. SHT AF-212 DETAIL 3 INDICATES "TEACHING APT 224". | | WILL THERE BE PATIENTS STAYING IN THE APT OVERNIGHT, | | WEEKLY ETC. PLEASE CLARIFY AS A WASH MACHINE HOOK MAY | | BE REQUIRED PER TABLE 403.1. | | | | 4. SHT AF-405 ACCESSIBLE LAV TO BE MAX 34" OFF THE | | FLOOR TO THE FLOOD RIM LEVEL PER SECTION 11-4.19.2. | | THIS IS SHOWN AS 36" ON TWO DETAILS.--ACCESSIBLE | | W/C'S TO BE 17" TO 19" PER SECTION 11-4.16.3. DETAIL | | SHOWS 16-1/2" TO 19-1/2". PLEASE CORRECT DETAIL. | | | | 5. SUBMIT A DETAIL FOR THE ACCESSIBLE SHOWERS SHOWING | | COMPLIANCE WITH SECTION 11-4.21 AND ALL SUBSECTIONS. | | | | 6. TOILET ROOMS 112, 131, 152, 161 & 183. PLEASE | | INDICATE FINISH FOR THE FLOORS AND WALLS PER SECTIONS | | 1210.1 & 1210.2. BE MINDFULL THAT THE WALLS WITHIN 2' | | OF ALL URINALS AND WATER CLOSETS SHALL HAVE A "SMOOTH, | | HARD, NONABSORBENT SURFACE" UP TO 4' ABOVE THE FLOOR. | | (PAINTED SURFACES OR WALL PAPER DO NOT MEET THE "HARD" | | REQUIREMENT OF THE CODE SECTION. | | | | 7. PLEASE SUBMIT SANITARY PIPING PLAN VIEW THAT REFLECT | | THE RISER DIAGRAM FOR THE FIRST AND SECOND FLOOR. | | SECTION 106.3.5.1.3(4). | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | WITH A DESCRIPTION OF THE REVISION | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID | | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY | | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU | | FOR YOUR ANTICIPATED COOPERATION. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
P |
Date |
2008-07-16 |
|
|
Cont ID |
|
Sent By |
lmartine |
Date |
2008-07-16 |
Time |
15:43 |
Rev Time |
0.00 |
Received By |
lfranco |
Date |
2008-07-16 |
Time |
15:45 |
Sent To |
|
|
Notes |
2008-07-10 18:22:29 | PLANNING AND ZONING:**** PASSED **** | | | | MINOR AMENDMENT IN PROCESS WITH THE PLANNING AND ZONING | | DEPARTMENT ( PLANS FOR LANDSCAPE HAVE INCLUDED THE | | ADDTL. TREE AT THE MIDDLE TERMINAL ISLAND ON THE SOUTH | | SIDE OF THE BLDG. (REAR OF STRUCTURE). | | | | LINDA MIA FRANCO | | SENIOR PLANNER | | TEL: (561) 822-1443 | | EMAIL: [email protected] |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2007-11-27 |
|
|
Cont ID |
|
Sent By |
lfranco |
Date |
2007-11-08 |
Time |
18:46 |
Rev Time |
0.00 |
Received By |
lfranco |
Date |
2007-11-06 |
Time |
10:00 |
Sent To |
|
|
Notes |
2007-11-08 18:45:36 | INTERIOR BUILDING PERMIT ONLY (PASS) |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2007-08-22 |
|
|
Cont ID |
|
Sent By |
lfranco |
Date |
2007-08-22 |
Time |
16:32 |
Rev Time |
0.00 |
Received By |
lfranco |
Date |
2007-08-22 |
Time |
16:32 |
Sent To |
|
|
Notes |
|
|
|