Review Stop B BUILDING (STRUCTURAL)
Rev No 13 Status P Date 2008-07-25 Cont ID  
Sent By jwitmer Date 2008-07-25 Time 16:29 Rev Time 0.77
Received By jwitmer Date 2008-07-25 Time 16:29 Sent To  
Notes
2008-07-25 16:30:22GV-102 REVISION # 5

Review Stop B BUILDING (STRUCTURAL)
Rev No 12 Status P Date 2008-07-25 Cont ID  
Sent By jwitmer Date 2008-07-25 Time 16:16 Rev Time 0.77
Received By jwitmer Date 2008-07-25 Time 16:16 Sent To  
Notes
2008-07-25 16:17:08SHEET GV-102 REVISION# 5 OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 11 Status P Date 2008-07-16 Cont ID  
Sent By jwitmer Date 2008-07-16 Time 10:43 Rev Time 0.77
Received By jwitmer Date 2008-07-16 Time 10:43 Sent To FIRE
Notes
2008-07-16 10:44:46BUILDING PLAN REVIEW
 PERMIT: 07040621
 ADD: 5205 GREENWOOD
 CONT: HEDRICK BROTHERS
 TEL: (561)689-8880
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVISIONREVIEW
 ACTION: REVIEWED
  
 REVISONAF-321 NEW SHEET WALL PENETRATION DETAILS
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 10 Status F Date 2008-07-16 Cont ID  
Sent By jwitmer Date 2008-07-16 Time 10:21 Rev Time 0.55
Received By jwitmer Date 2008-07-16 Time 10:21 Sent To  
Notes
2008-07-16 10:27:02BUILDING PLAN REVIEW
 PERMIT: 07040621
 ADD: 5205 GREENWOOD
 CONT: HEDRICK BROTHERS
 TEL: (561)689-8880
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVISIONREVIEW
 ACTION: DENIED
  
 REVISON TO CS-101 REVISION 5 PR#10 IS A REVISION TO
 STAIRS AND HANDRAIL, DETAIL 7/ CS501 THERE IS NO
 NARATIVE NOR DETAIL INDICATING WHAT HAS CHANGED, ONLY
 THERE IS A CHANGE. 106.1.2 ADDITIONAL INFORMATION
 REQUIRED.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status F Date 2008-06-30 Cont ID  
Sent By jwitmer Date 2008-06-30 Time 10:10 Rev Time 1.77
Received By jwitmer Date 2008-06-30 Time 10:10 Sent To PC
Notes
2008-06-30 10:53:06BUILDING PLAN REVIEW
 PERMIT: 07040621
 ADD: 5205 GREENWOOD
 CONT: HEDRICK BROTHERS
 TEL: (561)689-8880
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVISIONREVIEW
 ACTION: DENIED
  
 SHEET GV-102 THE REVISION INDICATES THE REMOVAL OF
 RATED SMOKE PARTITIONS FOR THE INCIDENTIAL MECHANICAL
 CHASE AND ELECTRICAL ROOM ON THE SECOND FLOOR LEVEL.
 INCIDENTIAL USE AREAS AS PER TABLE
 302.1.1.1REQUIRES A 1 HOUR SEPERATION WITH THE
 EXCEPTION FOR FULLY SPRINKLED BUILDINGS WHICH THIS HAS.
 IN 302.1.1.1 WHERE TABLE 302.1.1 PERMITS AN AUTOMATIC
 FIRE -EXTINGUISHING SYSTEM WITHOUT A FIRE-BARRIER, THE
 INCIDENTIAL USE AREA SHALL BE SEPERATED BY CONSTRUCTION
 CAPABLE OF RESISTING THE PASSAGE OF SMOKE.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2008-05-05 Cont ID  
Sent By lmartine Date 2008-05-05 Time 13:16 Rev Time 0.00
Received By lmartine Date 2008-05-05 Time 13:16 Sent To  
Notes
2008-05-05 13:18:37RESTAMP BUILDING PAGES ONLY LM

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2008-02-26 Cont ID  
Sent By jwitmer Date 2008-02-26 Time 11:02 Rev Time 1.11
Received By jwitmer Date 2008-02-26 Time 11:01 Sent To  
Notes
2008-02-26 11:03:08REV# PR# 7 DATED 01-03-08

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2008-01-25 Cont ID  
Sent By jwitmer Date 2008-01-25 Time 16:17 Rev Time 0.77
Received By jwitmer Date 2008-01-25 Time 16:17 Sent To  
Notes
2008-01-25 16:18:38MISSING SHEETS FROM THE APPROVED SET OF PLANS IN-101,
 IN-102 & AF-102

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2008-01-15 Cont ID  
Sent By jwitmer Date 2008-01-15 Time 17:20 Rev Time 2.22
Received By jwitmer Date 2008-01-15 Time 17:20 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-11-02 Cont ID  
Sent By jwitmer Date 2007-11-02 Time 13:36 Rev Time 4.44
Received By jwitmer Date 2007-11-02 Time 13:36 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-11-02 Cont ID  
Sent By jwitmer Date 2007-11-02 Time 09:04 Rev Time 4.44
Received By jwitmer Date 2007-11-02 Time 08:33 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-08-31 Cont ID  
Sent By jwitmer Date 2007-08-31 Time 12:13 Rev Time 4.44
Received By jwitmer Date 2007-08-30 Time 17:37 Sent To  
Notes
2007-08-31 12:14:415205 GREENWOOD AVE
 BUILD-OUT3RD REVIEW
  
  
  
  
 BUILDING PLAN REVIEW
 PERMIT: 07040621
 ADD: 5205 GREENWOOD
 CONT: HEDRICK BROTHERS
 TEL: (561)689-8880
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
 3RDREVIEW
 ACTION: DENIED
  
 NOTE! THIS PROJECT HAS BEEN SUBMITTED AS A PHASED
 PROJECT, THERE HAS BEEN A REMODEL ELEMENT, AND AN
 ADDITION TO THIS STRUCTURE.
 PLEASE NOTE THAT THESE PLANS WILL BE REVIEWED UNDER THE
 2004 EXISTING BUILDING CODE 2006 EDITION , ALTERATIONS
 : LEVEL 3 AND CHAP 9 FOR ADDITIONS
 AS WELL AS 2006 FBC BUILDING..
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2 ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY
 COMMENCED WITHIN 90 DAYS AFTER THE RECORDING THEREOF,
 SUCH NOTICE IS NULL & VOID.
 NOTE: 713.13(6)THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION
 SITE BEFORE THE FIRST INSPECTION.
  
 3-4) COMPLIED.
  
 5) SEMI-COMPLIED.SHEET GV-101 DOOR 174A IS MISSING
 THE 18? ON THE PULL SIDE OF DOOR AT LATCH SIDE OF DOOR.
 11-4.13.6 MANEUVERING CLEARENCES AT DOORS. MINIMUM
 MANEUVERING CLEARANCES AT DOORS THAT ARE NOT AUTOMATIC
 OR POWER-ASSISTED SHALL BE AS SHOWN IN FIG. 25. THE
 FLOOR OR GROUND AREA WITH IN THE REQUIRED CLEARANCES
 SHALL BE CLEAR & LEVEL.
 6-7A) COMPLIED.
  
 7B) PROVIDE HOW THIS DOOR WILL CLOSE IF THE FIRE ALARMS
 OR FIRE SPRINKLERS ARE ACTIVATED?
  
 7C)2ND REQUEST. SEMI-COMPLIED, THE DETAIL# 03 ON
 AF-402 IS TO BE 1HR RATED WALL PLEASE PROVIDE THE UL
 NUMBER OR US GYPSUM NUMBER THAT ALLOWS DRYWALL ON ONLY
 ONE SIDE OF THE ASSEMBLY? PLEASE PROVIDE THE COMPLETE
 UL LISTING NUMBER, PROVIDE A DETAIL OF THE UL LISTING
 AND PROVIDE A SECTION OF THE L HOUR RATED WALL.706.3
 FIRE RESISTANCE RATINGS.
  
 7D-9) COMPLIED.
  
 10) 2ND REQUEST,GV-102 ELEVATOR LOBBY 200 INDICATES A
 PAIR OF DOORS AND THE OPPOSITE END OF THIS AREA THERE
 APPEARS TO BE GLASS, IT IS NOT CLEAR IF THIS IS A WALL
 OR IF IT IS A GLASS HANDRAIL, PLEASE PROVIDE A CUT
 THROUGH THIS SECTION. SEE ATRIUM REQUIREMENTS 404.5 SEE
 EXCEPTION (1).THE PLAN ACTUALLY INDICATES THE 1 HR
 RATED WALL TO FALL IN LINE WITH DOOR LINE. SHEET AF-601
 INDICATES DOORS AND FRAMES BUT NO DOOR SCHEDULE. PLEASE
 PROVIDE THIS INFORMATION FOR THESE DOORS AND THE RATED
 DOORS FOR THE FIRST FLOOR.
 SHEET EA101 & EA 102 INDICATE SYMBOLS THAT
 POSSIBLY TIE TO THE ALARM PANEL BUT SHEET
 EC-001 WHICH IS THE FIRE ALARM SYMBOLS AND NOTES IS
 MISSING PLEASE PROVIDE. ADDITIONAL INFORMATION REQUIRED
 106.1.2*.
  
 11) NOTE, BY DEFINITION, THIS AREA (LOBBY 100) IS AN
 ATRIUM. ATRIUM . AN OPENING CONNECTING TWO OR MORE
 STORIES OTHER THAN ENCLOSED STAIRWAYS, ELEVATORS,
 HOISTWAY, ESCALATORS, PLUMBING, ELECTRICAL,
 AIR-CONDITIONING OR OTHER EQUIPMENT, WHICH IS CLOSED AT
 THE TOP AND NOT DEFINED AS A MALL. STORIES, AS USED IN
 THIS DEFINITION, DO NOT INCLUDE BALCONIES WITHIN
 ASSEMBLY GROUPS OR MEZZANINES THAT COMPLY WITH SECTION
 505 .
  
 11A-11B) COMPLIED. SMOKE CONTROL NOT REQUIRED SECTION
 404 EXCEPTIONS.
  
 12-17) COMPLIED.
  
 18)SEMI-COMPLIED, THE FRONTS AND INTERIOR OF THE
 CABINETS ARE TO BE REMOVED FOR FRONTAL APPROACH
 11-4.24.3 KNEE CLEARANCE THAT IS AT LEAST 27" HIGH 30"
 WIDE, AND 19" DEEP SHALL BE PROVIDED UNDERNEATH SINKS.
 11-4.24.5 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE AT
 LEAST 30 INCHES BY 48 INCHES (760 MM BY 1219 MM)
 COMPLYING WITH SECTION 11-4.2.4 SHALL BE PROVIDED IN
 FRONT OF A SINK TO ALLOW FORWARD APPROACH. THE CLEAR
 FLOOR SPACE SHALL BE ON AN ACCESSIBLE ROUTE AND SHALL
 EXTEND A MAXIMUM OF 19 INCHES (485 MM) UNDERNEATH THE
 SINK.
  
 19-20) COMPLIED.
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC
 REQUIREMENT SHALL BE APPLICABLE.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-05-30 Cont ID  
Sent By jwitmer Date 2007-05-30 Time 13:01 Rev Time 3.33
Received By jwitmer Date 2007-05-30 Time 13:01 Sent To  
Notes
2007-05-30 16:57:08BUILDING PLAN REVIEW
 PERMIT: 07040621
 ADD: 5205 GREENWOOD
 CONT: HEDRICK BROTHERS
 TEL: (561)689-8880
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
  
 NOTE! THIS PROJECT HAS BEEN SUBMITTED AS A PHASED
 PROJECT, THERE HAS BEEN A REMODEL ELEMENT, AND AN
 ADDITION TO THIS STRUCTURE.
 PLEASE NOTE THAT THESE PLANS WILL BE REVIEWED UNDER THE
 2004 EXISTING BUILDING CODE 2006 EDITION , ALTERATIONS
 : LEVEL 3 AND CHAP 9 FOR ADDITIONS
 AS WELL AS 2006 FBC BUILDING..
  
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2 ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY
 COMMENCED WITHIN 90 DAYS AFTER THE RECORDING THEREOF,
 SUCH NOTICE IS NULL & VOID.
 NOTE: 713.13(6)THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION
 SITE BEFORE THE FIRST INSPECTION.
  
 3A) SHEET GV-101 TYPE OF CONSTRUCTION: IV HEAVY TIMBER
 PLEASE LOOK AT
 SECTION 602 FOR BUILDING CONSTRUCTION CLASSIFICATIONS
 AND TABLE 503.THIS BUILDING IS NOT
 A HEAVY TIMBER DESIGN. NOTE IF IT IS AN "A OR B"
 CLASSIFICATION.
  
 3B) GV-101 INDICATES 9006 SQ FT FIRST FLOOR WHILE THE
 2ND FLOOR HAS 9170, THE FOOTPRINT ON THE FIRST FLOOR IS
 LARGER HAVING MORE ARERA, PLEASE RECALCULATE PLUS
 COVERED WALKWAY!
  
 3C) NOTE INCREASES THAT CAN BE TAKEN FOR A FULLY
 SPRINKLERED BUILDING(AREA INCREASES)!
  
 4) PLANS ALSO INDICATE THE BUILDING DESIGN IS THE 2004
 FBC, PLANS SUBMITTED
 AFTER DEC 12,2006 FALL IN UNDER THE 2006 FBC.
  
 5)SHEET GV-101 INDICATES DOORWAYS IN THE CORRIDOR
 THAT DO NOT HAVE IDENTIFYING TAGS, THE FIRST DOOR ISUE
  
 IS LOCATED BETWEEN ROOM 167 AND ROOM 171, THE SECOND
 DOOR IS LOCATED BETWEEN
 ROOMS 193 AND 125B. IN BOTH CASES IT APPEARS THERE IS
 NOT 18" ON THE LATCH SIDE OF THE DOORWAY. 11-4.13.6
 MANEUVERING CLEARENCES AT DOORS. MINIMUM MANEUVERING
 CLEARANCES
 AT DOORS THAT ARE NOT AUTOMATIC OR POWER-ASSISTED SHALL
 BE AS SHOWN IN FIG. 25. THE FLOOR OR
 GROUND AREA WITH IN THE REQUIRED CLEARANCES SHALL BE
 CLEAR & LEVEL.
  
 6)PLANS INDICATE THIS IS A BUSINESS OCCUPANCY, THE
 PLANS DO NOT IDENTIFY IF IT IS A SINGLE TENANT? THE
 FIRST FLOOR DOES HAVE TWO
 WAITING ROOMS 110 AND 150? 106.1.2* ADD INFO REQUIRED
 AND708.1(5).
  
 7) GV-102 THE PLANS INDICATE ON THE MAIN ENTRY STAIR
 WITH ACOILING FIRE RATED DOOR AT THE HEAD OF THE
 SECOND STORY LANDING AND WHAT APPEARS TO BE A 1 HOUR
 RATED WALL.
 SHEET AF-402 DETAIL 03 INDICATES A HORIZONTAL COILING
 FIRE DOOR.
 7A) PLEASE SUBMIT PRODUCT INFORMATION FOR A 1 HR RATED
 ASSEMBLY.
 7B) PROVIDE HOW THIS DOOR WILL CLOSE IF THE FIRE ALARMS
 OR FIRE SPRINKLERS ARE ACTIVATED?
 7C) THE DETAIL# 03 ON AF-402 IS TO BE 1HR RATED WALL
 PLEASE PROVIDE THE UL NUMBER OR US GYPSUM NUMBER THAT
 ALLOWS DRYWALL ON ONLY ONE SIDE OF THE ASSEMBLY? 7D)
 PLEASE INDICATE HOW ONE WOULD GAIN ACCESS TO DO
 MAINTENCE WORK ON THE COILED FIRE DOOR ? ADDITIONAL
 COMMENTS MAY APPEAR ON THESE ITEMS ONCE THE RESPONCES
 ARE REVIEWED.
  
 8)GV-102 PLANS APPEAR TO HAVE A SLEEP STUDY AREA WITH
 A CONTROL ROOM. PLEASE PROVIDE ADDITIONAL INFORMATION
 AS TOTHE FUCTION OF THIS AREA? WILL THE PATIENTS BE
 THERE OVER 24 HRS?
 WILL THE PATIENTS BE MEDICATED? AND WILL THERE BE MORE
 THAN ONE PATEINT THERE SLEEPING?
  
 9)GV-102 ROOM 210 CONFERENCE PRESENTATION THERE
 APPEARS TO BE A SEPERATE ROOM IN THE UPPER RIGHT CORNER
 WITH NO IDENTIFICATION? PLEASE PROVIDE ADDITIONAL
 INFORMATION. 106.1.2*
  
 10) GV-102 ELEVATOR LOBBY 200 INDICATES A PAIR OF DOORS
 AND THE OPPOSITE END OF THIS AREA THERE APPEARS TO BE
 GLASS, IT IS NOT CLEAR IF THIS IS A WALL OR IF IT IS A
 GLASS HANDRAIL, PLEASE PROVIDE A CUT THROUGH THIS
 SECTION. SEE ATRUIM REQUIREMENTS 404.5 SEE EXCEPTION
 (1).THE PLAN ACTUALLY INDICATES THE 1 HR RATED WALL
 TO FALL IN LINE WITH DOOR LINE. SHEET AF-601 INDICATES
 DOORS AND FRAMES BUT NO DOOR SCHEDULE. PLEASE PROVIDE
 THIS INFORMATION FOR THESE DOORS AND THE RATED DOORS
 FOR THE FIRST FLOOR.
  
 11) NOTE, BY DEFINITION, THIS AREA (LOBBY 100) IS AN
 ATRIUM. ATRIUM . AN OPENING CONNECTING TWO OR MORE
 STORIES OTHER THAN ENCLOSED STAIRWAYS, ELEVATORS,
 HOISTWAY, ESCALATORS, PLUMBING, ELECTRICAL,
 AIR-CONDITIONING OR OTHER EQUIPMENT, WHICH IS CLOSED AT
 THE TOP AND NOT DEFINED AS A MALL. STORIES, AS USED IN
 THIS DEFINITION, DO NOT INCLUDE BALCONIES WITHIN
 ASSEMBLY GROUPS OR MEZZANINES THAT COMPLY WITH SECTION
 505 .
  
 11A)404.4 SMOKE CONTROL. A SMOKE CONTROL SYSTEM SHALL
 BE INSTALLED IN ACCORDANCE WITH SECTION 909 .
 11B)404.6 STANDBY POWER. EQUIPMENT REQUIRED TO
 PROVIDE SMOKE CONTROL SHALL BE CONNECTED TO A STANDBY
 POWER SYSTEM IN ACCORDANCE WITH SECTION 909.11 .
  
 12) GV-102ROOM 223 PLEASE SHOW THE CLEAR FLOOR SPACE
 REQUIRED FOR PLUMBING FIXTURES, IT APPEARS THAT THE
 DOORWAY MAY SWING INTO THE LAV CLEAR FLOOR SPACE.
 11-4.19.3 CLEAR FLOOR SPACE .
 A CLEAR FLOOR SPACE 30 INCHES BY 48 INCHES (760 MM BY
 1219 MM) COMPLYING WITH SECTION 11-4.2.4 SHALL BE
 PROVIDED IN FRONT OF A LAVATORY TO ALLOW FORWARD
 APPROACH. SUCH CLEAR FLOOR SPACE SHALL ADJOIN OR
 OVERLAP AN ACCESSIBLE ROUTE AND SHALL EXTEND A MAXIMUM
 OF 19 INCHES (485 MM) UNDERNEATH THE LAVATORY (SEE
 FIGURE 32 ).
  
 13) GV-102 ROOM XXX SHELL IS THIS THE SAME TENANT
 SPACE?
  
 14)PLEASE DEVELOP A DOOR IDENIFICATION SYSTEM NO
 DOORS ARE IDENTIFIED ON EITHER FLOOR.
  
 15) GV-102 CONFERENCE ROOM 210 HAS AN OCCUPANT LOAD OF
 APPROX 114 PEOPLE PLEASE SEE TABLE 1016.1 FOR ASSEMBLY
 OCCUPANCIES, OCCUPANT LOADS SERVED BY CORRIDORS, TABLE
 1016.1WITH SPRINKLERS SYSTEMS AND OCCUPANT LOADS >30
 REQUIRING 1 HR RATED CORRIDORS.
  
 16) GV-102 ROOM 211 ELEVATOR MACHINE ROOM. 3006.4
 MACHINE ROOMS AND MACHINERY SPACES.
 ELEVATOR MACHINE ROOMS AND MACHINERY SPACES SHALL BE
 ENCLOSED WITH CONSTRUCTION HAVING A FIRE-RESISTANCE
 RATING NOT LESS THAN THE REQUIRED RATING OF THE
 HOISTWAY ENCLOSURE SERVED BY THE MACHINERY. OPENINGS
 SHALL BE PROTECTED WITH ASSEMBLIES HAVING A
 FIRE-RESISTANCE RATING NOT LESS THAN THAT REQUIRED FOR
 THE HOISTWAY ENCLOSURE DOORS.
  
 17) GV-102 ROOM 211 3006.1 ACCESS.AN APPROVED MEANS
 OF ACCESS SHALL BE PROVIDED TO ELEVATOR MACHINE ROOMS .
 AN APPROVED ACCESS DOES NOT HAVE MEANS OF EGRESS
 THROUGH TENANT SPACES.
  
 18)AF-210 LOUNGE SINK IS CABINET ELEVATION INDICATES
 A 3'-0" ELEVATION. SINKS:11-4.24.2 SINKS, HEIGHT.
 SINKS SHALL BE MOUNTED WITH THE COUNTER NO HIGHER THAN
 34" ABOVE THE FINISH FLOOR.
 11-4.24.3 KNEE CLEARANCE THAT IS AT LEAST 27" HIGH
 30" WIDE, AND 19" DEEP SHALL BE PROVIDED UNDERNEATH
 SINKS. 11-4.24.5 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE
 AT LEAST 30 INCHES BY 48 INCHES (760 MM BY 1219 MM)
 COMPLYING WITH SECTION 11-4.2.4 SHALL BE PROVIDED IN
 FRONT OF A SINK TO ALLOW FORWARD APPROACH. THE CLEAR
 FLOOR SPACE SHALL BE ON AN ACCESSIBLE ROUTE AND SHALL
 EXTEND A MAXIMUM OF 19 INCHES (485 MM) UNDERNEATH THE
 SINK.
  
 19) AF-320 VARIOUS WALLS INDICATE THAT SOME MAY REQUIRE
 FIRE RATINGS, PLEASE PROVIDEINFORMATION ON THE FLOOR
 TO FLOOR ORFLOOR TO ROOF/ CEILING ASSEMBLIES. 713.1
 GENERAL. JOINTS INSTALLED IN OR BETWEEN
 FIRE-RESISTANCE-RATED WALLS, FLOOR OR FLOOR/CEILING
 ASSEMBLIES AND ROOFS OR ROOF/CEILING ASSEMBLIES SHALL
 BE PROTECTED BY AN APPROVED FIRE-RESISTANT JOINT SYSTEM
 DESIGNED TO RESIST THE PASSAGE OF FIRE FOR A TIME
 PERIOD NOT LESS THAN THE REQUIRED FIRE-RESISTANCE
 RATING OF THE WALL, FLOOR OR ROOF IN OR BETWEEN WHICH
 IT IS INSTALLED. FIRE-RESISTANT JOINT SYSTEMS SHALL BE
 TESTED IN ACCORDANCE WITH SECTION 713.3 . THE VOID
 CREATED AT THE INTERSECTION OF A FLOOR/CEILING ASSEMBLY
 AND AN EXTERIOR CURTAIN WALL ASSEMBLY SHALL BE
 PROTECTED IN ACCORDANCE WITH SECTION 713.4 .
  
 20) AF-401 GRAND STAIR SECTION AT THE TOP OF THE
 STAIRCASE THE HORIZONTAL PROJECTION OFTHE HANDRAIL IS
 TO BE A MINIMUM OF 1'-0" LONG. 11-4.9.4
  
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 9 Status P Date 2008-05-04 Cont ID  
Sent By dpalmer Date 2008-05-04 Time 10:42 Rev Time 0.00
Received By dpalmer Date 2008-05-04 Time 10:00 Sent To  
Notes
2008-05-04 10:43:04** DENIED/PASSED REVIEW **
  
  
 1) NOTE: PLEASE SEE SOME OF THE REVISED SHEETS
 SUBMITTED ARE STAMPED OK FOR ELECTRICAL HOWEVER SOME
 ARE *FAILED*.
 PLEASE SEE THE FOLLOWING SHEETS LISTED ARE OK.
 EL-101, EL-102, EL-103, EE-301, EL-104, EE-310, EE-311,
 EE-401. THESE SHEETS ARE OK AND ONCE FIRE MARSHAL
 REVIEW IS DONE THESE CAN BE RELEASED.
  
 ** PLEASE SEE THE FOLLOWING SHEETS ARE FAILED BASED ON
 THE FACT THESE SHEETS ARE ALREADY IN FILE AS BEING
 REVISED PREVIOUSLY. THEY HAVE BEEN STAMPED WITH A VOID
 STAMP AS NOT TO GET CONFUSED WITH ACTUAL SHEETS WHICH
 ARE OK.
  
 ** PLEASE KNOW ONCE FIRE REVIEW IS DONE AND IS OK, ONE
 SET OF ELECTRICAL PLANS AND FIRE ALARM REVISIONS NEED
 TO BE RETAINED FOR RECORD SET.
 FIRE ALARM SHEETS HAVE BEEN REVISED FROM FILE SET
 PLANS. THESE ARE NOT RE-STAMPS.
  
  
 IF THERE ARE ANY QUESTIONS, PLEASE DO NOT HESITATE IN
 CONTACTING THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 8 Status F Date 2008-02-15 Cont ID  
Sent By dpalmer Date 2008-02-15 Time 08:51 Rev Time 0.00
Received By dpalmer Date 2008-02-14 Time 19:27 Sent To  
Notes
2008-02-15 08:52:092008-02-15 08:52:09
  
 *** DENIEDREVISIONS***
  
 1) NOTE: PLEASE SEE AS REQUESTED ON ALL PREVIOUS
 REVIEWS. PLEASE SUBMIT AND SHOW THE LIGHTING LEVELS FOR
 EGRESS PATHS FOR STAIRS UNDER NORMAL AND EMERGENCY
 CONDITIONS PER LS 1017.8.1.3 AND 7.9.2.2.
 THE ONLY SUBMITTED LEVELS ARE THE LEVELS UNDER
 EMERGENCY WHICH ARE OK, HOWEVER NO LEVELS UNDER NORMAL.
 THE NORMAL LIGHTING LEVELS FOR STAIRS IS TEN FOLD WHAT
 IS REQUIRED AS A MINIMUM UNDER EMERGENCY.
 ONCE AGAIN, PLEASE SEE 7.8.1.3 WHICH REQUIRES * 10FT
 CANDLES MINIMUM. THE FOLLOWING IS TEXT WHICH HAS BEEN
 CUT AND PASTED DIRECTLY FROM NFPA-101 2003.
 ***
 7.8.1.3* THE FLOORS AND OTHER WALKING SURFACES WITHIN
 AN EXIT AND WITHIN THE PORTIONS OF THE EXIT ACCESS AND
 EXIT DISCHARGE DESIGNATED IN 7.8.1.1 SHALL BE
 ILLUMINATED AS FOLLOWS:
 (1)DURING CONDITIONS OF STAIR USE, THE MINIMUM
 ILLUMINATION FOR NEW STAIRS SHALL BE AT LEAST 108 LUX
 (10 FT-CANDLE), MEASURED AT THE WALKING SURFACES.
  
 PLEASE SUBMIT
  
 2) NOTE: PLEASE SEE 700.12F FOR CIRCUITING OF EMERGENCY
 OR EXIT LIGHTS. THERE ARE EXCEPTIONS HOWEVER BASED ON
 THE LIGHTING AND CIRCUITING ON PLANS THE EXIT LIGHTS IN
 MAIN ENTRANCE AREA NEED TO BE CIRCUITED AHEAD OF ANY
 SWITCHING OR CONTROL DEVICES AND TO LOCAL BRANCH
 CIRCUIT.
 PLEASE THERE IS THE OCTAGONAL NOTE #1 ON THE NHP-8
 CIRCUIT IN MAIN LOBBY, HOWEVER OCTAGONAL NOTE #1 SHOWS
 THIS AS *NOT USED*.
 PLEASE COORDINATE.
  
  
 PLEASE SUBMIT THE ABOVE. SHEETS EE-001, EP-101, EP-102
 AND EC-102 APPEAR TO BE OK AT THIS TIME. THE OTHER
 SHEETS SUCH AS RISER SHEET WHICH SHOWS LOADS AND PANEL
 SCHEDULES WILL BE GETTING REVISED BASED ON NOTES
 ABOVE.
 REDLINED NEC 517.1 AS THIS APPLIES TO OCCUPANCY AND
 SCOPE OF WORK.
 ONLY SHEETS NOTED AS EE-001, EP-101, EP-102 AND EC-102
 ARE BEING STAMPED. ONE COPY OF THESE SHEETS ARE REMOVED
 FROM ONE SET AND KEPT FOR FILE SET OF PLANS. ONE SET OF
 SHEETS ARE GIVEN BACK FOR THE CONTRACTORS ON-SITE SET.
  
 ** IF THERE ARE QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2008-02-14 19:38:482008-02-14 19:38:49
  
 NOTES TO FOLLOW ONCE COMPLETED. SOME SHEETS ARE OK,
 SOME REMAIN WITH COMMENTS.
2008-02-14 19:27:502008-02-14 19:27:50
  
 IN ELEC FOR REVIEW, PLANS CONTAINS REVISIONS FOR FIRE,
 MECH, BLDG ALSO NOT ONLY ELECTRICAL AS INDICATED ON
 COVER SHEET.

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2008-01-24 Cont ID  
Sent By dpalmer Date 2008-01-24 Time 12:28 Rev Time 0.00
Received By dpalmer Date 2008-01-24 Time 12:28 Sent To B
Notes
2008-01-24 12:29:14STAMPED THREE SHEETS LEFT FROM PREVIOUS SETS.

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2008-01-09 Cont ID  
Sent By dpalmer Date 2008-01-09 Time 13:38 Rev Time 0.00
Received By dpalmer Date 2008-01-09 Time 13:37 Sent To  
Notes
2008-01-09 13:38:12 
 ** THE FOLLOWING WILL BE ATTACHED AS PROVISO.
  
 1) NOTE: PLEASE SEE THE LIGHTING LEVELS IN STAIRS WILL
 BE REQUIRED TO SHOW 10FT CANDLES UNDER NORMAL FOR A
 MINIMUM AND IS PERMITTED DOWN TO 1FT CANDLE UNDER
 EMERGENCY.
 PLEASE SEE 7.8.1.3, 7.9.2.2.
 PLANS SHOWS LEVELS ABOVE 10FT CANDLES FOR BOTH. THIS
 INCLUDES A NEW UPS/IPS SYSTEM WHICH IS NOT REQUIRED.
 ENGINEERS MENTIONED SYSTEM WILL BE REMOVED.
  
 2) NOTE: PLEASE SEE THE CIRCUITING FOR REAR STAIRS AND
 NOTES FOR LIGHTING AS NOTED FOR NHP-6 AND NHP-8 WILL BE
 REQUIRED TO BE UPDATED.
  
 3) NOTE: MAXIMUM TIMES NOT SHOWN ON SYMBOL LEGEND FOR
 OC DEVICE.
 MAXIMUM TIME TO BE 30MINS PER 13-415.1.ABC.1.1.
  
 4) NOTE: MISSING OC DEVICE IN ROOM 159, RED-LINED PER
 13-415.1.ABC.1.1 AND .1.2.
  
 IF THERE ARE ANY QUESTIONS, PLEASE ONCE AGAIN CONTACT
 THIS OFFICE/REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2008-01-07 Cont ID  
Sent By dpalmer Date 2008-01-07 Time 16:25 Rev Time 0.00
Received By dpalmer Date 2008-01-07 Time 16:25 Sent To  
Notes
2008-01-07 16:26:15*** TEMP FAILED STATUS***
  
 1) NOTE: 2ND SET OF PLANS MISSING SHEET EP101 AND
 EP102. CALLED ARCHITECT AND WILL FED-EX NEW SHEETS TO
 OFFICE.
  
  
  
 ** THE FOLLOWING WILL BE ATTACHED AS PROVISO.
  
 1) NOTE: PLEASE SEE THE LIGHTING LEVELS IN STAIRS WILL
 BE REQUIRED TO SHOW 10FT CANDLES UNDER NORMAL FOR A
 MINIMUM AND IS PERMITTED DOWN TO 1FT CANDLE UNDER
 EMERGENCY.
 PLEASE SEE 7.8.1.3, 7.9.2.2.
 PLANS SHOWS LEVELS ABOVE 10FT CANDLES FOR BOTH. THIS
 INCLUDES A NEW UPS/IPS SYSTEM WHICH IS NOT REQUIRED.
 ENGINEERS MENTIONED SYSTEM WILL BE REMOVED.
  
 2) NOTE: PLEASE SEE THE CIRCUITING FOR REAR STAIRS AND
 NOTES FOR LIGHTING AS NOTED FOR NHP-6 AND NHP-8 WILL BE
 REQUIRED TO BE UPDATED.
  
 3) NOTE: MAXIMUM TIMES NOT SHOWN ON SYMBOL LEGEND FOR
 OC DEVICE.
 MAXIMUM TIME TO BE 30MINS PER 13-415.1.ABC.1.1.
  
 4) NOTE: MISSING OC DEVICE IN ROOM 159, RED-LINED PER
 13-415.1.ABC.1.1 AND .1.2.
  
 IF THERE ARE ANY QUESTIONS, PLEASE ONCE AGAIN CONTACT
 THIS OFFICE/REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2007-12-23 Cont ID  
Sent By dpalmer Date 2007-12-23 Time 11:37 Rev Time 0.00
Received By dpalmer Date 2007-12-22 Time 17:04 Sent To  
Notes
2007-12-23 11:37:352007-12-23 11:37:35
 ** DENIED4TH **
  
 ** PLANS CONTAIN SOME ITEMS WHICH MAY BE REDLINED AND
 WILL NEED TO BE REVISED BEFORE ROUGH HOWEVER PLEASE SEE
 SOME ITEMS BELOW WHICH MUST BE DONE AT THIS TIME. THE
 NOTES WITH ** MUST BE ADDRESSED AT THIS TIME. THE NOTES
 WITHOUT ** WILL STILL NEED TO BE ADDRESSED, HOWEVER MAY
 BE DONE AT THIS TIME OR BEFORE ROUGH.
  
  
 ** 1) NOTE: PLEASE SEE THE RESPONSE LETTER MENTIONS
 LIGHTING PERFORMANCE DONE UNDER TABLE *B* FOR SPACE BY
 SPACE HOWEVER THERE ARE ALSO SHEETS FOR FORM 400C?
 PLEASE KNOW THAT IN EITHER CASE, THE SEPARATE LIGHTING
 PERFORMANCE CALCULATIONS SUBMITTED EACH MUST CONTAIN A
 COMPLETED TITLE BLOCK FROM THE DESIGN FIRM/ENGINEER OF
 RECORD ALONG WITH EACH SHEET SIGNED, DATED AND SEALED.
 PLEASE SEE FAC 61G15-23.002, FS 471.023.
 PLEASE KNOW THESE MAY BE SENT AND PLACED WITH PLANS AS
 THE CALCULATIONS ARE OK.
 AS NEW FORM 400C IS NOW BEING SUBMITTED FOR THE FIRST
 TIME, MECHANICAL REVIEW WILL BE REQUIRED EVEN AS THIS
 WAS PREVIOUSLY PASSED.
  
 2) NOTE: PLEASE CLARIFY WHERE THE MAXIMUM TIMES ON
 OCCUPANCY SENSORS ARE?
 PLEASE CLARIFY TYPE OF OCCUPANCY DEVICE. IR? ETC
 13-415.1.ABC.1.1, .1.2
 PLEASE SEE MISSING DEVICE FROM ROOM 159.
  
 ** 3) NOTE: PLEASE CLARIFY THE NEW UPS WHICH HAS NOW
 BEEN ADDED TO PLANS WHICH WAS NOT ON PREVIOUS PLANS.
 THE RESPONSE LETTER MENTIONS THE FIXTURES WOULD NOT
 PROVIDE THE OUTPUT FOR MINIMUM LIGHTING LEVELS, HOWEVER
 AS MENTIONED ON ALL PREVIOUS REVIEWS THE LIGHTING
 LEVELS UNDER NORMAL FOR STAIRS IS 10FT CANDLES PER
 7.8.1.3 AND IS PERMITTED TO GO DOWN TO 1FT CANDLE UNDER
 EMERGENCY CONDITIONS PER 7.9.2.2. THE AVERAGE FT CANDLE
 LEVELS UNDER EMERGENCY ARE NOT SHOWN HOWEVER BASED ON
 THE NUMBER OF POINTS AND THE LEVELS SHOWN IT SEEMS
 PERHAPS PREVIOUS NOTES WERE NOT TYPED IN A MANOR WHICH
 WAS UNDERSTOOD.
 PLEASE CLARIFY RESPONSE AND LIGHTING LEVELS BEING
 SHOWN. PLEASE SEE THE
 REAR STAIR ON PLANS CONTAIN A NOTE WHICH MENTIONS TO
 PLACE ON LOBBY 100 NHP-6 CIRCUIT YET THIS SAME REAR
 STAIR HAS A NOTE TO CIRCUIT LIGHTS TO NHP-8. HOW WILL
 THIS WORK AS THIS PLACES 220/240V ON FIXTURES. THIS
 MUST BE A MISPRINT.
 PLEASE SEE THE PANEL SCHEDULE DOES NOT INDICATE ANY
 CIRCUITING TO THE UPS AND SHOWS CIRCUITS TO FIXTURE
 UNITS.
 PLEASE CALL TO GO OVER THIS FOR LIGHTING.
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-12-23 11:37:072007-12-23 09:57:07
 REVIEW COMMENCED.
2007-12-22 17:04:412007-12-22 17:04:41
  
 IN ELECTRICAL FOR REVIEW.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-10-29 Cont ID  
Sent By dpalmer Date 2007-10-29 Time 15:24 Rev Time 0.00
Received By dpalmer Date 2007-10-27 Time 12:23 Sent To  
Notes
2007-10-29 15:25:04 
 ** DENIED 3RD REVIEW **
  
 ** PLEASE SEE NOTES FROM PREVIOUS TWO REVIEWS WHICH
 STILL NEED TO BE ADDRESSED.
 PLEASE SEE AS STATED ON PREVIOUS REVIEWS, REVIEW NOTES
 CAN ONLY BE GIVEN ON PLANS AND DOCUMENTATION SUBMITTED.
 AS NOTED THERE MAY ALSO BE NEW NOTES FOR ITEMS WHICH
 COULD NOT BE REVIEWED PREVIOUSLY.
  
 1) NOTE: PLEASE SEE AS NOTED ON PREVIOUS REVIEW, PLEASE
 INDICATE AREAS WHICH WIRING METHODS FOR NEC 517 WILL BE
 REQUIRED. PLEASE SEE THE RESPONSE IN LETTER AND MEETING
 HELD BEFORE PLANS WERE SUBMITTED WAS THAT THE BUILDING
 WAS ONLY GOING TO BE BUSINESS AND ADMINISTRATIVE
 OFFICES.
 PLEASE KNOW THAT IT HAS COME TO OUR ATTENTION AND PER
 PLANS SUBMITTED THERE WILL BE ROOMS IN WHICH DOCTORS
 WILL BE DOING EXAMS ALONG WITH EQUIPMENT. THE OCCUPANCY
 DOES NEED TO BE DESIGNATED AS A HEALTH CARE FACILITY IN
 ORDER FOR WIRING METHODS IN 517 TO BE REQUIRED IN SOME
 ROOMS. PLEASE SEE AREAS SUCH AS THE DOCTOR'S ADMIN
 OFFICES, RECEPTION, HALLWAYS, ETC ARE NOT AREAS WHICH
 FALL UNDER 517, HOWEVER EXAM ROOMS AND THE LIKE ARE.
 PLEASE ADJUST NOTES AND WIRING METHODS PER 517. PLEASE
 SEE 517.1, 517.10 AND 517.13.
 PLEASE SEE THE FOLLOWING WHICH IS TAKEN DIRECTLY FROM
 THE NEC COMMENTARY.
  
 *THE REQUIREMENTS OF ARTICLE 517 ARE INTENDED TO APPLY
 TO ALL TYPES OF HEALTH CARE FACILITIES. THE
 REQUIREMENTS FOR EACH TYPE OF HEALTH CARE FACILITY ARE
 NEVERTHELESS INTENDED TO BE APPLIED IN A VERY SPECIFIC
 MANNER. FOR EXAMPLE, IN A SUITE OF DOCTORS' OFFICES
 WITHIN AN OFFICE BUILDING, A DOCTOR'S BUSINESS OFFICE
 WOULD BE TREATED AS AN ORDINARY OCCUPANCY AND WOULD BE
 REQUIRED TO MEET ONLY THE APPLICABLE PORTIONS OF OTHER
 PARTS OF THIS CODE. HOWEVER, THE EXAMINING ROOMS
 ATTACHED TO THE DOCTOR'S BUSINESS OFFICE WOULD BE
 REQUIRED TO MEET THE PROVISIONS OF PART II AND 517.45
 IN ARTICLE 517.*
  
 THIS IS ONLY ONE PART OF THE NEC PROVIDED. PLEASE KNOW
 THAT ANY WORK DONE UNDER SHELL/ADDITION PHASE II PERMIT
 MAY BE AFFECTED.
  
 2) NOTE: PLEASE SEE FBC CHAPTER 13 (ALL). PLEASE SEE
 THAT THE TWO PREVIOUS REVIEWS MENTIONED THERE WERE
 SEVERAL SECTIONS OF THIS CHAPTER WHICH NEEDED TO BE
 ADDRESSED AS DESIGN FOR CHAPTER 13 LIGHTING CONTROLS
 HAD NOT BEEN SHOWN.
 PLEASE SEE THERE ARE STILL ITEMS FOR SEVERAL LOCATIONS
 WHICH HAVE NOT HAD THE COMMENTS ADDRESSED.
  
 A) PLEASE SEE THERE ARE SEVERAL SEPARATE SPACES WHERE
 NO LIGHTING CONTROLS FOR OVER RIDES ARE SHOWN. PLEASE
 SEE PREVIOUS TWO REVIEWS SECTION 13-415.1.ABC.1.2.
 PLEASE SEE FOR EXAMPLE SOME OF THESE LOCATIONS ARE THE
 SAME IN WHICH WAS REDLINED ON PREVIOUS PLANS. PLEASE
 SEE 123, 183, 161, 162, 159, 131, 110, 112, 209, 208
 ETC. THESE ARE NOTED FOR SOME OF THESE LOCATIONS WHICH
 CONTAIN THE FLOOR TO CEILING HEIGHT PARTITIONS AS
 STATED IN THE CODE; HOWEVER NO OVER RIDE DEVICES ARE
 SHOWN.
  
 B) PLEASE SEE AREAS IN WHICH THE OCCUPANT MUST SEE THE
 LIGHTING IN WHICH IS BEING OVER RIDDEN OR CONTROLLED.
 PLEASE SEE THERE IS AN EXCEPTION HOWEVER NO DETAILS FOR
 THE EXCEPTION FOR INDICATOR/PILOT LIGHTS ARE SHOWN.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2. PLEASE SEE FOR
 EXAMPLE THE FIRST FLOOR FOR CIRCUITS 60, 30 AND 32
 WHICH ARE LV SWITCHES SHOWN AS THE LOBBY AREA HOWEVER
 FROM THIS LOCATION THE OCCUPANT CAN NOT SEE THE
 LIGHTING THEY ARE CONTROLLING.
 PLEASE SEE TENANT SPACES ALSO FOR EXAMPLE AS THE COMMON
 AREA LIGHTING DOES NOT INDICATE ANY OVER RIDE
 CONTROL(S). THE OCCUPANT ENTERING INTO THE SPACE/AREA
 NEEDS TO HAVE AN OVER RIDE OF THE TIMED SCHEDULED
 SYSTEM.
 PLEASE SEE FOR EXAMPLE THE OCTAGONAL NOTE #4 ON SHEET
 EL-101 AS THIS MENTIONS CIRCUIT NHP-11 YET THIS CIRCUIT
 ON PANEL SCHEDULE IS FOR THE 2ND FLOOR AND FOR A
 RECEPTACLE CIRCUIT AND NOTED FOR SHELL. HOW IS THIS
 POSSIBLE?
 PLEASE ALSO SEE FOR EXAMPLE THE LIGHTING WHICH IS SHOWN
 FOR HOUSE FOR SHELL FOR SECOND FLOOR WHICH DOES NOT
 SHOW ANY OVER RIDE DEVICES.
 PLEASE ALSO SEE FOR EXAMPLE THE LOBBY AREA WHICH IS
 BEING ILLUMINATED BY LIGHTING IN THE CEILING FROM THE
 2ND FLOOR LIGHTING CONTROL PANEL. WHERE ARE THE OVER
 RIDE DEVICES FOR THE FRONT ENTRANCE AREA? THIS IS AN
 OPEN AREA FOR THE FIRST FLOOR.
 PLEASE CLARIFY CIRCUITING FOR FOUNDATION ROOM,
 CONFERENCE ROOM ON SECOND FLOOR AS THESE ARE SHOWN TO
 CIRCUIT 42 AND ALSO A 42A AND 42B? THIS IS UNCLEAR HOW
 THESE ARE CIRCUITED AS PANEL SCHEDULE IS BEING ASSUMED
 TO BE NHP2. THIS PANEL SCHEDULE ONLY INDICATES ONE #42
 CIRCUIT. *LIGHTING*.
 THE FLOORS ARE REQUIRED TO BE SEPARATED.
 THESE ARE SOME EXAMPLES, AND IN NO WAY NOTES ALL
 POSSIBLE SCENERIOS.
 ** PLEASE SEE THAT THERE ARE SEVERAL AREAS IN WHICH
 LIGHTING CONTROLS ARE NOT YET COMPLETE FOR CHAPTER 13
 AS NOTED.
  
 C) PLEASE SEE THE METHOD OF CALCULATIONS SUBMITTED AS
 *WHOLE BUILDING * METHOD *A* MAY NOT BE USED. THIS IS
 AN EXISTING BUILDING WHICH IS CURRENTLY BEING REMODELED
 UNDER METHOD *B*.
 THIS ALSO FALLS UNDER RENOVATED BUILDINGS PER
 13-101.1.3. PLEASE SEE AS STATED ON PREVIOUS REVIEW THE
 METHOD CALCULATION WOULD DEPEND ON KNOWN FACTORS AND AS
 THERE ARE STILL PORTIONS OF THIS BUILDING NOT
 COMPLETED, METHOD *A* COULD NOT BE USED EITHER PER
 13-101.6.
 PLEASE SUBMIT THE CORRECT METHOD WHICH AS STATED IN THE
 TWO SECTIONS GIVEN COULD BE *B* OR *C*.13-415.1.B.1
 PLEASE SEE LIGHTING PERFORMANCE CALCULATIONS SHALL MEET
 13-415.
 ** PLEASE SEE MECHANICAL COMMENTS AS THIS MAY ALSO BE
 PART OF THEIR REVIEW NOTES.
  
 D) PLEASE SUBMIT COMPLETE INFORMATION FOR LIGHTING
 CONTROL PANELS/SYSTEM BEING PROPOSED. PLEASE SEE THE
 PLANS ONLY FOR A *LIGHTING CONTROL PANEL* WHICH DOES
 NOT PROVIDE THE INFORMATION AS NEEDED FOR COMPLIANCE
 WITH SECTIONS A AND B OF THIS SAME NOTE #2
  
 E) PLEASE PROVIDE NOTE ON PLANS FOR 13-413.1.ABC.2
 WHICH CONTAINS SUB SECTIONS 2.1 AND 2.2.
 THIS WAS RECENTLY CONFIRMED WITH THE FLORIDA BUILDING
 COMMISSION.
  
 3) NOTE: PLANS NOW INDICATE THE PHOTO-METRICS FOR
 EGRESS PATHS FOR NORMAL CONDITIONS, HOWEVER COULD NOT
 LOCATE LEVELS FOR EMERGENCY CONDITIONS. THIS COMMENT IS
 NOT FOR STAIRS AS THE SAME FIXTURES ARE FOR BOTH
 CONDITIONS.
 PLEASE CLARIFY THE EGRESS PATHS FOR CORRIDORS AS THE
 LEVELS ARE DONE SHOWING GENERAL FIXTURES AS WELL AS
 EMERGENCY.
 LS 101 7.8 AND 7.9.
 FAC 61G15-33.004
  
 4) NOTE: PLEASE SEE THE ENLARGED ELECTRICAL ROOMS WHICH
 ARE ON EE-401. PLEASE CLARIFY THE DESIGNATIONS AS ROOM
 #216 IS BEING NOTED FOR 2ND FLOOR HOWEVER 216 ON THE
 SECOND FLOOR IS A CORRIDOR. PLEASE SEE THE ROOM FOR THE
 ELECTRICAL CLOSET IS SHOWN AS 203 ON EL-102. THIS IS A
 MINOR COMMENT HOWEVER AS PLANS ARE COMING BACK FOR
 OTHER COMMENTS, PLEASE CORRECT AT THIS TIME.
  
 5) NOTE: PLEASE SEE THE PREVIOUS REVIEW GAVE NOTICE TO
 FLORIDA STATUTES 553.80(2)(B). THERE ARE CODES WHICH
 WERE REPEATED ONCE AGAIN WHICH WERE NOTED THREE TIMES.
 THERE WILL BE A FEE ASSESSED AS REQUIRED BY THE
 STATUTES. THE FEE AMOUNT IS DUE BEFORE PLANS MAY BE
 RESUBMITTED. IT IS RECOMMENDED THAT THE COMMENTS ARE
 GONE OVER BEFORE PLANS ARE RESUBMITTED. ONE COPY OF THE
 ELECTRICAL SHEETS IS BEING RETAINED BY THIS OFFICE.
  
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-10-29 10:17:40 
  
 REVIEW COMMENCED.
2007-10-27 12:23:512007-10-27 12:23:51
  
 IN ELEC FOR REVIEW

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-08-25 Cont ID  
Sent By dpalmer Date 2007-08-25 Time 16:54 Rev Time 0.00
Received By dpalmer Date 2007-08-25 Time 14:23 Sent To  
Notes
2007-08-25 16:54:222007-08-25 16:54:22
  
 *** DENIED 2ND REVIEW ***
  
 PALM HEALTH CARE
 PHASE 3 INTERIOR BUILD OUT.
  
  
 ** PLEASE SEE THERE NOTES FROM PREVIOUS REVIEW ARE
 STILL IN NEED OF ADDRESSING ALONG WITH SOME NEW
 COMMENTS BASED ON INFORMATION NOW PLACED ON PLANS OR
 INFORMATION NOW SUBMITTED WHICH WAS NOT ON PREVIOUS
 PLANS.
  
 ** THERE ARE STILL ITEMS WHICH WERE NOT SUBMITTED;
 THEREFORE A REVIEW FOR CODE COMPLIANCE CAN NOT BE DONE.
 WHEN INFORMATION PREVIOUSLY REQUESTED IS NOT SUBMITTED
 AND A REVIEW OF THOSE ITEMS CAN NOT BE DONE, THEN MORE
 OFTEN THAN NOT THERE ARE NEW COMMENTS TWO, THREE OR
 FOUR REVIEWS LATER AS THE INFORMATION WAS NEVER
 SUBMITTED FOR REVIEW. PLEASE SEE NOTES BELOW. (#3)
  
  
 1) NOTE:THIS NOTE WILL REMAIN FROM PREVIOUS REVIEW AS
 THE SHELL PLANS HAVE NOT YET BEEN PERMITTED AND CHANGES
 WILL BE FORTH COMING BASED ON COMMENTS FROM THIS REVIEW
 AND PREVIOUS REVIEW ON SHELL PERMIT REVIEW.
 PLEASE KNOW THAT IT IS MOST IMPORTANT TO COORDINATE
 PLANS WITH THE PLANS WHICH WERE SUBMITTED FOR SHELL
 BUILDING AND ADDITION.
 FBC 106.3.5.1.2, 106.1.2
  
 2) NOTE:PLEASE SEE THIS IS THE 2ND REQUEST: PLEASE
 SEE THE ENERGY CALCULATIONS SUBMITTED FOR THE BUILD OUT
 OF SPACE.
 PLEASE SEE THAT THE RESPONSE LETTER MENTIONS THESE WILL
 BE SUBMITTED AND DONE HOWEVER PLEASE SUBMIT *TWO*
 COMPLETE SETS OF ENERGY CALCULATIONS, SIGNED DATED AND
 SEALED BY THE RESPONSIBLE DESIGNER(S) OF RECORD AS
 REQUIRED PER FBC 13-103.1.1.1 , FAC 61G15-23.002, FS
 471.025, 481.221.
  
 PLEASE KNOW THAT BASED ON THE BUILD OUT BEING SUBMITTED
 FOR PERMIT, THE KNOWN ENERGY CONSUMPTION ETC AND METHOD
 FOR SHELL PERMIT WOULD CHANGE.
 PLEASE BE SURE TO COORDINATE ALL FIXTURES, FIXTURE
 WATTAGES, TYPE OF FIXTURES, CONTROLS AND NUMBER OF
 FIXTURES BETWEEN PLANS AND ENERGY CALCULATIONS. AS THE
 CONTROLS AND AREAS ON THE PLANS MAY CHANGE THIS MAY
 AFFECT THE CALCULATIONS. .
 PLEASE SEE ELECTRIC TYPE WATER HEATERS FOR EXAMPLE ARE
 BEING SHOWN ON THE IDR, YET THE PLANS DO NOT SHOW
 THIS?
 PLEASE SUBMIT AND SHOW DETAILED CODE COMPLIANCE FOR
 LIGHTING CONTROLS AS REQUIRED PER CHAPTER 13 OF THE
 2004 FBC. PLEASE SEE THAT SOME REFERENCES TO A LIGHTING
 CONTROL PANEL IS BEING NOTED HOWEVER THERE ARE TOO MANY
 AREAS WHICH ARE MISSING THE REQUIRED OVER RIDES FOR
 SPACES AND ZONES. PLEASE KNOW THAT ONE LIGHTING CONTROL
 PANEL MAY NOT FEED TWO FLOORS AS THE LCP SUBMITTED
 INDICATES.
  
 PLEASE SEE THE ELECTRICAL LIGHTING PLANS SUBMITTED ARE
 NOT COMPLETE WITH LIGHTING CONTROLS NOT ONLY REQUIRED
 PER CHAPTER 13, BUT MANY ROOMS AND AREAS DO NOT
 INDICATE ANY CONTROL FOR LIGHTING AT ALL. SOME
 LOCATIONS SHOWS A SYMBOL FOR A SWITCH HOWEVER MOST DO
 NOT SHOW ANY DEVICES
 PLEASE KNOW THAT STATING ONE NOTE (#5) WHICH MENTIONS
 OCCUPANCY DEVICE REQUIRED, DOES NOT SHOW CODE
 COMPLIANCE.
 PLEASE SHOW SCHEDULE IF A SYSTEM IS DESIGNED, OR
 INSTALLED. PLEASE INDICATE ALL MAXIMUM TIMES ON OVER
 RIDE DEVICES; PLEASE SHOW ALL DEVICES ON PLANS SO THAT
 COVERAGE FOR CODE COMPLIANCE AND SPACE CONTROLS CAN BE
 REVIEWED.
 13-415.1.ABC.1.1, .1.2, .1.3. 13-415.1.AB.1.1,
 13-415.2
 PLEASE PROVIDE WORST CASE VOLTAGE DROP FOR
 BRANCH/CIRCUITS AND FEEDERS PER 13-413.1ABC.1.1, .1.2.
 THE VD FOR FEEDERS WERE LOCATED ON THE RISER HOWEVER
 PLEASE CLARIFY WHERE THE WORST CASE FOR BRANCH
 CIRCUIT(S) ARE SHOWN.
 THIS INFORMATION IS REQUIRED TO BE SIGNED, DATED AND
 SEALED BY THE RESPONSIBLE DESIGN PROFESSIONAL ALONG
 WITH TITLE BLOCK INFORMATION ON PLANS AND SHEETS.
 13-103.1.1.1
  
 ** PLEASE KNOW AT THIS TIME PLANS DO NOT INDICATE
 COMPLIANCE WITH THE 2004 FBC CHAPTER 13 AND MANY ITEMS
 REQUIRED FOR REVIEW ARE MISSING. PLEASE KNOW THERE MAY
 BE NEW COMMENTS ON THE FOLLOWING REVIEW AS INFORMATION
 WAS NOT SUBMITTED.
 PLEASE SEE CHAPTER 13 IN THE 2004 FBC .
  
 3) NOTE: PLEASE SEE THE PREVIOUS REVIEW REQUESTED
 PHOTO-METRICS. SOME OF THESE WERE ADDED HOWEVER NEED
 LEVELS UNDER NORMAL AND EMERGENCY CONDITIONS. FLORIDA
 ADMINISTRATIVE CODE 61G15-33.004
 ** PREVIOUS REVIEW NOTE: PLEASE SEE THAT THE PLANS ARE
 MISSING THE REQUIRED EGRESS PHOTO-METRICS AS PREVIOUSLY
 REQUESTED ON SHELL/ADDITION PLANS. AS THE
 SHELL/ADDITION PLANS ARE NOT ISSUED AT THIS TIME AND DO
 NOT INDICATE COMPLIANCE, PLEASE SUBMIT THE REQUIRED PER
 NFPA-101 7.8.1.3, 7.9.2.2
 PLEASE ALSO SEE THE MULTI-USE BATHROOMS WILL BE
 REQUIRED TO CONTAIN A BATTERY BACK UP FIXTURE OF SOME
 TYPE.
 PLEASE SEE NOTES UNDER MAIN BUILDING SHELL/ADDITION
 PERMIT.
  
 4) NOTE:PLEASE SEE THE RISER HAS NOW BEEN COMPLETELY
 CHANGED AND REVISED AND HAD CREATED SOME NEW COMMENTS.
 THERE ARE ALSO SOME COMMENTS WHICH STILL REMAIN FROM
 PREVIOUS REVIEW.
 PLEASE SEE THE RISER NOW SHOWS TWO NEW 400AMP MAINS
 FROM THE SUPPOSED EXISTING GUTTER FEEDING A NEW GUTTER.
 NO INFORMATION FOR THESE MAINS WAS SUBMITTED. NO TAP
 CONDUCTOR SIZES FROM THE EXISTING GUTTER, NOT
 CONDUCTORS FROM THE MAINS TO THE NEW GUTTER. (240.21,
 240.4, 310.16) PLEASE VERIFY THE RISER AS THIS SHOWS NO
 METERING DEVICES ON THESE TWO MAINS. PLEASE OBTAIN
 INFORMATION FROM FPL.
 PREVIOUS NOTE # 5 REQUESTED THE RISER TO BE COMPLETE
 FOR ALL INFORMATION.
  
 5) NOTE: PLEASE SEE AIC RATINGS ARE NOT SUBMITTED FOR
 ALL EQUIPMENT AS REQUESTED ON THE PREVIOUS REVIEW.
 STATING THE AVAILABLE FAULT CURRENT AT MOST LOCATIONS
 ON THE RISER IS FINE HOWEVER THIS DOES NOT GIVE THE
 INFORMATION FOR THE REQUIRED MINIMUM RATINGS FOR
 EQUIPMENT.
 110.9
 FBC 106.3.5.1.2
 **REQUESTED ON PREVIOUS REVIEW NOTE # 5
  
 6) NOTE: PLEASE SEE THE RISER NOW SHOWS THE *GROUNDING
 ELECTRODE CONDUCTOR* AFTER THE FIRST MEANS OF
 DISCONNECT WHICH IS NOT PERMITTED AND NOT INSTALLED AS
 THE CODE REQUIRES PER 250.6, 250.24, 250.50 ETC. PLEASE
 SEE THIS WAS REQUESTED ON THE PREVIOUS REVIEW NOTE #5
  
 7) NOTE: PLEASE SEE MISSING *EQUIPMENT GROUNDING
 CONDUCTORS AFTER THE FIRST MEANS OF DISCONNECT AS
 REQUIRED PER 250.110, 250.24, 250.122.
  
 8) NOTE: PLEASE SEE THE RISER IS STILL IN QUESTION AS
 SHOWN AS THE RISER NOW CONTAINS TWO 400AMP MAINS AND A
 800AMP MAIN ON SERVICE ENTRANCE CONDUCTORS RATED AT
 950AMPS.
 THE SERVICE CALCULATIONS SUBMITTED ARE BASED ON SOME
 AREAS AS SHELL AND NOT CLEAR ON THE COMPLETE SCOPE AND
 LOADS AND WHY 1600AMPS WORTH OF MAINS ARE BEING PLACED
 ON A SERVICE ONLY RATED AT 975AMPS BASED ON THE
 CONDUCTORS.
 THE RISER IS ALSO STILL IN QUESTION AS BASED ON THE
 TOTAL AMOUNT OF METER AND MAIN DISCONNECTS SHOWN. THE
 RISER LENDS TO TWO TENANTS ON THE FIRST FLOOR HOWEVER
 THE BUILD OUT PLANS ONLY INDICATE ONE TENANT. IF THIS
 IS INDEED ONE TENANT AND OCCUPANT, ONLY ONE METER IS
 PERMITTED.
 PLEASE ALSO SEE THE RISER LENDS TO THREE POSSIBLE
 TENANTS UPSTAIRS, YET THE PLANS ONLY LEND TO TWO. THE
 AMOUNT OF METERS PERMITTED TO EACH TENANT IS ONE.
 (HOUSE IS NIC)
 THIS INFORMATION WILL BE SENT TO ZONING AND BUILDING
 BASED ON OCCUPANCY AND TENANT SEPARATIONS ETC. PLEASE
 CLEAR UP RISER AND PROVIDE INFORMATION FOR THIS AS
 SHOWN.
 215.5, 230.70, 230 ETC
 90.4
 FBC 106.1.2, 106.3.5.1.2 FOR ADDITIONAL INFORMATION
 NEEDED.
  
 9) NOTE:THIS IS FROM PREVIOUS REVIEW NOTE #9. PLEASE
 SEE FBC 2004 11-4.28.1, .2 AND .3(4) AND STATE THE
 MINIMUM HORN, STROBE LEVELS ON PLANS FOR ADA REQUIRED
 AREAS. DEVICES ARE BEING SHOWN ON PLANS/LEGEND. PLEASE
 CORRELATE WITH PLANS, AND FA SHEETS SUBMITTED.
 ** PLEASE KNOW THAT THE FIRE ALARM WILL BE UNDER A
 SEPARATE PERMIT HOWEVER THE BASE LIFE SAFETY SYSTEM IS
 REQUIRED ON BASE PLANS AS SHOWN. DO NOT REMOVE FROM
 SETS.
 FBC 106.3.5.1.2
 ** THE RESPONSE MENTIONS TO SEE THE HORNS ARE SET AT
 1WATT AND CD LEVELS AT 15CD. THE RESPONSE LETTER
 SPECIFICALLY STATES TO SEE *EC 001* HOWEVER PLEASE SEE
 THE PLANS SUBMITTED CONTAIN A EE-001 AND EC-301 HOWEVER
 NO EC-001. IN EITHER CASE THESE MINIMUM LEVELS COULD
 NOT BE LOCATED ON THESE SHEETS.
 THE LEVELS ARE SUBSTANTIALLY HIGHER THAN THAT OF
 NFPA-72
  
 10) NOTE:SAME AS PREVIOUS REVIEW NOTE #10: PLEASE
 KNOW THAT THE LOW VOLTAGE SECURITY PLANS FOR CAMERAS
 ETC ARE TO BE UNDER SEPARATE PERMITS.
 THE RESPONSE LETTER SPECIFICALLY STATES THAT THIS IS
 NOT PART OF THE PACKAGE, HOWEVER PLEASE CLARIFY HOW AND
 WHY THESE PLANS ARE STILL BEING SUBMITTED.
  
 11) NOTE: PREVIOUS NOTE #11:
 PLEASE COMPETE ALL CIRCUITING ON PLANS AND CORRELATE
 WITH THE SUBMITTED PANEL SCHEDULES. PLEASE BE SURE TO
 SEE PREVIOUS PLANS FOR SHELL BUILDING AND CIRCUITING
 PER 700.12F FOR ALL EMERGENCY AND EXIT LIGHTS.
 106.1.2,
 408.4 NEC.THE FOLLOWING TEXT IS TAKEN DIRECTLY FROM
 THE NEC. PLEASE BE SURE ALL AREAS, ROOMS DESIGNATIONS
 ETC COORDINATE WITH THE CIRCUITS ON PANEL SCHEDULES
 SPECIFIC.
  
 **SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO
 REQUIRE THAT THE IDENTIFICATION FOR EVERY CIRCUIT
 SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND
 CLEARLY STATE THE SPECIFIC PURPOSE FOR WHICH THE
 CIRCUIT IS USED. CIRCUITS USED FOR THE SAME PURPOSE
 MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR EXAMPLE,
 SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY OUTLETS IN
 THE KITCHEN, DINING ROOM, AND KITCHEN COUNTERTOPS.
 IDENTIFYING THE CIRCUITS AS SMALL APPLIANCE BRANCH
 CIRCUITS IS NOT ACCEPTABLE; INSTEAD, THEY SHOULD BE
 IDENTIFIED AS ``KITCHEN WALL RECEPTACLES,'' ``DINING
 ROOM FLOOR RECEPTACLE,'' OR ``KITCHEN COUNTERTOP
 RECEPTACLES LEFT OF SINK.'' CIRCUIT DIRECTORIES
 CONTAINING MULTIPLE ENTRIES WITH ONLY ``LIGHTS'' OR
 ``OUTLETS'' DO NOT PROVIDE THE SUFFICIENT DETAIL
 REQUIRED BY THIS SECTION.*
 408.4, 310.16, 240.4 ETC
 FBC 106.3.5.4
  
 ** PLEASE SEE THE SECTION OF THE COMMENTARY WAS ADDED
 TO POWER AND LIGHTING SHEETS WHICH IS NOT WHAT COMMENT
 WAS REQUESTING. PLEASE SEE THIS COMMENT WAS STATING THE
 CIRCUITS WHICH ARE ALREADY SHOWN ON THE SUBMITTED PANEL
 SCHEDULE WERE TO BE MORE SPECIFIC AND NOT TO ONLY STATE
 *OUTLET* OR *LIGHTING*. MAY USE ALPHA OR NUMERIC
 DESIGNATIONS OF CIRCUITS.
 PLEASE SEE THE PLANS WHICH HAD THIS NOT STATE ON PLANS
 ALSO IS QUOTING THE INCORRECT CODE SECTION.
 THIS APPEARS TO HAVE BEEN A MISPRINT.
  
 12) NOTE:PLEASE SEE 517 OF THE NEC AND EXPAND ON ANY
 LOCATIONS PER 517 AND 517.13(A) AND (B)
 PLEASE EXPAND ON THE GROUNDING REQUIRED.
 THIS JURISDICTION HAS HAD SEVERAL INSTANCES WHERE
 CORRECT GROUNDING METHODS ARE NOT BEING DONE IN THE
 FIELD. WE ARE REQUIRING ADDITIONAL NOTES ON PLANS TO
 HELP ALLEVIATE POSSIBLE DELAYS IN PROJECTS. MANY TIMES
 THESE LOCATIONS HAVE TO BE COMPLETELY RE-WIRED DUE TO
 IMPROPER GROUNDING WHICH ONLY DELAYS AND HOLDS UP ALL
 INVOLVED.
 **MANY CONTRACTORS ARE AWARE OF CORRECT INSTALLATIONS
 IN MEDICAL OFFICES/PATIENT CARE AREAS, AND MANY ARE
 NOT.
  
 13) NOTE: PLEASE COORDINATE PLANS WITH THE ELECTRICAL
 RISER DIAGRAM.
 PLEASE SEE THE MAIN ELECTRICAL ROOM LAYOUT DOES NOT
 CONTAIN ALL THE EQUIPMENT AS SHOWN ON RISER. PLEASE
 ALSO PROVIDE THE SIZES FOR THE GUTTER AS SHOWN. PLEASE
 SEE 110.26, 366.
 PLEASE SEE THE FOLLOWING EXTRACTED FROM THE NEC FOR USE
 OF READING AS THE GUTTER SHALL NOT EXTEND INTO THE
 WORKING CLEARANCE AREA BY MORE THAN 6 INCHES.
  
 *110.26(A)(3)
 (3) HEIGHT OF WORKING SPACE THE WORK SPACE SHALL BE
 CLEAR AND EXTEND FROM THE GRADE, FLOOR, OR PLATFORM TO
 THE HEIGHT REQUIRED BY 110.26(E). WITHIN THE HEIGHT
 REQUIREMENTS OF THIS SECTION, OTHER EQUIPMENT THAT IS
 ASSOCIATED WITH THE ELECTRICAL INSTALLATION AND IS
 LOCATED ABOVE OR BELOW THE ELECTRICAL EQUIPMENT SHALL
 BE PERMITTED TO EXTEND NOT MORE THAN 150 MM (6 IN.)
 BEYOND THE FRONT OF THE ELECTRICAL EQUIPMENT.
 ** COMMENTARY**
 IN ADDITION TO REQUIRING A WORKING SPACE TO BE CLEAR
 FROM THE FLOOR TO A HEIGHT OF 61/2 FT OR TO THE HEIGHT
 OF THE EQUIPMENT, WHICHEVER IS GREATER, 110.26(A)(3)
 PERMITS ELECTRICAL EQUIPMENT LOCATED ABOVE OR BELOW
 OTHER ELECTRICAL EQUIPMENT TO EXTEND INTO THE WORKING
 SPACE NOT MORE THAN 6 IN. THIS REQUIREMENT ALLOWS THE
 PLACEMENT OF A 12 IN. ? 12 IN. WIRE-WAY ON THE WALL
 DIRECTLY ABOVE OR BELOW A 6 IN. DEEP PANEL-BOARD
 WITHOUT IMPINGING ON THE WORKING SPACE OR COMPROMISING
 PRACTICAL WORKING CLEARANCES. THE REQUIREMENT CONTINUES
 TO PROHIBIT LARGE DIFFERENCES IN DEPTH OF EQUIPMENT
 BELOW OR ABOVE OTHER EQUIPMENT THAT SPECIFICALLY
 REQUIRES WORKING SPACE.**
  
 PLEASE SIZE GUTTERS ACCORDINGLY WHICH ARE BEING SHOWN
 DIRECTLY IN FRONT OF MAINS, EQUIPMENT AND METERS WHICH
 COULD BE A SAFETY HAZARD.
  
 14) NOTE: PLEASE BE SURE TO GO OVER LOAD CALCULATIONS.
 PLEASE BE SURE TO SEE THE PREVIOUS REVIEW COMMENTS FOR
 ALL LOADS TO BE SHOWN.
 PLEASE SEE THE 2005 NEC FOR REQUIRED METHODS. 220.12,
 220.14, 220.42, 220.44 AND ALL PREVIOUS SECTIONS AS
 PREVIOUSLY NOTED.
 PLEASE SUBMIT COMPLETE LOAD CALCULATIONS FOR SERVICE
 AND EACH OF THE PANELS AS BEING SHOWN EVEN THOSE BEING
 SET ASIDE FOR FUTURE USE.
 PLEASE SEE THE ENERGY CALCULATIONS INDICATE TWO
 ELECTRIC WATER HEATERS YET THE CALCULATIONS DO NOT
 INCLUDE THESE, PANEL SCHEDULES? PLEASE SEE 422.13 AS
 THESE ARE REQUIRED TO BE SHOWN AT 125%.
 PLEASE SEE ALL OF 220.
 PLEASE ALSO SEE 215.3, 230.42 ETC FOR ALL CONTINUOUS
 LOADS AND LARGEST MOTORS LOADS AT 125%.
 FBC ADMIN SECTION 106.3.5.1.2, 106.1.2
  
 15) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS.
 THIS IS ONLY A NOTICE GIVEN AT THIS TIME.
 ONE COPY OF PLANS MAY BE RETAINED BY THIS OFFICE.
  
 AS STATED ON PREVIOUS REVIEW:
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-04-26 Cont ID  
Sent By dpalmer Date 2007-04-26 Time 15:59 Rev Time 0.00
Received By dpalmer Date 2007-04-26 Time 14:05 Sent To  
Notes
2007-04-26 15:59:54** UNSAT **
  
 ** PLEASE SEE THAT ANY REFERENCES TO THE FBC CHAPTER 1
 ARE FROM THE ADMINISTRATIVE CODE ADOPTED BY THE CITY OF
 WEST PALM BEACH.
  
  
 1) NOTE: PLEASE SEE CODES REFLECTED ON PLANS ARE NOT
 CORRECT.
 PLEASE SEE THAT MANY OF THE CODES REFLECTED WENT OUT IN
 OCT 1ST OF 2005. PLEASE SEEMOST OF THE CODES ARE
 STILL FROM THE 2001 CODE AND ADOPTED STANDARDS AND
 CODES FROM THAT TIME. THERE ARE SEVERAL CODES WHICH ARE
 STILL BEING REFLECTED FROM THE *2001 FBC* , THE 2000
 FLORIDA ACCESSIBILITY CODE ETC?
 PLEASE ALSO SEE THAT AS OF DECEMBER 8TH, 2006 THE
 CODES CHANGED TO THE 2006 REVISIONS TO THE 2004 FBC.
 PLEASE SEE THIS INCLUDES ALL MECHANICAL, PLUMBING
 BUILDING ETC.
 PLEASE SEE THAT AS OF THAT SAME DATE THE STATE ALSO
 ADOPTED THE NEW 2005 NFPA-70 (NEC).
 PLEASE SEE THE INCORRECT NFPA-101, 1 AND 72 ARE
 REFLECTED ALONG WITH THE INCORRECT NFPA-70 WHICH IS
 SHOWN AS THE 2002.
 PLEASE LIST THE FOLLOWING AT A MINIMUM ON ARCHITECTURAL
 COVER SHEET AND ELECTRICAL PLANS AT A MINIMUM. 2005
 NFPA-70, 2002 NFPA-72, 2003 NFPA-101, 2003 NFPA-1.
  
 ** PLEASE KNOW THAT OTHER CODES FROM OTHER TRADES MAY
 ALSO BE STATED TO BE DONE. THIS IS FOR ELECTRICAL
 REVIEW ONLY HOWEVER ALL CORRECTED CODES MUST BE STATED
 FOR DESIGN WHETHER OR NOT COMMENTS ARE MADE BY ANY OF
 THE OTHER TRADES.
  
 2) NOTE: PLEASE KNOW THAT IT IS MOST IMPORTANT TO
 COORDINATE PLANS WITH THE PLANS WHICH WERE SUBMITTED
 FOR SHELL BUILDING AND ADDITION.
 FBC 106.3.5.1.2, 106.1.2
  
 3) NOTE: PLEASE SEE THAT NO ENERGY CALCULATIONS WERE
 SUBMITTED FOR THE BUILD OUT OF SPACE.
 PLEASE KNOW THAT BASED ON THE BUILD OUT BEING SUBMITTED
 FOR PERMIT, THE KNOWN ENERGY CONSUMPTION ETC AND METHOD
 FOR SHELL PERMIT WOULD CHANGE.
 PLEASE SEE THAT NO REVIEW OF CODE COMPLIANCE CAN BE
 DONE AT THIS TIME. PLEASE BE SURE TO COORDINATE ALL
 FIXTURES, FIXTURE WATTAGES, TYPE OF FIXTURES, CONTROLS
 AND NUMBER OF FIXTURES BETWEEN PLANS AND ENERGY
 CALCULATIONS.
 PLEASE SUBMIT AND SHOW DETAILED CODE COMPLIANCE FOR
 LIGHTING CONTROLS AS REQUIRED PER CHAPTER 13 OF THE
 2004 FBC.
 PLEASE SEE THE ELECTRICAL LIGHTING PLANS SUBMITTED ARE
 NOT COMPLETE WITH LIGHTING CONTROLS NOT ONLY REQUIRED
 PER CHAPTER 13, BUT MANY ROOMS AND AREAS DO NOT
 INDICATE ANY CONTROL FOR LIGHTING AT ALL.
 PLEASE KNOW THAT STATING ONE NOTE (#5) WHICH MENTIONS
 OCCUPANCY DEVICE REQUIRED, DOES NOT SHOW CODE
 COMPLIANCE.
 PLEASE SHOW SCHEDULE IF A SYSTEM IS DESIGNED, OR
 INSTALLED. PLEASE INDICATE ALL MAXIMUM TIMES ON OVER
 RIDE DEVICES; PLEASE SHOW ALL DEVICES ON PLANS SO THAT
 COVERAGE FOR CODE COMPLIANCE AND SPACE CONTROLS CAN BE
 REVIEWED.
 13-415.1.ABC.1.1, .1.2, .1.3. 13-415.1.AB.1.1,
 13-415.2
 PLEASE PROVIDE WORST CASE VOLTAGE DROP FOR
 BRANCH/CIRCUITS AND FEEDERS PER 13-413.1ABC.1.1, .1.2.
 THIS INFORMATION IS REQUIRED TO BE SIGNED, DATED AND
 SEALED BY THE RESPONSIBLE DESIGN PROFESSIONAL ALONG
 WITH TITLE BLOCK INFORMATION ON PLANS AND SHEETS. THESE
 WOULD BE INCORPORATED IN PLAN SETS NOT SUBMITTED AS
 LOOSE SHEETS.13-103.1.1.1
  
 ** PLEASE KNOW AT THIS TIME PLANS DO NOT INDICATE
 COMPLIANCE WITH THE 2004 FBC CHAPTER 13 AND MOST ITEMS
 REQUIRED FOR REVIEW ARE MISSING. PLEASE KNOW THERE MAY
 BE NEW COMMENTS ON THE FOLLOWING REVIEW AS INFORMATION
 WAS NOT SUBMITTED.
 PLEASE SEE CHAPTER 13 IN THE 2004 FBC .
  
 4) NOTE: PLEASE SEE THAT THE PLANS ARE MISSING THE
 REQUIRED EGRESS PHOTO-METRICS AS PREVIOUSLY REQUESTED
 ON SHELL/ADDITION PLANS. AS THE SHELL/ADDITION PLANS
 ARE NOT ISSUED AT THIS TIME AND DO NOT INDICATE
 COMPLIANCE, PLEASE SUBMIT THE REQUIRED PER NFPA-101
 7.8.1.3, 7.9.2.2
 PLEASE SEE NOTES UNDER MAIN BUILDING SHELL/ADDITION
 PERMIT.
  
 5) NOTE: PLEASE SEE THAT THE RISER ON SHELL/ADDITION
 PERMIT HAS NOTES WHICH REQUIRES CHANGES.
 PLEASE SEE THERE IS MORE INFORMATION TO BE SUBMITTED
 WITH MORE COMPLETEDINFORMATION FOR CONDUCTORS,
 CONDUITS ETC, HOWEVER THERE ARE STILL SOME ITEMS WHICH
 NEED TO BE INCLUDED FOR CODE COMPLIANCE AS PREVIOUSLY
 NOTED.
 PLEASE SEE THE RISER AS SUBMITTED IS STILL NOT COMPLETE
 AT THIS TIME AND THERE ARE SEVERAL ITEMS WHICH CAN NOT
 BE REVIEWED FOR CODE COMPLIANCE.
 PLEASE SUBMIT A COMPLETE ELECTRICAL RISER DIAGRAM WITH
 ALL SERVICE ENTRANCE CONDUCTORS, FEEDERS, GROUNDING,
 SIZES OF ALL EQUIPMENT, LOCATIONS OF ALL EQUIPMENT, AIC
 RATINGS FOR ALL SERVICE EQUIPMENT ETC.
 ** PLEASE SEE SOME OF THE ITEMS WHICH ARE STILL
 MISSING.
 A) NO GROUNDING ELECTRODE SYSTEM.
 B) NO AIC RATINGS FOR ALL SERVICE EQUIPMENT.
 C) AN EQUIPMENT GROUNDING CONDUCTOR MAY NOT BE
 INSTALLED BEFORE THE FIRST MEANS OF DISCONNECT AS NOW
 SHOWN ON RISER. (250.6, 250.24)
 D) LOADS CAN NOT BE VERIFIED FOR SERVICE RISER AS SHOWN
 WHICH WILL BE NOTED BELOW TO VERIFY IF THE CONDUCTORS
 ETC SHOWN ARE OF ADEQUATE SIZE ETC.
 SECTIONS AS GIVEN IN PREVIOUS REVIEW.
 ** PLEASE SEE 110.9, 215.5, 240.4, 310.16, 230.70,
 230.76, 230.79,250.50, 250.54, 250.56, 250.66, 240.24,
 110.26 ETC.
 PLEASE SEE THAT THESE ARE ALL FROM THE 2005 NEC.
  
 6) NOTE: PLEASE SEE PLANS MENTION A LOCK OFF/ON DEVICE
 IS TO BE INSTALLED HOWEVER NO NOTES COULD BE LOCATED
 FOR TYPE OF DEVICE WHICH IS REQUIRED TO BE INSTALLED AS
 NOTED ON PREVIOUS REVIEW.
 ** PLEASE KNOW THAT ANY LOCK-OFF DEVICES SHALL INCLUDE
 SUCH A DEVICE WHICH INCLUDES THE DEVICE AS AN INTEGRAL
 PART OF THE BREAKER. A *SNAP ON/CLIP ON* TYPE DEVICE IS
 NOT ACCEPTABLE TO THIS AHJ.
 110.3, 90.4.
  
 7) NOTE:PLEASE SEE NOTE UNDER SHELL/ADDITION PERMIT
 WITH RESPECT TO LOAD CALCULATIONS.
 PLEASE SEE THE SEPARATE SHEETS SUBMITTED FOR PANEL NHP
 DOES NOT PROVIDE THE REQUIRED AND REQUESTED INFORMATION
 FOR COMPLETE LOAD CALCULATIONS FOR SERVICE AND ALL
 EQUIPMENT BY THE DESIGNER OF RECORD.ALL INFORMATION
 SHALL BE INCLUDED IN RECORD SETS OF PLANS AND NOT
 SUBMITTED ON LOOSE SHEETS WHICH DO NOT CONTAIN THE
 COMPLETED INFORMATION OR DONE BY THE DESIGNER OR
 RECORD.
 PLEASE SEE THE 2005 NEC FOR REQUIRED METHODS. 220.12,
 220.14, 220.42, 220.44 AND ALL PREVIOUS SECTIONS AS
 PREVIOUSLY NOTED.
 PLEASE SUBMIT COMPLETE LOAD CALCULATIONS FOR SERVICE
 AND EACH OF THE PANELS AS BEING SHOWN EVEN THOSE BEING
 SET ASIDE FOR FUTURE USE. PLEASE SEE THE ONLY PANEL
 SHOWN WHICH IS THE NHP AND THIS DOES NOT INCLUDE A LOAD
 SUMMARY OR HOW THE SERVICE WAS SIZED OR CORRECT LOAD
 CALCULATIONS FOR THIS PANEL OR SERVICE.
 PLEASE SEE NOTE #9 ABOVE AS THE SERVICE SIZE OR
 CONDUCTORS ARE NOT COMPLETE THE SIZE OF THE SERVICE CAN
 NOT BE DETERMINED AT THIS TIME.
 PLEASE SEE ALL OF 220.
 PLEASE ALSO SEE 215.3, 230.42 ETC FOR ALL CONTINUOUS
 LOADS AND LARGEST MOTORS LOADS AT 125%.
 FBC ADMIN SECTION 106.3.5.1.2, 106.1.2
  
 8) NOTE:THIS IS ONE OF THE SAME NOTES UNDER BASE
 BUILDING/SHELL PLANS.
 PLEASE SEE THIS SAME COMMENT FROM PREVIOUS REVIEW WHICH
 REMAINS AS NOT INFORMATION WAS SUBMITTED. PLEASE SEE
 NOTE ABOVE (#13) WHICH REQUEST THE AIC RATINGS FOR ALL
 EQUIPMENT. PLEASE BE SURE THESE CORRELATE WITH THE
 DIVISION SPEC SUBMITTED. 106.1.2. NEC 110.9
  
 9) NOTE: PLEASE SEE FBC 2004 11-4.28.1, .2 AND .3(4)
 AND STATE THE MINIMUM HORN, STROBE LEVELS ON PLANS FOR
 ADA REQUIRED AREAS. DEVICES ARE BEING SHOWN ON
 PLANS/LEGEND. PLEASE CORRELATE WITH PLANS, AND FA
 SHEETS SUBMITTED.
 ** PLEASE KNOW THAT THE FIRE ALARM WILL BE UNDER A
 SEPARATE PERMIT HOWEVER THE BASE LIFE SAFETY SYSTEM IS
 REQUIRED ON BASE PLANS AS SHOWN. DO NOT REMOVE FROM
 SETS.
 FBC 106.3.5.1.2
  
 10) NOTE: PLEASE KNOW THAT THE LOW VOLTAGE SECURITY
 PLANS FOR CAMERAS ETC ARE TO BE UNDER SEPARATE
 PERMITS.
  
 11) NOTE: PLEASE COMPETE ALL CIRCUITING ON PLANS AND
 CORRELATE WITH THE SUBMITTED PANEL SCHEDULES. PLEASE BE
 SURE TO SEE PREVIOUS PLANS FOR SHELL BUILDING AND
 CIRCUITING PER 700.12E FOR ALL EMERGENCY AND EXIT
 LIGHTS.
 106.1.2,
 408.4 NEC.THE FOLLOWING TEXT IS TAKEN DIRECTLY FROM
 THE NEC. PLEASE BE SURE ALL AREAS, ROOMS DESIGNATIONS
 ETC COORDINATE WITH THE CIRCUITS ON PANEL SCHEDULES
 SPECIFIC.
  
 **SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO
 REQUIRE THAT THE IDENTIFICATION FOR EVERY CIRCUIT
 SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND
 CLEARLY STATE THE SPECIFIC PURPOSE FOR WHICH THE
 CIRCUIT IS USED. CIRCUITS USED FOR THE SAME PURPOSE
 MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR EXAMPLE,
 SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY OUTLETS IN
 THE KITCHEN, DINING ROOM, AND KITCHEN COUNTERTOPS.
 IDENTIFYING THE CIRCUITS AS SMALL APPLIANCE BRANCH
 CIRCUITS IS NOT ACCEPTABLE; INSTEAD, THEY SHOULD BE
 IDENTIFIED AS ``KITCHEN WALL RECEPTACLES,'' ``DINING
 ROOM FLOOR RECEPTACLE,'' OR ``KITCHEN COUNTERTOP
 RECEPTACLES LEFT OF SINK.'' CIRCUIT DIRECTORIES
 CONTAINING MULTIPLE ENTRIES WITH ONLY ``LIGHTS'' OR
 ``OUTLETS'' DO NOT PROVIDE THE SUFFICIENT DETAIL
 REQUIRED BY THIS SECTION.*
 408.4, 310.16, 240.4 ETC
 FBC 106.3.5.4
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 8 Status N Date 2008-07-22 Cont ID  
Sent By mawillia Date 2008-07-22 Time 10:31 Rev Time 0.00
Received By mawillia Date 2008-07-22 Time 10:17 Sent To B
Notes
2008-07-22 10:25:24*****NOT NEEDED*****
  
  
 NO FIRE-STAMPEING NEEDED TO THE COVER SHEET OR AF-321
 SHEET.

Review Stop FIRE FIRE DEPARTMENT
Rev No 7 Status P Date 2008-06-24 Cont ID  
Sent By mawillia Date 2008-06-24 Time 11:46 Rev Time 0.00
Received By mawillia Date 2008-06-24 Time 11:37 Sent To B
Notes
2008-06-24 11:46:08*****REVISION 4, DATED 6/11/08, APPROVED*****
  
  
 REVISED PLAN SHEET GV-102 STAMPED, INTIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status P Date 2008-05-09 Cont ID  
Sent By mwennerg Date 2008-05-09 Time 10:44 Rev Time 0.00
Received By mwennerg Date 2008-05-09 Time 10:44 Sent To  
Notes
2008-05-09 10:45:41SHEETS EL-101 - EL-104 WERE STAMPED, SIGNED AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status F Date 2008-02-26 Cont ID  
Sent By mawillia Date 2008-02-26 Time 17:48 Rev Time 0.00
Received By mawillia Date 2008-02-26 Time 16:55 Sent To  
Notes
2008-02-26 17:40:19*****REVISION, DATED 01/21/08, PARTIAL APPROVAL*****
  
 REVISED PLAN SHEETS GV-102, AR-102, AND EA-102 WERE
 STAMPED, INITIALED, AND DATED;HOWEVER SHEETS EL-101
 THRU EL-104 TO BE FIRE-STAMPED WHEN THE ELECTRICAL
 REVIEW IS SATISFIED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2008-01-14 Cont ID  
Sent By mawillia Date 2008-01-14 Time 13:04 Rev Time 0.00
Received By mawillia Date 2008-01-14 Time 12:05 Sent To  
Notes
2008-01-14 12:46:43*****APPROVED*****
  
 PLAN SHEETS GV-101&102, AF-201, AR-101&102, IF-101&102,
 FS-101, FD-101&102, FK-101&102, EA-101&102, EC-301, AND
 EL-101&102WERE STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-11-26 Cont ID  
Sent By mawillia Date 2007-11-26 Time 11:27 Rev Time 0.00
Received By mawillia Date 2007-11-26 Time 09:39 Sent To  
Notes
2007-11-26 11:16:21*****PROVISO*****
  
  
 THE APPROPIATE PLAN SHEET(S) TO BE FIRE-STAMPED WHEN
 THE FOLLOWING COMMENT TAKEN FROM THE PREVIOUS FIRE PLAN
 REVIEWS HAS BEEN ADDRESSED:
  
  
 09.INTERIOR FLOOR FINISH SHALL COMPLY WITH SECTION
 10.2 OF NFPA 101;INTERIOR FLOOR FINISH IN EXIT
 ENCLOSURES SHALL BE CLASS I OR CLASS II.BE SPECIFIC
 PLEASE ADDRESS/INDICATE COMMENT IN THE PLANS AND/OR
 SPECIFICATIONS
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE THE ITEMS WERE ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-09-24 Cont ID  
Sent By mawillia Date 2007-09-24 Time 12:28 Rev Time 0.00
Received By mawillia Date 2007-09-24 Time 11:10 Sent To  
Notes
2007-09-24 12:28:45*****DENIED*****
 THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE
 PLAN REVIEW STILL NEED TO BE ADDRESSED:
  
  
 08.PLEASE CLARIFY/INDICATE SYMBOL FOR THE EMERGENCY
 LIGTS ON SHEETS AR-101, AR-102, EL-101, AND EL102. YOUR
 RESPONSE STILL DOES NOT CLARIFY/IDENTIFY TO DETERMINE
 EMERGENCY LIGHTING
  
 09.INTERIOR FLOOR FINISH SHALL COMPLY WITH SECTION
 10.2 OF NFPA 101;INTERIOR FLOOR FINISH IN EXIT
 ENCLOSURES SHALL BE CLASS I OR CLASS II.BE SPECIFIC
 PLEASE ADDRESS/INDICATE COMMENT IN THE PLANS AND/OR
 SPECIFICATIONS
  
 18.ELEVATORS SHALL COMPLY WITH THE REQUIREMENTS OF
 ASME A17.1 (NEW ELEVATORS) OR ASME A17.3 (EXISTING
 ELEVATORS). COULD NOT LOCATE ON SHEET EP-101 AND EC-101
 AS PER YOUR RESPONSE LETTER INDICATES
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE THE ITEMS WERE ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-06-28 Cont ID  
Sent By mawillia Date 2007-06-27 Time 07:40 Rev Time 0.00
Received By mawillia Date 2007-06-26 Time 10:25 Sent To  
Notes
2007-06-27 12:56:21*****DENIED*****
  
  
 01.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 02.AS PERTAINS TO THE PROJECT CODE DATA ON GV-101,
 REFERENCE THE FOLLOWING:NFPA 1 (2003 EDITION),NFPA
 101 (2003 EDITION),ANDFLORIDA FIRE PREVENTION CODE
 (2004 EDITION).
  
 03.ON SHEET GV-101, EXPLAIN THE DIFFERENCE BETWEEN FE
 AND FHV LEGEND SYMBOLS.BOTH INDICATE FIRE
 EXTINGUISHER.
  
 04.ON THE APPROPIATE EXTERIOR ELEVATION WHICH FRONTS
 GREENWOOD AVENUE, SHOW/DISPLAY THE NUMERICAL ADDRESS ON
 THE BUILDING.PLEASE BE REMINDED EVEN A MARKEE OR
 MONUMENT SIGN IS USED AT GREENWOOD AVENUE, THE
 NUMERICAL ADDRESS SHALL BE ON THE STRUCTURE AS PER WEST
 PALM BEACH ADDRESSING CODE.
  
 05.PLANS INDICATE THAT THIS BUILDING WILL BE FIRE
 SPRINKLERED IN CONJUNCTION WITH A FIRE ALARM SYSTEM.
 SHOW THE LOCATION OF THE REQUIRED PREMISES ACCESS/KNOX
 BOX AT THE APPROPIATE EXTERIOR ELEVATION.FOR
 APPLICATIONS, CONTACT THE WPB FIRE PREVENTION AT
 561-804-4724.
  
 06.ON SHEET GV-102,EXPLAIN THE USE OF THE SLEEP
 ROOM (226).
  
 07.ON SHEET GV-102, EXPLAIN THE AREA LOCATED IN THE
 TOP RIGTH CORNER IN THE CONFERENCE PRESENTATION ROOM
 (210).HOW IS ACESS GAINED?
  
 08.PLEASE CLARIFY/INDICATE SYMBOL FOR THE EMERGENCY
 LIGTS ON SHEETS AR-101, AR-102, EL-101, AND EL102.
  
 09.INTERIOR FLOOR FINISH SHALL COMPLY WITH SECTION
 10.2 OF NFPA 101;INTERIOR FLOOR FINISH IN EXIT
 ENCLOSURES SHALL BE CLASS I OR CLASS II.BE SPECIFIC
  
 10.INTERIOR WALL AND CEILING FINISH MATERIALS SHALL
 BE CLASS A OR CLASS B IN EXITS AND EXIT ACCESS
 CORRIDORS;SHALL BE CLASS A, CLASS B, OR CLASS C IN
 ALL OTHER AREAS.
  
 11.ON SHEET FS-101, INDICATE FROM WHOM THE FIRE FLOW
 DATA WAS OBTAINED.
  
 12.SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 FIRE SPRINKLER REMODEL AND FIRE ALARM SYSTEMS SCOPE OF
 WORK.
  
 13.FIRE ALARM SYSTEM TO BE CLASS A OR FULLY
 ADDRESSABLE.
  
 14.FIRE ALARM SYSTEM SHALL BE UL CERTIFIED FOR
 CENTRAL STATION SERVICE.
  
 15.DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE
 ALARM IN ACCORDANCE WITH LOCAL REQUIREMENTS.
  
 16.DOORS AS A MEANS OF EGRESS COMPONENT SHALL COMPLY
 WITH SECTION 7.2.1 OF NFPA 101.
  
 17.ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM AN
 AREA HAVING AN OCCUPANT LOAD OF 100 OR MORE PERSONS
 SHALL BE PERMITTED TO BE PROVIDED WITH A LATCH OR LOCK
 ONLY IF THE LOCK OR LATCH IS PANIC HARDWARE OR FIRE
 EXIT HARDWARE.
  
 18.ELEVATORS SHALL COMPLY WITH THE REQUIREMENTS OF
 ASME A17.1 (NEW ELEVATORS) OR ASME A17.3 (EXISTING
 ELEVATORS).
  
 19.WARNING SIGNS (DO NOT USE IN THE EVENT OF A FIRE)
 ARE REQUIRED IN THE ELEVATOR LOBBIES.
  
 20.ALL FIRE DOORS AND WINDOWS TO COMPLY WITH NFPA 80,
 FIRE DOORS AND WINDOWS.
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE THE ITEMS WERE ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2008-07-24 Cont ID  
Sent By adarroug Date 2008-07-24 Time 11:49 Rev Time 0.00
Received By adarroug Date 2008-07-24 Time 11:49 Sent To B
Notes
2008-07-24 11:49:39TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2008-07-03 Cont ID  
Sent By adarroug Date 2008-07-03 Time 10:06 Rev Time 0.00
Received By adarroug Date 2008-07-03 Time 10:06 Sent To  
Notes
2008-07-03 10:06:38TO "COMM" BD#52

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2008-07-03 Cont ID  
Sent By adarroug Date 2008-07-03 Time 09:50 Rev Time 0.00
Received By adarroug Date 2008-07-03 Time 09:50 Sent To  
Notes
2008-07-03 09:53:28TO "COMM" BD#55

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2008-06-24 Cont ID  
Sent By adarroug Date 2008-06-24 Time 15:59 Rev Time 0.00
Received By adarroug Date 2008-06-24 Time 15:59 Sent To B
Notes
2008-06-24 15:59:54TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2008-06-13 Cont ID  
Sent By adarroug Date 2008-06-13 Time 11:09 Rev Time 0.00
Received By adarroug Date 2008-06-13 Time 11:09 Sent To FIRE
Notes
2008-06-13 11:09:49TO "F" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2008-05-02 Cont ID  
Sent By adarroug Date 2008-05-02 Time 09:22 Rev Time 0.00
Received By adarroug Date 2008-05-02 Time 09:22 Sent To P
Notes
2008-05-02 09:23:02TO "P" BOX/RESTAMP

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2008-04-22 Cont ID  
Sent By adarroug Date 2008-04-22 Time 11:23 Rev Time 0.00
Received By adarroug Date 2008-04-22 Time 11:23 Sent To  
Notes
2008-04-22 11:28:24TO "COMM" BD#36

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-02-11 Cont ID  
Sent By adarroug Date 2008-02-11 Time 11:53 Rev Time 0.00
Received By adarroug Date 2008-02-11 Time 11:53 Sent To  
Notes
2008-02-12 10:21:58TO "COMM" BD#15
2008-02-11 11:55:18WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-01-22 Cont ID  
Sent By adarroug Date 2008-01-22 Time 13:44 Rev Time 0.00
Received By adarroug Date 2008-01-22 Time 13:44 Sent To E
Notes
2008-01-22 13:44:45TO "DPALMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-12-20 Cont ID  
Sent By mmiller Date 2007-12-20 Time 18:06 Rev Time 0.00
Received By mmiller Date 2007-12-20 Time 18:06 Sent To  
Notes
2007-12-20 18:06:58SENT TO COMMERICAL BOARD # 38 MMILLER

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-10-04 Cont ID  
Sent By adarroug Date 2007-10-04 Time 08:52 Rev Time 0.00
Received By adarroug Date 2007-10-04 Time 08:52 Sent To  
Notes
2007-10-25 15:43:10TO "COMM" BD#58--PLANS ON RACK/4 ROLLS AND BOOKS
2007-10-04 08:53:30WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-08-07 Cont ID  
Sent By lmartine Date 2007-08-07 Time 15:41 Rev Time 0.00
Received By lmartine Date 2007-07-24 Time 15:43 Sent To  
Notes
2007-08-07 18:43:48TO COMM BOARD #43.
2007-08-07 15:41:57WAITING FOR COMM. BOARD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-06-27 Cont ID  
Sent By mawillia Date 2007-06-27 Time 11:56 Rev Time 0.00
Received By mawillia Date 2007-06-27 Time 11:57 Sent To  
Notes
2007-04-20 14:47:17TO "COMM" BD#43

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2008-07-29 Cont ID  
Sent By hmoser Date 2008-07-29 Time 14:21 Rev Time 0.00
Received By hmoser Date 2008-07-29 Time 14:19 Sent To  
Notes
2008-07-29 14:20:557/29/08
 TEST AND BALANCE REPORT OK HM.

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2008-04-28 Cont ID  
Sent By rregueir Date 2008-04-28 Time 10:52 Rev Time 0.00
Received By rregueir Date 2008-04-28 Time 10:52 Sent To  
Notes
2008-04-28 10:52:50RESTAMP PAGE MH-102 ORIGINALLY REVIEWED 2/26/08.
 REVISION #3

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2008-02-26 Cont ID  
Sent By rregueir Date 2008-02-26 Time 14:27 Rev Time 0.00
Received By rregueir Date 2008-02-26 Time 14:23 Sent To  
Notes
2008-02-26 14:24:21REVISED MH-102

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2008-01-17 Cont ID  
Sent By rregueir Date 2008-01-17 Time 15:12 Rev Time 0.00
Received By rregueir Date 2008-01-17 Time 15:12 Sent To PC
Notes
2008-01-17 15:12:34RESTAMP

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-11-15 Cont ID  
Sent By rregueir Date 2007-11-15 Time 15:35 Rev Time 0.00
Received By rregueir Date 2007-11-15 Time 14:31 Sent To  
Notes
2007-11-15 15:36:06PASSED PENDING ACCEPTANCE OF ENERGY CALCULATIONS BY ALL
 OTHER INTERESTED TRADES.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-08-14 Cont ID  
Sent By rregueir Date 2007-08-14 Time 16:33 Rev Time 0.00
Received By rregueir Date 2007-08-14 Time 16:11 Sent To  
Notes
2007-08-14 16:33:48REVIEW #: 2ND
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 AMENDMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS EVIEW COMMENTS FOR THE PURPOSE OF CONTINUITY.
  
 1. OK
  
 2. BUILDING RELIEF SHOULD ONLY BE USED IF A BUILDING IS
 UNDER AN UNUSUALLY HIGH POSITIVE PRESSURE. THIS SYSTEM
 IS NOT BALANCED AS SUCH. THE AIR BALANCE ON FIRST FLOOR
 IS NOW AT -1365 CFM. AN OVERALL NEGATIVE PRESSURE IN
 THE BUILDING IS NOT ALLOWED. THE MECHANICAL SYSTEM
 SHALL BE DESIGNED TO ASSURE THAT THE BUILDING IS
 PRESSURIZED WITH RESPECT TO THE OUTDOORS IN ACCORDANCE
 WITH FBC 13-409.1.ABC.2. PROVIDE AN OVERALL AIR BALANCE
 SCHEDULE FOR THE BUILDING SHOWING COMPLIANCE WITH THIS
 SECTION.
  
 3. OK
  
 4. OK
  
 5. PLEASE SHOW HOW ONE 600 CFM TRANSFER (TD-5 ON
 SCHEDULE) WILL ALLOW FOR 950 CFM OF MAKE-UP AIR. ALSO,
 WHEN THIS COMMENT IS ADDRESSED, PLEASE TAKE INTO
 ACCOUNT THE ISSUE RAISED BY THE LATEST COMMENT #2.
  
 6. OK
  
 7. OK
  
 8. SOME REVISIONS HAVE TAKEN PLACE IN THIS AREA ON
 ARCHITECTURAL PLANS. IT APPEARS THAT A FIRE DAMPER HAS
 BEEN UNNECESSARILY ADDED TO THE OA DUCT THROUGH THE
 WALL BETWEEN ROOMS 150 AND 103. ALSO, A FIRE DAMPER IS
 MISSING IN THE 6X6 SUPPLY DUCT WHICH TERMINATES AT THE
 WALL BETWEEN ROOMS 101 AND 110. AS FOR BALANCED RETURN,
 THERE IS NO EXCEPTION IN FBC,M 601.4 FOR DOORS WITH
 HOLD-OPEN DEVICES. PROVIDE BALANCED RETURN.
  
 9. OK
  
 10. SEE COMMENT #2.
  
 11. THERE ARE DOORS BETWEEN ROOMS 200 AND 201. PROVIDE
 BALANCED RETURN PER FBC,M 601.4.
  
 12. OK
  
 13. OK
  
 14. OK
  
 15. SEE COMMENT #11.
  
 16. OK
  
 17. OK
  
 18. PRODUCT APPROVAL WITH INSTALLATION INSTRUCTIONS
 SHALL BE ON SITE FOR INSPECTION.
  
 19. OK
  
 20. A) PROVIDE TWO SETS OF ENERGY CALCULATIONS, EACH
 WITH THE ORIGINAL SIGNATURE AND SEAL OF THE DESIGNER
 PER FBC 13-103.1.1.1. NO PHOTOCOPIED SIGNATURES OR
 SEALS WILL BE ACCEPTED.
 B) BUILDING OWNER OR OWNER'S ARCHITECT SHALL CERTIFY
 THAT THE BUILDING IS IN COMPLIANCE WITH CHAPTER 13 OF
 THE FBC PER FBC 13-400.3.ABC.2.
 C) VERIFY THAT THE TYPES OF BUILDING COMPONENTS USED IN
 THE INPUT DATA REPORT MATCHES THE TYPES SHOWN ON THE
 PLANS AND/OR THE BUILDING. EXAMPLE: THIS IS NOT A METAL
 BUILDING WITH R-19 BATTS AS IS SHOWN ON ENERGY
 CALCULATIONS. IS THE EXTERIOR OF THIS BUILDING 6" METAL
 STUDS WITH R-13 BATTS?
  
 21. OK
  
 22. PG MC-702 DETAIL 1: NOTE #9, FCU'S SHALL BE SHUT
 DOWN BY DUCT SMOKE DETECTOR OR AREA SMOKE DETECTOR PER
 FBC,M 606.2.1.
  
 23. OK
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-05-08 Cont ID  
Sent By rregueir Date 2007-05-08 Time 10:05 Rev Time 0.00
Received By rregueir Date 2007-05-07 Time 07:40 Sent To  
Notes
2007-05-08 10:05:23--------------DENIED----------------
  
 FBC 2004 CODE FAMILY W/2006 REVISIONS
 FBC CH 1 AS AMENDED BY THE CITY OF WEST PALM BEACH
 ASHRAE 15-01
 ASHRAE 62.1-04
  
 1. MH-101: THERE ARE MANY AREAS THROUGHOUT THIS FLOOR
 WHERE TRANSFER DUCTS ABOVE CEILING ARE TOO SMALL TO
 RETURN THE REQUIRED CFM BASED ON TD SCHEDULE ON MM-501.
 THERE ARE ALSO MANY ROOMS WHICH DO NOT HAVE ANY
 TRANSFER DUCT ABOVE CEILING TO ALLOW RETURN AIR FROM
 SPACE EVEN THOUGH THE SPACE IS SEPARATED FROM THE FCU
 BY A PARTITION. THERE ARE TOO MANY TO LIST, BUT HERE
 ARE SOME EXAMPLES: ROOMS 169,175,129,126,117,100.
 BALANCED RETURN IS REQUIRED FROM ALL HABITABLE ROOMS
 PER FBC,M 601.4.
  
 2. MH-101: ROOM AIR DATA SCHEDULE DOES NOT ACCOUNT FOR
 1510 CFM OF EXHAUST FROM OED'S (KEY NOTES 3&4). THE
 AMOUNT OF SUPPLY IS TO BE APPROXIMATELY EQUAL TO RETURN
 AND EXHAUST AIR PER FBC,M 403.1. SCHEDULE SHOWS 9080
 CFM SUPPLY WITH 8220 R/A + 715 CFM EA +1510 EA. THERE
 IS A TOTAL OF 10445 CFM R/A AND EA VS 9080 CFM SUPPLY.
 BALANCE IS OFF BY 1365 CFM. PLEASE SHOW COMPLIANCE WITH
 THIS SECTION WHILE MAINTAINING MIN. REQUIRED
 VENTILATION RATES IN ACCORDANCE WITH FBC,M 403.3.
  
 3. ERV-1 IS RATED FOR 2200 CFM ON SCHEDULE. TOTAL OA
 REQUIRED BY ALL FCU'S FED BY ERV-1 AS STATED ON FCU
 SCHEDULE IS 2510. PLEASE COORDINATE EQUIPMENT,SCHEDULES
 AND VENTILATION RATES IN CUNJUNCTION WITH REVIEW
 COMMENT #2.
  
 4. MH-101: THE FOLLOWING FCU'S ARE MISSING A SIZE FOR
 OA DUCT: 1-6, 1-7, 1-9, 1-14. FCU 1-5 SHOWS 10X12 OA
 DUCT FOR 140 CFM. IS THIS CORRECT? PLEASE CLARIFY. FBC
 106.1.1.
  
 5. MH-101: 18X14 OED IS LOCATED IN CEILING SPACE ABOVE
 ROOM 182. THIS SPACE IS ISOLATED FROM OTHER CEILING
 SPACES EXCEPT FOR TD-3. IS TD-3 FOR THE PURPOSE OF
 RETURN BACK TO FCU OR IS IT TO ALLOW EXHAUST TO REACH
 OED? A) TD-3 IS TOO SMALL TO TRANSFER 950 CFM OF
 EXHAUST AND B) IT CANNOT BOTH ALLOW EXHAUST IN AND
 RETURN AIR OUT OF SPACE SIMULTANEOUSLY. PERHAPS THE OED
 CAN BE RELOCATED TO A LARGER OPEN PLENUM AREA TO ALLOW
 PROPER EXHAUST FLOW AND RETURN AIR FLOW FROM ROOM 182.
 BALANCED RETURN IS REQUIRED PER FBC,M 601.4.
  
 6. MH-101: WHAT IS THE SIZE OF 2ND SUPPLY DROP IN
 WAITING 110? WHAT IS THE SIZE OF DUCT/GRILL AT
 ELECTRICAL CLOSET 101? FBC 106.1.1.
  
 7. MH-101: THE FOLLOWING FCU'S SHOW CFM'S ON ROOM AIR
 DATA SCHEDULE WHICH DIFFER FROM THOSE SHOWN ON FCU
 SCHEDULE (MM-603): 1-2,1-3,1-4,1-6,1-8,1-10. WHICH IS
 CORRECT? PLEASE CLARIFY PER FBC 106.1.1.
  
 8. MH-101: DUCTS ARE SHOWN PENETRATING 1-HOUR RATED
 WALLS FROM FCU-10 INTO LOBBY 100 AND ELECTRICAL ROOM
 104. ALSO THE RETURN OPENING FROM LOBBY 100 INTO
 WAITING 110.
 A) WHAT SIZE IS RETURN OPENING?
 B) PLEASE SHOW THESE OPENINGS IN RATED ASSEMBLIES TO BE
 PROTECTED PER FBC,M 607.5.
  
 9. MH-102: THE FOLLOWING FCU'S HAVE CFM VALUES ON ROOM
 AIR DATA SCHEDULE WHICH DIFFER FROM THOSE SHOWN ON FCU
 SCHEDULE: 2-1, 2-2. WHICH IS CORRECT? FBC 106.1.1.
  
 10. MH-102: PLEASE SEE REVIEW COMMENT #2: SUPPLY IS NOT
 BALANCED WITH RETURN AND EXHAUST. 6990 CFM SUPPLY VS
 5575 R/A+ 1920 CFM EA FOR A TOTAL OF 7495 CFM R/A AND
 EA.SYSTEM IS OUT OF BALANCE BY 505 CFM. FBC,M 403.1.
  
 11. MH-102: DUCT AND TRANSFER OPENING IN RATED WALL AT
 ELEV. VESTIBULE 200. PLEASE SHOW OPENING PROTECTIVES
 PER FBC,M 607.5.
  
 12. MH-102: ROOM AIR DATA SCHEDULE SHOWS EXEC.
 CONFERENCE ROOM AS 205A, FLOOR PLAN SHOWS CONFERENCE
 206. PLEASE COORDINATE SCHEDULE AND FLOOR PLAN.
  
 13. MH-102: PLEASE SHOW SIZES OF ALL EXHAUST BRANCH
 DUCTS SUCH AS IN LAVATORY 218 AND WC 223.
  
 14. MH-102: CONFERENCE ROOM 206 SHOWS 570 CFM SUPPLY
 WITH ONE TD-2 TRANSFER DUCT WHICH IS RATED FOR MAX. 250
 CFM ON PG MM-501. PLEASE SHOW BALANCED RETURN IN THIS
 AREA PER FBC,M 601.4.
  
 15. MH-102: VESTIBULE 200 IS SHOWN TO HAVE ONE SUPPLY
 DROP AT 200 CFM WITH ONE TD-1 FOR TRANSFER WHICH HAS A
 MAX. OF 175 CFM PER MM-501. PLEASE SHOW BALANCED RETURN
 PER FBC,M 601.4. ALSO, PLAN SHOWS SOME TYPE OF
 RECTANGLE INTAKE GRILL IN CEILING. PLEASE CLARIFY.
  
 16. MM-501 DETAIL #6:
 A) PLEASE SHOW MEANS OF ATTACHMENT OF SUPPORTS TO
 STRUCTURE AS WELL AS TYPE/SIZE OF SUPPORTS TO STRUCTURE
 AS WELL AS TYPE/SIZE OF SUPPORTS TO BE USED.
 B) PLEASE SHOW MEANS OF CONDENSATE SECONDARY/AUXILIARY
 DRAIN PROTECTION PER FBC,M 307.2.3.
  
 17. MM-502 DETAIL #1: CONDENSATE DRAINS SHALL BE
 TRAPPED AS REQUIRED BY THE EQUIPMENT OR APPLIANCE
 MANUFACTURER. FBC,M 307.2.4
  
 18. MM-502 DETAIL #5: ROOF MOUNTED MECHANICAL UNITS
 SHALL BE MOUNTED ON CURBS RAISED A MINIMUM OF 8 INCHES
 (203 MM) ABOVE THE ROOF SURFACE, OR WHERE ROOFING
 MATERIALS EXTEND BENEATH THE UNIT, ON RAISED EQUIPMENT
 SUPPORTS PROVIDING A MINIMUM CLEARANCE HEIGHT IN
 ACCORDANCE WITH TABLE 1509.7. ALSO, PRE-ENGINNERED A/C
 STANDS ARE STRUCTURAL ELEMENTS AS DEFINED BY FAC 9B-72.
 THEREFORE, PRODUCT APPLROVAL IS REQUIRED.
  
 19. PLEASE SHOW OUTDOOR AIR CALCULATIONS. FBC,M 403.3
 AND FBC 106.1.2.
  
 20. ENERGY CALCULATIONS SHALL BE MADE A PART OF THE
 PLANS AND SPECIFICATIONS OF THE BUILDING PER FBC
 13-103.2. DESIGN PROFESSIONALS RESPONSIBLE UNDER
 FLORIDA LAW FOR THE DESIGN OF LIGHTING, ELECTRICAL,
 MECHANICAL, AND PLUMBING SYSTEMS AND THE BUILDING
 SHELL, SHALL CERTIFY COMPLIANCE OF THOSE BUILDING
 SYSTEMS WITH THE CODE BY SIGNING AND PROVIDING THEIR
 PROFESSIONAL REGISTRATION NUMBER ON THE ENERGY CODE
 FORM PROVIDED AS PART OF THE PLANS AND SPECIFICATIONS
 TO THE BUILDING DEPARTMENT. FBC 13-103.1.1.1.
  
 21. MM-601: PLEASE PROVIDE SIZES ON CHILLED WATER
 SCHEMATIC AND DUCT RISER DIAGRAMS. ALSO, PLEASE SHOW
 PUMP LOCATION AND REMOVE THE NOTE STATING "OPTIONAL".
 FBC 106.1.1.
  
 22. FAN SHUT-DOWN BY SMOKE DETECTOR IS REQUIRED FOR ALL
 SUPPLY FANS IN THE A/C SYSTEM, INCLUDING ERV'S PER
 FBC,M 607.2.2. EXCEPTIONS: AC-1 AND EMU-1.
  
 23. ABOVE CEILING AREAS ARE USED AS PLENUMS. PLEASE
 ENSURE THAT ALL AMTERIALS EXPOSED IN PLENUMS ARE IN
 COMPLIANCE WITH FBC,M 602.2.1, INCLUDING TAGS,
 EQUIPMENT LABELS AND PIPE MARKERS AS LISTED IN
 SPECIFICATIONS BOOK SEC. 15075. ALSO SEE SEC. 15181-7
 REGARDING CONDENSATE PIPING. PVC CANNOT BE USED IN A
 PLENUM AS IT DOES NOT MEET THE REQUIREMENTS OF
 602.2.1.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 4 Status P Date 2008-01-11 Cont ID  
Sent By kstevens Date 2008-01-11 Time 15:01 Rev Time 0.00
Received By kstevens Date 2008-01-11 Time 15:01 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2007-12-04 Cont ID  
Sent By kstevens Date 2007-12-04 Time 11:17 Rev Time 0.00
Received By kstevens Date 2007-12-04 Time 11:17 Sent To  
Notes
2007-12-04 11:17:49DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FBC-2004 BUILDING
  
 ****FROM PREVIOUS REVIEW:
 ******FROM PREVIOUS REVIEWS:
  
 1. SHT AF-210 DETAILS 6 & 9 LOUNGE (RMS 130 & 159)
 SINKS SHALL BE ACCESSIBLE. PLEASE SUBMIT A DETAIL
 SHOWING COMPLIANCE WITH SECTION 11-4.24 AND ALL
 SUBSECTIONS.
 ****RESPONSE NOTED, BUT SHOW COMPLIANCE WITH THE
 FOLLOWING:
 A. OK
 B. OK
 C. 11-4.24.5 CLEAR FLOOR SPACE - FORWARD APPROACH
 REQUIRED - CABINET DOORS UNDER SINK NOT APPROVED IN
 CLEAR FLOOR SPACE. PLEASE REMOVE.
 ******RESPONSE NOTED, BUT THE CLEAR FLOOR SPACE IS NOT
 SHOWN ON THE FLOOR PLAN. SEE FIG. 32 IN CHAPTER 11.
 D. OK
 C. OK
  
 2. OK
 3. OK
 4. OK
 5. OK
  
 6. TOILET ROOMS 112, 131, 152, 161 & 183. PLEASE
 INDICATE FINISH FOR THE FLOORS AND WALLS PER SECTIONS
 1210.1 & 1210.2. BE MINDFULL THAT THE WALLS WITHIN 2'
 OF ALL URINALS AND WATER CLOSETS SHALL HAVE A "SMOOTH,
 HARD, NONABSORBENT SURFACE" UP TO 4' ABOVE THE FLOOR.
 (PAINTED SURFACES OR WALL PAPER DO NOT MEET THE "HARD"
 REQUIREMENT OF THE CODE SECTION.
 ****RESPONSE NOTED, BUT THE SPECIFICATION APPENDIX A
 FINISH SCHEDULE DOES NOT REFLECT THE INFORMATION SHOWN
 ON SHT AF-211 DETAIL (2). PLEASE SUBMIT THE INFORMATION
 FOR ROOMS 208 & 209 AS WELL. ALSO THE PERSONAL SEAL,
 SIGNATURE AND DATE OF THE ARCHITECT SHALL APPEAR ON ALL
 ARCHITECTURAL DOCUMENTS TO BE FILED FOR PUBLIC RECORD
 PER FAC 61G1-16.003. THE TITLE BLOCK WITH ALL REQUIRED
 INFORMATION IS ALSO REQUIRED ON EACH SPECIFICATION
 APPENDIX A SHEET. THIS IS REQUIRED FOR ALL SHEETS
 SUBMITTED FOR PUBLIC RECORD SUCH AS THE DOOR SCHEDULE
 AND OTHER 8-1/2" BY 11" SHEETS SUBMITTED WITH
 SPECIFICATION INFORMATION.
 ******RESPONSE NOTED, BUT THE TITLE BLOCK INFORMATION
 REQUIRED IN NOT ON THE SHEETS AS REQUESTED.
 (SPOKE TO MR. ERNIEPALMER AND HE INDICATED THE INDEX
 FOR THE SPECIFICATION SHEETS HAS THE APPROPRIATE TITLE
 BLOCK INFORMATION) KSTEVENS
  
 7. OK
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-09-08 Cont ID  
Sent By kstevens Date 2007-09-08 Time 07:22 Rev Time 0.00
Received By kstevens Date 2007-09-08 Time 07:21 Sent To  
Notes
2007-09-08 10:12:01DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FBC-2004 BUILDING
  
 ****FROM PREVIOUS REVIEW:
  
 1. SHT AF-210 DETAILS 6 & 9 LOUNGE (RMS 130 & 159)
 SINKS SHALL BE ACCESSIBLE. PLEASE SUBMIT A DETAIL
 SHOWING COMPLIANCE WITH SECTION 11-4.24 AND ALL
 SUBSECTIONS.
 ****RESPONSE NOTED, BUT SHOW COMPLIANCE WITH THE
 FOLLOWING:
 A. 11-4.24.3 KNEE CLEARANCE
 B. 11-4.24.4 SINK DEPTH
 C. 11-4.24.5 CLEAR FLOOR SPACE - FORWARD APPROACH
 REQUIRED - CABINET DOORS UNDER SINK NOT APPROVED IN
 CLEAR FLOOR SPACE. PLEASE REMOVE.
 D. 11-4.24.6 EXPOSED PIPES & SURFACES
 C. 11-4.24.7 FAUCETS
  
 2. SHT AF-212 DETAIL 5 KITCHEN SINK SHALL BE
 ACCESSIBLE. PLEASE SUBMIT A DETAIL SHOWING COMPLIANCE
 WITH SECTION 11-4.24 AND ALL SUBSECTIONS. ****RESPONSE
 STATES SINK HEIGHTS REVISED, BUT DETAIL DELETED. PLEASE
 CLARIFY. SECTION 106.1.1.
  
 3. OK
 4. OK
 5. OK
  
 6. TOILET ROOMS 112, 131, 152, 161 & 183. PLEASE
 INDICATE FINISH FOR THE FLOORS AND WALLS PER SECTIONS
 1210.1 & 1210.2. BE MINDFULL THAT THE WALLS WITHIN 2'
 OF ALL URINALS AND WATER CLOSETS SHALL HAVE A "SMOOTH,
 HARD, NONABSORBENT SURFACE" UP TO 4' ABOVE THE FLOOR.
 (PAINTED SURFACES OR WALL PAPER DO NOT MEET THE "HARD"
 REQUIREMENT OF THE CODE SECTION.
 ****RESPONSE NOTED, BUT THE SPECIFICATION APPENDIX A
 FINISH SCHEDULE DOES NOT REFLECT THE INFORMATION SHOWN
 ON SHT AF-211 DETAIL (2). PLEASE SUBMIT THE INFORMATION
 FOR ROOMS 208 & 209 AS WELL. ALSO THE PERSONAL SEAL,
 SIGNATURE AND DATE OF THE ARCHITECT SHALL APPEAR ON ALL
 ARCHITECTURAL DOCUMENTS TO BE FILED FOR PUBLIC RECORD
 PER FAC 61G1-16.003. THE TITLE BLOCK WITH ALL REQUIRED
 INFORMATION IS ALSO REQUIRED ON EACH SPECIFICATION
 APPENDIX A SHEET. THIS IS REQUIRED FOR ALL SHEETS
 SUBMITTED FOR PUBLIC RECORD SUCH AS THE DOOR SCHEDULE
 AND OTHER 8-1/2" BY 11" SHEETS SUBMITTED WITH
 SPECIFICATION INFORMATION.
  
 7. PLEASE SUBMIT SANITARY PIPING PLAN VIEW THAT REFLECT
 THE RISER DIAGRAM FOR THE FIRST AND SECOND FLOOR.
 SECTION 106.3.5.1.3(4).
 ****RESPONSE NOTED, AND I WILL VERIFY INFORMATION ON
 PERMIT #07010472.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-06-02 Cont ID  
Sent By kstevens Date 2007-06-02 Time 14:35 Rev Time 0.00
Received By kstevens Date 2007-06-02 Time 14:35 Sent To  
Notes
2007-06-02 14:54:15DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FBC-2004 BUILDING
  
 1. SHT AF-210 DETAILS 6 & 9 LOUNGE (RMS 130 & 159)
 SINKS SHALL BE ACCESSIBLE. PLEASE SUBMIT A DETAIL
 SHOWING COMPLIANCE WITH SECTION 11-4.24 AND ALL
 SUBSECTIONS.
  
 2. SHT AF-212 DETAIL 5 KITCHEN SINK SHALL BE
 ACCESSIBLE. PLEASE SUBMIT A DETAIL SHOWING COMPLIANCE
 WITH SECTION 11-4.24 AND ALL SUBSECTIONS.
  
 3. SHT AF-212 DETAIL 3 INDICATES "TEACHING APT 224".
 WILL THERE BE PATIENTS STAYING IN THE APT OVERNIGHT,
 WEEKLY ETC. PLEASE CLARIFY AS A WASH MACHINE HOOK MAY
 BE REQUIRED PER TABLE 403.1.
  
 4. SHT AF-405 ACCESSIBLE LAV TO BE MAX 34" OFF THE
 FLOOR TO THE FLOOD RIM LEVEL PER SECTION 11-4.19.2.
 THIS IS SHOWN AS 36" ON TWO DETAILS.--ACCESSIBLE
 W/C'S TO BE 17" TO 19" PER SECTION 11-4.16.3. DETAIL
 SHOWS 16-1/2" TO 19-1/2". PLEASE CORRECT DETAIL.
  
 5. SUBMIT A DETAIL FOR THE ACCESSIBLE SHOWERS SHOWING
 COMPLIANCE WITH SECTION 11-4.21 AND ALL SUBSECTIONS.
  
 6. TOILET ROOMS 112, 131, 152, 161 & 183. PLEASE
 INDICATE FINISH FOR THE FLOORS AND WALLS PER SECTIONS
 1210.1 & 1210.2. BE MINDFULL THAT THE WALLS WITHIN 2'
 OF ALL URINALS AND WATER CLOSETS SHALL HAVE A "SMOOTH,
 HARD, NONABSORBENT SURFACE" UP TO 4' ABOVE THE FLOOR.
 (PAINTED SURFACES OR WALL PAPER DO NOT MEET THE "HARD"
 REQUIREMENT OF THE CODE SECTION.
  
 7. PLEASE SUBMIT SANITARY PIPING PLAN VIEW THAT REFLECT
 THE RISER DIAGRAM FOR THE FIRST AND SECOND FLOOR.
 SECTION 106.3.5.1.3(4).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 3 Status P Date 2008-07-16 Cont ID  
Sent By lmartine Date 2008-07-16 Time 15:43 Rev Time 0.00
Received By lfranco Date 2008-07-16 Time 15:45 Sent To  
Notes
2008-07-10 18:22:29PLANNING AND ZONING:**** PASSED ****
  
 MINOR AMENDMENT IN PROCESS WITH THE PLANNING AND ZONING
 DEPARTMENT ( PLANS FOR LANDSCAPE HAVE INCLUDED THE
 ADDTL. TREE AT THE MIDDLE TERMINAL ISLAND ON THE SOUTH
 SIDE OF THE BLDG. (REAR OF STRUCTURE).
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 TEL: (561) 822-1443
 EMAIL: [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2007-11-27 Cont ID  
Sent By lfranco Date 2007-11-08 Time 18:46 Rev Time 0.00
Received By lfranco Date 2007-11-06 Time 10:00 Sent To  
Notes
2007-11-08 18:45:36INTERIOR BUILDING PERMIT ONLY (PASS)

Review Stop Z ZONING
Rev No 1 Status P Date 2007-08-22 Cont ID  
Sent By lfranco Date 2007-08-22 Time 16:32 Rev Time 0.00
Received By lfranco Date 2007-08-22 Time 16:32 Sent To  
Notes
***NONE***