Plan Review Details - Permit 07040544
Plan Review Stops For Permit 07040544
Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-07-02 Cont ID  
Sent By adarroug Date 2007-07-02 Time 11:37 Rev Time 0.00
Received By adarroug Date 2007-07-02 Time 11:37 Sent To M
Notes
2007-07-02 11:38:04TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-04-20 Cont ID  
Sent By adarroug Date 2007-04-20 Time 10:03 Rev Time 0.00
Received By adarroug Date 2007-04-20 Time 10:03 Sent To M
Notes
2007-04-20 10:03:44TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-04-19 Cont ID  
Sent By tgordon Date 2007-04-19 Time 09:01 Rev Time 0.00
Received By tgordon Date 2007-04-18 Time 11:16 Sent To  
Notes
2007-04-18 11:16:52TO "M" BOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-07-03 Cont ID  
Sent By tgordon Date 2007-07-03 Time 13:48 Rev Time 0.30
Received By tgordon Date 2007-07-03 Time 13:48 Sent To  
Notes
2007-07-03 13:53:28*** PROVISO ***
 1) HAVE AN ENGINEERED DETAIL FOR WALL MOUNTED CONDENSER
 STANDS SHOWING THEY WILL WITHSTAND 140 MPH WINDS, PER
 2004 FBC 1609, SIGNED AND SEALED BY AN ENGINEER, ON THE
 JOB SITE AT TIME OF INSPECTION FOR WPB MECHANICAL
 INSPECTOR (2 COPY'S).
  
 2) 2004 FBC/M 606.2.2 COMMON SUPPLY, RETURN AIR AND
 SUPPLY AIR SYSTEMS.
 WHERE MULTIPLE AIR-HANDLING SYSTEMS SHARE COMMON SUPPLY
 OR RETURN AIR DUCTS OR PLENUMS WITH A COMBINED DESIGN
 CAPACITY GREATER THAN 2,000 CFM (0.9 M 3 /S), THE
 RETURN AIR AND SUPPLY AIR SYSTEM SHALL BE PROVIDED WITH
 SMOKE DETECTORS IN ACCORDANCE WITH SECTION 606.2.1 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-04-20 Cont ID  
Sent By tgordon Date 2007-04-20 Time 15:45 Rev Time 0.30
Received By tgordon Date 2007-04-20 Time 15:45 Sent To  
Notes
2007-04-20 15:52:26*** PROVISO ***
 1) HAVE AN ENGINEERED DETAIL FOR WALL MOUNTED CONDENSER
 STANDS SHOWING THEY WILL WITHSTAND 140 MPH WINDS, PER
 2004 FBC 1609, SIGNED AND SEALED BY AN ENGINEER, ON THE
 JOB SITE AT TIME OF INSPECTION FOR WPB MECHANICAL
 INSPECTOR (2 COPY'S).
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-04-19 Cont ID  
Sent By tgordon Date 2007-04-19 Time 08:43 Rev Time 0.30
Received By tgordon Date 2007-04-19 Time 08:43 Sent To  
Notes
2007-04-19 08:57:19*** DENIED ***
 1) SMOKE DETECTORS ARE REQUIRED IN THE RETURN AIR DUCTS
 ALSO, SEE 2004 FBC/M 606.2.2, PLEASE CORRECT.
  
 2) PLEASE SHOW THE SIZES OF THE SUPPLY AIR DUCTS ON THE
 PLANS.
  
 3) OUTDOOR AIR REQUIRED 250 CFM'S FOR EACH BAY, SEE
 2004 FBC/M TABLE 403.3 WAREHOUSES REQUIRE 0.05 CFM/SQ.
 FT., 5000 SQ. FT. X 0.05 = 250. PLEASE CORRECT.
  
 4) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-600.3.ABC.2.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.