Plan Review Details - Permit 07040544
Plan Review Stops For Permit 07040544 |
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2007-07-02 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-07-02 |
Time |
11:37 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-07-02 |
Time |
11:37 |
Sent To |
M |
|
Notes |
2007-07-02 11:38:04 | TO "M" BOX/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2007-04-20 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-04-20 |
Time |
10:03 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-04-20 |
Time |
10:03 |
Sent To |
M |
|
Notes |
2007-04-20 10:03:44 | TO "M" BOX/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2007-04-19 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2007-04-19 |
Time |
09:01 |
Rev Time |
0.00 |
Received By |
tgordon |
Date |
2007-04-18 |
Time |
11:16 |
Sent To |
|
|
Notes |
2007-04-18 11:16:52 | TO "M" BOX |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2007-07-03 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2007-07-03 |
Time |
13:48 |
Rev Time |
0.30 |
Received By |
tgordon |
Date |
2007-07-03 |
Time |
13:48 |
Sent To |
|
|
Notes |
2007-07-03 13:53:28 | *** PROVISO *** | | 1) HAVE AN ENGINEERED DETAIL FOR WALL MOUNTED CONDENSER | | STANDS SHOWING THEY WILL WITHSTAND 140 MPH WINDS, PER | | 2004 FBC 1609, SIGNED AND SEALED BY AN ENGINEER, ON THE | | JOB SITE AT TIME OF INSPECTION FOR WPB MECHANICAL | | INSPECTOR (2 COPY'S). | | | | 2) 2004 FBC/M 606.2.2 COMMON SUPPLY, RETURN AIR AND | | SUPPLY AIR SYSTEMS. | | WHERE MULTIPLE AIR-HANDLING SYSTEMS SHARE COMMON SUPPLY | | OR RETURN AIR DUCTS OR PLENUMS WITH A COMBINED DESIGN | | CAPACITY GREATER THAN 2,000 CFM (0.9 M 3 /S), THE | | RETURN AIR AND SUPPLY AIR SYSTEM SHALL BE PROVIDED WITH | | SMOKE DETECTORS IN ACCORDANCE WITH SECTION 606.2.1 . | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2007-04-20 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2007-04-20 |
Time |
15:45 |
Rev Time |
0.30 |
Received By |
tgordon |
Date |
2007-04-20 |
Time |
15:45 |
Sent To |
|
|
Notes |
2007-04-20 15:52:26 | *** PROVISO *** | | 1) HAVE AN ENGINEERED DETAIL FOR WALL MOUNTED CONDENSER | | STANDS SHOWING THEY WILL WITHSTAND 140 MPH WINDS, PER | | 2004 FBC 1609, SIGNED AND SEALED BY AN ENGINEER, ON THE | | JOB SITE AT TIME OF INSPECTION FOR WPB MECHANICAL | | INSPECTOR (2 COPY'S). | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2007-04-19 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2007-04-19 |
Time |
08:43 |
Rev Time |
0.30 |
Received By |
tgordon |
Date |
2007-04-19 |
Time |
08:43 |
Sent To |
|
|
Notes |
2007-04-19 08:57:19 | *** DENIED *** | | 1) SMOKE DETECTORS ARE REQUIRED IN THE RETURN AIR DUCTS | | ALSO, SEE 2004 FBC/M 606.2.2, PLEASE CORRECT. | | | | 2) PLEASE SHOW THE SIZES OF THE SUPPLY AIR DUCTS ON THE | | PLANS. | | | | 3) OUTDOOR AIR REQUIRED 250 CFM'S FOR EACH BAY, SEE | | 2004 FBC/M TABLE 403.3 WAREHOUSES REQUIRE 0.05 CFM/SQ. | | FT., 5000 SQ. FT. X 0.05 = 250. PLEASE CORRECT. | | | | 4) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT | | ALSO, PER 2004 FBC 13-600.3.ABC.2. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. |
|
|
|