Plan Review Details - Permit 07040505
Plan Review Stops For Permit 07040505
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By mjacobs Date 2007-08-09 Time 14:07 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2007-07-13 Cont ID  
Sent By mjacobs Date 2007-07-13 Time 10:41 Rev Time 0.00
Received By mjacobs Date 2007-07-13 Time 08:39 Sent To  
Notes
2007-07-13 10:41:05 
  
 BUILDING PLAN REVIEW
 PERMIT:07040505
 ADD: 307 EVERNIA
 CONT:
 TEL: (561)###-####
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)KEY NOTE 2 INDICATE DRYWALL ON BOTH SIDES OF THE 3
 5/8 MTL STUDS. HOW CAN THIS BE ACHIVED WITH THE NEW
 WALLS IF ONE SIDE OF THE COLUM IS CLOSED OFF ALREADY?
 SHOW A WALL DETAIL FOR THE NEW WALL AROUND THE COLUMS.
  
 3)SHOW THE CHANGES AND THE REMOVAL OF THE DRINKING
 FOUNTAINS AND THE PROPOSED WATER COOLER ON THE FLOOR
 PLAN. THE WATER COOLER, IF APPROVED SHALL MEET THE
 REQUIREMENTS OF FBC.11-4.15
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-06-26 Cont ID  
Sent By mjacobs Date 2007-06-26 Time 06:53 Rev Time 0.00
Received By mjacobs Date 2007-06-26 Time 05:56 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-06-13 Cont ID  
Sent By mjacobs Date 2007-06-13 Time 07:33 Rev Time 0.00
Received By mjacobs Date 2007-06-12 Time 10:19 Sent To  
Notes
2007-06-12 12:59:03BUILDING PLAN REVIEW
 PERMIT:07040505
 ADD: 307 EVERNIA ST.
 CONT: RAYMOND NORDINE
 TEL: (561)655-1912
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 2ND
 ACTION: DENIED
  
 1)THE ARCHITECT NEEDS TO DATE THE DRAWINGS.
 481.221(2)ALL FINAL CONSTRUCTION DOCUMENTS AND
 INSTRUMENTS OF SERVICE WHICH INCLUDE DRAWINGS, PLANS,
 SPECIFICATIONS, OR REPORTS PREPARED OR ISSUED BY THE
 REGISTERED ARCHITECT AND BEING FILED FOR PUBLIC RECORD
 SHALL BEAR THE SIGNATURE AND SEAL OF THE REGISTERED
 ARCHITECT WHO PREPARED OR APPROVED THE DOCUMENT AND THE
 DATE ON WHICH THEY WERE SEALED. THE SIGNATURE, DATE,
 AND SEAL SHALL BE EVIDENCE OF THE AUTHENTICITY OF THAT
 TO WHICH THEY ARE AFFIXED. SEE ARCHITECTURAL SHEETS.
  
 2) THE DOOR SCHEDULE OF SHEET A-2.01 SHALL INDICATE THE
 DOOR RATING OFDOORS #103.3 AND #103.6 WHIC LEAD TO
 THE EXIT STAIRWAYS.
  
 3)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT TO INCLUDE
 STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL, INTERIOR
 FINISH, ARCHITECTURAL AND DESIGN FEES MARKETING COST,
 OVERHEAD AND PROFIT EXCLUDING LAND. OUR VALUATION
 REFERENCE IS ICC (BVD), MARSHALL-SWIFT AND MEANS COST
 ANALYSIS SERVICES PER 108.3 FBC*
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-04-24 Cont ID  
Sent By mjacobs Date 2007-04-24 Time 08:52 Rev Time 0.00
Received By mjacobs Date 2007-04-24 Time 05:39 Sent To  
Notes
2007-04-24 08:52:10BUILDING PLAN REVIEW
 PERMIT:07040505
 ADD: 307 EVERNIA STREET.
 CONT: RAYMONO NORDINE
 TEL: (561)655-1912
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST.
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE
 RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE:
 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT
 THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTINT PURPOSES, VALUATION OF BULIDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC
 (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 PER 108.3 FBC*
  
 4)SHOW THE ELEVATION DETAIL OF THE RECPTION DESKAND
 HOW IT WILL MEET THE REQUIREMENTS OF SECTION 11-7 FBC.
  
 5)SUBMIT THE MANUFACTURERS REQUIREMENTS FOR THE 3
 FORM PANEL WALLS AS MENTION ON THE DRAWINGS.
  
 6)THE ARCHITECT SEAL ON THE DRAWINGS SHALL BE
 LEGIBLE. SOME PAGES ON THE DRAWINGS STATE "NOT FOR
 CONSTRUCTION" IF THESE DRAWINGS ARE NOT FOR
 CONSTRUCTION, SUBMIT NEW DRAWINGS FOR THE PROPOSED
 PROJECT. THIS NOTE SHALL BE REMOVED FROM THE DRAWINGS.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY.
 FBC. 106.1.1.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-07-02 Cont ID  
Sent By btrobaug Date 2007-07-02 Time 13:51 Rev Time 0.00
Received By btrobaug Date 2007-07-02 Time 13:43 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-06-21 Cont ID  
Sent By btrobaug Date 2007-06-21 Time 08:50 Rev Time 0.00
Received By btrobaug Date 2007-06-21 Time 07:47 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-06-04 Cont ID  
Sent By btrobaug Date 2007-06-04 Time 15:14 Rev Time 0.50
Received By btrobaug Date 2007-06-04 Time 13:54 Sent To  
Notes
2007-06-04 15:14:31 
 REVISION DENIED/INCOMPLETE INFORMATION
  
 1 } SHEET #2 OF THE ENERGY GAUGE ONLY LISTS 3
 FLUORESCENT.FIXTURE SCHEDULE INDICATES 10 DIFFERENT
 TYPES. PLEASE CORRELATE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-04-23 Cont ID  
Sent By btrobaug Date 2007-04-23 Time 12:43 Rev Time 1.00
Received By btrobaug Date 2007-04-19 Time 07:53 Sent To  
Notes
2007-04-23 12:33:16 
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW
  
 1} INDICATE COMPLIANCE WITH 13-415.1ABC.1.1, FBC, SEE
 SPACE CONTROLS FOR LIGHTING ALSO.
  
 2} SHEET #2 OF THE ENERGY GAUGE ONLY LISTS 1
 FLUORESCENT. SUBMIT A FIXTURE SCHEDULE INDICATING
 DENSITY REQUIREMENTS, AND CORRELATE WITH THE ENERGY
 CALCULATIONS.
  
 3} RECEPTACLE CIRCUITS 27 & 29 DO NOT SERVE OFFICE
 106AS LISTED ON SCHEDULE.
  
 4} CIRCUIT 8 THROUGH 36 ON THE RIGHT SIDE OF THE PANEL
 DO NOT LISTS THE ROOMS THE RECEPTACLES ARE SERVING.
 408.4 2005 NEC: EVERY CIRCUIT AND CIRCUIT MODIFICATION
 SHALL BE LEGIBLY IDENTIFIED AS TO ITS CLEAR, EVIDENT,
 AND SPECIFIC PURPOSE OR USE. THE IDENTIFICATION SHALL
 INCLUDE SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE
 DISTINGUISHED FROM ALL OTHERS.
  
 5} PLEASE INDICATE THE CODE CYCLES THIS PROJECT WAS
 DESIGNED UNDER. 2004 FBC, 2005 NEC ETC. ADD TO NOTES
 FOR CLARITY IN THE FIELD.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
 FAX/:561/805-6676

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2007-08-09 Cont ID  
Sent By mawillia Date 2007-08-09 Time 14:40 Rev Time 0.00
Received By mawillia Date 2007-08-09 Time 14:23 Sent To  
Notes
2007-08-09 14:37:50*****APPROVED*****
  
  
 THE REVISED SCOPE OF WORK AS INDICATED AS #4 ON SHEETS
 A-1.01 AND A-1.02 HAS NO BEARING ON LIFE/FIRE SAFETY
 FACTORS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2007-07-17 Cont ID  
Sent By mawillia Date 2007-07-17 Time 18:54 Rev Time 0.00
Received By mawillia Date 2007-07-17 Time 18:38 Sent To  
Notes
2007-07-17 18:41:34*****UNSAT***** REVISION UNCLEAR
  
 PLEASE CLARIFY WHAT REVISION(S) TO THE "AS BUILT"
 IS/ARE BEING MADE.
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-06-14 Cont ID  
Sent By mcarsill Date 2007-06-14 Time 14:10 Rev Time 0.00
Received By mcarsill Date 2007-06-14 Time 14:03 Sent To  
Notes
2007-06-14 14:10:191. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241.
  
 2. EXITS ARE TO BE MAINTAINED DURING CONSTRUCTION.
  
 3. DEBRIS SHALL BE REMOVED FROM THE SITE DAILY.
  
 4. REMOVE EXIT SIGN IN FRONT OF ELEVATOR. ELEVATORS ARE
 NOT USED FOR EXITING PURPOSES.
  
 5. SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE ALARM
 SYSTEM REMODEL.
  
 6. SEPARATE PLANS AND PERMITS REQUIRED FOR ANY FIRE
 SPRINKLER SYSTEM REMODEL.
  
 7. SECURITY DEVICES IF INSTALLED SHALL NOT INTERFERE
 WITH ANY TENENT SPACE EXITING.
  
 8. SOFFITS SHALL NOT INTERFERE WITH ANY OPERATION OF
 ANY FIRE SPRINKLER HEADS.
  
 9. WORK IS SUBJECT TO FIELD INSPECTION AND APPROVAL.
  
 MIKE CARSILLO, BATTALION CHIEF OF FIRE PREVENTION
 804-4709 PHONE
 804-4774 FAX

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-04-24 Cont ID  
Sent By mawillia Date 2007-04-24 Time 17:10 Rev Time 0.00
Received By mawillia Date 2007-04-24 Time 15:52 Sent To  
Notes
2007-04-24 15:55:29*****DENIED*****
  
  
 1. NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 2. UNLESS IT IS WALL RECESSED, RELOCATE THE PLACEMENT
 OF THE FIRE EXTINGUISHER FROM THE EXTERIOR WALL OF THE
 MACHINE ROOM AS TO NOT INTRUDING IN THE PATH OF THE
 EXIT ACCESS CORRIDOR.
  
 3. BE SPECIFIC IN IDENTIFYING THE MINIMUM INTERIOR
 FINISH FOR WALLS AND CEILINGSIN THE EXITS, EXIT
 ACCESS CORRIDORS, AND OTHER SPACES AS CLASS A, CLASS B,
 OR CLASS C.
  
 4.AS PER WEST PALM BEACH FIRE PREVENTION, DUCT
 DETECTORS SHALL INITIATE A GENERAL FIRE ALARM.
  
 5.IF THE FIRE ALARM SYSTEM IS MODIFIED DUE TO THE
 SCOPE OF WORK BEING CONDUCTED, SEPARATE PLANS AND
 PERMIT WILL BE REQUIRED.
  
 6.ON PLAN SHEET E-2.01 INDICATES AN ACCESS CONTROL
 DOOR.WILL EGRESS THROUGH THIS DOOR BE IMPACTED?
 PLEASE BE ADVISED THAT DOORS IN THE MEANS OF EGRESS
 SHALL BE PERMITTED TO BE EQUIPPED WITH AN APPROVED
 ENTRANCE AND EGRESS ACCESS CONTROL SYSTEM PROVIDED THAT
 THE CRITERIA OF NFPA 101 CHAPTER 7.2.1.6.2 ARE MET.
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2007-08-07 Cont ID  
Sent By ssherman Date 2007-08-07 Time 18:02 Rev Time 0.00
Received By ssherman Date 2007-08-07 Time 18:02 Sent To  
Notes
2007-08-07 18:02:32TO BOB BD # 11

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2007-08-01 Cont ID  
Sent By adarroug Date 2007-08-01 Time 11:14 Rev Time 0.00
Received By adarroug Date 2007-08-01 Time 11:14 Sent To P
Notes
2007-08-01 11:14:44TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2007-08-01 Cont ID  
Sent By adarroug Date 2007-08-01 Time 10:29 Rev Time 0.00
Received By adarroug Date 2007-08-01 Time 10:29 Sent To  
Notes
2007-08-01 10:29:27WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2007-07-20 Cont ID  
Sent By adarroug Date 2007-07-20 Time 08:32 Rev Time 0.00
Received By adarroug Date 2007-07-20 Time 08:32 Sent To M
Notes
2007-07-20 08:33:03TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-07-12 Cont ID  
Sent By adarroug Date 2007-06-27 Time 14:43 Rev Time 0.00
Received By adarroug Date 2007-06-27 Time 14:43 Sent To  
Notes
2007-07-12 14:44:26TO "BOB"#13

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-06-28 Cont ID  
Sent By adarroug Date 2007-06-28 Time 09:15 Rev Time 0.00
Received By adarroug Date 2007-06-28 Time 09:15 Sent To P
Notes
2007-06-28 09:15:57TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-06-28 Cont ID  
Sent By adarroug Date 2007-06-28 Time 09:03 Rev Time 0.00
Received By adarroug Date 2007-06-28 Time 09:03 Sent To M
Notes
2007-06-28 09:04:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-06-28 Cont ID  
Sent By adarroug Date 2007-06-28 Time 08:59 Rev Time 0.00
Received By adarroug Date 2007-06-28 Time 08:59 Sent To E
Notes
2007-06-28 08:59:52TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-06-19 Cont ID  
Sent By adarroug Date 2007-06-19 Time 13:28 Rev Time 0.00
Received By adarroug Date 2007-06-19 Time 13:28 Sent To  
Notes
2007-06-20 13:40:30TO "BOB"#12
2007-06-19 13:28:56WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-05-23 Cont ID  
Sent By adarroug Date 2007-05-23 Time 09:28 Rev Time 0.00
Received By adarroug Date 2007-05-23 Time 09:28 Sent To  
Notes
2007-06-01 08:50:52TO "BOB"#16
2007-05-23 09:29:08WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-04-25 Cont ID  
Sent By jleech Date 2007-04-25 Time 15:15 Rev Time 0.00
Received By jleech Date 2007-04-17 Time 13:08 Sent To  
Notes
2007-04-17 13:10:34TO "BOB"#13

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2007-07-20 Cont ID  
Sent By tgordon Date 2007-07-20 Time 15:55 Rev Time 0.25
Received By tgordon Date 2007-07-20 Time 15:55 Sent To  
Notes
2007-07-20 15:56:08REVISION TO MECHANICAL PLAN PAGE M-1.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-06-28 Cont ID  
Sent By tgordon Date 2007-06-28 Time 15:36 Rev Time 0.40
Received By tgordon Date 2007-06-28 Time 15:35 Sent To  
Notes
2007-06-28 15:37:53*** PROVISO ***
 1) RETURN AIR FOR OFFICE 101 MUST PERMIT AIR TO RETURN
 TO ATU 1. SEE 2004 FBC/M 601.4.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-06-01 Cont ID  
Sent By tgordon Date 2007-06-01 Time 14:38 Rev Time 0.25
Received By tgordon Date 2007-06-01 Time 14:38 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-04-24 Cont ID  
Sent By tgordon Date 2007-04-24 Time 10:51 Rev Time 0.30
Received By tgordon Date 2007-04-24 Time 10:51 Sent To  
Notes
2007-04-24 11:07:07*** DENIED ***
 1) SEE MECHANICAL PLANS M-1, 8X8 SUPPLY AIR DUCT TO
 HALL 108 WILL NEED A FIRE DAMPER AS THE DUCT IS NOT
 ABOVE THE CEILING IN THE ADJOINING ROOM, AS THE
 BUILDING WAS PERMITTED IN 2001 SEE 2001 FBC/M 607.1.3
 (4), AND 2001 FBC 412.6.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 5 Status F Date 2007-08-27 Cont ID  
Sent By mperson Date 2007-08-27 Time 08:47 Rev Time 0.00
Received By mperson Date 2007-08-27 Time 08:47 Sent To PC
Notes
2007-08-27 09:15:19REVISION DENIED
 REFERENCE:
 ** FBC-2004 PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS,
 SOME BASED ON PLANS NOW SUBMITTED, NEW DOCUMENTS BEING
 REVIEWED FOR THE FIRST TIME AND SOME NEW COMMENTS NOT
 MADE ON PREVIOUS REVIEWS.
  
 ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM
 PREVIOUS REVIEW WITH A NO, OK OR A NO/OK.
 THESE WILL BE FOR THE EXACT NUMERICAL NOTATION OF THE
 PREVIOUS REVIEW NOTES.
  
 A NO IS IF THE COMMENT WAS NOT FULLY ADDRESSED AND/OR
 FURTHER EXPLANATION OR CHANGES IN PLANS OR DOCUMENTS
 ARE STILL NEEDED. THIS REVIEWER WILL TRY TO BETTER
 EXPLAIN NOTE ABOVE PREVIOUS REVIEW COMMENT.
  
 AN OK WILL BE LABELED AS SUCH ON THE SAME NUMERICAL
 COMMENT AND WILL HAVE OLD NOTE REMOVED FROM COMMENTS.
  
 A NO/OK MEANS PART OF THE COMMENT MAY HAVE BEEN
 ADDRESSED, HOWEVER NOT ALL OF THE PREVIOUS REVIEW
 COMMENT MAY HAVE BEEN FULLY ADDRESSED.
  
 ** PLEASE SEE ANY NEW NOTES WILL BE ADDED TO THE END OF
 THE PREVIOUS REVIEW COMMENTS AND NOTED AS SUCH.
  
 1. **OK** RESPONSE NOTED (SHEET P-1.01)
  
 2. **NO** SANITARY AND WATER RISER DIAGRAMS ARE
 REQUIRED AND SHOULD NOT BE DELETED. (SHEET P-1.01)
 NOTE: THE RESUBMITTED REVISION MUST REFLECT THE FIELD
 CHANGES, THEY CAN NOT BE DELETED. PER FBC-2004 CHAPTER
 1, SECTION 106.3.5.1.3 PLUMBING (3), (4) (10) AND (13).
 PLEASE CORRECT AND RESUBMIT.
  
 3. **NO/OK** IS THE INSTA HOT BEING DELETED? IF SO
 ELECTRICAL REVISION REQUIRED. (SHEET P-1.01)
 NOTE: THE RESUBMITTED PLANS INDICATE THE INSTA HOT
 BEING RELOCATED ABOVE CEILING. THE RESUBMITTED REVISED
 WATER RISER DIAGRAM NEEDS TO REFLECT THIS. PLEASE
 CORRECT AND RESUBMIT.
  
 4. PLEASE CLOUD ALL CHANGES AND PROVIDE REVISION
 NUMBERS AND DATES ON THE RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL= [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 4 Status F Date 2007-07-24 Cont ID  
Sent By jleech Date 2007-07-24 Time 10:46 Rev Time 0.00
Received By jleech Date 2007-07-24 Time 10:45 Sent To  
Notes
2007-07-24 11:03:05DENIED;
 1. BOTTLE WATER CANNOT REPLACE A DRINKING FOUNTAIN. SEE
 FBC-2004 PLUMBING SECTION 410.1.
 2. SANITARY AND WATER RISER DIAGRAMS ARE REQUIRED AND
 SHOULD NOT BE DELETED.
 3.IS THE INSTA HOT BEING DELETED? IF SO ELECTRICAL
 REVISION REQUIRED.
 4. PLEASE CLOUD ALL CHANGES EVEN DELETED SECTIONS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 3 Status F Date 2007-07-16 Cont ID  
Sent By jleech Date 2007-07-16 Time 10:27 Rev Time 0.00
Received By jleech Date 2007-07-16 Time 10:27 Sent To  
Notes
2007-07-16 10:35:04DENIED;
 DRINKING FOUNTAIN IS REQUIRED IT CANNOT BE REPLACED BY
 BOTTLE WATER COOLER. SEE FBC-2004 PLUMBING TABLE
 403.1(2B), SECTION 410.1. THE DRINKING FOUNTAIN MUST
 COMPLY WITH THE FLORIDA ACCESSIBILITY CODE SECTIONS
 11-4.1(10), AND SECTIONS 11-4.15.2 THRU 11-4.15.5.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-06-09 Cont ID  
Sent By jleech Date 2007-06-09 Time 10:37 Rev Time 0.00
Received By jleech Date 2007-06-09 Time 10:37 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-04-25 Cont ID  
Sent By jleech Date 2007-04-25 Time 15:07 Rev Time 0.00
Received By jleech Date 2007-04-25 Time 15:06 Sent To  
Notes
2007-04-25 15:14:46DENIED;
 1. DETAILS REQUIRED FOR BREAK SINK AND DRINKING
 FOUNTAIN.
 A) BREAK SINK SHALL COMPLY WITH FBC-2004
 BUILDING CHAPTER 11, SECTIONS 11-4.24.1 THRU .7 SHOW
 ALL MESSUREMENT REQUIRED. MUST BE A FRONTAL APPROACH.
 SHOW CLEAR FLOOR SPACE ON FLOOR PLAN.
 B) DRINKING FOUNTAIN TO COMPLY WITH SECTIONS
 11-4.15.1 THRU .5
 PLUMBING PLAN REVIEW BY
 JOHN LEECH
 805-6695