Plan Review Details - Permit 07040404
Plan Review Stops For Permit 07040404
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-06-01 Cont ID  
Sent By mjacobs Date 2007-06-01 Time 08:32 Rev Time 0.00
Received By mjacobs Date 2007-05-31 Time 15:30 Sent To  
Notes
2007-05-31 15:59:25BUILDING PLAN REVIEW
 PERMIT: 07040404
 ADD:901 45TH STREET.
 CONT: STATIC ELECTRIC CO.
 TEL: (561)684-6100
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST
 ACTION: DENIED
  
 1) 2004 FL. BLD CODE 1603.1.4 THE
 FOLLOWING INFORMATION RELATED TO WIND
 SHALL BE SHOWN ON THE CONSTRUCTION
 DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 2)GENERATOR SLAB & ANCHOR REQUIREMENT
 PLEASE PROVIDE SIZE OF GENERATOR(WXL),
 PLUS PROVIDE PLANS WITH THE INFORMATION
 DEPICTING HOLD DOWN BRACKETS, TYPE OF
 FASTENER, AND THE MINIMUM EDGE DISTANCE
 THE DEVICE REQUIRES WITHOUT LOAD
 REDUCTION.
 SECOND, PROVIDE INFORMATION ON THE
 SLAB, THICKNESS, WIDTH AND LENGTH, IF
 WIREMESH, FIBER MESH OR IF STEEL REBAR
 WILL BEUSED.
 THE NEW SLAB AND HOLD DOWN DETAILS:
 104.2.1* ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN.
  
 3)PROVIDE PLANS ENOUGH TO VERIFY LOCATION
 OF GENERATOR VERSES BUILDING OPENINGS
 WINDOWS, DOORS OR SOFFIT TYPE VENTS,
 ETC.
 M501.2 OUTDOOR DISCHARGE.
 THE AIR REMOVED BY EVERY MECHANICAL
 EXHAUST SYSTEM SHALL BE DISCHARGED
 OUTDOORS AT A POINT WHERE IT WILL NOT
 CAUSE A NUISANCE AND FROM WHICH IT
 CANNOT AGAIN BE READILY DRAWN IN BY A
 VENTILATING SYSTEM. AIR SHALL NOT BE
 EXHAUSTED INTO AN ATTIC OR CRAWL SPACE
  
 M401.5 OPENING LOCATION.
 OUTDOOR AIR EXHAUST AND INTAKE OPENINGS
 SHALL BE LOCATED A MINIMUM OF 10 FEET
 (3048 MM) FROM LOT LINES OR BUILDINGS ON
 THE SAME LOT. WHERE OPENINGS FRONT ON A
 STREET OR PUBLIC WAY, THE DISTANCE SHALL
 BE MEASURED TO THE CENTERLINE OF THE
 STREET OR PUBLIC WAY.
  
 4) 106.1.3 THE BUILDING OFFICIAL
 MAY SET STANDARDS THROUGH DEPARTMENTAL
 POLICY STANDARDS FOR PLANS AND SPRCIFICA
 TIONS. "NO WHITE OUT OR HAND WRITING ON PLANS".
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-04-30 Cont ID  
Sent By dpalmer Date 2007-04-30 Time 11:45 Rev Time 0.00
Received By dpalmer Date 2007-04-27 Time 17:00 Sent To I
Notes
2007-04-30 11:45:27** UNSAT **
  
 ** PLEASE SEE THAT ANY REFERENCES TO THE FBC CHAPTER 1
 ARE FROM THE ADMINISTRATIVE CODE ADOPTED BY THE CITY OF
 WEST PALM BEACH.
  
  
 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS
 WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES
 PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
  
 2) NOTE: PLEASE VERIFY SYSTEM BEING INSTALLED AND
 PROPOSED. PLEASE SEE THE GENERATOR LOAD CALCULATIONS
 AND SPECIFICATIONS INDICATE THIS UNIT AS 120/240 SINGLE
 PHASE, AND THE PLANS INDICATE THE EQUIPMENT/PANEL BEING
 120/208V.
 PLEASE ALSO SEE THAT PART OF THE RISER SHOWS THIS
 SERVICE AS THREE PHASE.?
 FBC 106 .1.2
  
 3) NOTE: PLEASE SEE THE RISER STILL SEEMS TO SHOW A
 CONNECTION FROM THE GUTTER TO THE SAME PANEL WHICH IS
 BEING FED FROM THE GENERATOR?
 PLEASE CLARIFY RISER AS SHOWN AS THE EXISTING
 CONNECTION FROM GUTTER WOULD BE REQUIRED TO BE REMOVED
 INCLUDING CONDUIT.
 PLEASE CLARIFY RISER AS SHOWN WITH THE FEED FROM FPL.
 DOES THIS COME THROUGH THE METER? IS THIS A 600AMP
 METER/ OR CT.
 FBC 106.1.2,
 NEC 215.5
  
 4) NOTE: PLEASE CLARIFY THE LOAD CALCULATIONS AS SHOWN.
 PLEASE SEE THESE MENTION APARTMENT LOADS, HOWEVER THE
 LOADS ARE NOT COMPLETE FOR APARTMENTS.
 PLEASE SEE THE LOADS MUST BE BASED ON THE NEC. 220
 (2005 NEC).
 FBC 106.1.2
  
 5) NOTE: PLEASE SEE THE LOAD CALCULATION SHEET
 INDICATES THE GENERATOR BREAKERAT 200AMPS, THE RISER
 SHOWS THIS AS 150AMPS, AND THE SPECS INDICATES 175AMP?
 PLEASE COORDINATE ALL, AT THIS TIME THE SIZES OF
 CONDUCTORS ETC CAN NOT BE VERIFIED.
 240.4, 310.16 ETC.
 FBC 106.3.5.1.2, 106.1.2
  
 6) NOTE: PLEASE SEE THE SPECS SUBMITTED FOR THE ATS
 DOES NOT INDICATE A DISCONNECTING MEANS FOR THE
 LINE/NORMAL SIDE AND A BREAKER/DISCONNECT FOR THE
 GENERATOR/EM SIDE?
 PLEASE REVISE SPECS OR RISER TO INCLUDE A DISCONNECTING
 MEANS AT THE SERVICE LOCATION.
 225.31-225.39.
 ** PLEASE KNOW, AS ZONING COMMENTS WILL MOST LIKELY
 REQUIRE THIS UNIT TO BE IN AN ENCLOSURE THE BREAKER ON
 THE GENERATOR MAY NOT BE USED.
  
 7) NOTE: PLEASE PROVIDE ALL ELECTRICAL EQUIPMENT ON THE
 PLAN LAYOUT SHEET.
 FBC 106.1.2
 LOCATIONS NEED TO BE VERIFIED FOR 230, 225 ETC.
  
 8) NOTE: PLEASE SEE THE SPECIFICATIONS INDICATES THIS
 AS BEING CONNECTED TO A PROPANE TANK, YET THE GAS
 PERMIT APPLICATION MENTIONS THIS WILL BE A NATURAL GAS
 UNIT?
 PLEASE SEE COMMENTS FROM PLUMBING.
  
 9) NOTE: PLEASE SEE THE NOC SUBMITTED AS EXPIRED PER FS
 713.13(2).
 PLEASE SEE THE NOC WILL BE REQUIRED TO BE RE-RECORD
 BEFORE PICKING UP THE PERMIT.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-04-27 17:00:40PLANS REMOVED FROM INCOMING/TABLE IN ELEC FOR REVIEW.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-06-05 Cont ID  
Sent By mawillia Date 2007-06-05 Time 14:39 Rev Time 0.00
Received By mawillia Date 2007-06-05 Time 14:13 Sent To  
Notes
2007-06-05 14:39:02*****DENIED*****
  
  
 1.PLEASE INDICATE THE PROPOSED USE OF THE GENERATOR.
  
 2.STATIONARY GENERATORS FOR EMERGENCY USE OR STANDBY
 POWER SHALL BE INSTALLED IN ACCORDANCE WITH NFPA 110.
  
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, ACKNOWLEDGE THE
 ABOVE COMMENTS ON YOUR PLANS.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-06-09 Cont ID  
Sent By kstevens Date 2007-06-09 Time 05:39 Rev Time 0.00
Received By kstevens Date 2007-06-09 Time 05:39 Sent To  
Notes
2007-06-09 05:50:09DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 A. THE FOLLOWING ITEMS NEED CLARIFICATION:
  
 1. TYPE OF GAS, (LP OR NATURAL). THE APPLICATION
 INDICATES NATURAL GAS, BUT THE MANUF. SPECIFICATION
 SHEETS ARE INDICATING PROPANE. PLEASE CLARIFY.
  
 2. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33). THE RISER DIAGRAM INDICATES 500,000 BTU, BUT
 THE FUEL CONSUMPTION FOR NATURAL GAS IS 560 CU FT/HR
 BTU AT 100% RATED LOAD, AND 222.3 CU FT/HR FOR PROPANE.
 PLEASE CLARIFY.
  
 B. IF LP GAS THE FOLLOWING COMMENTS APPLY:
  
 3. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 4. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6721
 E-MAIL [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-04-20 Cont ID  
Sent By adarroug Date 2007-04-20 Time 14:33 Rev Time 0.00
Received By adarroug Date 2007-04-20 Time 14:33 Sent To E
Notes
2007-05-01 14:32:09TO "COMM" BD#5
2007-04-20 14:34:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-06-09 Cont ID  
Sent By kstevens Date 2007-06-09 Time 05:50 Rev Time 0.00
Received By kstevens Date 2007-04-13 Time 13:43 Sent To  
Notes
2007-04-13 13:43:29TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-05-02 Cont ID  
Sent By rregueir Date 2007-05-02 Time 09:13 Rev Time 0.00
Received By rregueir Date 2007-05-02 Time 08:54 Sent To  
Notes
2007-05-02 09:13:15---------------DENIED-----------------
  
 PLEASE VERIFY TYPE OF FUEL TO BE USED. SUBMITTED SPECS
 INDICATE PROPANE, BUT A GAS PERMIT APPLICATION WAS ALSO
 SUBMITTED TO FUEL THE GENERATOR. PLEASE CORRECT AND
 RESUBMIT.
  
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2007-04-19 Cont ID  
Sent By mcruz Date 2007-04-19 Time 18:35 Rev Time 0.00
Received By mcruz Date 2007-04-19 Time 18:33 Sent To I
Notes
2007-04-19 18:32:05PLANNING & ZONING: ** FAILED**
  
 1.PLEASE PROVIDE RESPONSE IN WRITING.
  
 2.PURSUANT TO SECTION 94-444, OF THE CITY OF WEST
 PALM BEACH ZONING AND LAND DEVELOPMENT REGULATIONS,
 APPROPRIATE SCREENING SHALL BE PROVIDED FOR GENERATORS.
 SCREENING SHALL BE CONSTRUCTED OF BRICK, DECORATIVE
 CONCRETE, OTHER DECORATIVE MASONRY, OR COMPARABLY
 DURABLE WOOD AND STEEL. WALLS SHALL BE LANDSCAPED WITH
 SHRUBS AND HEDGES PLANTED AT TWO-FOOT INTERVALS.
  
 3.QUANTUM HOUSE IS LOCATED WITHIN THE ST. MARY'S
 COMMUNITY SERVICE PLANNED DEVELOPMENT (CSPD) AND MUST
 APPLY FOR A MINOR PLANNED DEVELOPMENT (PD) AMENDMENT
 PRIOR TO RECEIVING ZONING APPROVAL OF THE BUILDING
 PERMIT FOR THE GENERATOR.THE DEVELOPMENT APPLICATION
 IS AVAILABLE ON THE PLANNING DEPARTMENT'S WEBPAGE AT:
 WWW.CITYOFWPB.COM\PLAN.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ME.
  
 MARGARITA CRUZ
 ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 561-822-1444