Plan Review Details - Permit 07040341
Plan Review Stops For Permit 07040341
Review Stop G GAS REVIEW
Rev No 3 Status P Date 2008-02-27 Cont ID  
Sent By mperson Date 2008-02-27 Time 10:59 Rev Time 0.00
Received By mperson Date 2008-02-27 Time 10:59 Sent To PC
Notes
2008-02-27 11:02:21REVISION #2: "OK" BBQ DESIGNATED "FUTURE" APPLIANCE AND
 CAPPED GAS TIGHT.
  
  
 ****************PROVISO****************
 A}FUTURE GENERATOR GAS PIPING AT OWN RISK, SEPERATE
 GEN/RES PERMIT REQUIRED WITH ZONING APPROVAL OF
 GENERATOR PLACEMENT.
 NOTE: PER FBC-2004 FUEL GAS SECTION, 404.12 OUTLET
 CLOSURES. GAS OUTLETS THAT DO NOT CONNECT TO APPLIANCES
 SHALL BE CAPPED GAS TIGHT. IF GAS DELIVERY PRESSURE IS
 2 PSI OR GREATER MP REGULATORS SHALL BE INSTALLED PRIOR
 TO FINAL INSPECTION.
  
 B} PER FBC-2004 FUEL GAS, SECTION 409.4 MP REGULATOR
 VALVES: A LISTED SHUTOFF VALVE SHALL BE INSTALLED
 IMMEDIATELY AHEAD OF EACH MP REGULATOR.
  
 IF DRYER ROOM IS A CONFINED SPACE, OPENINGS REQUIRED
 PER SECTION 304.5 OR SECTION 304.6 SHALL BE INSTALLED.
 MINIMUM 1,000 CUBIC FEET REQUIRED.

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2007-06-07 Cont ID  
Sent By mperson Date 2007-06-07 Time 14:31 Rev Time 0.45
Received By mperson Date 2007-06-07 Time 14:31 Sent To PC
Notes
2007-06-07 14:40:01REVISION: INSTALL NAT/GAS LINE TO 2ND FLOOR FIREPLACE.
  
 ****************PROVISO****************
 A}FUTURE GENERATOR GAS PIPING AT OWN RISK, SEPERATE
 GEN/RES PERMIT REQUIRED WITH ZONING APPROVAL OF
 GENERATOR PLACEMENT.
 NOTE: PER FBC-2004 FUEL GAS SECTION, 404.12 OUTLET
 CLOSURES. GAS OUTLETS THAT DO NOT CONNECT TO APPLIANCES
 SHALL BE CAPPED GAS TIGHT. IF GAS DELIVERY PRESSURE IS
 2 PSI OR GREATER MP REGULATORS SHALL BE INSTALLED PRIOR
 TO FINAL INSPECTION.
  
 B} PER FBC-2004 FUEL GAS, SECTION 409.4 MP REGULATOR
 VALVES: A LISTED SHUTOFF VALVE SHALL BE INSTALLED
 IMMEDIATELY AHEAD OF EACH MP REGULATOR.
  
 IF DRYER ROOM IS A CONFINED SPACE, OPENINGS REQUIRED
 PER SECTION 304.5 OR SECTION 304.6 SHALL BE INSTALLED.
 MINIMUM 1,000 CUBIC FEET REQUIRED.

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2007-04-23 Cont ID  
Sent By mperson Date 2007-04-23 Time 08:39 Rev Time 0.55
Received By mperson Date 2007-04-23 Time 08:39 Sent To PC
Notes
2007-04-23 08:56:44****************PROVISO****************
 A}FUTURE GENERATOR GAS PIPING AT OWN RISK, SEPERATE
 GEN/RES PERMIT REQUIRED WITH ZONING APPROVAL OF
 GENERATOR PLACEMENT.
 NOTE: PER FBC-2004 FUEL GAS SECTION, 404.12 OUTLET
 CLOSURES. GAS OUTLETS THAT DO NOT CONNECT TO APPLIANCES
 SHALL BE CAPPED GAS TIGHT. IF GAS DELIVERY PRESSURE IS
 2 PSI OR GREATER MP REGULATORS SHALL BE INSTALLED PRIOR
 TO FINAL INSPECTION.
  
 B} PER FBC-2004 FUEL GAS, SECTION 409.4 MP REGULATOR
 VALVES: A LISTED SHUTOFF VALVE SHALL BE INSTALLED
 IMMEDIATELY AHEAD OF EACH MP REGULATOR.
  
 IF DRYER ROOM IS A CONFINED SPACE, OPENINGS REQUIRED
 PER SECTION 304.5 OR SECTION 304.6 SHALL BE INSTALLED.
 MINIMUM 1,000 CUBIC FEET REQUIRED.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-02-25 Cont ID  
Sent By adarroug Date 2008-02-25 Time 12:27 Rev Time 0.00
Received By adarroug Date 2008-02-25 Time 12:27 Sent To G
Notes
2008-02-25 12:27:51TO "G" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-05-22 Cont ID  
Sent By adarroug Date 2007-05-22 Time 15:52 Rev Time 0.00
Received By adarroug Date 2007-05-22 Time 15:52 Sent To G
Notes
2007-05-22 15:52:21TO "G" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-04-23 Cont ID  
Sent By mperson Date 2007-04-23 Time 09:59 Rev Time 0.00
Received By mperson Date 2007-04-11 Time 11:04 Sent To  
Notes
2007-04-11 11:04:45TO "G" BOX