Plan Review Details - Permit 07040257
Plan Review Stops For Permit 07040257
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status N Date 2007-05-29 Cont ID  
Sent By mjacobs Date 2007-05-29 Time 12:20 Rev Time 0.00
Received By mjacobs Date 2007-05-29 Time 11:57 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-04-28 Cont ID  
Sent By mjacobs Date 2007-04-28 Time 07:20 Rev Time 0.00
Received By mjacobs Date 2007-04-28 Time 05:56 Sent To PC
Notes
2007-04-28 07:20:39BUILDING PLAN REVIEW
 PERMIT:
 ADD:
 CONT:
 TEL: (561)###-####
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)INDICATE ON THE DRAWINGS THE TOTAL SQUARE FOOTAGE
 OF THE POOL DECK. ALSO STATE WHAT TYPE OF DECK WILL BE
 INSTALLED FOR RECORD PURPOSES.
  
 2)R4101.17.1 OUTDOOR SWIMING POOLS SHALL BE PROVIDED
 WITH A BARRIER COMPLYING WITH R4101.17.1.1 THROUGH
 R4101.17.1.14. STATE ON THE DRAWINGS WHICH TYPE OF
 SAFETY FEATURE WILL BE INSTALL. FBC 13-612.1.ABC.2.3.2
 COVERS REQUIRED. SPAS AND HEATED SWIMMING POOLS SHALL
 BE
 EQUIPPED WITH A COVER DESIGNED TO MINIMIZE HEAT LOSS.
  
 3)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC
 (BVD),MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 PER 108.3 FBC*
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-05-18 Cont ID  
Sent By btrobaug Date 2007-05-18 Time 14:45 Rev Time 0.22
Received By btrobaug Date 2007-05-18 Time 14:38 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2007-04-16 Cont ID  
Sent By btrobaug Date 2007-04-16 Time 13:33 Rev Time 0.33
Received By btrobaug Date 2007-04-16 Time 12:23 Sent To P
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2007-05-23 Cont ID  
Sent By mperson Date 2007-05-23 Time 11:08 Rev Time 0.00
Received By mperson Date 2007-05-23 Time 11:08 Sent To B
Notes
2007-05-23 11:09:55CONTRACTOR INFORMATION
 NOTE: GAS PERMIT REQUIRED. GAS CONTRAC-
 TOR TO SUBMIT PLANS WITH PERMIT APPLICA-
 TION. ALL GAS INSPECTIONS TO BE COMPLETE
 BEFORE FINAL POOL INSPECTION.
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2007-04-24 Cont ID  
Sent By mperson Date 2007-04-24 Time 11:16 Rev Time 0.00
Received By mperson Date 2007-04-24 Time 11:16 Sent To B
Notes
2007-04-24 11:17:51CONTRACTOR INFORMATION
 NOTE: GAS PERMIT REQUIRED. GAS CONTRAC-
 TOR TO SUBMIT PLANS WITH PERMIT APPLICA-
 TION. ALL GAS INSPECTIONS TO BE COMPLETE
 BEFORE FINAL POOL INSPECTION.
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-05-18 Cont ID  
Sent By adarroug Date 2007-05-18 Time 13:13 Rev Time 0.00
Received By adarroug Date 2007-05-18 Time 13:13 Sent To E
Notes
2007-05-18 13:13:43TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-05-14 Cont ID  
Sent By adarroug Date 2007-05-14 Time 16:33 Rev Time 0.00
Received By adarroug Date 2007-05-14 Time 16:33 Sent To Z
Notes
2007-05-14 16:33:24TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-04-12 Cont ID  
Sent By adarroug Date 2007-04-12 Time 10:09 Rev Time 0.00
Received By adarroug Date 2007-04-12 Time 10:09 Sent To E
Notes
2007-04-12 10:09:32TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2007-04-28 Time   Rev Time 0.00
Received By adarroug Date 2007-04-09 Time 14:23 Sent To  
Notes
2007-04-09 14:24:06TO "Z" BOX

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-05-23 Cont ID  
Sent By mperson Date 2007-05-23 Time 11:07 Rev Time 0.33
Received By mperson Date 2007-05-23 Time 11:07 Sent To G
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-04-24 Cont ID  
Sent By mperson Date 2007-04-24 Time 10:54 Rev Time 0.33
Received By mperson Date 2007-04-24 Time 10:54 Sent To G
Notes
2007-04-24 11:15:53DENIED
 REFERENCE:
 *** FBC-2004 SECTION 424.2 AND R4101 SWIMMING POOLS:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. THE EQUIPMENT LAYOUT IS MISLABELED. THE EQUIPMENT
 LAYOUT MUST CORRELATE WITH THE LEGEND. PLEASE CORRECT
 AND RESUBMIT.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop Z ZONING
Rev No 2 Status P Date 2007-05-15 Cont ID  
Sent By choops Date 2007-05-15 Time 16:23 Rev Time 0.00
Received By choops Date 2007-05-15 Time 16:23 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2007-04-10 Cont ID  
Sent By jroach Date 2007-04-10 Time 17:48 Rev Time 0.00
Received By jroach Date 2007-04-10 Time 17:48 Sent To I
Notes
2007-04-10 17:52:19***FAILED***
  
 1) SETBACK DIMENSION SHALL BE PROVIDED FROM THE POOL
 EQUIPMENT TO THE PROPERTY LINE.
  
 2) EVERY SWIMMING POOL SHALL BE ENCLOSED BY A FENCE OR
 SIMILAR STRUCTURE WHICH IS INSTALLED TO OBSTRUCT ACCESS
 BY PERSONS OTHER THAN THE OWNERS OR OCCUPANTS OF THE
 RESIDENCE WITHIN WHICH A SWIMMING POOL IS LOCATED.
 BARRIERS OR FENCES SHALL BE AT LEAST FOUR FEET IN
 HEIGHT ABOVE GRADE.
  
 3) ACCESS TO AN ACCESSORY SWIMMING POOL MUST BE THROUGH
 A BUILDING OR THROUGH A SELF-CLOSING AND SELF-LATCHING
 GATE OR THROUGH A SCREEN ENCLOSURE DOOR WITH LATCHES
 PLACED AT LEAST 54 INCHES ABOVE BOTTOM OF GATE.(CHILD
 SAFETY BARRIERS DO NOT SATISFY THIS REQUIREMENT).AT
 LEAST 90 PERCENT OF THE SURFACE AREA OF ALL SCREEN
 ENCLOSURES SHALL BE SCREENING MATERIAL THROUGH WHICH
 AIR SHALL FLOW. ALL POOLS LOCATED ON A CORNER LOT SHALL
 BE SCREENED AT THE CORNER LOT LINE BY AT LEAST A
 42-INCH HIGH LANDSCAPE BUFFER, AS MEASURED FROM GRADE,
 AT THE PROPERTY LINE, TO ENSURE PRIVACY.
  
 AS THE SURVEY DOES NOT SHOW AN EXISTING FENCE
 SURROUNDING THE POOL, A FENCE PERMIT SHALL BE SUBMITTED
 CONCURRENTLY AND SHALL CONFORM TO THE MINIMUM STANDARDS
 PROVIDED ABOVE.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.
  
  