Plan Review Details - Permit 07040226
Plan Review Stops For Permit 07040226
Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2007-09-20 Cont ID  
Sent By shill Date 2007-09-20 Time 18:55 Rev Time 0.00
Received By shill Date 2007-09-20 Time 18:55 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2007-09-14 Cont ID  
Sent By shill Date 2007-09-14 Time 15:24 Rev Time 0.00
Received By shill Date 2007-09-14 Time 15:24 Sent To  
Notes
2007-08-23 10:02:08****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.)PLEASE REVISE ANCHOR SCHEDULE.A 3" EDGE DISTANCE
 REQUIRES A FACTOR OF .83, SEE SHEET 14 OF THE PRODUCT
 APPROVAL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2007-07-26 Cont ID  
Sent By shill Date 2007-07-26 Time 10:21 Rev Time 0.00
Received By shill Date 2007-07-26 Time 10:21 Sent To  
Notes
2007-07-26 10:21:58****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.)COMMENT FROM FIRST TWO LISTS, REVISE EXPOSURE
 CATEGORY. ON THE INSTALLATION SCHEDULE YOU'VE STATED
 THAT THIS IS EXPOSURE C BUT RAN WIND LOAD SOFTWARE AS
 EXPOSURE B. THE PRESSURES SHOULD BE OVER -40PSF.THE
 ANCHOR SPACING YOU HAVE SPECIFIED IS NOT COMPLIANT FOR
 EXPOSURE C.
  
 NEW COMMENT:
  
 2.)PROVIDE TWO IDENTIAL COLLATED SETS FOR PERMIT
 ISSUANCE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2007-07-06 Cont ID  
Sent By shill Date 2007-07-06 Time 10:11 Rev Time 0.00
Received By shill Date 2007-07-06 Time 10:11 Sent To  
Notes
2007-07-06 10:14:05****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)COMMENT FROM FIRST LIST, REVISE EXPOSURE CATEGORY.
 ON THE INSTALLATION SCHEDULE YOU'VE STATED THAT THIS IS
 EXPOSURE C BUT RAN WIND LOAD SOFTWARE AS EXPOSURE B.
 THE PRESSURES SHOULD BE OVER -40PSF.THE ANCHOR
 SPACING YOU HAVE SPECIFIED IS NOT COMPLIANT FOR
 EXPOSURE C.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2007-06-25 Cont ID  
Sent By shill Date 2007-06-25 Time 11:02 Rev Time 0.00
Received By shill Date 2007-06-25 Time 11:02 Sent To  
Notes
2007-06-25 11:03:58****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC*CITY OF WEST PALM BEACH AMENDMENTS TO THE
 FBC2004
 FACFLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTES
  
 1.)ANCHOR SPACING WAS LEFT BLANK ON THE INSTALLATION
 SCHEDULE.
  
 2.)TWO SETS OF ALL PERMIT DOCUMENTS REQUIRED.ONLY
 ONE INSTALLATION SCHEDULE WAS SUBMITTED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-06-11 Cont ID  
Sent By shill Date 2007-06-11 Time 15:52 Rev Time 0.00
Received By shill Date 2007-06-11 Time 15:52 Sent To  
Notes
2007-06-11 15:56:57****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
  
  
 1.)THE SHUTTER MOUNTING CONNECTION TYPE (A THROUGH L,
 PAGES 14-15) SHOULD REFER TO THE SPECIFIC CONNECTION
 TYPE FOR THAT OPENING (NOT THE ANCHOR).
  
 CONNECTION TYPES G AND H ARE CIRCLED ON THE PRODUCT
 APPROVAL.IT SHOULD BE ON THE INSTALLATION SCHEDULE,
 ESPECIALLY AS THE ANCHORING CIRCLED IS NOT CONSISTENT
 WITH THE ANCHORING ON THE SCHEDULE.
  
 2.)FLOOR MOUNT, H, REQUIRES 8.5" SPACING, BUT THE
 INSTALLATION SCHEDULE SPECIFIES 10" FOR THE BOTTOM
 TRACK.PLEASE COMPLETE THE INSTALLATION SCHEDULE (SEE
 ITEM 1 ABOVE) AND CONFIRM THAT ANCHOR SPACING ON THE
 SCHEDULE IS CONSISTENT WITH THE CONNECTION TYPE YOU ARE
 USING.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-05-03 Cont ID  
Sent By shill Date 2007-05-03 Time 16:40 Rev Time 0.00
Received By shill Date 2007-05-03 Time 16:40 Sent To  
Notes
2007-05-03 16:45:44****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 1.)SEE THE PRODUCT APPROVAL WHICH I HAVE HIGHLIGHTED
 (MARKED WITH A POST IT NOTE).SHUTTER MOUNTING
 CONNECTION TYPES A, G, AND H ARE FOR A POURED CONCRETE
 SUBSTRATE.YOU HAVE STATED THAT THIS IS CONCRETE
 BLOCK, SO YOU SHOULD BE USING CONNECTION TYPES FOR
 CONCRETE BLOCK (NOT POURED CONCRETE).
  
 2.)THE SHUTTER MOUNTING CONNECTION TYPE (A THROUGH L,
 PAGES 14-15) SHOULD REFER TO THE SPECIFIC CONNECTION
 TYPE FOR THAT OPENING (NOT THE ANCHOR).
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-04-18 Cont ID  
Sent By shill Date 2007-04-18 Time 17:32 Rev Time 0.00
Received By shill Date 2007-04-18 Time 17:32 Sent To  
Notes
2007-04-18 17:33:19****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 SHUTTER PERMIT APPLICATION, ONLY CHECKED ITEMS APPLY
  
 ____1.A NOTICE OF COMMENCEMENT MUST BE FILED WITH
 THE CLERK OF COURTS BEFORE A PERMIT CAN BE ISSUED,
 FS713.13.
  
 ____2.PROVIDE BUILDING HEIGHT ON THE PLAN.DESIGN
 PRESSURES FOR BUILDINGS OVER 60FEET ARE REQUIRED TO BE
 DESIGNED USING ASCE7, FBC1609.1.1 AND MUST BE DONE BY A
 DESIGN PROFESSIONAL. DOCUMENTS PREPARED BY AN ENGINEER
 AND SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED SEALED
 ORIGINALS FAC61G15-23.002.
  
 ____3.PROVIDE A COPY OF THE CONDO ASSOCIATION
 APPROVAL.
  
 _XX_4.COMPLETE THE ATTACHED INSTALLATION SCHEDULE
 OR PROVIDE ALL INFORMATION TO SHOW CODE COMPLIANCE IN
 ANOTHER FORMAT.
  
 ____5.FLORIDA STATE OR LOCAL PRODUCT APPROVAL
 REQUIRED, FAC9B72, WWW.FLORIDABUILDING.ORG.
  
 ____6.ON THE PRODUCT APPROVAL, MARK WHICH DETAILS
 APPLY TO THIS JOB.PLEASE USE INK RATHER THAN A
 HIGHLIGHTER.
  
 ____7.SHOW THE EMERGENCY MEANS OF ESCAPE, FBC
 R310.
  
 ____8.PROVIDE A FLOOR PLAN SHOWING WHERE THE
 SHUTTERS WILL BE INSTALLED AND PANEL SIZES WHICH
 CORRELATES WITH THE INSTALLATION SCHEDULE, ITEM 4
 ABOVE.
  
 _XX_9.REVISE EXPOSURE CATEGORY FBC1609.6.2.1(2),
 FBC R301.2.1.4.NOTE THAT THE DEFINITION FOR EXPOSURE
 C HAS CHANGED EFFECTIVE DECEMBER 8, 2006 FBC1609.4, FBC
 R301.2.1.4.
  

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2007-09-20 Cont ID  
Sent By adarroug Date 2007-09-20 Time 11:06 Rev Time 0.00
Received By adarroug Date 2007-09-20 Time 11:06 Sent To B
Notes
2007-09-20 11:06:44TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2007-09-13 Cont ID  
Sent By adarroug Date 2007-09-13 Time 16:53 Rev Time 0.00
Received By adarroug Date 2007-09-13 Time 16:53 Sent To B
Notes
2007-09-13 16:54:23TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-08-03 Cont ID  
Sent By adarroug Date 2007-08-03 Time 11:08 Rev Time 0.00
Received By adarroug Date 2007-08-03 Time 11:08 Sent To B
Notes
2007-08-03 11:08:37TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-07-13 Cont ID  
Sent By adarroug Date 2007-07-13 Time 15:34 Rev Time 0.00
Received By adarroug Date 2007-07-13 Time 15:34 Sent To B
Notes
2007-07-13 15:34:19TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-06-29 Cont ID  
Sent By adarroug Date 2007-06-29 Time 15:21 Rev Time 0.00
Received By adarroug Date 2007-06-29 Time 15:21 Sent To B
Notes
2007-06-29 15:21:33TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-06-19 Cont ID  
Sent By adarroug Date 2007-06-19 Time 14:09 Rev Time 0.00
Received By adarroug Date 2007-06-19 Time 14:09 Sent To B
Notes
2007-06-19 14:09:42TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-05-21 Cont ID  
Sent By adarroug Date 2007-05-21 Time 09:55 Rev Time 0.00
Received By adarroug Date 2007-05-21 Time 09:55 Sent To B
Notes
2007-05-21 09:55:45TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-05-02 Cont ID  
Sent By adarroug Date 2007-05-02 Time 16:01 Rev Time 0.00
Received By adarroug Date 2007-05-02 Time 16:01 Sent To B
Notes
2007-05-02 16:01:20TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-05-02 Cont ID  
Sent By adarroug Date 2007-04-18 Time 16:00 Rev Time 0.00
Received By adarroug Date 2007-04-06 Time 17:24 Sent To  
Notes
2007-04-06 17:24:25TO MISC # 1