2007-04-06 15:02:07 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBCFLORIDA BUILDING CODE 2004 |
| FBC EBFLORIDA BUILDING CODE 2004 |
| EXISTING BUILDING CODE |
| FBC*CITY OF WEST PALM BEACH |
| AMENDMENTS TO THE FBC2004 |
| |
| ROOFING PERMIT; ONLY CHECKED ITEMS APPLY |
| |
| ____1.)A NOTICE OF COMMENCEMENT MUST BE FILED WITH |
| THE CLERK OF COURTS PRIOR TO PERMIT PICKUP, FS713.13. |
| |
| ____2.)CONTRACTOR IS TO PROVIDE THE FOLLOWING |
| INFORMATION ON THE APPLICATION, SEE ATTACHED POLICY: |
| |
| MEAN ROOF HEIGHT |
| ROOF PITCH |
| ROOF DECK TYPE |
| AREA OF EACH ROOF TYPE |
| |
| _XX_3.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL |
| REQUIRED, FAC9B72.WWW.FLORIDABUILDING.ORGTHE TILE |
| PRODUCT APPROVAL IS "APPLIED FOR".A LOCAL PRODUCT |
| APPROVAL WILL BE ISSUED IF THE APPLICATION IS NOT |
| "APPROVED" WHEN RESUBMITTING.THIS COMMENT DOES NOT |
| NEED TO BE ADDRESSED. |
| |
| ____4.)FOR THE FLAT DECK, SELECT THE APPROVED |
| ASSEMBLY YOU ARE USING.ALSO INDICATE WHICH FASTENER |
| YOU ARE USING IF THE OPTIONS HAVE DIFFERENT PRESSURE |
| LIMITATIONS. |
| |
| ____5.)FOR THE FLAT DECK, SPECIFY THE ENHANCED |
| FASTENING FOR CORNER AND PERIMETER ZONES. |
| |
| _XX_ 6.)ON THE TILE PRODUCT APPROVAL, INDICATE WHICH |
| METHOD OF ATTACHMENT YOU ARE USING. |
| |
| _XX_ 7.)TWO COMPLETE SETS OF ALL DOCUMENTS REQUIRED. |