Plan Review Details - Permit 07040128
Plan Review Stops For Permit 07040128
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-09-28 Cont ID  
Sent By mjacobs Date 2007-09-28 Time 06:45 Rev Time 0.00
Received By mjacobs Date 2007-09-28 Time 06:12 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-05-29 Cont ID  
Sent By mjacobs Date 2007-05-29 Time 07:22 Rev Time 0.00
Received By mjacobs Date 2007-05-29 Time 06:58 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-04-13 Cont ID  
Sent By mjacobs Date 2007-04-13 Time 11:50 Rev Time 0.00
Received By mjacobs Date 2007-04-13 Time 11:03 Sent To  
Notes
2007-04-13 11:50:18BUILDING PLAN REVIEW
 PERMIT: 07040128
 ADD: 1617 N. FLAGLER DR. APT, 9A
 CONT: RICKEY J. WILSON CONST. INC.
 TEL: (561)###-####
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)106.1IF THE DESIGN PROFESSIONAL IS AN ARCHITECT
 OR ENGINEER LEGALLY REGISTERED UNDER THE LAWS OF THIS
 STATE REGULATING THE PRACTICE OF ARCHITECTURE AS
 PROVIDED FOR IN CHAPTER 481, FLORIDA STATUTES, PART 1,
 OR ENGINEERING AS PROVIDED FOR IN CHAPTER471, FLORIDA
 STATUTES, THEN HE OR SHE SHALL AFFIX HIS OR HER
 OFFICIAL SEAL, SIGNATURE AND DATE TO SAID DRAWINGS.
  
 3)108.3*THE CLAIMED VALUATION ON THE PERMIT
 APPLICATION IS LOW. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT
 COST EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS
 ICC (BVD) MARSHALL-SWIFT AND MEANS COST ANALYSIS
 SERVICES.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-10-10 Cont ID  
Sent By btrobaug Date 2007-10-10 Time 11:12 Rev Time 0.00
Received By btrobaug Date 2007-10-10 Time 10:48 Sent To PC
Notes
2007-10-10 11:02:27 
  
 CANNOT FIND FILE COPY.PER LUIS, REVIEWED FOR CODE
 COMPLIANCE AND CALLED FOR PICK UP./WRT.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-05-10 Cont ID  
Sent By btrobaug Date 2007-05-10 Time 16:31 Rev Time 0.50
Received By btrobaug Date 2007-05-10 Time 16:19 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-04-16 Cont ID  
Sent By btrobaug Date 2007-04-16 Time 17:02 Rev Time 0.50
Received By btrobaug Date 2007-04-16 Time 16:41 Sent To  
Notes
2007-04-16 17:02:30 
  
 NONCOMPLIANT
  
 THE ARCHITECTURAL FIRM WHOSE TITLE BLOCK APPEARS ON THE
 PLANS, MUST SIGN AND SEAL THE PLAN PER
 481.221(1)(B)FS.
  
 1} R313.1.1 SMOKE ALARMS SHALL BE LOCATED AS REQUIRED
 IN NEW DWELLINGS WHEN REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR. SEE ARTICLE FOR COMPLETE TEXT.
  
 2} NFPA-72 REQUIRES ALARMS OR DETECTORS WITHIN 20 FEET
 OF COOKING APPLIANCES BE SILENCING OR PHOTOELECTRIC.
 SEE 11.8.3.5(4).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-05-16 Cont ID  
Sent By mwennerg Date 2007-05-16 Time 15:23 Rev Time 0.00
Received By mwennerg Date 2007-05-16 Time 15:23 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-04-13 Cont ID  
Sent By mwennerg Date 2007-04-13 Time 14:04 Rev Time 0.00
Received By mwennerg Date 2007-04-13 Time 14:04 Sent To  
Notes
2007-04-13 14:08:15***DENIED***
  
 1) PLANS ARE REQUIRED TO BE SIGNED, SEALED AND DATED BY
 DESIGN PROFESSIONAL IN ACCORDANCE WITH FLORIDA
 STATUTES.
  
 2) PLEASE PROVIDE INFORMATION REGARDING HOW MANY FIRE
 SPRINKLER HEADS WILL BE IMPACTED BY THIS WORK. SEPARATE
 SHOP DRAWINGS AND PERMIT MAY BE REQUIRED.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-09-17 Cont ID  
Sent By adarroug Date 2007-09-17 Time 11:53 Rev Time 0.00
Received By adarroug Date 2007-09-17 Time 11:53 Sent To  
Notes
2007-09-24 15:51:43TO "BOB"#7
2007-09-17 11:53:26WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-05-03 Cont ID  
Sent By adarroug Date 2007-05-03 Time 16:17 Rev Time 0.00
Received By adarroug Date 2007-05-03 Time 16:17 Sent To  
Notes
2007-05-07 13:19:24TO "BOB"#5
2007-05-03 16:17:55WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2007-04-20 Time   Rev Time 0.00
Received By spalmer Date 2007-04-05 Time 17:39 Sent To  
Notes
2007-04-05 17:39:58TO BOB # 8

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-05-14 Cont ID  
Sent By jleech Date 2007-05-14 Time 09:12 Rev Time 0.00
Received By jleech Date 2007-05-14 Time 09:12 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-04-09 Cont ID  
Sent By jleech Date 2007-04-09 Time 09:13 Rev Time 0.00
Received By jleech Date 2007-04-09 Time 09:13 Sent To  
Notes
2007-04-09 09:22:00DENIED;
 PLANS ARE REQUIRED TO BE SEALED SIGNED AND DATED BY THE
 DESIGN PROFESSIONAL. SEE CHAPTER 481 FLORIDA STAUTES
 PART 1.
 PLUMBING PLAN REVIEW OK. WILL STAMP WHEN PLANS ARE
 SIGNED AND SEALED.
 PLUMBING PLAN REVIEW BY
 JOHN LEECH
 805-6695