Plan Review Details - Permit 07040094
Plan Review Stops For Permit 07040094
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-05-14 Cont ID  
Sent By shill Date 2008-05-14 Time 15:15 Rev Time 0.00
Received By shill Date 2008-05-13 Time 13:55 Sent To  
Notes
2008-05-14 15:40:13****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 COMMENTS FROM PREVIOUS LIST:
  
 1. NOTE CORRECTION SUBMITTAL
 WHEN RE-SUBMITTING CORRECTED PLANS FOR PERMITTING,
 PLEASE REMOVE AND REPLACE ANY SHEETS AS NECESSARY.
 INCLUDE A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER WITH A DESCRIPTION OF THE
 REVISION MADE. IDENTIFY THE SHEET OR SPECIFICATION
 PAGE
 WHERE THE CHANGES CAN BE FOUND AND INCLUDE THE OLD
 SHEETS IN THE RE-SUBMITTAL PACKAGE FOR THE PLAN
 REVIEWER'S REFERENCE.
 THIS SHALL HELP TO EXPEDITE YOUR PERMIT. THANK YOU
 FOR
 YOUR ANTICIPATED COOPERATION.
  
 2. F.S. 713.13 NOTICE OF COMMENCEMENT
 FILE NOTICE WITH THE CLERK OF COURT RECORDING
 DIVISION.
 IF THE WORK DESCRIBED IN THE NOTICE IS NOT COMMENCED
  
 WITHIN 90 DAYS OF FILING THE NOTICE WILL BECOME NULL
  
 AND VOID. SUBMIT THE NOTICE AT THE TIME OF PERMIT
 ISSUANCE AND POST A COPY AT THE JOB SITE BEFORE THE
 FIRST INSPECTION.
  
 3. NOTES SHEET 2.1
  
 (A) ADDRESSED.
  
 (B) PROJECT INFORMATION - PLEASE COMPLETE ON PLAN
 INFORMATION
 CONSTRUCTION TYPE
  
 3RD REVIEW, TYPE DECLARED IS TYPE II, BUT DETAILS SHOW
 WOOD TRUSSES.NO INFORMATION PROVIDED REGARDING THE
 EXISTING OFFICE BUILDING, SEE FBC503.1.3.
  
 OCCUPANT LOAD
  
 3RD REVIEW, SEE FBC 1004, OCCUPANT LOAD CANNOT BE LESS
 THAN FBC TABLE 1004.2.1.
  
 OTHER INFORMATION WAS REQUESTED AND PROVIDED, BUT DUE
 TO INCORRECT/INCOMPLETE INFORMATION, CODE COMPLIANCE
 CANNOT BE DETERMINED.COMPLETE INFORMATION REGARDING
 THE TWO BUILDINGS MUST BE PROVIDED AS WELL AS
 INFORMATION REGARDING HOW YOU ARE COMPLYING WITH FBC
 TABLE 601, FBC TABLE 602, FBC TABLE 503, FBC TABLE
 704.8.WITHOUT ALL INFORMATION REQUIRED, CODE
 COMPLIANCE CANNOT BE DETERMINED.NO INFORMATION
 REGARDING HOW THIS PROJECT COMPLIES WAS PROVIDED.SEE
 FIRST COMMENT LIST, ALL CALCULATIONS REGARDING ANY AREA
 INCREASES ARE TO BE ON THE PLAN.NO AREA INCREASES
 WERE TAKEN BUT THE WRONG BUILDING TYPE DECLARED.NOT
 ENOUGH INFORMATION PROVIDED TO DETERMINE CODE
 COMPLIANCE.
  
  
 FBC 501.2 PREMISES IDENTIFICATION.
 3RD REVIEW, PLEASE NOTE THAT THIS WAS ADDRESSED AS
 REQUESTED.HOWEVER, CITY OF WEST PALM BEACH MUNICIPAL
 CODE 78-6(1) AND ALSO NFPA 101/FLORIDA FIRE PREVENTION
 CODE REQUIRE 6IN HIGH, 1IN WIDE MINIMUM.PLEASE NOTE
 THAT HAD ALL OTHER ITEMS BEEN ADDRESSED, THIS WOULD
 HAVE BEEN A REDLINE/PROVISO ITEM.
  
 FBC 602.2 TYPES I AND II.
 TYPE I AND II CONSTRUCTION ARE THOSE TYPES OF
 CONSTRUCTION IN WHICH THE BUILDING ELEMENTS LISTED
 IN
  
 TABLE 601 ARE OF NONCOMBUSTIBLE MATERIALS.
  
 3RD REVIEW, WOOD TRUSSES SHOWN; TYPE II IS TO BE
 NONCOMBUSTIBLE.ALSO A OR B MUST BE DECLARED AND ANY
 FIRE RESISTANCE RATINGS REQUIRED SHOWN ON THE PLAN, FBC
 TABLE 601.NO INFORMATION PROVIDED IN REGARDS TO
 EXISTING OFFICE BUILDING; SEE OTHER COMMENTS.
  
 COMMENT 3D) FBC 11-4.1.6 II ACCESSIBLE BUILDINGS -
 ALTERATIONS
 PLANS DO NOT INDICATE OR IDENTIFY THE ACCESSIBLE
 ENTRANCE INTO THE BUILDING. PLANS INDICATE A 4?IN
 DIFFERENCE IN ELEVATION AT ENTRANCES FROM PARKING AREA
 TO UNIT SPACES.
  
 3RD REVIEW, PLAN STILL SHOW A 4IN ELEVATION CHANGE AT
 THE RAMP, SHEET 2.1, EAST SIDE.SEE OTHER COMMENTS
 REGARDING ACCESSIBLE ROUTE.
  
 11-4.3.1-. ALL WALKS/HALLS/CORRIDORS SHALL BE
 ACCESSIBLE
  
 3E.FBC 1210.1 AND 1210.2 FLOORS / WALLS
 URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD,
  
 NON-ABSORBENT SURFACE
  
 3RD REVIEW, DRYWALL SHOWN ON THE PLAN.THIS IS NOT A
 HARD NON-ABSORBENT SURFACE.
  
 3.
 B) USE AND OCCUPANCY COMPLETE INFORMATION
 C) TYPE OF CONSTRUCTION
 E) SPRINKLER SYSTEM REQUIREMENT
  
 3RD REVIEW, NOT COMPLETELY ADDRESSED.PLEASE SEE OTHER
 COMMENTS.
  
 4. FBC EXISTING 812.4.2
 HAZARD CATEGORIES IN REGARD TO HEIGHT AND AREA SHALL
 BE
 IN ACCORDANCE WITH TABLE 812.4.2.
 SEE TABLE FOR CLASSIFICATIONS
  
 I WAS UNABLE TO LOCATE WHERE THIS WAS ADDRESSED ON THE
 PLAN.PLEASE ADVISE.ALSO IT IS NOT CLEAR IF YOU ARE
 TREATING THIS AS ONE BUILDING OR TWO BUILDINGS WITH AN
 ASSUMED PROPERTY LINE, FBC503.1.3.
  
 5. WALL INSULATION VALUES ON ENERGY
 CALCULATIONS DOT NOT MATCH PLAN
  
 3RD REVIEW, INPUT DATA REPORT FOR ENERGY CALCS NOT
 INCLUDED.INCOMPLETE INFORMATION; NO REVIEW CAN BE
 DONE AT THIS TIME.
  
 ROOFING SYSTEM TAMKO, HIGHLIGHT SYSTEM USED
 AND MATCH ENERGY CALCULATIONS FOR SPECIFIED
 MATERIALS
  
 IN SYSTEM
  
 3RD REVIEW, A SYSTEM WAS SELECTED BUT REQUIRES
 ENGINEERING FOR THE ENHANCED FASTENING FOR ZONES 2 AND
 3.THIS MAY BE PROVIDED AT THIS TIME OR AT THE TIME OF
 ROOF PERMIT APPLICATION (PROVISO ITEM).
  
 NOTE THAT A PRELIMINARY REVIEW WAS DONE ON THE NOA
 SUBMITTED, BUT IF THIS BUILDING IS A TYPE II, WOOD DECK
 CANNOT BE USED AND THE APPROPRIATE NOA SUBMITTED.
  
 6-7.ADDRESSED.
  
 8.FURNISH TRUSS ENGINEERED DRAWINGS FOR REVIEW
  
 THIS WAS REQUESTED BY PREVIOUS PLANS EXAMINER AND NOT
 ADDRESSED.THIS PERMIT MAY BE ISSUED WITH A PROVISO
 THAT THEY BE SUBMTTED FOR REVIEW PRIOR TO INSTALLATION,
 BUT THERE ARE OTHER ISSUES WITH THE ROOF FRAMING PLAN.
 IT IS NOT CLEAR ON SHEET 5.1 WHERE I AND J ARE TO BE
 INSTALLED. WHAT DO THE ARROWS ON THE TIE DOWN SCHEDULE
 MEAN?WHY ARE THE COLUMNS FOR CALCULATED LATERAL LOAN
 BLANK?IF ARROWS INDICATE THE ONES TO BE USED, WHY ARE
 THEY BLANK BUT OTHER CONNECTORS HAVE DATA?PROVIDE
 DESIGN LOAD CRITERIA (WIND UPLIFT, LATERAL) WITH
 CALCULATIONS.
  
 NEW COMMENTS (A RESULT OF PLAN CHANGES WHEN ADDRESSING
 PREVIOUS COMMENTS):
  
 9.SHEET 3.1 SHOWS AN ACUSTIC CEILING.DO YOU MEAN
 ACOUSTIC?THE CEILING SPECIFIED ON 6.1 IS A HUNG
 CEILING, BUT THAT IS NOT WHAT IS SHOWN GRAPHICALLY ON
 WALL SECTIONS; THEY ARE SHOWN AS ATTACHED TO THE
 TRUSSES.PLEASE CLARIFY; PROVIDE A SPECIFICATION FOR
 ATTACHMENT.
  
 10.FBC1008.1.8, THE HANDRAIL TO THE RAMP OBSTRUCTS
 THE DOOR SWING.PLEASE EXPLAIN LOGIC OF HAVING A DOOR
 BLOCKING THE CORRIDOR TO THE REQUIRED EXIT, SEE SHEET
 6.1.
  
 11.THE BUILDING IS NOTED AS FULLY SPRINKLERED, NO
 FIRE ALARM NOTES.SEE FBC11-4.28 AND SHOW REQUIRED
 ALARMS IN AREAS SPECIFIED (SUCH AS BATHROOMS).
  
 12.SEE OTHER TRADES? COMMENTS REGARDING ENERGY CALCS.
 ALL BUILDING COMPONENTS TO BE INCLUDE.THE SQUARE FOOT
 AREA DOES NOT MATCH PLAN.ENERGY CALCS ARE TO BE
 PREPARED BY A DESIGN PROFESSIONAL, NOT CLEAR WHO HAS
 SIGNED THIS.PROVIDE A SEAL AND PRINTED NAME.
  
 13.SHEET 2.1, CLARIFY WALL FINISH SHOWN AS VINYL
 COMPOSITE TILE; APPEARS TO BE FLOORING.
  
 14.SPRINKLER PLANS ARE REQUIRED IF SPRINKLERS ARE
 REQUIRED FOR CODE COMPLIANCE.
  
 15.SHEET 2.1, A NOTE WAS ADDED STATING THAT THIS
 BUILDING IS A SEPARATE BUILDING FROM THE EXISTING
 BUILDING.ANY TIME THAT AN ADDITIONAL STRUCTURE IS
 ADDED TO A PARCEL, CODE COMPLIANCE FOR THE NEW
 STRUCTURE AS WELL AS THE EXISTING STRUCTURE MUST BE
 SHOWN.THE EXISTING STRUCTURE WAS REVIEWED FOR CODE
 COMPLIANCE REGARDING DISTANCE TO THE PROPERTY LINE,
 SIZE, ETC.ADDING ANOTHER STRUCTURE TO THE PARCEL
 CHANGES THE HAZARD TO THE EXISTING BUILDING.
  
 16.SHEET 2.1, DEAD END REFERENCE INCORRECT.
  
 17.SHEET 2.1, IT APPEARS THAT YOU ARE USING DESIGN
 CRITERIA FOR A FULLY SPRINKLERED BUILDING.SEE OTHER
 COMMENTS; IF SPRINKLERS ARE REQUIRED FOR CODE
 COMPLIANCE SPRINKLER PLANS MUST BE PROVIDED PRIOR TO
 PERMIT ISSUANCE.THIS HAS BEEN VERIFIED BY A
 DECLARATORY STATEMENT FROM THE STATE,
 FBC*106.3.5.1.1(5), FS553.79 (2).
  
 18. SHEET 2.1, SQUARE FOOT AREA 4184, DOES NOT MATCH
 OCCUPANT LOAD SQUARE FOOT AREA (2396 AND 1617), AND
 DOES NOT MATCH ENERGY CALCS 4023.
  
 19. SHEET 2.1, CORRIDOR FIRE RESISTANCE RATING PER FBC
 TABLE 1016.1, REQUIREMENTS NOT CLEAR AS A FULLY
 SPRINKLERED BUILDING WAS DECLARED, BUT NO INFORMATION
 PROVIDED REGARDING THE OTHER BUILDING OR WHETHER THIS
 WILL BE A SEPARATE BUILDING WITH AN ASSUMED PROPERTY
 LINE, AND NO FIRE SPRINKLER PLANS PROVIDED.
  
 20.MAXIMUM DEAD END, SHEET 2.1, WRONG CODE
 REFERENCE.
  
 21.EXITING FROM THE OTHER BUILDING AND HOW ACCESSIBLE
 EXITING HAS BEEN AFFECTED IS NOT CLEAR.IS THE ROUTE
 THROUGH THE NEW BUILDING TO THE PUBLIC WAY ALSO AN
 ACCESSIBLE EXIT FOR THE OTHER BUILDING, OR DOES IT HAVE
 EXITS ON THE OTHER SIDE OF THE BUILDING?IT APPEARS
 THAT THE EXISTING BUILDING CURRENTLY HAS AN ACCESSIBLE
 ROUTE TO THE PUBLIC WAY THROUGH THE EXISTING PARKING
 LOT.THIS IS NOW BLOCKED BY THE NEW BUILDING, UNLESS
 THEY USE THE CORRIDOR THROUGH THE NEW BUILDING.NO
 FIRE RESISTANCE RATING SHOWN, BUT MAY BE REQUIRED.
  
 22.THE NOTE REGARDING MAXIMUM TRAVEL ON SHEET 2.1 IS
 NOT CLEAR.IT STATES 85FEET PER NOTE D, TABLE 1018.2.
 THIS TABLE IS FOR BUILDINGS WITH ONE EXIT, AND NOTE D
 IS APPLICABLE FOR BUSINESS OCCUPANCY, BUT THE NEW
 BUILDING IS M AND S1 OCCUPANCY.AND, NOTHING ON THE
 TABLE SPECIFIES 85FEET.
  
 23. (FROM PREVIOUS LIST)FBC 1609.1.4 IMPACT
 PROTECTION FOR GLAZED OPENINGSTHIS WILL REQUIRE A
 SHUTTER PERMIT AND PRODUCT
 APPROVALS SUBMITTED
  
 USE OF REMOVABLE SHUTTERS ON COMMERCIAL BUILDINGS MUST
 BE APPROVED BY THE BUILDING OFFICIAL.SEE ATTACHED
 POLICY, ITEM 13.A PLAN INCLUDING ALL INFORMATION
 REFERENCED MUST BE SUBMITTED. THIS MAY BE DONE PRIOR TO
 RESUBMITTAL OF THE BUILDING PERMIT PLANS FOR
 PRELIMINARY REVIEW, [email protected] TO HAVE
 THE PRE STORM PREPARATION PLAN APPROVED PRIOR TO
 RESUBMITTAL OF THE PERMIT PACKAGE MAY RESULT IN DELAYS
 IN PERMITTING.
  
 SEE PREVIOUS LIST, IMPACT PROTECTION REQUIRED
 FBC1609.1.4.IF USE OF SHUTTERS IS PROPOSED, ATTACHED
 INSTALLATION SCHEDULE MUST BE COMPLETED.
  
 24.THE COMMENT REGARDING IMPACT FEES WAS ADDRESSED.
 PLEASE KEEP THE STAMPED PLAN AND THE RECEIPT IN THE
 PACKAGE.
  
 25.DETAIL 3 3.1 SHOWS A CEILING OVER NEW HALL.
 SPECIFY THE NEW CEILING, FBC*106.
  
 26.DETAIL 4 4.1 TEST STATES THAT A 1 ? IN WATERSTOP
 WILL BE INSTALLED; NONE SHOWN.
  
 27. DETAIL 7 4.1 SHOWS A FLASHING DETAIL AT A FRAME
 WALL.TYPE II IS DECLARED.WHERE WILL THIS BE
 INSTALLED?
  
 28.A VALUE ADJUSTMENT WAS DONE USING ICC TABLES. THIS
 VALUE MAY CHANGE PENDING CORRECT INFORMATION ON PLANS.
 (BUILDING TYPE, SQUARE FOOT AREA)
  
 29.SHEET 5.1, CLARIFY ROOF DRAIN CALCULATIONS.SEE
 PLUMBING COMMENTS REGARDING CALCULATIONS AND ROOF
 DRAINAGE.ALSO SHOW PARAPET DIMENSION ON THE PARAPET
 WALL DETAIL.
  
 30.ROOF COMPONENTS AND CLADDING DESIGN PRESSURES
 REQUIRED, FBC1603.1.4.
  
 31.SEE ATTACHED FS553.80(2)(B).A 4X PLAN REVIEW
 WILL BE CHARGED IF COMMENTS ARE NOT PROPERLY ADDRESSED
 A THIRD TIME.A FEE MAY BE ASSESSED AT THIS TIME AS
 SOME COMMENTS ARE FROM THE FIRST LIST.A SET HAS BEEN
 RETAINED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-09-18 Cont ID  
Sent By jjohnsto Date 2007-09-18 Time 12:13 Rev Time 3.50
Received By jjohnsto Date 2007-09-18 Time 07:45 Sent To  
Notes
2007-09-18 12:12:53CONSTRUCTION SERVICES DEPARTMENT
 200 SECOND STREET, 3RD FLOOR, WEST PALM BEACH,
 FLORIDA33401
 TEL:561-805-6713FAX:
 561-805-6731
  
 JAMES JOHNSTON,CBO PERMIT NO 07040094
 BUILDING PLAN EXAMINERII PROJECT GRATITUDE
 GUILD, INC.
 E-MAIL:JJOHNSTON @WPB.ORG ADDRESS 1700 NORTH
 DIXIE HIGHWAY CONTRACTOR FRED BLAU &
 ASSOCIATES
  DATE SEPTEMBER18, 2007
  
  
 STRUCTURALPLANREVIEW
  
 1. NOTE CORRECTION SUBMITTAL
 WHEN RE-SUBMITTING CORRECTED PLANS FOR PERMITTING,
 PLEASE REMOVE AND REPLACE ANY SHEETS AS NECESSARY.
 INCLUDE A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER WITH A DESCRIPTION OF THE
 REVISION MADE. IDENTIFY THE SHEET OR SPECIFICATION PAGE
 WHERE THE CHANGES CAN BE FOUND AND INCLUDE THE OLD
 SHEETS IN THE RE-SUBMITTAL PACKAGE FOR THE PLAN
 REVIEWER?S REFERENCE.
 THIS SHALL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2. F.S.713.13NOTICE OF COMMENCEMENT
 FILE NOTICE WITH THE CLERK OF COURT RECORDING DIVISION.
 IF THE WORK DESCRIBED IN THE NOTICE IS NOT COMMENCED
 WITHIN 90 DAYS OF FILING THE NOTICE WILL BECOME NULL
 AND VOID. SUBMIT THE NOTICE AT THE TIME OF PERMIT
 ISSUANCE AND POST A COPY AT THE JOB SITE BEFORE THE
 FIRST INSPECTION.
  
 3. NOTESSHEET 2.1
  
 (A) CODES
 FLORIDA BUILDING CODE2004 WITH 2005 AND 2006
 REVISIONS
 FLORIDA BUILDING CODE EXISTING BUILDINGWITH 2005 AND
 2006 REVISIONS
 WEST PALM BEACH AMENDMENTS
  
 (B) PROJECT INFORMATION?PLEASE COMPLETE ON PLAN
 INFORMATION?
 CONSTRUCTION TYPE
 LEVEL OF ALTERATION III
 OCCUPANCY M / ?IDENTIFY THE STORAGE SPACE
 USING FBCCHPT. 311.1
 OCCUPANT LOAD
 OCCUPANT LOAD
 NUMBER OF FLOORS 2
 FIRST FLOOR S.F.
 SECOND FLOOR S.F.
 TOTAL EXISTING S.F.
  
  
  
  
 FBC 501.2 PREMISES IDENTIFICATION.
 APPROVED NUMBERS OR ADDRESSES SHALL BE PROVIDED FOR NEW
 BUILDINGS IN SUCH A POSITION AS TO BE CLEARLY VISIBLE
 AND LEGIBLE FROM THE STREET OR ROADWAY FRONTING THE
 PROPERTY. LETTERS OR NUMBERS SHALL BE A MINIMUM 3
 INCHES (76 MM) IN HEIGHT AND STROKE OF MINIMUM 0.5 INCH
 (12.7 MM) OF A CONTRASTING COLOR TO THE BACKGROUND
 ITSELF.
  
 FBC 602.2 TYPES I AND II.
 TYPE I AND II CONSTRUCTION ARE THOSE TYPES OF
 CONSTRUCTION IN WHICH THE BUILDING ELEMENTS LISTED IN
 TABLE 601 ARE OF NONCOMBUSTIBLE MATERIALS.
  
  
 COMMENT3D) FBC 11-4.1.6 IIACCESSIBLE BUILDINGS -
 ALTERATIONS
 PLANS DO NOT INDICATE OR IDENTIFY THE ACCESSIBLE
 ENTRANCE INTO THE BUILDING. PLANS INDICATE A 4?
 DIFFERENCE IN ELEVATION AT ENTRANCES FROM PARKING AREA
 TO UNIT SPACES.
 FBC 11-4.2??.SPACE ALLOWANCE AND REACH RANGES FBC
 11-4.3.1?.ALL WALKS/HALLS/CORRIDORS SHALL BE
 ACCESSIBLE
 FBC11-4.3.8?CHANGES IN LEVELS ALONG ACCESSIBLE
 ROUTE
 FBC11-4.1.3 (10)DRINKING FOUNTAIN MUST COMPLY WITH
 ACCESSIBILITY CODE
  
 COMMENT3E)FBC1210.1AND 1210.2 FLOORS / WALLS
 URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD,
 NON-ABSORBENT SURFACE
  
 COMMENTS 3 )
 B)USE AND OCCUPANCYCOMPLETE INFORMATION
 C) TYPE OF CONSTRUCTION
 E)SPRINKLER SYSTEM REQUIREMENT
  
 DEFINE STORAGE AREA TYPE S-1 OR S-2
 311.1 STORAGE GROUP S.
 STORAGE GROUP S OCCUPANCY INCLUDES, AMONG OTHERS, THE
 USE OF A BUILDING OR STRUCTURE, OR A PORTION THEREOF,
 FOR STORAGE THAT IS NOT CLASSIFIED AS A HAZARDOUS
 OCCUPANCY.
 311.2 MODERATE-HAZARD STORAGE, GROUP S-1.
 311.3 LOW-HAZARD STORAGE, GROUP S-2.
  
 COMMENT 4)FBC EXISTING812.4.2
 HAZARD CATEGORIES IN REGARD TO HEIGHT AND AREA SHALL BE
 IN ACCORDANCE WITH TABLE 812.4.2 .
 SEE TABLE FOR CLASSIFICATIONS
  
 COMMENT 5) WALL INSULATION VALUES ON ENERGY
 CALCULATIONS DOT NOT MATCH PLAN
  ROOFING SYSTEM TAMKO, HIGHLIGHT SYSTEM USED
 AND MATCH ENERGY CALCULATIONS FOR SPECIFIED MATERIALS
 IN SYSTEM
  
 FBC 1609.1.4IMPACT PROTECTION FOR GLAZED OPENINGS
 THIS WILL REQUIRE A SHUTTER PERMIT AND PRODUCT
 APPROVALS SUBMITTED
  
  
 F.S.713.13NOTICE OF COMMENCEMENT
 FILE NOTICE WITH THE CLERK OF COURT RECORDING DIVISION.
 IF THE WORK DESCRIBED IN THE NOTICE IS NOT COMMENCED
 WITHIN 90 DAYS OF FILING THE NOTICE WILL BECOME NULL
 AND VOID. SUBMIT THE NOTICE AT THE TIME OF PERMIT
 ISSUANCE AND POST A COPY AT THE JOB SITE BEFORE THE
 FIRST INSPECTION.
  
  
  
  
 IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT MAY BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY.
 THE PERMITTED SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 PALM BEACH COUNTY ASSESSMENT
 PALM BEACH COUNTY IMPACT FEE ASSESSMENT HAS MOVED TO:
 2300 N JOG ROAD, SUITE 2 WPB 33411
  
 COMMENT 5)WINDOWS / DOORS PRODUCT APPROVALS
 WPB ADMINISTRATIVE CODE 106.3 REGULATED BY DCA RULE
 9B-72FLORIDA PRODUCT APPROVAL
 SUBMIT TWO COPIES OF EACH APPROVAL WITH FLORIDA PRODUCT
 APPROVAL COVER SHEET THE ARCHITECT?S / ENGINEER?S
 SIGNATURE AS APPLICABLE, STATING ?TO THE BEST OF THEIR
 KNOWLEDGE THE PRODUCT APPROVAL COMPLIES WITH THE PLANS
 AND SPECIFICATIONS.SEE:WEB SITE
 WWW.FLORIDABUILDING.COM
 NOTE: SEE DIVISION FACTOR TO BE USED IN DESIGN PRESSURE
 BY LEGACYFPA
  
 PRODUCT APPROVALS
 OUT SWING STEEL DOOR FLORIDA PRODUCT APPROVAL
 MANUFACTURER IS SUBMITTED AS JELD-WEN
 MIAMI-DADE PRODUCT APPROVAL NOTICES DOOR- CRAFT THE
 ENGINEER OF RECORD DID NOT STAMP HIS ACCEPTANCE ON THE
 MIAMI-DADE PRODUCT APPROVAL
 STORM PANEL PRODUCT APPROVAL ONLY ONE COPY SUBMITTED
 ALSO IDENTIFY WHICH SHUTTER IS BEING USED
 PLEASE REVIEW EACH PRODUCT APPROVAL, ACKNOWLEDGE EACH
 PRODUCT APPROVAL AS BEING ACCEPTED FOR THIS PROJECT AND
 IDENTIFY WHICH PRODUCT IS BEING USED
  
 DETAIL 3-3.1 IDENTIFIES THE FOOTING TO BE PLACED IN THE
 EXISTING SLAB, HOW WILL THE EXISTING FOOTING BE
 ATTACHED TO ITSELF AFTER IT IS ISOLATED BY THE NEW
 FOOTING?
  
 FURNISH TRUSS ENGINEERED DRAWINGS FOR REVIEW

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-06-11 Cont ID  
Sent By jwitmer Date 2007-06-11 Time 12:45 Rev Time 3.33
Received By jwitmer Date 2007-06-11 Time 10:49 Sent To PC
Notes
2007-06-11 16:25:16BUILDING PLAN REVIEW
 PERMIT: 07040094
 ADD: 1700 N DIXIE HWY
 CONT: FRED BLAU & ASSOC
 TEL: (561)309-7638
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2 ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2)IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3 ) 110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OF THE CODE UNDER WHICH
 THE PROJECT ISDESIGNED.
 NOTE: THE 2004 FBC W/ 2006REVISIONS ALSO SEE 2006
 EXISTING BUILDING CODE, PROVIDE WHAT LEVEL OF
 ALTERATION TO BE COMPLETED UNDER THIS PERMIT.
 SEE CHAPTER 6 FOR LEVEL II ALTERATIONS
 AND CHAPTER 8 FOR CHANGE IN OCCUPANCY.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 NOTE THIS WILL BE FOR THE COMPLETE BUILDING
 (FOOTPRINT) , CONSISTING OF A 7,061 SQ FT TWO STORY,
 1,973 SQ FT CONCRETE PASS THROUGH AND 11,245 SQ FT
 RENOVATION TO BE
 COMPLETED UNDER THIS PERMIT.SEE DEFINITION OF
 BUILDING AREA, (FOOTPRINT). PROVIDE ANY AREA INCREASES
 IF TAKEN, PROVIDE CALCULATIONS.
 D) THE OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
 G)NUMBER OF FLOORS
 H) SQ. FT. FOOTPRINT
  
 3) SHEET A-2
 3A) GENERAL NOTE# 2 PLANS INDICATE CODE SECTION
 3401.8.2.3. PLEASE CORRECT AND UPDATE.
  
 3B) GENERAL NOTE# 3 DRAFT STOPPING PER 705.3.2 PLEASE
 CORRECT AND UPDATE.
  
 3C) IS THERE TO BE A NEW FLOOR SLAB POURED AS WORK
 COMPLETED UNDER THIS PERMIT.
  
 3D) PLANS DO NOT INDICATE OR IDENTIFY THE ACCESSIBLE
 ENTRANCE INTO THE BUILDING. SHEET A-3 DETAIL C DOES
 INDICATE FROM GRADE A 4" SLAB WITH NO ACCESSIBLE ROUTE
 OR ENTRANCE.2006 EXISTING BUILDING CODE, 806.1 GENERAL.
 ACCESSIBILITY IN PORTIONS OF BUILDINGS UNDERGOING A
 CHANGE OF OCCUPANCY CLASSIFICATION SHALL COMPLY WITH
 CHAPTER 11 OF THE FLORIDA BUILDING CODE, BUILDING
 11-4.1.2 ( 1)AT LEAST ONE ACCESSIBLE ROUTE COMPLYING
 WITH SECTION 11-4.3 SHALL BE PROVIDED WITHIN THE
 BOUNDARY OF THE SITE FROM PUBLIC TRANSPORTATION STOPS,
 ACCESSIBLE PARKING SPACES, PASSENGER LOADING ZONES IF
 PROVIDED, AND PUBLIC STREETS OR SIDEWALKS, TO AN
 ACCESSIBLE BUILDING ENTRANCE.
 (2)AT LEAST ONE ACCESSIBLE ROUTE COMPLYING WITH
 SECTION 11-4.3 SHALL CONNECT ACCESSIBLE BUILDINGS,
 ACCESSIBLE FACILITIES, ACCESSIBLE ELEMENTS, AND
 ACCESSIBLE SPACES THAT ARE ON THE SAME SITE.
  
 3E) CHANGING ROOM 11-4.35.2 CLEAR FLOOR SPACE.
 A CLEAR FLOOR SPACE ALLOWING A PERSON USING A
 WHEELCHAIR TO MAKE A 180-DEGREE TURN SHALL BE PROVIDED
 IN EVERY ACCESSIBLE DRESSING ROOM ENTERED THROUGH A
 SWINGING OR SLIDING DOOR. NO DOOR SHALL SWING INTO ANY
 PART OF THE TURNING SPACE. TURNING SPACE SHALL NOT BE
 REQUIRED IN A PRIVATE DRESSING ROOM ENTERED THROUGH A
 CURTAINED OPENING AT LEAST 32 INCHES (815 MM) WIDE IF
 CLEAR FLOOR SPACE COMPLYING WITH SECTION 11-4.2 RENDERS
 THE DRESSING ROOM USABLE BY A PERSON USING A
 WHEELCHAIR.
  
 11-4.35.3 DOORS.
 ALL DOORS TO ACCESSIBLE DRESSING ROOMS SHALL BE IN
 COMPLIANCE WITH SECTION 11-4.13 .
  
 11-4.35.4 BENCH.
 EVERY ACCESSIBLE DRESSING ROOM SHALL HAVE A 24 INCHES
 BY 48 INCHES (610 MM BY 1219 MM) BENCH FIXED TO THE
 WALL ALONG THE LONGER DIMENSION. THE BENCH SHALL BE
 MOUNTED 17 INCHES TO 19 INCHES (430 MM TO 485 MM)
 ABOVE THE FINISH FLOOR. CLEAR FLOOR SPACE SHALL BE
 PROVIDED ALONGSIDE THE BENCH TO ALLOW A PERSON USING A
 WHEELCHAIR TO MAKE A PARALLEL TRANSFER ONTO THE BENCH.
 THE STRUCTURAL STRENGTH OF THE BENCH AND ATTACHMENTS
 SHALL COMPLY WITH SECTION 11-4.26.3 . WHERE INSTALLED
 IN
 CONJUNCTION WITH SHOWERS, SWIMMING POOLS, OR OTHER WET
 LOCATIONS, WATER SHALL NOT ACCUMULATE UPON THE SURFACE
 OF THE BENCH AND THE BENCH SHALL HAVE A SLIP-RESISTANT
 SURFACE.
  
 11-4.35.5 MIRROR.
 WHERE MIRRORS ARE PROVIDED IN DRESSING ROOMS OF THE
 SAME USE, THEN IN AN ACCESSIBLE DRESSING ROOM, A
 FULL-LENGTH MIRROR, MEASURING AT LEAST 18 INCHES WIDE
 BY 54 INCHES HIGH (460 MM BY 1370 MM), SHALL BE MOUNTED
 IN A POSITION AFFORDING A VIEW TO A PERSON ON THE BENCH
 AS WELL AS TO A PERSON IN A STANDING POSITION.
  
 3E) NEW HANDICAPPED RESTROOM, WALL FINISHES:1210.1 IN
 OTHER THAN DWELLING UNITS, TOILET AND BATHING ROOM
 FLOORS SHALL HAVE A SMOOTH, HARD, NONABSORBENT SURFACE
 THAT EXTENDS UPWARD ONTO THE WALLS AT LEAST 6 INCHES
 (152 MM).
  
 1210.2 WALLS.
 WALLS WITHIN 2 FEET (610 MM) OF URINALS AND WATER
 CLOSETS SHALL HAVE A SMOOTH, HARD, NONABSORBENT
 SURFACE, TO A HEIGHT OF 4 FEET (1219 MM) ABOVE THE
 FLOOR, AND EXCEPT FOR STRUCTURAL ELEMENTS, THE
 MATERIALS USED IN SUCH WALLS SHALL BE OF A TYPE THAT IS
 NOT ADVERSELY AFFECTED BY MOISTURE.
  
 3F) THE STORAGE AREA WITHIN THENEW THRIFT STORE
 PLEASE DECLARE IF TYPE S1 OR S2?TABLE 302.3.2.
  
 4)2006 FL EXISTING BUILDING CODE- 812.1 COMPLIANCE
 WITH CHAPTER 7 . THE OCCUPANCY CLASSIFICATION OF AN
 EXISTING BUILDING MAY BE CHANGED, PROVIDED THAT THE
 BUILDING MEETS ALL OF THE REQUIREMENTS OF CHAPTER 7
 APPLIED THROUGHOUT THE BUILDING FOR THE NEW OCCUPANCY
 GROUP AND COMPLIES WITH THE REQUIREMENTS OF SECTIONS
 802 THROUGH 812 .
 2006 FL EXISTING BUILDING CODE, CHAPTER 7 LEVEL III
 ALTERATION 708.1 MINIMUM REQUIREMENTS. ALTERATIONS
 SUBJECT TO THIS CHAPTER SHALL COMPLY WITH THE
 REQUIREMENTS OF CHAPTER 13 OF THE FLORIDA BUILDING
 CODE, BUILDING. SEE A-3 DETAILC DOESN'T INDICATE ANY
 ROOF INSULATION.
  
 5) ENERGY CALCS ARE MISSING THE DESIGN PROFESSIONAL
 SEAL & SIGNATURE.
 PLANS, SPECIFICATIONS, REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 6)FL BLD CODE 1609.1.4: COMPONENTS & CLADDING,
 PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT INSPECTOR)
 OF PRODUCT TESTING REPORTS ,MISSING REPORTS ARE AS
 FOLLOWS:
 6 A) JELD-WEN DOOR THE WRONG MIAMI-DADE WAS SUBMITTED
 THAT TIES TO THE FL NUMBER
 6 B) STORM PANELS- ADDITIOAL INFORMATION REQUIRED:
 PROVIDE STORM PANEL INFORMATION WITH INSTALLATION
 SCHEDULE AND KEY PLAN WITH
 SPECIFIC ANCHORS AND MOUNTING TO BE USED FOR ALL
 NON-IMPACT GLAZING.
 FBC 1606.1.4.
  
 FL BLD CODE 2004SECTION 103.6,
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
  
 C) TAMKO ROOFING ) THIS ROOF IS MISSING OR NOT IN
 COMPLIANCE WITH THE FOLLOW ITEMS:
  
 _X__ THE SYSTEM PROVIDED HAS A LOW
 PRESSURE FOR ZONE _2&3__ .
  
 _X__ THE SYSTEM PROVIDED STATES
 LIMITATION# 7, SHOULD THE FASTENER
 RESISTANCE BE LESS THAN THAT
 REQUIRED, AS DETERMINED BY THE
 BUILDING OFFICIAL, A REVISED
 FASTENER SPACING, PREPARED , SIGNED
 AND SEALED BY A FLORIDA REGISTERED
 PROFESSIONAL ENGINEER, REGISTERED
 ARCHITECT OR REGISTERED ROOF
 CONSULTANT MAY BE SUBMITTED.
  
 7)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL
 INFORMATION REQUESTED ADDITIONAL COMMENTS MAY APPEAR
 THAT WERE NOT PART OF THIS REVIEW.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-05-04 Cont ID  
Sent By dpalmer Date 2008-05-04 Time 11:22 Rev Time 0.00
Received By dpalmer Date 2008-05-04 Time 11:22 Sent To  
Notes
2008-05-04 11:22:58** DENIED 3RD REVIEW **
  
 ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING ALONG WITH NEW COMMENT(S) WHICH
 ARE BASED ON NEW DOCUMENTS NOW SUBMITTED.
  
 1) NOTE: PLEASE SEE 13-400.3.A AS THE VERSION OF THE
 SUBMITTED ENERGY CALCULATIONS MAY NOT BE USED.
 PLEASE KNOW VERSION 2.5 IS THE ADOPTED VERSION WHICH
 INCORPORATES ENERGY GAUGE SUMMIT 3.0-3.14. THIS VERSION
 IS STILL 2.5 AS ADOPTED. THIS HAS BEEN CONFIRMED WITH
 THE DEPARTMENT OF COMMUNITY AFFAIRS/FLORIDA BUILDING
 COMMISSION.
 ** PLEASE ALSO SEE THAT THE CALCULATIONS SUBMITTED ARE
 NOT COMPLETE. PLEASE SEE THE INPUT DATA REPORT WAS NOT
 SUBMITTED WHICH IS ESSENTIAL TO THE REVIEW FOR CODE
 COMPLIANCE. PLEASE SEE SHEET #2 ON THE SUMMARY SHEETS
 WHICH SPECIFICALLY STATES THE INPUT DATA REPORT MUST
 ACCOMPANY THE CALCULATIONS.
 ** PLEASE BE SURE ALL COMPONENTS OF THE BUILDING IS
 SHOWN ON THE IDR. PLEASE KNOW AS THIS BUILDING IS AN
 EXISTING BUILDING THE ONLY WAY TO USE METHOD A IS ALL
 COMPONENTS MUST MEET CURRENT CODES FOR INSULATIONS,
 WINDOWS ETC. ALL MUST BE PLACED INTO THE CALCULATIONS.
 PLEASE SEE 13-400.3.B, 13-101.1.3 AS THIS BUILDING DOES
 FALL UNDER THE DEFINITION OF A RENOVATION. PLEASE SEE
 THE CODE, AS A RENOVATION METHOD B OR C IS STATED.
 ** THIS IS IMPORTANT, METHOD *A* MAY ONLY BE USED IF
 ALL COMPONENTS ARE KNOWN AND MEET CURRENT CODE FOR
 TRADE OFF ALLOWANCES FOR *WHOLE BUILDING* ETC.
 THIS COMMENT IS FOR ALL TRADES WHETHER OR NOT COMMENT
 IS MADE BY ANY OTHER REVIEWER(S).
 PLEASE BE SURE TO SEE 13-415.2 FOR LIGHTING
 PERFORMANCE. PLEASE SEE 13-415.2.ABC.1.1, .1.2 AND
 .1.3.
 THIS OFFICE CAN NOT EMPHASIZE ENOUGH TO PLEASE BE SURE
 ALL LIGHTING AND OTHER COMPONENTS ON PLANS COORDINATE
 WITH THE SUBMITTED ENERGY CALCULATIONS AND THE INPUT
 DATA REPORT.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 PLEASE BE SURE THE OWNER/AGENT HAS SIGNED THE
 COMPLIANCE CERTIFICATION SHEETS.
  
 2) NOTE: PLEASE SEE FPL STANDARDS OF METERING. PLEASE
 VERIFY WITH A FPL SERVICE PLANNER THAT ALL METERING
 DEVICES ARE GROUPED. AS THE RISER DOES NOT SHOW ANY
 METERING FOR INDIVIDUAL MAINS THIS CAN NOT BE VERIFIED
 AT THIS TIME.
  
 3) NOTE: PLEASE SEE THE RISER HAS NOW INCLUDED
 CONDUCTORS FROM GUTTER TO THE MAIN HOWEVER PLEASE SEE
 THAT AN * EQUIPMENT GROUNDING CONDUCTOR* IS NOW BEING
 SHOWN WHICH IS NOT PERMITTED PER 250.6, 250.24.
 AS THE GROUNDED CONDUCTOR IS REQUIRED TO BE BONDED AT
 THE FIRST MEANS OF DISCONNECT IF AN EQUIPMENT GROUNDING
 CONDUCTOR WAS INSTALLED THIS WOULD PARALLEL THE NEUTRAL
 WHICH CREATES *OBJECTIONABLE CURRENTS*.
 PLEASE VERIFY ACTUAL FIRST MEANS OF DISCONNECT AND
 ADJUST.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-08-29 Cont ID  
Sent By dpalmer Date 2007-08-29 Time 19:51 Rev Time 0.00
Received By dpalmer Date 2007-08-29 Time 19:10 Sent To  
Notes
2007-08-29 19:51:552007-08-29 19:51:55
  
 ** DENIED2ND REVIEW**
  
 1) NOTE: PLEASE SEE THE PREVIOUS REVIEW NOTE #2 WHICH
 SPECIFICALLY GAVE A *HEADS-UP* ON THE ENERGY
 CALCULATIONS.
 PLEASE BE SURE WHEN SUBMITTING THE INPUT DATA REPORT
 THAT THE INFORMATION SHOWN ON THIS REPORT COORDINATES
 WITH THE NUMBER OF FIXTURES ON PLANS, THE TOTAL WATTAGE
 OF EACH FIXTURE AND THE METHOD FO CONTROLS.
 PLEASE SEE THE LUMINARIES SHOWN ON THE PLANS DO NOT
 MATCH WITH THE IDR.
 PLEASE SEE THE TYPE OF INPUT FOR *HOTEL/MOTEL* WHICH IS
 NOT POSSIBLE.
 PLEASE SEE THE METHOD OF CONTROLS IS BEING SHOWN AS
 *MANUAL ON/OFF* ON THE INPUT DATA REPORT HOWEVER
 AUTOMATE CONTROLS ARE SHOWN ON PLANS. PLEASE COORDINATE
 PLANS WITH THE CALCULATIONS.
 PLEASE ALSO SEE THE NEW REVISED ENERGY CALCULATIONS
 WHICH ARE NOT SIGNED, DATED AND SEALED AS REQUIRED PER
 FBC 13-103.1.1.1, FS 471.025, FAC 61G15-23.002
  
 2) NOTE: PLEASE SEE MISSING LIGHT FIXTURE WHICH IS
 REDLINED ON PLANS.
 FBC 106.1.2
  
 3) NOTE: PLEASE INDICATE LOAD ON THE EXISTING GUTTER
 FOR ADDING NEW LOADS.
 NEC 220
 FBC 106.3.5.1.2
  
 4) NOTE: PLEASE SEE NO CONDUCTORS ARE BEING SHOWN FROM
 GUTTER TO NEW MAIN.
 230, 310.16, 240.4, ETC
 FBC 106.3.5.1.2
  
 5) NOTE: PLEASE SEE MISSING NEUTRAL TO THE MEANS OF
 DISCONNECT AT THE DETACHED BUILDING.
 250.32
 EVEN AS A NEUTRAL IS NOT NEEDED FROM THE MAIN AT THE
 DETACHED BUILDING TO THE TRANSFORMER FOR THE SEPARATELY
 DERIVED SYSTEM, A NEUTRAL IS STILL REQUIRED TO THE
 MAIN.
 PLEASE SEE MISSING COLD WATER PIPE AT THE DETACHED
 STRUCTURE PER 250.50
 PLEASE VERIFY THE GROUNDING ELECTRODE FOR THE
 TRANSFORMER PER 250.58.
  
 AS STATED ON THE PREVIOUS REVIEW:
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-04-16 Cont ID  
Sent By dpalmer Date 2007-04-16 Time 07:37 Rev Time 0.00
Received By dpalmer Date 2007-04-15 Time 19:59 Sent To  
Notes
2007-04-16 07:38:35** UNSAT **
  
 ** PLEASE SEE ANY REFERENCES IN PLAN REVIEW NOTES TO
 CHAPTER 1 OF THE FBC ARE THAT WHICH IS ADOPTED BY THE
 CITY OF WEST PALM BEACH.
  
 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH
 ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS
 UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLANS AT THIS TIME DO NOT INDICATE ANY CODES.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2003 NFPA-101
  
 2) NOTE: PLEASE COMPLETE THE ENERGY CALCULATIONS
 SUBMITTED. 13-415.1.AB.1.1, 13-415.2
 PLEASE SEE THE SQ FT ON THE ENERGY CALCULATIONS DOES
 NOT CORRELATE WITH PLANS.
 PLEASE BE SURE TO SUBMIT THE *INPUT DATA REPORT* ALONG
 WITH FRONT SHEET(S) FOR PROJECT SUMMARY. (NOTE: THE
 CALCULATIONS ARE NOT VALID WITHOUT THE INPUT DATA
 REPORT)
 PLEASE BE SURE THE ENERGY CALCULATIONS ARE SIGNED,
 DATED AND SEALED BY THE RESPONSIBLE DESIGNER OF
 RECORD.13-103.1.1.1
 PLEASE BE SURE THAT ALL LIGHTING FIXTURES, WATTAGES ETC
 COORDINATE WITH THE ELECTRICAL PLANS.
 PLEASE THE BASED ON THE LIGHTING POWER DENSITIES NOTED
 ON PLANS, THESE MENTION *X* WATTAGE PROVIDED, YET BASED
 ON THE FIXTURE LEGEND AND THE FIXTURE WATTAGES, THE LPD
 SEEMS TO BE HIGHER THAN THE AMOUNT SHOULD BE BASED ON
 THE FIXTURES AND WATTAGES LISTED.
 PLEASE SUBMIT A DETAIL ON LIGHTING CONTROL PANEL AS
 NOTED ON PLANS. THE REQUIRED LOCATIONS OF OVER RIDES
 FOR POINTS OF INGRESS AND EGRESS COULD NOT BE LOCATED
 AT THESE DOORS. ONLY ONE TIMER TYPE WAS FOUND ON PLANS.
 13-415.1.ABC.1.1
 PLEASE INDICATE THE MAXIMUM AMOUNT OF TIME ON THE OC
 TYPE DEVICES AS LISTED ON THE SYMBOL.
 PLEASE SEE THE STORAGE AREA WHICH CONTAINS WALL MOUNTED
 TYPE OCCUPANCY TYPE DEVICES ARE OK AS LONG AS COVERAGE
 FOR THE AREA IS MET. IF THIS IS A STORAGE AREA, HOW
 WILL A WALL MOUNTED DEVICE PROVIDE COVERAGE FOR THE
 OCCUPANTS? ARE THESE COMBINATION TYPE DEVICES?
 PLEASE KNOW THAT IN THE EVENT OF THE BUILDING BEING
 OCCUPIED AFTER HOURS AND THE TIMER TYPE DEVICE TURNS
 OFF, WHAT LIGHTING WILL AN OCCUPANT HAVE TO MAKE THEIR
 WAY SAFETY TO TURN LIGHTING BACK ON? WILL THERE BE A
 *NIGHT LIGHT* OR WILL AN OCCUPANCY TYPE DEVICE PROVIDE
 THAT COVERAGE? ONLY ONE *NL* INDICATE IN THE FRONT PART
 OF THE BUILDING IN RETAIL AREA.
 PLEASE CONSIDER.
 PLEASE SEE ALL OF THE NEW 2004 FBC W/2006 REVISIONS AS
 THERE WERE CHANGES FORM THE PREVIOUS 05, 2004 FBC.
 13-415.1.ABC.1.1, .1.2 AND .1.3
  
 3) NOTE: PLEASE SEE THE PLANS SEEM TO INDICATE THE MAIN
 SERVICE AND DISCONNECT LOCATED ON A DIFFERENT BUILDING.
 WHERE IS THE GUTTER AND DISCONNECTS LOCATED? PLEASE SEE
 225.31-225.39
  
 4) NOTE: PLEASE SEE 250.32 FOR GROUNDING AT DETACHED
 BUILDINGS. AS THE LOCATION OF THE SERVICE IS NOT CLEAR
 AND THE MAIN SERVICE IS BEING SHOWN AT A DETACHED
 BUILDING, PLEASE SUBMIT THE DETAIL ON RISER.
  
 5) NOTE: PLEASE COMPLETE PANEL SCHEDULE FOR LIGHTING
 AND RECEPTACLES.
 PLEASE SEE THE FOLLOWING TEXT WHICH IS FROM THE 2005
 NEC 408.4.
 **SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO
 REQUIRE THAT THE IDENTIFICATION FOR EVERY CIRCUIT
 SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND
 CLEARLY STATE THE SPECIFIC PURPOSE FOR WHICH THE
 CIRCUIT IS USED. CIRCUITS USED FOR THE SAME PURPOSE
 MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR EXAMPLE,
 SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY OUTLETS IN
 THE KITCHEN, DINING ROOM, AND KITCHEN COUNTERTOPS.
 IDENTIFYING THE CIRCUITS AS SMALL APPLIANCE BRANCH
 CIRCUITS IS NOT ACCEPTABLE; INSTEAD, THEY SHOULD BE
 IDENTIFIED AS ``KITCHEN WALL RECEPTACLES,'' ``DINING
 ROOM FLOOR RECEPTACLE,'' OR ``KITCHEN COUNTERTOP
 RECEPTACLES LEFT OF SINK.'' CIRCUIT DIRECTORIES
 CONTAINING MULTIPLE ENTRIES WITH ONLY ``LIGHTS'' OR
 ``OUTLETS'' DO NOT PROVIDE THE SUFFICIENT DETAIL
 REQUIRED BY THIS SECTION.*
 408.4, 310.16, 240.4 ETC
 FBC 106.3.5..1.2
  
 6) NOTE: PLEASE SEE THE NOTES INDICATE WIRING FOR EM
 AND EXTLTS TO BE PER 700.12F, YET THIS SHOULD BE
 700.12E. THE *F* SEEMS TO BE A MISPRINT).
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-04-16 07:04:082007-04-16 07:04:08
 IN REVIEW
2007-04-15 20:07:492007-04-15 20:07:49
 REVIEW TO CONTINUE ON 4/16

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2008-05-19 Cont ID  
Sent By mawillia Date 2008-05-19 Time 12:48 Rev Time 0.00
Received By mawillia Date 2008-05-19 Time 12:18 Sent To  
Notes
2008-05-19 12:43:34*****DENIED*****
  
 * THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE
 PLAN REVIEWS STILL NEED TO BE ADDRESSED:
  
  
 7.SPECIFY THE INTERIOR WALL AND CEILING FINISH
 MATERIAL AS CLASS A, CLASS B, OR CLASS C FOR EXITS,
 EXIT ACCESS CORRIDORS, AND ALL OTHER AREAS.PLEASE
 ADDRESS ON THE APPROPIATE PLAN SHEET
  
 * NEW COMMENTS
  
 C.PROVIDE A LAYOUT OF THE SPRINKLER SYSTEM FOR
 STRUCTURE.PLEASE BE ADVISED THAT SEPARATE PLANS AND
 PERMIT WILL BE REQUIRED FOR SPRINKLER INSTALLATION
 AND/OR REMODEL.
  
 D. DOES THE STRUCTURE HAVE OR WILL HAVE A FIRE ALARM
 SYSTEM.IF SO, PROVIDE A LAYOUT OF THE FIRE ALARM
 SYSTEM.PLEASE BE ADVISED THAT SEPARATE PLANS AND
 PERMIT WILL BE REQUIRED FOR ITS INSTALLATION AND/OR
 REMODEL.
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-09-25 Cont ID  
Sent By mawillia Date 2007-09-25 Time 10:46 Rev Time 0.00
Received By mawillia Date 2007-09-25 Time 09:14 Sent To  
Notes
2007-09-25 10:46:41*****DENIED*****
  
 * THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE
 PLAN REVIEW STILL NEED TO BE ADDRESSED:
  
 4.THE DEMOLITION AND/OR THE STOCKING OF NEW BUILDING
 MATERIALS & SUPPLIES SHALL NOT INTERFERE WITH EMERGENCY
 RESPONSE ACCESS TO THE PROPERTY OR THE VICINITY THEREOF
 (INCLUDING STREETS, ALLEYS, FIRE LANES).AMEND
 SPELLING TO READ FIRE LANES, NOT FINE LINES AS
 INDICATED ON SHEET 2.1
  
 5.PLEASE DECLARE THE OCCUPANCY CLASSIFICATION FOR
 THIS/THESE STRUCTURE(S).NOT SHOWN IN THE PROJECT DATA
 ON SHEET 2.1
  
 7.SPECIFY THE INTERIOR WALL AND CEILING FINISH
 MATERIAL AS CLASS A, CLASS B, OR CLASS C FOR EXITS,
 EXIT ACCESS CORRIDORS, AND ALL OTHER AREAS.PLEASE
 ADDRESS ON THE APPROPIATE PLAN SHEET
  
 * NEW COMMENTS
  
 A.DECLARE WHAT IS TO BE STORED IN THE NEW STORAGE
 STRUCTURE AND ITS HAZARD CONTENTS IN TERMS OF LOW,
 MODERATE, OR HIGH.
  
 B.NO EMERGENCY LIGHTS NOTED IN THE NEW STORAGE
 STRUCTURE.PLEASE EXPLAIN OR AMEND.
  
 C.PROVIDE A LAYOUT OF THE SPRINKLER SYSTEM FOR
 STRUCTURE.PLEASE BE ADVISED THAT SEPARATE PLANS AND
 PERMIT WILL BE REQUIRED FOR SPRINKLER INSTALLATION
 AND/OR REMODEL.
  
 D. DOES THE STRUCTURE HAVE OR WILL HAVE A FIRE ALARM
 SYSTEM.IF SO, PROVIDE A LAYOUT OF THE FIRE ALARM
 SYSTEM.PLEASE BE ADVISED THAT SEPARATE PLANS AND
 PERMIT WILL BE REQUIRED FOR ITS INSTALLATION AND/OR
 REMODEL.
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-05-30 Cont ID  
Sent By mawillia Date 2007-05-30 Time 16:33 Rev Time 0.00
Received By mawillia Date 2007-05-30 Time 15:37 Sent To  
Notes
2007-05-30 16:31:55*****DENIED*****
  
  
 1.PROVIDE A SITE PLAN WHICH WOULD RELAY THE LOCATION
 OF BUILDING TO SURROUNDING STREETS, ROADS, ETC
  
 2.NFPA 101, THE LIFE SAFETY CODE, 2003 EDITION SHALL
 BE REFERENCED.
  
 3.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 4.THE DEMOLITION AND/OR THE STOCKING OF NEW BUILDING
 MATERIALS & SUPPLIES SHALL NOT INTERFERE WITH EMERGENCY
 RESPONSE ACCESS TO THE PROPERTY OR THE VICINITY THEREOF
 (INCLUDING STREETS, ALLEYS, FIRE LANES).
  
 5.PLEASE DECLARE THE OCCUPANCY CLASSIFICATION FOR
 THIS/THESE STRUCTURE(S).
  
 6.PLEASE PROVIDE OCCUPANT LOAD/EGRESS REQUIREMENTS
  
 7.SPECIFY THE INTERIOR WALL AND CEILING FINISH
 MATERIAL AS CLASS A, CLASS B, OR CLASS C FOR EXITS,
 EXIT ACCESS CORRIDORS, AND ALL OTHER AREAS.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-04-22 Cont ID  
Sent By adarroug Date 2008-04-22 Time 10:02 Rev Time 0.00
Received By adarroug Date 2008-04-22 Time 10:02 Sent To  
Notes
2008-04-22 10:04:45TO "COMM" BD#62

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-08-06 Cont ID  
Sent By adarroug Date 2007-08-06 Time 16:25 Rev Time 0.00
Received By adarroug Date 2007-08-06 Time 16:25 Sent To  
Notes
2007-08-29 14:50:35TO "COMM" BD#24
2007-08-06 16:25:54WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-06-11 Cont ID  
Sent By jwitmer Date 2007-06-11 Time 10:49 Rev Time 0.00
Received By jwitmer Date 2007-04-03 Time 17:51 Sent To  
Notes
2007-04-04 18:01:01TO COMM BOARD # 13
2007-04-03 17:51:49WAITING FOR COMM BOARD

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2008-05-01 Cont ID  
Sent By tgordon Date 2008-05-01 Time 08:32 Rev Time 1.00
Received By tgordon Date 2008-05-01 Time 08:32 Sent To  
Notes
2008-05-01 08:32:45PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2005, 2006 REVISIONS, AND CHAPTER
 1 CITY OF WEST PALM BEACH AMENDMENTS.
  
 *** DENIED ***
 1) THE SIGNATURE OF THE PREPARER ON THE ENERGY
 CALCULATIONS CAN NOT BE READ TO DETERMINE WHO'S SIGNED.
 AS NOTED IN LAST TWO REVIEWS 5-1-07 NOTE #3 AND 8-20-07
 NOTE #1. ENERGY CALCULATIONS "PREPARED BY" NEED TO BE
 SIGNED AND SEALED BY AN ARCHITECT OR ENGINEER, SEE 2004
 FBC 13-103.1.1.1 EXCEPTION.
  
 *** 2004 FBC 13-103.1.1.1 ENERGY CALCULATIONS
 COMMERCIAL APPLICATIONS. COMPLETION OF PROCEDURES
 DEMONSTRATING COMPLIANCE WITH THIS CODE FOR COMMERCIAL
 BUILDINGS SHALL BE SIGNED AND SEALED BY AN ARCHITECT OR
 ENGINEER LICENSED TO PRACTICE IN THE STATE OF FLORIDA,
 WITH THE EXCEPTION OF BUILDINGS EXCLUDED BY SECTION
 481.229, FLORIDA STATUTES , OR SECTION 471.003, FLORIDA
 STATUTES. CALCULATIONS FOR BUILDINGS FALLING WITHIN THE
 EXCEPTION OF SECTION 471.003, FLORIDA STATUTES , MAY BE
 PERFORMED BY AIR CONDITIONING OR MECHANICAL CONTRACTORS
 LICENSED IN ACCORDANCE WITH CHAPTER 489, FLORIDA
 STATUTES , OR BY STATE OF FLORIDA CERTIFIED COMMERCIAL
 BUILDING ENERGY RATERS.
 DESIGN PROFESSIONALS RESPONSIBLE UNDER FLORIDA LAW FOR
 THE DESIGN OF LIGHTING, ELECTRICAL, MECHANICAL, AND
 PLUMBING SYSTEMS AND THE BUILDING SHELL, SHALL CERTIFY
 COMPLIANCE OF THOSE BUILDING SYSTEMS WITH THE CODE BY
 SIGNING AND PROVIDING THEIR PROFESSIONAL REGISTRATION
 NUMBER ON THE ENERGY CODE FORM PROVIDED AS PART OF THE
 PLANS AND SPECIFICATIONS TO THE BUILDING DEPARTMENT.
 EXCEPTION: TYPED NAMES AND REGISTRATION NUMBERS MAY BE
 PROVIDED IN LIEU OF A SIGNATURE WHERE ALL RELEVANT
 INFORMATION HAS BEEN INCLUDED ON SIGNED AND SEALED
 PLANS.
  
 2) AS NOTED IN LAST TWO REVIEWS 5-1-07 NOTE #4 AND
 8-20-07 NOTE #2. ENERGY CALCULATIONS NEED A "MECHANICAL
 DESIGNER" WHO IS A ENGINEER, OR AN ARCHITECT, AIR
 CONDITIONING CONTRACTOR, OR MECHANICAL CONTRACTOR IF
 APPLICABLE, SEE 2004 FBC 13-103.1.1.1 AND F.S. 471.003
 (H). (NOT NELSON MARIN).
  
 3) AS NOTED IN LAST TWO REVIEWS 5-1-07 NOTE #5 AND
 4-20-07 NOTE #3. SEE MECHANICAL PLANS, TITLE BLOCK,
 (NELSON MARIN) IF NOT A LICENSE ENGINEER MAY NOT DO
 COMMERCIAL MECHANICAL PLANS, SEE F.S. 471.003. IF A
 LICENSE ENGINEER THEN HE NEEDS TO PUT HIS INFORMATION
 IN THE TITLE BLOCK, SEE FAC 61G15-23.002. LICENSE
 #CAC055529 BELONGS TO JERONIMO MARIN (NOT NELSON MARIN)
 PLEASE HAVE JERONIMO MARIN SIGN MECHANICAL PLANS.
  
 4) AS NOTED IN LAST TWO REVIEWS 5-1-07 NOTE #6 AND
 8-20-07 NOTE #4. THE COMMERCIAL MECHANICAL PLANS NEED
 TO BE DONE BY AN ENGINEER, OR A/C CONTRACTOR,
 MECHANICAL CONTRACTOR IF APPLICABLE, SEE F.S. 471.003.
 (NOT NELSON MARIN) PLEASE HAVE JERONIMO MARIN SIGN
 MECHANICAL PLANS.
  
 5) AS NOTED IN LAST TWO REVIEWS 5-1-07 NOTE #2 AND
 8-20-07 NOTE #5. PLEASE PROVIDE OUTDOOR AIR
 CALCULATIONS, AND OUTDOOR AIR, SEE 2004 FBC/M 403.1.
 (NEED TO SHOW THE CALCULATIONS ON THE MECHANICAL PLAN
 NOT JUST SHOW A FRESH AIR VENT).
  
 6) AS NOTED IN LAST REVIEW 8-20-07 NOTE #8.PLEASE
 SUBMIT COOLING LOAD CALCULATIONS, SEE 2004 FBC
 13-407.1.ABC.1.
  
 7)ENERGY CALCULATIONS NEED TO BE SIGNED BY
 OWNER/AGENT ALSO, PER 2004 FBC 13-103.3.
  
 8) INPUT REPORT PRINT-OUT IS MISSING FROM THE ENERGY
 CALCULATIONS (SHOWING THE WALL INSULATION) PLEASE
 CORRECT.
  
 9) ONLY ONE SET OF PLANS HAVE A MECHANICAL PLAN PAGE
 M-1 IN THEM BOTH SETS NEED TO HAVE A MECHANICAL PLAN
 WITH THEM, SEE 2004 FBC 106.3.5.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL: [email protected].

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-08-20 Cont ID  
Sent By tgordon Date 2007-08-20 Time 08:47 Rev Time 0.45
Received By tgordon Date 2007-08-20 Time 08:47 Sent To  
Notes
2007-08-20 15:51:05RETURNED TO INCOMING WAITING TO GET ON COMM. BOARD.
2007-08-20 08:57:07PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2005, 2006 REVISIONS, AND CHAPTER
 1 CITY OF WEST PALM BEACH AMENDMENTS.
  
 *** DENIED ***
 1) AS NOTED IN LAST REVIEW 5-1-07NOTE #3. ENERGY
 CALCULATIONS "PREPARED BY" NEED TO BE SIGNED AND SEALED
 BY AN ARCHITECT OR ENGINEER, SEE 2004 FBC 13-103.1.1.1.
 (NOT NELSON MARIN).
  
 2) AS NOTED IN LAST REVIEW 5-1-07 NOTE #4. ENERGY
 CALCULATIONS NEED A "MECHANICAL DESIGNER" WHO IS A
 ENGINEER, OR AN ARCHITECT, AIR CONDITIONING CONTRACTOR,
 OR MECHANICAL CONTRACTOR IF APPLICABLE, SEE 2004 FBC
 13-103.1.1.1 AND F.S. 471.003 (H). (NOT NELSON MARIN).
  
 *** 2004 FBC 13-103.1.1.1 COMMERCIAL APPLICATIONS.
 COMPLETION OF PROCEDURES DEMONSTRATING COMPLIANCE WITH
 THIS CODE FOR COMMERCIAL BUILDINGS SHALL BE SIGNED AND
 SEALED BY AN ARCHITECT OR ENGINEER LICENSED TO PRACTICE
 IN THE STATE OF FLORIDA, WITH THE EXCEPTION OF
 BUILDINGS EXCLUDED BY SECTION 481.229, FLORIDA STATUTES
 , OR SECTION 471.003, FLORIDA STATUTES. CALCULATIONS
 FOR BUILDINGS FALLING WITHIN THE EXCEPTION OF SECTION
 471.003, FLORIDA STATUTES , MAY BE PERFORMED BY AIR
 CONDITIONING OR MECHANICAL CONTRACTORS LICENSED IN
 ACCORDANCE WITH CHAPTER 489, FLORIDA STATUTES , OR BY
 STATE OF FLORIDA CERTIFIED COMMERCIAL BUILDING ENERGY
 RATERS.
 DESIGN PROFESSIONALS RESPONSIBLE UNDER FLORIDA LAW FOR
 THE DESIGN OF LIGHTING, ELECTRICAL, MECHANICAL, AND
 PLUMBING SYSTEMS AND THE BUILDING SHELL, SHALL CERTIFY
 COMPLIANCE OF THOSE BUILDING SYSTEMS WITH THE CODE BY
 SIGNING AND PROVIDING THEIR PROFESSIONAL REGISTRATION
 NUMBER ON THE ENERGY CODE FORM PROVIDED AS PART OF THE
 PLANS AND SPECIFICATIONS TO THE BUILDING DEPARTMENT.
 EXCEPTION: TYPED NAMES AND REGISTRATION NUMBERS MAY BE
 PROVIDED IN LIEU OF A SIGNATURE WHERE ALL RELEVANT
 INFORMATION HAS BEEN INCLUDED ON SIGNED AND SEALED
 PLANS.
  
 3) AS NOTED IN LAST REVIEW 5-1-07 NOTE #5. SEE
 MECHANICAL PLANS, TITLE BLOCK,(NELSON MARIN) IF NOT A
 LICENSE ENGINEER MAY NOT DO COMMERCIAL MECHANICAL
 PLANS, SEE F.S. 471.003. IF A LICENSE ENGINEER THEN HE
 NEEDS TO PUT HIS INFORMATION IN THE TITLE BLOCK, SEE
 FAC 61G15-23.002. LICENSE #CAC055529 BELONGS TO
 JERONIMO MARIN (NOT NELSON MARIN).
  
 4) AS NOTED IN LAST REVIEW 5-1-07 NOTE #6. THE
 COMMERCIAL MECHANICAL PLANS NEED TO BE DONE BY AN
 ENGINEER, OR A/C CONTRACTOR, MECHANICAL CONTRACTOR IF
 APPLICABLE, SEE F.S. 471.003. (NOT NELSON MARIN).
  
 5) AS NOTED IN LAST REVIEW 5-1-07 NOTE #2. PLEASE
 PROVIDE OUTDOOR AIR CALCULATIONS, AND OUTDOOR AIR, SEE
 2004 FBC/M 403.1. (NEED TO SHOW THE CALCULATIONS ON THE
 MECHANICAL PLAN NOT JUST SHOW A FRESH AIR VENT).
  
 6)SEE ATTACHED NOTICE FS 553.80 (2) (B) REGARDING
 FOUR TIMES THE FEE.
  
 7) PLEASE BE ADVISED A COPY OF THE MECHANICAL PLANS AND
 ENERGY CALCULATIONS ARE BEING RETAINED AND MAY BE SENT
 TO THE DEPARTMENT OF BUSINESS AND PROFESSIONAL
 REGULATIONS.
  
 8) PLEASE SUBMIT COOLING LOAD CALCULATIONS, SEE 2004
 FBC 13-407.1.ABC.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL: [email protected].

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-05-01 Cont ID  
Sent By tgordon Date 2007-05-01 Time 14:22 Rev Time 1.00
Received By tgordon Date 2007-05-01 Time 14:22 Sent To  
Notes
2007-05-01 14:29:37*** DENIED ***
 1) THE BATHROOM WILL REQUIRE AN EXHAUST FAN, SEE 2004
 FBC/M 403.3, PLEASE CORRECT.
  
 2) PLEASE PROVIDE OUTDOOR AIR CALCULATIONS, AND OUTDOOR
 AIR, SEE 2004 FBC/M 403.1.
  
 3)ENERGY CALCULATIONS "PREPARED BY" NEED TO BE SIGNED
 AND SEALED BY AN ARCHITECT OR ENGINEER, SEE 2004 FBC
 13-103.1.1.1.
  
 4) ENERGY CALCULATIONS NEED A "MECHANICAL DESIGNER" WHO
 IS A ENGINEER, OR AN ARCHITECT, AIR CONDITIONING
 CONTRACTOR, OR MECHANICAL CONTRACTOR IF APPLICABLE, SEE
 2004 FBC 13-103.1.1.1 AND F.S. 471.003 (H).
  
 *** 2004 FBC 13-103.1.1.1 COMMERCIAL APPLICATIONS.
 COMPLETION OF PROCEDURES DEMONSTRATING COMPLIANCE WITH
 THIS CODE FOR COMMERCIAL BUILDINGS SHALL BE SIGNED AND
 SEALED BY AN ARCHITECT OR ENGINEER LICENSED TO PRACTICE
 IN THE STATE OF FLORIDA, WITH THE EXCEPTION OF
 BUILDINGS EXCLUDED BY SECTION 481.229, FLORIDA STATUTES
 , OR SECTION 471.003, FLORIDA STATUTES. CALCULATIONS
 FOR BUILDINGS FALLING WITHIN THE EXCEPTION OF SECTION
 471.003, FLORIDA STATUTES , MAY BE PERFORMED BY AIR
 CONDITIONING OR MECHANICAL CONTRACTORS LICENSED IN
 ACCORDANCE WITH CHAPTER 489, FLORIDA STATUTES , OR BY
 STATE OF FLORIDA CERTIFIED COMMERCIAL BUILDING ENERGY
 RATERS.
 DESIGN PROFESSIONALS RESPONSIBLE UNDER FLORIDA LAW FOR
 THE DESIGN OF LIGHTING, ELECTRICAL, MECHANICAL, AND
 PLUMBING SYSTEMS AND THE BUILDING SHELL, SHALL CERTIFY
 COMPLIANCE OF THOSE BUILDING SYSTEMS WITH THE CODE BY
 SIGNING AND PROVIDING THEIR PROFESSIONAL REGISTRATION
 NUMBER ON THE ENERGY CODE FORM PROVIDED AS PART OF THE
 PLANS AND SPECIFICATIONS TO THE BUILDING DEPARTMENT.
 EXCEPTION: TYPED NAMES AND REGISTRATION NUMBERS MAY BE
 PROVIDED IN LIEU OF A SIGNATURE WHERE ALL RELEVANT
 INFORMATION HAS BEEN INCLUDED ON SIGNED AND SEALED
 PLANS.
  
 5) SEE MECHANICAL PLANS, TITLE BLOCK,(NELSON MARIN)
 IF NOT A LICENSE ENGINEER MAY NOT DO COMMERCIAL
 MECHANICAL PLANS, SEE F.S. 471.003. IF A LICENSE
 ENGINEER THEN HE NEEDS TO PUT HIS INFORMATION IN THE
 TITLE BLOCK, SEE FAC 61G15-23.002.
  
 6) THE COMMERCIAL MECHANICAL PLANS NEED TO BE DONE BY
 AN ENGINEER, OR A/C CONTRACTOR, MECHANICAL CONTRACTOR
 IF APPLICABLE, SEE F.S. 471.003.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 3 Status F Date 2008-04-28 Cont ID  
Sent By kstevens Date 2008-04-28 Time 14:41 Rev Time 0.00
Received By kstevens Date 2008-04-28 Time 14:41 Sent To  
Notes
2008-04-28 15:52:42DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 ****FROM PREVIOUS REVIEW:
  
 ******FROM PREVIOUS REVIEWS:
  
  
 1. OK
  
 2. PER TABLE 403.1 A DRINKING FOUNTAIN AND A SERVICE
 SINK ARE REQUIRED. PLEASE SHOW THE LOCATION OF EACH ON
 THE FLOOR PLAN.
 ****DRINKING FOUNTAIN NOTED, BUT NO SERVICE SINK
 INDICATED.
 ******NO RESPONSE, COMMENT NOT ADDRESSED. SERVICE SINK
 NOT SHOWN.
  
 3. SHT A-3 INDICATES NEW PARAPET WALLS HAVE BEEN ADDED.
 SUBMIT A ROOF PLAN DETAIL SHOWING THE LOCATION OF ALL
 PRIMARY & SECONDARY ROOF DRAINS. SUBMIT CALCULATIONS
 FOR PRIMARY & SECONDARY ROOF DRAINS. SHOW THE SQUARE
 FOOTAGE OF EACH AREA BEING DRAIN BY EACH ROOF DRAIN AS
 WELL AS 1/2 AREA OF ALL VERTICAL WALLS, INCLUDING
 PARAPETS ADDED TO THE ROOF AREA OF EACH DRAIN SHOWING
 THE TOTAL AREA. SHOW THE ELEVATION OF THE ROOF & THE
 ELEVATION OF THE PARAPET WALLS. SHOW THE NORTH AND THE
 SOUTH BUILDING ELEVATIONS. SECTIONS 106.1.2, 1106 &
 1107 AS WELL AS TABLE 1106.3.
 ****ROOF PLAN INDICATED ON SHT 5.1. THE LOCATION OF THE
 SECONDARY ROOF DRAINS ARE NOT INDICATED. PLEASE SHOW
 THE LOCATION OF ALL SECONDARY ROOF DRAINS. CALCULATIONS
 INDICATE 6 RWL'S, BUT ROOF PLAN ONLY SHOWS 4. IF THERE
 ARE ONLY 4 RD'S THEN 4" RD'S AND PIPING WILL BE
 REQUIRED PER TABLE 1106.3. PLEASE CLARIFY. INDICATE THE
 SLOPE OF THE ROOF TO THE ROOF DRAINS. THE EXISTING
 CONCRETE PASS THROUGH ROOF APPEARS TO BE ABOVE THE TWO
 STORY SECTION OF THE BUILDING. PLEASE INDICATE IF ANY
 OF THIS ROOF DRAINS ON TO THE ROOF BELOW. ALSO INDICATE
 THE HEIGHT & WIDTH DIMENSIONS OF THE VERTICAL WALL
 ADJACENT TO THE LOWER ROOF ATTACHED TO THE PASS THROUGH
 ROOF. 1/2 THE AREA OF THIS WALL SHALL BE ADDED TO THE
 CALCULATIONS ALONG WITH THE PARAPET WALLS.
 ******NO COMMENT RESPONSE. THE SQUARE FOOTAGE OF EACH
 AREA IS NOT INDICATED. THE PARAPETS ARE INDICATED AS
 350.66 IN LENGHT WITH AN AVERAGE HEIGHT OF 2'0". 1/2 OF
 THAT AREA WOULD BE 350.66SF NOT 293.80SF. NO RESPONSE
 TO THE QUESTION CONCERNING THE EXISTING CONCRETE PASS
 THROUGH ROOF, NOR IS THERE ANY RESPONSE TO THE HEIGHT
 OF THE WALLL TO THE WEST SIDE OF THE NEW ROOF.--
 SHT 5.1 DETAIL FOR THE PARAPET WALL, PLEASE INDICATE
 THE ELEVATION TO THE TOP OF THE PARAPET, AS WELL AS THE
 ELEVATION OF THE ROOF AT THE PARAPET.--SUBMIT A
 SECTION FROM THE EAST SIDE OF THE NEW ROOF THRU THE
 PASS THRU ROOF SHOWING ALL ELVATIONS FOR THE ROOFS AND
 PARAPETS.--SUBMIT A DETAIL FOR THE EMERGENC
 OVERFLOW SCUPPERS SHOWING COMPLIANCE WITH SECTION
 1503.4.3.
  
 4. SUBMIT A DETAIL FOR THE REQUIRED DRINKING FOUNTAIN
 SHOWING COMPLIANCE WITH SECTION 11-4.15 WITH ALL
 SUBSECTIONS AS WELL SECTION 11-4.1.3(10)(A) PROVISIONS
 FOR THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING.
 ****DETAIL NOTED, BUT THE PROVISIONS FOR THOSE WHO HAVE
 DIFFICULTY BENDING OR STOOPING HAS NOT BEEN ADDRESSED.
 ******DETAIL NOTED, BUT THE PROVISIONS FOR THOSE WHO
 HAVE DIFFICULTY BENDING OR STOOPING HAS NOT BEEN
 ADDRESSED.
  
 5. OK
 6. OK
 7. OK - (DELETED)
 8. OK
  
 **********NEW COMMENT**********
  
 1B. OK
 2B. OK
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 ******NO RESPONSE, NOT ADDRESSED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-09-19 Cont ID  
Sent By kstevens Date 2007-09-19 Time 15:40 Rev Time 0.00
Received By kstevens Date 2007-09-19 Time 15:40 Sent To  
Notes
2007-09-19 17:36:55DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 ****FROM PREVIOUS REVIEW:
  
  
 1. OK
  
 2. PER TABLE 403.1 A DRINKING FOUNTAIN AND A SERVICE
 SINK ARE REQUIRED. PLEASE SHOW THE LOCATION OF EACH ON
 THE FLOOR PLAN.
 ****DRINKING FOUNTAIN NOTED, BUT NO SERVICE SINK
 INDICATED.
  
 3. SHT A-3 INDICATES NEW PARAPET WALLS HAVE BEEN ADDED.
 SUBMIT A ROOF PLAN DETAIL SHOWING THE LOCATION OF ALL
 PRIMARY & SECONDARY ROOF DRAINS. SUBMIT CALCULATIONS
 FOR PRIMARY & SECONDARY ROOF DRAINS. SHOW THE SQUARE
 FOOTAGE OF EACH AREA BEING DRAIN BY EACH ROOF DRAIN AS
 WELL AS 1/2 AREA OF ALL VERTICAL WALLS, INCLUDING
 PARAPETS ADDED TO THE ROOF AREA OF EACH DRAIN SHOWING
 THE TOTAL AREA. SHOW THE ELEVATION OF THE ROOF & THE
 ELEVATION OF THE PARAPET WALLS. SHOW THE NORTH AND THE
 SOUTH BUILDING ELEVATIONS. SECTIONS 106.1.2, 1106 &
 1107 AS WELL AS TABLE 1106.3.
 ****ROOF PLAN INDICATED ON SHT 5.1. THE LOCATION OF THE
 SECONDARY ROOF DRAINS ARE NOT INDICATED. PLEASE SHOW
 THE LOCATION OF ALL SECONDARY ROOF DRAINS. CALCULATIONS
 INDICATE 6 RWL'S, BUT ROOF PLAN ONLY SHOWS 4. IF THERE
 ARE ONLY 4 RD'S THEN 4" RD'S AND PIPING WILL BE
 REQUIRED PER TABLE 1106.3. PLEASE CLARIFY. INDICATE THE
 SLOPE OF THE ROOF TO THE ROOF DRAINS. THE EXISTING
 CONCRETE PASS THROUGH ROOF APPEARS TO BE ABOVE THE TWO
 STORY SECTION OF THE BUILDING. PLEASE INDICATE IF ANY
 OF THIS ROOF DRAINS ON TO THE ROOF BELOW. ALSO INDICATE
 THE HEIGHT & WIDTH DIMENSIONS OF THE VERTICAL WALL
 ADJACENT TO THE LOWER ROOF ATTACHED TO THE PASS THROUGH
 ROOF. 1/2 THE AREA OF THIS WALL SHALL BE ADDED TO THE
 CALCULATIONS ALONG WITH THE PARAPET WALLS.
  
 4. SUBMIT A DETAIL FOR THE REQUIRED DRINKING FOUNTAIN
 SHOWING COMPLIANCE WITH SECTION 11-4.15 WITH ALL
 SUBSECTIONS AS WELL SECTION 11-4.1.3(10)(A) PROVISIONS
 FOR THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING.
 ****DETAIL NOTED, BUT THE PROVISIONS FOR THOSE WHO HAVE
 DIFFICULTY BENDING OR STOOPING HAS NOT BEEN ADDRESSED.
  
 5. SHT A-3 SHOW COMPLIANCE WITH THE FOLLOW:
 ___FOR THE W/C:
 A. 11-4.16.5 FLUSH CONTROLS
 ****DETAIL SHOWS THE FLUSH CONTROLS ON THE WRONG SIDE
 OF THE TANK.
 ___FOR THE LAV:
 A. OK
  
 6. OK
 7. OK - (DELETED)
 8. OK
  
 **********NEW COMMENT**********
  
 1B. SHT 6.1 THE SANITARY PLUMBING ISOMETRIC RISER
 DIAGRAM DOES NOT MEET CODE REQUIREMENTS FOR SECTION
 901.2.1. A VENT IS REQUIRED FOR THE DRINKING FOUNTAIN.
 ALSO HORIZONTAL DRY VENTS ARE NOT APPROVED PER SECTIONS
 905.3 & 905.4. THE VENTS BETWEEN THE LAVS ARE NOT
 REQUIRED AND ARE HORIZONTAL DRY VENTS. DELETE FROM
 FLOOR PLAN AND RISER DIAGRAM. VENT AT EACH LAV WILL BE
 SUFFICIENT.
  
 2B. FLORIDA ENERGY CALCULATIONS INDICATE NO WATER
 HEATER, BUT THE FLOOR PLAN AND THE RISER DIAGRAM SHOW A
 WATER HEATER. PLEASE CORRELATE THE INFORMATION ON THE
 ENERGY CALCULATIONS WITH THE FLOOR PLAN. SECTION
 13-103.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-06-08 Cont ID  
Sent By kstevens Date 2007-06-08 Time 15:54 Rev Time 0.00
Received By kstevens Date 2007-06-08 Time 15:31 Sent To  
Notes
2007-06-08 16:12:32DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 1. PER TABLES 1004.1.2 & 403.1 SEPARATE FACILITIES ARE
 REQUIRED FOR THE MEN & WOMEN AND AS STATED IN SECTION
 403.2 UNLESS AN EXCEPTION TO THIS SECTION IS INDICATED
 ON THE PLANS AND APPROVED.
  
 2. PER TABLE 403.1 A DRINKING FOUNTAIN AND A SERVICE
 SINK ARE REQUIRED. PLEASE SHOW THE LOCATION OF EACH ON
 THE FLOOR PLAN.
  
 3. SHT A-3 INDICATES NEW PARAPET WALLS HAVE BEEN ADDED.
 SUBMIT A ROOF PLAN DETAIL SHOWING THE LOCATION OF ALL
 PRIMARY & SECONDARY ROOF DRAINS. SUBMIT CALCULATIONS
 FOR PRIMARY & SECONDARY ROOF DRAINS. SHOW THE SQUARE
 FOOTAGE OF EACH AREA BEING DRAIN BY EACH ROOF DRAIN AS
 WELL AS 1/2 AREA OF ALL VERTICAL WALLS, INCLUDING
 PARAPETS ADDED TO THE ROOF AREA OF EACH DRAIN SHOWING
 THE TOTAL AREA. SHOW THE ELEVATION OF THE ROOF & THE
 ELEVATION OF THE PARAPET WALLS. SHOW THE NORTH AND THE
 SOUTH BUILDING ELEVATIONS. SECTIONS 106.1.2, 1106 &
 1107 AS WELL AS TABLE 1106.3.
  
 4. SUBMIT A DETAIL FOR THE REQUIRED DRINKING FOUNTAIN
 SHOWING COMPLIANCE WITH SECTION 11-4.15 WITH ALL
 SUBSECTIONS AS WELL SECTION 11-4.1.3(10)(A) PROVISIONS
 FOR THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING.
  
 5. SHT A-3 SHOW COMPLIANCE WITH THE FOLLOW:
 ___FOR THE W/C:
 A. 11-4.16.5 FLUSH CONTROLS
 ___FOR THE LAV:
 A. 11-4.19.3 CLEAR FLOOR SPACE
  
 6. SUBMIT A WATER RISER DIAGRAM SHOWING ALL PIPE SIZES,
 VAVES ETC. SECTION 106.3.5.1.3(3)(10)(13).
  
 7. PER SECTION 11-4.35.4 A BENCH IS REQUIRED IN THE
 CHANGING ROOM.
  
 8. AN RPZV BACKFLOW IS REQUIRED ON THE WATER SERVICE TO
 THE BUILDING. SECTION 608.13.2.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 3 Status P Date 2008-04-25 Cont ID  
Sent By kdfreema Date 2008-04-25 Time 10:10 Rev Time 0.00
Received By kdfreema Date 2008-04-25 Time 10:10 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2007-09-10 Cont ID  
Sent By bpowell Date 2007-09-10 Time 18:07 Rev Time 0.00
Received By bpowell Date 2007-09-10 Time 17:53 Sent To  
Notes
2007-09-10 18:05:081. AN INFORMAL SITE PLAN REVIEW WILL BE REQUIRED PER
 SEC. 94-35 OF THE CITY'S ZONING AND LAND DEVELOPMENT
 REGULATIONS.
  
 THE FOLLOWING COMMENTS ARE GENERAL COMMENTS PROVIDED
 FOR GUIDANCE, THE PLANNING DEPARTMNET RESERVES THE
 RIGHT TO MAKE ADDITONAL COMMENTS UPON SUBMITTAL OF A
 SITE PLAN.
  
 A. THE LANDSCAPING SHALL BE BROUGHT INTO COMPLIANCE PER
 SEC. 94-443 OF THE CITY'S ZONING AND LAND DEVELOPMENT
 REGULATIONS.
  
 B.ALL PARKING SHALL BE DOUBLE STRIPPED, AT LEAST ONE
 (1) DISABLED SPACE SHALL BE PROVIDED FOR EACH 25
 PARKING SPACES OR FRACTION THEREOF.
  
 C.IT IS RECOMMENDED THAT THE APPLICANT SCHEDULE AN
 APPOINTMENT WITH MYSELF OR ANOTHER PLANNER BEFORE
 SUBMITTING FOR THE INFORMAL SITE PLAN REVIEW.
  
 FOR QUESTIONS OR COMMENTS CONTACT BOBBY POWELL JR.,
 PLANNER, CITYOFWPB.ORG, (561) 822-1435

Review Stop Z ZONING
Rev No 1 Status F Date 2007-04-13 Cont ID  
Sent By bpowell Date 2007-04-13 Time 11:55 Rev Time 0.00
Received By bpowell Date 2007-04-13 Time 11:35 Sent To  
Notes
2007-04-13 11:44:431. AN INFORMAL SITE PLAN REVIEW WILL BE REQUIRED PER
 SEC.94-35 OF THE CITY'S ZONING AND LAND DEVELOPMENT
 REGULATIONS.
  
 THE FOLLOWING COMMENTS ARE GENERAL COMMENTS PROVIDED
 FOR GUIDANCE, THE PLANNING DEPARTMENT RESERVES THE
 RIGHT TO MAKE ADDITIONAL COMMENTS UPON SUBMITTAL OF A
 SITE PLAN.
  
 A. ADDITIONAL PARKING WILL BE REQUIRED TO REPLACE THE
 PARKING THAT WILL BE TAKEN AWAY, AND FOR THE USE OF THE
 NEW BUILDING PER SEC. 94-486 OF THE CITY'S ZONING AND
 LAND DEVELOPMENT REGULATIONS.
  
 B. THE LANDSCAPING SHALL BE BROUGHT INTO COMPLIANCE PER
 SEC. 94-443 OS THE CITY'S ZONING AND LAND DEVELOPMENT
 REGULATIONS.
  
 BOBBY POWELL, PLANNER,
 [email protected]
 (561) 822-1435