Plan Review Stops For Permit 07040088 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
6 |
Status |
P |
Date |
2007-08-28 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2007-08-28 |
Time |
19:21 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2007-08-28 |
Time |
19:21 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
5 |
Status |
F |
Date |
2007-08-21 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2007-08-21 |
Time |
07:54 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2007-08-21 |
Time |
07:54 |
Sent To |
|
|
Notes |
2007-08-21 07:56:06 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBCFLORIDA BUILDING CODE 2004 | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | CODE | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | FAC FLORIDA ADMINISTRATIVE CODE | | FSFLORIDA STATUTE | | | | 1.)THE APPLICATION AND PLANS (PRODUCT APPROVALS, | | FLOOR PLAN, ETC.) ARE REQUIRED FOR PERMIT ISSUANCE. | | THE REVISED INSTALLATION SCHEDULE SUBMITTED SHOULD | | REPLACE THE OLD INSTALLATION SCHEDULE AND SUBMIT AS ONE | | PACKAGE AT THE FRONT COUNTER.ONLY THE INSTALLATION | | SCHEDULE WITH A RESUB FORM WAS PROVIDED. | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
F |
Date |
2007-07-30 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2007-07-30 |
Time |
09:51 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2007-07-30 |
Time |
09:51 |
Sent To |
|
|
Notes |
2007-07-30 10:03:06 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBCFLORIDA BUILDING CODE 2004 | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | CODE | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* | | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC | | FLORIDA ADMINISTRATIVE CODE | | FSFLORIDA STATUTE | | | | | | COMMENT FROM PREVIOUS LIST: | | | | 1.)THE SPAN SHOULD BE LARGER THAN THE OPENING HEIGHT. | | SPAN IS BLADE LENGTH.THIS MAY AFFECT ANCHOR SPACING | | FOR SOME OPENINGS.PLEASE REVISE SPANS AND CONFIRM | | ANCHOR SPACING. | | | | 4TH REVIEW - THE SPANS ARE NOW SMALLER THAN THE OPENING | | HEIGHT.THIS MAY BE THE CASE FOR AN INSIDE (TRAPPED) | | MOUNT, BUT NOT FOR A WALL MOUNT.YOU HAVE WRITTEN TWO | | NOTES ON THE INSTALLATION SCHEDULE.ONE STATES "ANCHOR | | SPACING IS FINE."PLEASE SEE OPENING 7.WITH A HEIGHT | | OF 100", WHEN YOU ADD THE 1 1/2 TO THE TOP AND BOTTOM | | OF THE OPENING FOR A WALL MOUNT, THE SPAN IS 103", OR | | 8'7", REQUIRING USE OF THE 9' SPAN CHART RATHER THAN | | THE 8' SPAN CHART AS WOULD BE REQUIRED FOR THE 96" SPAN | | YOU HAVE SPECIFIED.THIS DOES NOT AFFECT THE TOP MOUNT | | BUT DOES AFFECT ANCHOR SPACING FOR THE BOTTOM. | | | | THE SECOND NOTE STATES "WHAT ELSE KNOW?"IF YOU NEED | | ASSISTANCE, OR DO NOT UNDERSTAND THE CORRECTIONS, | | PLEASE HAVE THE QUALIFIER SCHEDULE A MEETING. | | | | NEW COMMENT: | | | | 2.)TWO COMPLETE COLLATED IDENTICAL SETS REQUIRED FOR | | PERMITTING.ONLY ONE NEW INSTALLATION SCHEDULE WAS | | SUBMITTED.IF THIS WAS THE ONLY COMMENT, I WOULD HAVE | | PRINTED THIS FOR YOU.HOWEVER, DUE TO WORKLOAD, I AM | | GENERALLY NOT ABLE TO PROVIDE COPIES AT THIS TIME. | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2007-07-05 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2007-07-05 |
Time |
16:06 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2007-07-05 |
Time |
16:06 |
Sent To |
|
|
Notes |
2007-07-05 16:08:23 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBCFLORIDA BUILDING CODE 2004 | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | CODE | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | FAC FLORIDA ADMINISTRATIVE CODE | | FSFLORIDA STATUTE | | | | | | 1.0THE SPAN SHOULD BE LARGER THAN THE OPENING HEIGHT. | | SPAN IS BLADE LENGTH.THIS MAY AFFECT ANCHOR SPACING | | FOR SOME OPENINGS.PLEASE REVISE SPANS AND CONFIRM | | ANCHOR SPACING. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2007-05-04 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2007-05-04 |
Time |
11:45 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2007-05-04 |
Time |
11:45 |
Sent To |
|
|
Notes |
2007-05-04 11:46:46 | ****CORRECTIONS**** | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBCFLORIDA BUILDING CODE 2004 | | FBC EBFLORIDA BUILDING CODE 2004 | | EXISTING BUILDING CODE | | FBC*CITY OF WEST PALM BEACH | | AMENDMENTS TO THE FBC2004 | | | | 1.)SEE PREVIOUS LIST, ITEM 4.COMPLETE THE | | INSTALLATION SCHEDULE OR PROVIDE ALL REQUIRED | | INFORMATION TO DETERMINE CODE COMPLIANCE IN ANOTHER | | FORMAT.THE WIND DESIGN PRESSURES FROM THE ENGINEER | | DOES NOT SATISFY THIS REQUIREMENT.THE INSTALLATION | | SCHEDULE WAS STILL IN THE PACKAGE, BLANK.IT NEEDS TO | | BE COMPLETED. | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2007-04-07 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2007-04-07 |
Time |
14:28 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2007-04-07 |
Time |
14:28 |
Sent To |
|
|
Notes |
2007-04-07 14:28:55 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBC FLORIDA BUILDING CODE 2004 | | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | SHUTTER PERMIT APPLICATION, ONLY CHECKED ITEMS APPLY | | | | ____1.A NOTICE OF COMMENCEMENT MUST BE FILED WITH | | THE CLERK OF COURTS BEFORE A PERMIT CAN BE ISSUED, | | FS713.13. | | | | ____2.PROVIDE BUILDING HEIGHT ON THE PLAN.DESIGN | | PRESSURES FOR BUILDINGS OVER 60FEET ARE REQUIRED TO BE | | DESIGNED USING ASCE7, FBC1609.1.1 AND MUST BE DONE BY A | | DESIGN PROFESSIONAL. DOCUMENTS PREPARED BY AN ENGINEER | | AND SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED SEALED | | ORIGINALS FAC61G15-23.002. | | | | ____3.PROVIDE A COPY OF THE CONDO ASSOCIATION | | APPROVAL. | | | | _XX_4.COMPLETE THE ATTACHED INSTALLATION SCHEDULE | | OR PROVIDE ALL INFORMATION TO SHOW CODE COMPLIANCE IN | | ANOTHER FORMAT. | | | | ____5.FLORIDA STATE OR LOCAL PRODUCT APPROVAL | | REQUIRED, FAC9B72, WWW.FLORIDABUILDING.ORG. | | | | ____6.ON THE PRODUCT APPROVAL, MARK WHICH DETAILS | | APPLY TO THIS JOB.PLEASE USE INK RATHER THAN A | | HIGHLIGHTER. | | | | ____7.SHOW THE EMERGENCY MEANS OF ESCAPE, FBC | | R310. | | | | ____8.PROVIDE A FLOOR PLAN SHOWING WHERE THE | | SHUTTERS WILL BE INSTALLED AND PANEL SIZES WHICH | | CORRELATES WITH THE INSTALLATION SCHEDULE, ITEM 4 | | ABOVE. | | | | ____9.REVISE EXPOSURE CATEGORY FBC1609.6.2.1(2), | | FBC R301.2.1.4.NOTE THAT THE DEFINITION FOR EXPOSURE | | C HAS CHANGED EFFECTIVE DECEMBER 8, 2006 FBC1609.4, FBC | | R301.2.1.4. | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2007-08-13 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-08-13 |
Time |
11:14 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-08-13 |
Time |
11:14 |
Sent To |
B |
|
Notes |
2007-08-13 11:15:17 | TO "SHILL" DESK/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2007-07-20 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-07-20 |
Time |
09:06 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-07-20 |
Time |
09:06 |
Sent To |
B |
|
Notes |
2007-07-20 09:06:21 | TO "SHILL" DESK/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2007-06-25 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-06-25 |
Time |
16:47 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-06-25 |
Time |
16:47 |
Sent To |
B |
|
Notes |
2007-06-25 16:47:59 | TO "SHILL" DESK/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2007-05-03 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2007-05-03 |
Time |
11:47 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2007-05-03 |
Time |
11:47 |
Sent To |
B |
|
Notes |
2007-05-03 11:48:00 | TO "SHILL" DESK/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2007-04-07 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2007-04-07 |
Time |
14:29 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2007-04-03 |
Time |
18:22 |
Sent To |
|
|
Notes |
2007-04-03 18:22:54 | TO MISC # 1 |
|
|