Plan Review Details - Permit 07040088
Plan Review Stops For Permit 07040088
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2007-08-28 Cont ID  
Sent By shill Date 2007-08-28 Time 19:21 Rev Time 0.00
Received By shill Date 2007-08-28 Time 19:21 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2007-08-21 Cont ID  
Sent By shill Date 2007-08-21 Time 07:54 Rev Time 0.00
Received By shill Date 2007-08-21 Time 07:54 Sent To  
Notes
2007-08-21 07:56:06****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)THE APPLICATION AND PLANS (PRODUCT APPROVALS,
 FLOOR PLAN, ETC.) ARE REQUIRED FOR PERMIT ISSUANCE.
 THE REVISED INSTALLATION SCHEDULE SUBMITTED SHOULD
 REPLACE THE OLD INSTALLATION SCHEDULE AND SUBMIT AS ONE
 PACKAGE AT THE FRONT COUNTER.ONLY THE INSTALLATION
 SCHEDULE WITH A RESUB FORM WAS PROVIDED.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2007-07-30 Cont ID  
Sent By shill Date 2007-07-30 Time 09:51 Rev Time 0.00
Received By shill Date 2007-07-30 Time 09:51 Sent To  
Notes
2007-07-30 10:03:06****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 COMMENT FROM PREVIOUS LIST:
  
 1.)THE SPAN SHOULD BE LARGER THAN THE OPENING HEIGHT.
 SPAN IS BLADE LENGTH.THIS MAY AFFECT ANCHOR SPACING
 FOR SOME OPENINGS.PLEASE REVISE SPANS AND CONFIRM
 ANCHOR SPACING.
  
 4TH REVIEW - THE SPANS ARE NOW SMALLER THAN THE OPENING
 HEIGHT.THIS MAY BE THE CASE FOR AN INSIDE (TRAPPED)
 MOUNT, BUT NOT FOR A WALL MOUNT.YOU HAVE WRITTEN TWO
 NOTES ON THE INSTALLATION SCHEDULE.ONE STATES "ANCHOR
 SPACING IS FINE."PLEASE SEE OPENING 7.WITH A HEIGHT
 OF 100", WHEN YOU ADD THE 1 1/2 TO THE TOP AND BOTTOM
 OF THE OPENING FOR A WALL MOUNT, THE SPAN IS 103", OR
 8'7", REQUIRING USE OF THE 9' SPAN CHART RATHER THAN
 THE 8' SPAN CHART AS WOULD BE REQUIRED FOR THE 96" SPAN
 YOU HAVE SPECIFIED.THIS DOES NOT AFFECT THE TOP MOUNT
 BUT DOES AFFECT ANCHOR SPACING FOR THE BOTTOM.
  
 THE SECOND NOTE STATES "WHAT ELSE KNOW?"IF YOU NEED
 ASSISTANCE, OR DO NOT UNDERSTAND THE CORRECTIONS,
 PLEASE HAVE THE QUALIFIER SCHEDULE A MEETING.
  
 NEW COMMENT:
  
 2.)TWO COMPLETE COLLATED IDENTICAL SETS REQUIRED FOR
 PERMITTING.ONLY ONE NEW INSTALLATION SCHEDULE WAS
 SUBMITTED.IF THIS WAS THE ONLY COMMENT, I WOULD HAVE
 PRINTED THIS FOR YOU.HOWEVER, DUE TO WORKLOAD, I AM
 GENERALLY NOT ABLE TO PROVIDE COPIES AT THIS TIME.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-07-05 Cont ID  
Sent By shill Date 2007-07-05 Time 16:06 Rev Time 0.00
Received By shill Date 2007-07-05 Time 16:06 Sent To  
Notes
2007-07-05 16:08:23****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.0THE SPAN SHOULD BE LARGER THAN THE OPENING HEIGHT.
 SPAN IS BLADE LENGTH.THIS MAY AFFECT ANCHOR SPACING
 FOR SOME OPENINGS.PLEASE REVISE SPANS AND CONFIRM
 ANCHOR SPACING.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-05-04 Cont ID  
Sent By shill Date 2007-05-04 Time 11:45 Rev Time 0.00
Received By shill Date 2007-05-04 Time 11:45 Sent To  
Notes
2007-05-04 11:46:46****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)SEE PREVIOUS LIST, ITEM 4.COMPLETE THE
 INSTALLATION SCHEDULE OR PROVIDE ALL REQUIRED
 INFORMATION TO DETERMINE CODE COMPLIANCE IN ANOTHER
 FORMAT.THE WIND DESIGN PRESSURES FROM THE ENGINEER
 DOES NOT SATISFY THIS REQUIREMENT.THE INSTALLATION
 SCHEDULE WAS STILL IN THE PACKAGE, BLANK.IT NEEDS TO
 BE COMPLETED.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-04-07 Cont ID  
Sent By shill Date 2007-04-07 Time 14:28 Rev Time 0.00
Received By shill Date 2007-04-07 Time 14:28 Sent To  
Notes
2007-04-07 14:28:55****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 SHUTTER PERMIT APPLICATION, ONLY CHECKED ITEMS APPLY
  
 ____1.A NOTICE OF COMMENCEMENT MUST BE FILED WITH
 THE CLERK OF COURTS BEFORE A PERMIT CAN BE ISSUED,
 FS713.13.
  
 ____2.PROVIDE BUILDING HEIGHT ON THE PLAN.DESIGN
 PRESSURES FOR BUILDINGS OVER 60FEET ARE REQUIRED TO BE
 DESIGNED USING ASCE7, FBC1609.1.1 AND MUST BE DONE BY A
 DESIGN PROFESSIONAL. DOCUMENTS PREPARED BY AN ENGINEER
 AND SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED SEALED
 ORIGINALS FAC61G15-23.002.
  
 ____3.PROVIDE A COPY OF THE CONDO ASSOCIATION
 APPROVAL.
  
 _XX_4.COMPLETE THE ATTACHED INSTALLATION SCHEDULE
 OR PROVIDE ALL INFORMATION TO SHOW CODE COMPLIANCE IN
 ANOTHER FORMAT.
  
 ____5.FLORIDA STATE OR LOCAL PRODUCT APPROVAL
 REQUIRED, FAC9B72, WWW.FLORIDABUILDING.ORG.
  
 ____6.ON THE PRODUCT APPROVAL, MARK WHICH DETAILS
 APPLY TO THIS JOB.PLEASE USE INK RATHER THAN A
 HIGHLIGHTER.
  
 ____7.SHOW THE EMERGENCY MEANS OF ESCAPE, FBC
 R310.
  
 ____8.PROVIDE A FLOOR PLAN SHOWING WHERE THE
 SHUTTERS WILL BE INSTALLED AND PANEL SIZES WHICH
 CORRELATES WITH THE INSTALLATION SCHEDULE, ITEM 4
 ABOVE.
  
 ____9.REVISE EXPOSURE CATEGORY FBC1609.6.2.1(2),
 FBC R301.2.1.4.NOTE THAT THE DEFINITION FOR EXPOSURE
 C HAS CHANGED EFFECTIVE DECEMBER 8, 2006 FBC1609.4, FBC
 R301.2.1.4.
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-08-13 Cont ID  
Sent By adarroug Date 2007-08-13 Time 11:14 Rev Time 0.00
Received By adarroug Date 2007-08-13 Time 11:14 Sent To B
Notes
2007-08-13 11:15:17TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-07-20 Cont ID  
Sent By adarroug Date 2007-07-20 Time 09:06 Rev Time 0.00
Received By adarroug Date 2007-07-20 Time 09:06 Sent To B
Notes
2007-07-20 09:06:21TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-06-25 Cont ID  
Sent By adarroug Date 2007-06-25 Time 16:47 Rev Time 0.00
Received By adarroug Date 2007-06-25 Time 16:47 Sent To B
Notes
2007-06-25 16:47:59TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-05-03 Cont ID  
Sent By shill Date 2007-05-03 Time 11:47 Rev Time 0.00
Received By shill Date 2007-05-03 Time 11:47 Sent To B
Notes
2007-05-03 11:48:00TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-04-07 Cont ID  
Sent By shill Date 2007-04-07 Time 14:29 Rev Time 0.00
Received By shill Date 2007-04-03 Time 18:22 Sent To  
Notes
2007-04-03 18:22:54TO MISC # 1