Plan Review Details - Permit 07040028
Plan Review Stops For Permit 07040028
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-04-12 Cont ID  
Sent By mjacobs Date 2007-04-12 Time 09:54 Rev Time 0.00
Received By mjacobs Date 2007-04-12 Time 08:45 Sent To  
Notes
2007-04-12 09:54:14BUILDING PLAN REVIEW
 PERMIT: 07040028
 ADD:1830 EMBASSY DR
 CONT: STRATICON CONST. SERVICES LLC.
 TEL: (954)464-9130
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST.
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE
 RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE:
 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT
 THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3)106.3.3* PRODUCT APPROVALS- 2004
 THOSE PRODUCTS THAT ARE RGULATED BY DCA
 RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITTING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.PROVIDE PRODUCT APPROVAL FOR
 THE EXTERIOR DOORS.
  
 4)THE VALUE IS TO LOW. 108.3*IF IN THE OPINION OF
 THE BUILDING OFFICIAL THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED.FOR PERMITTING PURPOSES, VALUATION SHALL BE
 THE TOTAL REPLACEMENT VALUE OF THE PROJECT. OUR
 VALUATION REFERENCE IS ICC (BVD), MARSHALL-SWIFT AND
 MEANS COST ANALYSIS SERVICES.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-04-16 Cont ID  
Sent By btrobaug Date 2007-04-16 Time 15:43 Rev Time 0.50
Received By btrobaug Date 2007-04-16 Time 15:21 Sent To  
Notes
2007-04-16 15:43:26 
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW
  
 1} THERE ARE TWO SHEETS LABLEDA1 WITH DIFERENT
 INFORMATION.PLEASE NUMBER THE SHEETS IN SOME ORDER.
 106.1.3 FBC.
  
 2} SEE PLUMBING REVIEW COMMENTS REGARDING DESCRIPTION
 AND PLANS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-04-13 Cont ID  
Sent By mwennerg Date 2007-04-13 Time 11:15 Rev Time 0.00
Received By mwennerg Date 2007-04-13 Time 11:15 Sent To  
Notes
2007-04-13 11:17:05***DENIED***
  
 1) PLEASE NOTE THAT PERMIT APPLICATION AND PLANS DON'T
 CORRELATE. PLEASE CLARIFY THE SCOPE OF WORK.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By spalmer Date 2007-04-02 Time 17:46 Sent To  
Notes
2007-04-03 18:14:11TO BOB # 9
2007-04-02 17:46:54WAITING FOR BOB

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-04-17 Cont ID  
Sent By tgordon Date 2007-04-17 Time 11:58 Rev Time 0.30
Received By tgordon Date 2007-04-17 Time 11:58 Sent To  
Notes
2007-04-17 12:27:08*** DENIED ***
 1) SEE PLANS PAGE A2 STATES, EXISTING VENTS FOR DRYERS
 TO BE REUSED. CONNECT TO NEW DRYERS. "DRYER VENT CAN
 ONLY MAKE (3) TURNS OF 90 DEGREES AND BE UNDER 10'-0"
 FROM UNIT TO VENT". SEE 2004 FBC/M 504.6 AND 504.7
 CLOTHES DRYER TRANSITION DUCTS USED TO CONNECT THE
 APPLIANCE TO THE EXHAUST DUCT SYSTEM SHALL BE LIMITED
 TO SINGLE LENGTHS NOT TO EXCEED 8 FEET (2438 MM) IN
 LENGTH AND SHALL BE LISTED AND LABELED FOR THE
 APPLICATION. TRANSITION DUCTS SHALL NOT BE CONCEALED
 WITHIN CONSTRUCTION, PLEASE CORRECT ON PLANS.
  
 2) IF LENGTHENING THE CLOTHES DRYER VENT PLEASE SEE
 2004 FBC/M 504 AND ADD DETAIL TO PLANS.
  
 3) IF CLOTHES DRYER VENT IS TO EXCEED THE 2004 FBC/M
 504 MAXIMUM LENGTH, PLEASE SUBMIT DETAILED
 MANUFACTURER'S SPECIFICATION'S AND INSTALLATION
 INSTRUCTIONS FOR THE CLOTHES DRYER.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729. .

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-04-06 Cont ID  
Sent By jleech Date 2007-04-06 Time 07:14 Rev Time 0.00
Received By jleech Date 2007-04-06 Time 07:14 Sent To  
Notes
2007-04-06 07:27:46DENIED;
 1. PROJECT DISCRIPTION ON PERMIT APPLICATION IS NOT THE
 SAME AS PLANS SHOW. APPLICATION STATES LAUNDRY ROOMS ON
 1 -2 & 5 TH FLOORS. PAGE A-1 PLUMBING RISER
 DIAGRAMSHOWS LAUNDRY ROOMS ON 2ND THRU 6 TH FLOORS.
 PLEASE CORRECT.
 2.SHOW THE NUMBER OF DWELLING UNITS, ON PLANS, AND
 THE NUMBER OF WASHING MACHINES. MUST COMPLY
 WITHFBC-2004 PLUMBING TABLE 403.1 R2.
 3. SECTION 412 REQUIRES FLOOR DRAINS FOR CENTRAL
 WASHING FACILITIES.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695