Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-04-12 Cont ID  
Sent By mjacobs Date 2007-04-12 Time 08:20 Rev Time 0.00
Received By mjacobs Date 2007-04-12 Time 07:40 Sent To  
Notes
2007-04-12 08:20:12BUILDING PLAN REVIEW
 PERMIT: 07031029
 ADD: 301 N.OLIVE AVE
 CONT: H.A. CONTRACTING CORP.
 TEL: (305)591-9212
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)61G1-16.004 TITLE BLOCK.
 A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR
 INTERIOR DESIGN DRAWINGS AND SPECIFICATION
 IDENTIFICATION SHEETS. THE TITLE BLOCK MUST, AT A
 MINIMUM, CONTAIN THE FOLLOWING INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER.
 (2) FIRM LICENSE NUMBER.
 (3) NAME OR IDENTIFICATION OF PROJECT.
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED SEAL.
 (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING
 THE DOCUMENT.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-10-14 Cont ID  
Sent By dpalmer Date 2007-10-14 Time 12:38 Rev Time 0.00
Received By dpalmer Date 2007-10-14 Time 12:27 Sent To  
Notes
2007-10-14 12:39:34RELINED MISSING MAXIMUM TIMES FOR OCCUPANCY SENSOR
 DEVICES PER 13-415.1.ABC.1.1.
 (MAX 30MINS)

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-03-31 Cont ID  
Sent By dpalmer Date 2007-03-31 Time 18:24 Rev Time 0.00
Received By dpalmer Date 2007-03-31 Time 18:23 Sent To  
Notes
2007-03-31 18:25:10** UNSAT **
  
 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH
 ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS
 UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 ** PLEASE SEE NOTES ON PLANS WHICH STATE THE 2001 FBC.
  
 2) NOTE: PLEASE KNOW IF THE ARCHITECT OF RECORD IS
 EMPLOYED BY THE CONTRACTOR THEN THE CONSTRUCTION
 COMPANY IS PROVIDING ARCHITECTURAL SERVICES AND MUST
 CONTAIN A CERTIFICATE OF AUTHORIZATION NUMBER. PLEASE
 CONTACT MR. DAVID MINACCI, STATES LEGAL COUNSEL TO THE
 BOARD OF ARCHITECTS.
 MUST OBTAIN THE CA/FIRM LICENSE NUMBER.
 FS 481.219, AND PLACE ON TITLE BLOCKS PER FAC
 61G1-16.004.
 ONE SET OF PLANS ARE BEING RETAINED BY THIS OFFICE.
 ** THIS COMMENT IS REQUIRED WHETHER OR NOT COMMENT IS
 MADE BY ANY OTHER TRADES. ANY STAMPED SHEETS ARE NOW
 VOID.
  
 3) NOTE: PLEASE PROVIDE MORE ELECTRICAL DETAIL ON
 PLANS. PLEASE INCLUDE ALL ELECTRICAL DEVICES FOR
 RECEPTACLES AND LIGHTING. NEW OR EXISTING?
 PLEASE PROVIDE LIGHTING DETAILS IF NEW, PLEASE INDICATE
 IF THERE IS A NEW OR EXISTING EMERGENCY LIGHT FIXTURE?
 PLEASE SEE 700.12E FOR CIRCUITING IF NEW.
 PLEASE SEE NFPA-101 7.8, 7.9
  
 4) NOTE: PLEASE PROVIDE CIRCUITING FOR NEW ELECTRICAL
 OR ARE THESE LOADS ON EXISTING CIRCUITS?
 FBC 106.1.2
  
 5) NOTE: PLEASE PROVIDE TIMES AND TYPES OF DEVICES FOR
 NEW OC SENSORS. PLEASE BE AWARE OF DEVICE IN ORDER TO
 PROPERLY PROVIDE COVERAGE FOR ALL AREAS. THIS MAY BE
 REQUIRED TO BE A COMBINATION DEVICE.
 PLEASE SEE MAXIMUM TIMES IN 13-415.1.ABC.1.1, .1.2.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-10-15 Cont ID  
Sent By mawillia Date 2007-10-15 Time 15:53 Rev Time 0.00
Received By mawillia Date 2007-10-15 Time 15:42 Sent To  
Notes
2007-10-15 15:42:49*****APPROVED*****
  
  
 PLAN SHEETS E1.3 AND E1.5 WERE STAMPED, INITIALED, AND
 DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2007-04-13 Cont ID  
Sent By mwennerg Date 2007-04-13 Time 10:54 Rev Time 0.00
Received By mwennerg Date 2007-04-13 Time 10:54 Sent To M
Notes
2007-04-13 10:55:08***PROVISO***
  
 1) FIRE REVIEW IS OK, HOWEVER PLEASE SEE BUILDING
 COMMENTS REGARDING TITLE BLOCK REQUIREMENTS.
  
 2) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH NFPA 241.
  
 3) WORK SHALL NOT INTERFERE WITH REQUIRED BUILDING FIRE
 PROTECTION EQUIPMENT AND MEANS OF EGRESS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-10-05 Cont ID  
Sent By adarroug Date 2007-10-05 Time 16:01 Rev Time 0.00
Received By adarroug Date 2007-10-05 Time 16:01 Sent To  
Notes
2007-10-14 12:39:54TO BOB, SPACE #3. DVP.
2007-10-05 16:01:28WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-04-13 Cont ID  
Sent By tgordon Date 2007-04-13 Time 12:25 Rev Time 0.00
Received By tgordon Date 2007-03-29 Time 18:59 Sent To  
Notes
2007-03-29 19:00:03TO BOB BOARD #6

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2007-10-18 Cont ID  
Sent By tgordon Date 2007-10-18 Time 08:50 Rev Time 0.25
Received By tgordon Date 2007-10-18 Time 08:50 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-11-01 Cont ID  
Sent By jleech Date 2007-11-01 Time 09:16 Rev Time 0.00
Received By jleech Date 2007-11-01 Time 09:16 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2007-03-31 Cont ID  
Sent By jleech Date 2007-03-31 Time 12:22 Rev Time 0.00
Received By jleech Date 2007-03-31 Time 12:22 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved