Plan Review Details - Permit 07031012
Plan Review Stops For Permit 07031012
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2007-05-18 Cont ID  
Sent By lursu Date 2007-05-18 Time 10:29 Rev Time 0.00
Received By lursu Date 2007-05-18 Time 10:29 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2007-09-11 Cont ID  
Sent By dpalmer Date 2007-09-11 Time 08:06 Rev Time 0.00
Received By dpalmer Date 2007-09-11 Time 08:06 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-04-15 Cont ID  
Sent By dpalmer Date 2007-04-15 Time 19:13 Rev Time 0.00
Received By dpalmer Date 2007-04-15 Time 19:13 Sent To  
Notes
2007-04-15 19:13:30REVIEW DONE UNDER 07031011

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2007-12-03 Cont ID  
Sent By mawillia Date 2007-12-03 Time 11:09 Rev Time 0.00
Received By mawillia Date 2007-12-03 Time 11:05 Sent To M
Notes
2007-12-03 11:09:41*****DENIED*****
  
  
 SEE MECHANICAL PLAN REVIEWER'S COMMENTS (REVISED PLAN
 TO BE FIRE-STAMPED WHEN MECHANICAL'S COMMENTS HAVE BEEN
 ADDRESSED)
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-09-10 Cont ID  
Sent By mawillia Date 2007-09-10 Time 16:04 Rev Time 0.00
Received By mawillia Date 2007-09-10 Time 15:59 Sent To M
Notes
2007-09-10 16:04:16*****APPROVED*****
  
  
 PLAN SHEET 1 OF 2 STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-05-17 Cont ID  
Sent By mawillia Date 2007-05-17 Time 13:51 Rev Time 0.00
Received By mawillia Date 2007-05-17 Time 13:43 Sent To  
Notes
2007-05-17 13:50:48*****DENIED*****
  
  
 MASTER PERMIT (07031011) HAS NOT BEEN ISSUED;
 SUB-PERMIT (07031012) SHALL NOT BE REVIEWED UNTIL THE
 MASTER IS ISSUED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-12-20 Cont ID  
Sent By rbrown Date 2007-12-20 Time 12:32 Rev Time 0.00
Received By rbrown Date 2007-12-20 Time 12:32 Sent To  
Notes
2007-12-20 12:33:02HOOD REVISION SENT TO "M" INBOX.ADVISED TOM GORDON.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-12-06 Cont ID  
Sent By adarroug Date 2007-12-06 Time 14:49 Rev Time 0.00
Received By adarroug Date 2007-12-06 Time 14:49 Sent To M
Notes
2007-12-06 14:53:20TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-11-30 Cont ID  
Sent By adarroug Date 2007-11-30 Time 14:26 Rev Time 0.00
Received By adarroug Date 2007-11-30 Time 14:26 Sent To M
Notes
2007-11-30 14:26:44TO "TGORDON" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-09-07 Cont ID  
Sent By tgordon Date 2007-09-07 Time 14:56 Rev Time 0.00
Received By tgordon Date 2007-09-07 Time 14:56 Sent To M
Notes
2007-09-07 14:56:57TO TOM G. DESK.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-05-17 Cont ID  
Sent By mawillia Date 2007-05-17 Time 13:43 Rev Time 0.00
Received By mawillia Date 2007-04-02 Time 17:11 Sent To  
Notes
2007-04-02 17:11:14TO COMM BOARD # 2

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2007-12-20 Cont ID  
Sent By tgordon Date 2007-12-20 Time 15:09 Rev Time 0.30
Received By tgordon Date 2007-12-20 Time 15:09 Sent To  
Notes
2007-12-20 15:11:01REVISION TO HOOD PLANS PAGES 1 OF 2 AND 2 OF 2.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2007-12-07 Cont ID  
Sent By tgordon Date 2007-12-07 Time 11:09 Rev Time 0.25
Received By tgordon Date 2007-12-07 Time 11:09 Sent To  
Notes
2007-12-07 11:16:39PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 ***REVISION DENIED ***
 1) CHANGES MAY NOT BE DONE BY HAND TO ENGINEER SEALED
 PLANS.
  
 2) THE CHANGES TO THE PLANS BY HAND DO NOT ADDRESS THE
 COMMENTS FROM THE LAST REVIEW 12-3-07 AND MAKE NO
 SENSE. PLEASE SEE NOTES FROM LAST REVIEW AND MAKE
 CORRECTIONS.
  
 ** NOTES FROM LAST REVIEW 12-3-07 **
 1) EXHAUST HOOD #1 HAS TWO 9"X16" EXHAUST DUCTS THE
 EXHAUST FAN IS 2,500 CFM'S , THAT WOULD PUT THE EXHAUST
 DUCT VELOCITY AT 1,250 CFM'S. SEE NOTE #4 ON PAGE 2 OF
 THE PLANS AND SEE 2004 FBC/M 506.3.4 STATES DUCT
 VELOCITY NOT LESS THAN 1,500 CFM'S. PLEASE CORRECT.
  
 2) PAGE 1 OF PLANS FRONT ELEVATION OF HOOD #1 SHOWS THE
 EXHAUST FAN AND CURB NOT TO BE SECURED TO THE ROOF,
 PLEASE COMPLY WITH 2004 FBC 1609.
  
 3) NEED TO ADD A FRONT VIEW FOR HOOD #2 TO THE PLANS.
  
 4) PAGE 1 SECTION VIEW FOR HOOD #1 IS LISTING THE
 SUPPLY AND EXHAUST FANS AS #1, PLEASE CORRECT.
  
 5) PLEASE LABEL HOODS AS #1 AND #2 ON PLAN.
  
 6) PAGE TWO HOOD SCHEDULE SHOWS HOOD 1 EXHAUST SIZE AS
 20X12, PLEASE CORRECT TO (2) 9X16.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2007-12-03 Cont ID  
Sent By tgordon Date 2007-12-03 Time 08:26 Rev Time 0.40
Received By tgordon Date 2007-12-03 Time 08:26 Sent To FIRE
Notes
2007-12-03 09:09:32PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 ***REVISION DENIED ***
 1) EXHAUST HOOD #1 HAS TWO 9"X16" EXHAUST DUCTS THE
 EXHAUST FAN IS 2,500 CFM'S , THAT WOULD PUT THE EXHAUST
 DUCT VELOCITY AT 1,250 CFM'S. SEE NOTE #4 ON PAGE 2 OF
 THE PLANS AND SEE 2004 FBC/M 506.3.4 STATES DUCT
 VELOCITY NOT LESS THAN 1,500 CFM'S. PLEASE CORRECT.
  
 2) PAGE 1 OF PLANS FRONT ELEVATION OF HOOD #1 SHOWS THE
 EXHAUST FAN AND CURB NOT TO BE SECURED TO THE ROOF,
 PLEASE COMPLY WITH 2004 FBC 1609.
  
 3) NEED TO ADD A FRONT VIEW FOR HOOD #2 TO THE PLANS.
  
 4) PAGE 1 SECTION VIEW FOR HOOD #1 IS LISTING THE
 SUPPLY AND EXHAUST FANS AS #1, PLEASE CORRECT.
  
 5) PLEASE LABEL HOODS AS #1 AND #2 ON PLAN.
  
 6) PAGE TWO HOOD SCHEDULE SHOWS HOOD 1 EXHAUST SIZE AS
 20X12, PLEASE CORRECT TO (2) 9X16.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-09-11 Cont ID  
Sent By tgordon Date 2007-09-11 Time 08:05 Rev Time 0.25
Received By tgordon Date 2007-09-11 Time 08:05 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-04-16 Cont ID  
Sent By tgordon Date 2007-04-16 Time 16:22 Rev Time 0.45
Received By tgordon Date 2007-04-16 Time 16:22 Sent To  
Notes
2007-04-16 16:26:24*** DENIED ***
 1) MASTER PERMIT # 07031011 NEEDS TO PASS REVIEW AND
 PERMIT PRINTED BEFORE ANY SUB-PERMITS MAY BE ISSUED.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop Z ZONING
Rev No 1 Status N Date 2007-04-10 Cont ID  
Sent By jroach Date 2007-04-10 Time 13:33 Rev Time 0.00
Received By jroach Date 2007-04-10 Time 13:33 Sent To  
Notes
***NONE***