Plan Review Details - Permit 07031011
Plan Review Stops For Permit 07031011
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2007-05-29 Cont ID  
Sent By lursu Date 2007-05-29 Time 11:16 Rev Time 0.00
Received By lursu Date 2007-04-16 Time 16:22 Sent To  
Notes
2007-04-17 15:50:47THE SITE ADDRESS ON THE APPLICATION IS 3010 S DIXIE
 HWY.THE ADDRESS WAS FIELD VERIFIED AND BELONGS TO
 PARCEL CONTROL NUMBER = 74 43 43 34 16 000 0010 AND NOT
 PCN = 74 43 43 34 04 002 0010 AS ON THE APPLICATION.THE
 OWNER INFO ON THE PAPA WEBSITE IS THE SAME FOR BOTH
 PARCELS.HOWEVER PERMIT IS APPLIED TO THE CORRECT PCN.
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-12-01 Cont ID  
Sent By mjacobs Date 2007-12-01 Time 06:12 Rev Time 0.00
Received By mjacobs Date 2007-12-01 Time 05:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-08-30 Cont ID  
Sent By mjacobs Date 2007-08-30 Time 07:13 Rev Time 0.00
Received By mjacobs Date 2007-08-30 Time 06:07 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-06-21 Cont ID  
Sent By mjacobs Date 2007-06-21 Time 14:29 Rev Time 0.00
Received By mjacobs Date 2007-06-21 Time 12:30 Sent To  
Notes
2007-06-21 14:28:29BUILDING PLAN REVIEW
 PERMIT: 07031011
 ADD: 3010 S. DIXIE HWY
 CONT: MIKE MOORE CONSTRUCTION
 TEL: (561)748-7000
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 2ND
 ACTION: DENIED
  
 **************NO RESPONSE WERE GIVEN***************
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)61G1-16.004 TITLE BLOCK.
 A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR
 INTERIOR DESIGN DRAWINGS AND SPECIFICATION
 IDENTIFICATION SHEETS. THE TITLE BLOCK MUST, AT A
 MINIMUM, CONTAIN THE FOLLOWING INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER.
 (2) FIRM LICENSE NUMBER.
 (3) NAME OR IDENTIFICATION OF PROJECT.
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED SEAL.
 (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING
 THE DOCUMENT.
  
 3)108.3* THE CLAIMED VALUATION ON THE PERMIT
 APPLICATION IS LOW.IF, IN THE OPINION OF THE BUILDING
 OFFICIAL, THE CLAIMED VALUATION OF BUILDING,
 ALTERATION, STRUCTURE, ELECTRUCAL, GAS, MECHANICAL OR
 PLUMBING SYSTEMS APPEARS TO BE UNDERESTIMATED ON THE
 APPLICATION, THE PERMIT SHALL BE DENIED. FOR PERMITTING
 PURPOSES, VALUATION SHALL BE THE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH ARCHITECTURAL AND DESIGN
 FEES, MARKETING COST, AND OVERHEAD AND PROFIT EXCLUDING
 LAND VALUE.
  
 4)110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING.
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PROJECT WAS DESIGNED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE DESIGN OCCUPANT LOAD, SEE 1004.
 D) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 E) SQ. FT. FOOTPRINT
 F) SQ. FT. UNDER ROOF (TOTAL)
 G) OCCUPANT LOAD
  
 5)11-4.32.2 SEATING.
 IF SEATING SPACES FOR PEOPLE IN WHEELCHAIRS ARE
 PROVIDED AT FIXED TABLES OR COUNTERS, CLEAR FLOOR SPACE
 COMPLYING WITH SECTION 11-4.2.4 SHALL BE PROVIDED. SUCH
 CLEAR FLOOR SPACE SHALL NOT OVERLAP KNEE SPACE BY MORE
 THAN 19 INCHES (485 MM) (SEE FIGURE 45 ). 11-4.32.3
 KNEE CLEARANCES.IF SEATING FOR PEOPLE IN WHEELCHAIRS IS
 PROVIDED AT TABLES OR COUNTERS, KNEE SPACES AT LEAST 27
 INCHES (685 MM) HIGH, 30 INCHES (760 MM) WIDE, AND 19
 INCHES (485 MM) DEEP SHALL BE PROVIDED (SEE FIGURE 45
 ). SHOW HOW THE TABLES ON SHEET A-1 WILL MEET THE
 REQUIREMENTS OF FIG 45 BY INDICATING THE DIMENTIONS OF
 THE TABLEAND SHOWING THE CLEAR FLOOR SPACE ON THE
 PLANS.
  
 6)INDICATE THE TYPE OF ALTERATION OF THE PROJECT IN
 ACCORDANCE WITH CH 3 OF THE 2004 FLORIDA EXISTING
 BUILDING CODE.
  
 7)FBC.1210.1 FLOORS. IN OTHER THAN DWELLING UNITS,
 TOILET AND BATHING ROOM FLOORS SHALL HAVE A SMOOTH,
 HARD, NONABSORBENT SURFACE THAT EXTENDS UPWARD ONTO THE
 WALLS AT LEAST 6 INCHES (152 MM).
  
 8)FBC.1210.2WALLS WITHIN 2 FEET (610 MM) OF URINALS
 AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD,
 NONABSORBENT SURFACE, TO A HEIGHT OF 4 FEET (1219 MM)
 ABOVE THE FLOOR, AND EXCEPT FOR STRUCTURAL ELEMENTS,
 THE MATERIALS USED IN SUCH WALLS SHALL BE OF A TYPE
 THAT IS NOT ADVERSELY AFFECTED BY MOISTURE.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-05-31 Cont ID  
Sent By mjacobs Date 2007-05-31 Time 14:59 Rev Time 0.00
Received By mjacobs Date 2007-05-31 Time 11:09 Sent To PC
Notes
2007-05-31 14:59:03 
  
  
  
  
 BUILDING PLAN REVIEW
 PERMIT: 07031011
 ADD: 3010 S. DIXIE HWY
 CONT: MIKE MOORE CONSTRUCTION
 TEL: (561)748-7000
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)61G1-16.004 TITLE BLOCK.
 A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR
 INTERIOR DESIGN DRAWINGS AND SPECIFICATION
 IDENTIFICATION SHEETS. THE TITLE BLOCK MUST, AT A
 MINIMUM, CONTAIN THE FOLLOWING INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER.
 (2) FIRM LICENSE NUMBER.
 (3) NAME OR IDENTIFICATION OF PROJECT.
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED SEAL.
 (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING
 THE DOCUMENT.
  
 3)108.3* THE CLAIMED VALUATION ON THE PERMIT
 APPLICATION IS LOW.IF, IN THE OPINION OF THE BUILDING
 OFFICIAL, THE CLAIMED VALUATION OF BUILDING,
 ALTERATION, STRUCTURE, ELECTRUCAL, GAS, MECHANICAL OR
 PLUMBING SYSTEMS APPEARS TO BE UNDERESTIMATED ON THE
 APPLICATION, THE PERMIT SHALL BE DENIED. FOR PERMITTING
 PURPOSES, VALUATION SHALL BE THE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH ARCHITECTURAL AND DESIGN
 FEES, MARKETING COST, AND OVERHEAD AND PROFIT EXCLUDING
 LAND VALUE.
  
 4)110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING.
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PROJECT WAS DESIGNED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE DESIGN OCCUPANT LOAD, SEE 1004.
 D) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 E) SQ. FT. FOOTPRINT
 F) SQ. FT. UNDER ROOF (TOTAL)
 G) OCCUPANT LOAD
  
 5)11-4.32.2 SEATING.
 IF SEATING SPACES FOR PEOPLE IN WHEELCHAIRS ARE
 PROVIDED AT FIXED TABLES OR COUNTERS, CLEAR FLOOR SPACE
 COMPLYING WITH SECTION 11-4.2.4 SHALL BE PROVIDED. SUCH
 CLEAR FLOOR SPACE SHALL NOT OVERLAP KNEE SPACE BY MORE
 THAN 19 INCHES (485 MM) (SEE FIGURE 45 ). 11-4.32.3
 KNEE CLEARANCES.IF SEATING FOR PEOPLE IN WHEELCHAIRS IS
 PROVIDED AT TABLES OR COUNTERS, KNEE SPACES AT LEAST 27
 INCHES (685 MM) HIGH, 30 INCHES (760 MM) WIDE, AND 19
 INCHES (485 MM) DEEP SHALL BE PROVIDED (SEE FIGURE 45
 ). SHOW HOW THE TABLES ON SHEET A-1 WILL MEET THE
 REQUIREMENTS OF FIG 45 BY INDICATING THE DIMENTIONS OF
 THE TABLEAND SHOWING THE CLEAR FLOOR SPACE ON THE
 PLANS.
  
 6)INDICATE THE TYPE OF ALTERATION OF THE PROJECT IN
 ACCORDANCE WITH CH 3 OF THE 2004 FLORIDA EXISTING
 BUILDING CODE.
  
 7)FBC. 1210.1 FLOORS. IN OTHER THAN DWELLING UNITS,
 TOILET AND BATHING ROOM FLOORS SHALL HAVE A SMOOTH,
 HARD, NONABSORBENT SURFACE THAT EXTENDS UPWARD ONTO THE
 WALLS AT LEAST 6 INCHES (152 MM).
  
 8)FBC. 1210.2WALLS WITHIN 2 FEET (610 MM) OF
 URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD,
 NONABSORBENT SURFACE, TO A HEIGHT OF 4 FEET (1219 MM)
 ABOVE THE FLOOR, AND EXCEPT FOR STRUCTURAL ELEMENTS,
 THE MATERIALS USED IN SUCH WALLS SHALL BE OF A TYPE
 THAT IS NOT ADVERSELY AFFECTED BY MOISTURE.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-11-29 Cont ID  
Sent By dpalmer Date 2007-11-29 Time 15:05 Rev Time 0.00
Received By dpalmer Date 2007-11-29 Time 15:05 Sent To  
Notes
2007-11-29 15:06:03REV FOR DEVICE AND LOCATION CHANGES.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-08-14 Cont ID  
Sent By dpalmer Date 2007-08-14 Time 10:58 Rev Time 0.00
Received By dpalmer Date 2007-08-14 Time 10:58 Sent To I
Notes
2007-08-14 11:18:44PLANS REMOVED FROM INCOMING , REVIEW OK, STAMPED FOR
 ELECTRICAL SHEETS AND SENT BACK TO INCOMING TABLE
 WAITING FOR COMM BOARD.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-06-22 Cont ID  
Sent By dpalmer Date 2007-06-22 Time 09:03 Rev Time 0.00
Received By dpalmer Date 2007-06-22 Time 07:01 Sent To  
Notes
2007-06-22 09:03:45*** UNSAT 2ND REVIEW ***
  
 *** PLEASE SEE MANY ITEMS FROM PREVIOUS REVIEW HAVE NOT
 BEEN ADDRESSED AND THERE ARE SOME NEW COMMENTS DUE TO
 CHANGES IN PLANS. PLEASE SEE THAT MOST OF THE ITEMS ARE
 FROM PREVIOUS REVIEW.
  
 ** ONCE AGAIN, DUE TO THE AMOUNT OF COMMENTS AND
 UN-LICENSED INFORMATION, ONE SET OF PLANS ARE BEING
 RETAINED BY THIS OFFICE.
  
 1) NOTE:PLEASE SEE THE TITLE BLOCKS FOR ARCHITECTURAL
 FIRM. AS STATED ON PREVIOUS REVIEW NOT CERTIFICATE OF
 AUTHORIZATION NUMBER IS ON PLANS AND NOT INFORMATION ON
 THE DEPARTMENT OF BUSINESS AND PROFESSIONAL REGULATION
 FROM THE STATE COULD BE LOCATED. PLANS ARE BEING
 RETAINED AND INFORMATION TO THE STATE BOARD OF
 ARCHITECTS AND STATE LEGAL COUNSEL TO THE BOARD WILL BE
 NOTIFIED.
 PLEASE SEE THE ARCHITECTURAL FIRM IS MISSING THE
 REQUIRED LICENSURE PER FS 481.219 AND FAC 61G1-16.004.
 PLEASE INCLUDE ON ALL SHEETS AND FOR ALL TRADES WHETHER
 OR NOT COMMENT IS MADE BY OTHER REVIEWERS.
  
 2) NOTE: PLEASE CORRELATE RISER, ELECTRICAL NOTES,
 PANEL SCHEDULE AND PLANS.
 PLEASE SEE THE ELECTRICAL RISER IS STILL SHOWING A NEW
 SERVICE WHICH IS NOT PERMITTED AND IS NOT GRANTED BY
 THIS OFFICE. PLEASE SEE THE PREVIOUS NOTES ON PLANS HAD
 SOME DIFFERENCES IN THE SIZE OF SERVICE AND NOW THEY
 HAVE BEEN CHANGED BUT HOWEVER ARE STILL NOT CORRECT.
 PLEASE SEE THE ELECTRICAL SERVICE IS BEING SHOWN AS A
 300A PANEL IN ONE NOTE, 200AMP IN ANOTHER NOTE.
 THIS LOCATION HAS BEEN LOOKED AT BY THIS OFFICE AND THE
 TENANT SPACE DOES NOT FALL UNDER THE DEFINITION OF A
 *BUILDING*. PLEASE SEE THAT COMPLETE INFORMATION FOR
 THE ENTIRE BUILDING NEEDS TO BE PROVIDED AS THIS SEEMS
 TO BE A TENANT SPACE WHICH IS PART OF A LARGER
 BUILDING. PLEASE KNOW THAT ADDITIONAL SERVICE IS NOT
 BEING GRANTED AS IT DOES NOT MEET 230.2. THERE IS NO
 INDICATION ON PLANS WHICH SHOWS COMPLIANCE WITH THE FBC
 TO CONSIDER THIS A *SEPARATE BUILDING BY DEFINITION*.
 PLEASE KNOW THAT THE SERVICE WHICH FEEDS THE BUILDING
 WILL NEED TO UP-GRADED IF THE EXISTING SERVICE IS NOT
 OF SUFFICIENT SIZE.
 ** PLEASE SUBMIT A COMPLETED RISER DIAGRAM FOR EXISTING
 SERVICE OR NEW. AS THE SERVICE AS PERMITTED HAS NOT
 BEEN SHOWN A REVIEW OF SERVICE CAN NOT BE DONE AT THIS
 TIME.
  
 3) NOTE: PLEASE SEE THE PREVIOUS NOTES REQUESTED A
 COMPLETED RISER HOWEVER SOME OF THE INFORMATION IS
 STILL NOT ON PLANS. PLEASE SEE THE GROUNDING ELECTRODE
 SYSTEM AS REQUIRED PER 250.50 IS NOW SHOWING THE
 BUILDING/FOOTER STEEL? THIS IS AN EXISTING BUILDING AND
 THE EXISTING FOOTER STEEL IS NOT REQUIRED TO BE
 UNCOVERED IF THE ATTACHMENT IS NOT ALREADY MADE. THIS
 WOULD INDEED AFFECT THE STRUCTURAL INTEGRITY OF THE
 EXISTING FOOTER
 PLEASE INCLUDE AIC RATINGS FOR ALL NEW SERVICE
 EQUIPMENT.
 PLEASE SEE 215.5, 110.9, 240.4, 310.16, 230.70
  
 4) NOTE: PLEASE SUBMIT PLANS WHICH ARE COMPLIANT WITH
 THE 2004 FBC W/2006 REVISIONS FOR CHAPTER 13 AS
 PREVIOUSLY REQUESTED. PLEASE SEE 13-413.1ABC.1,
 13-415.1.ABC.1.1, .1.2 AND .1.3. PLEASE SEE
 13-415.1.AB.1.1, 13-415.2.
 PLEASE SEE A LIGHTING CONTROL PANEL IS NOW NOTED BUT
 THE NO INFORMATION WAS SHOWN FOR THE LIGHTING CONTROL
 PANEL OR SYSTEM.
 PLEASE SEE NOT TIMED SCHEDULING WAS SUBMITTED.
 PLEASE SEE NO TIMES WERE INDICATED FOR OVER RIDES.
 PLEASE SEE NO SPECIFIC TYPES OF DEVICES ARE INDICATED.
 PLEASE SEE ALL LOCATIONS FOR OVER RIDES ARE NOT SHOWN
 AS REQUIRED PER SECTIONS ABOVE.
 PLEASE SEE NOT ALL SEPARATE SPACES ARE SHOWING REQUIRED
 DEVICES.
 PLEASE SEE THE LIGHTING POWER DENSITIES ARE NOT
 CORRECT.
 PLEASE SEE TRACK LIGHTING PER 13-415.2.ABC.1.2 WAS NOT
 SHOWN OR CORRECT.
 PLEASE SEE13-415.2.ABC.1.2 (3, 4)
 NO FIXTURE LEGEND WAS SUBMITTED WHICH INDICATES THE
 FIXTURES AS NOTED ON PLANS, NO WATTAGE ON FIXTURES ETC
 NO ENERGY CALCULATIONS/PERFORMANCE CALCULATIONS, ETC
 AS THERE IS MUCH INFORMATION FOR CHAPTER 13 WHICH WAS
 NOT SUBMITTED, REVIEW FOR MANY OF THESE ITEMS CAN NOT
 BE DONE AT THIS TIME.
  
 5) NOTE: PLEASE SUBMIT PLANS DESIGNED FOR COMMERCIAL
 LOAD CALCULATIONS. THIS WAS NOT DONE, IN FACT NO LOAD
 CALCULATIONS WERE SUBMITTED AND ONLY LOADS ON
 CIRCUITING ON PANEL SCHEDULES WAS SHOWN.
 PLEASE SEE 220.12, 220.14, 220.42, 220.44, 220.43
 215.5, 230.42 ETC.
 PLEASE SEE THAT ALL CONTINUOUS LOADS SHALL BE SHOWN AT
 125% 215.3, 230.42. THIS WAS SHOWN, HOWEVER PLEASE BE
 SURE TO FIGURE INTO SERVICE.
 ** PLEASE KNOW DEPENDING ON SERVICE, LOAD CALCULATIONS
 FOR THE EXISTING SERVICE OR NEW PROPOSED *BUILDING*
 SERVICE MAY BE NEEDED. AS NO INFORMATION FOR THE
 *BUILDINGS* SERVICE WAS GIVEN WE CAN NOT DETERMINE MANY
 THINGS.
  
 6) NOTE: PLEASE SHOW AND INDICATE ALL CIRCUITING ON
 PLANS AND CORRELATE WITH THE PANEL SCHEDULE(S) TO BE
 SUBMITTED. THIS NOTE REMAINS FROM PREVIOUS REVIEW AS
 SOME ITEMS ARE MISSING FROM PLANS.
  
 7) NOTE:PLEASE SEE NEW HORN/STROBES ARE SHOWN ON
 PLANS HOWEVER NO MINIMUM LEVELS FOR ADA COMPLIANCE WAS
 SHOWN.PLEASE SEE FBC 2004 11-4.28.1, .2 AND .3(4) AND
 STATE THE MINIMUM HORN, STROBE LEVELS ON PLANS FOR ADA
 REQUIRED AREAS. DEVICES ARE BEING SHOWN ON
 PLANS/LEGEND.(QUOTING THAT THE DEVICES WILL BE ADA
 COMPLIANT IN LIEU OF INDICATING THE MINIMUM LEVELS
 REQUIRED PER CODE IS NOT PERMITTED)
  
 ** PLEASE KNOW THAT THE FIRE ALARM DEVICES/SYSTEM WILL
 BE UNDER A SEPARATE PERMIT HOWEVER THE BASE LIFE SAFETY
 SYSTEM IS REQUIRED ON BASE PLANS AS SHOWN. DO NOT
 REMOVE FROM SETS.
 FBC 106.3.5.1.2
  
 8) NOTE:SAME NOTE FROM PREVIOUS REVIEW. NOTES WERE
 PLACED ON PLANS HOWEVER THE INDICATE OF THESE BREAKERS
 ON PANEL SCHEDULES COULD NOT BE LOCATED. PLEASE
 INDICATE ALL SHUNT TRIP CIRCUITS FOR ANY ELECTRICAL
 UNDER HOOD PER NFPA-96. CHAPTER 9 AND 10.
  
 9) NOTE: PLEASE SEE 210.8B3 FOR REQUIRED GFCI
 PROTECTION OF ALL 15/20AMP 120V CIRCUITS IN KITCHENS
 WHETHER OR NOT THEY ARE COUNTER SPACE CIRCUITS. PLEASE
 SEE NOTES WERE ADDED AND MOST ARE SHOWN HOWEVER NOT
 ALL.
  
 10) NOTE: PLEASE INDICATE LOADS FOR TRACK LIGHTING ON
 SERVICE PER 220.43B.
 THIS IS NOT THE SAME AS THE LOADS FIGURED FOR FBC
 CHAPTER 13 COMPLIANCE. PLEASE SEE THE LOADS FOR CHAPTER
 13 ARE MORE RESTRICTIVE FOR LPD.
 PLEASE SEE THIS IS THE SAME AS PREVIOUS REVIEW.
  
 12) NOTE: PLEASE SEE THE SIGN CIRCUIT AND WINDOW
 RECEPTACLES WERE ADDED TO PLANS HOWEVER PLEASE VERIFY
 THE NEW LIGHTING SWITCHES BEING ADDED TO PLANS ARE
 BEING SHOWN OUTSIDE THE FRONT OF THE STORE AS SHOWN ON
 PLANS?
  
 13) NOTE: PLEASE SEE MISSING DISCONNECT FOR WATER
 HEATER PER 422.30,.31
 MAY NOT QUOTE REQUIREMENT OR CODE.
  
 14) NOTE: PLEASE SEE MISSING DISCONNECT FOR A/C CU PER
 440.11.
 MAY NOT QUOTE REQUIREMENT OR CODE IN LIEU OF DETAIL.
  
 15) NOTE: PLEASE SEE MISSING GFI RECEPTACLE FOR CU.
 210.63,210.8B
  
 16) NOTE: PLEASE SEE NOTE ON PLANS MENTIONS NEW
 HARD-WIRED SMOKE DETECTORS WHICH TO BE INSTALLED
 HOWEVER NONE OF THESE COULD BE LOCATED ON PLANS ALONG
 WITH CIRCUITING. IF A FA SYSTEM IS GOING TO BE
 INSTALLED AS SHOWN ON PLANS, PLEASE SHOW HOW THESE SDS
 WILL BE CONNECTED.
  
 17) NOTE: PLEASE SEE THE CONDUCTORS ON PANEL SCHEDULE
 FOR FEEDERS TO PANEL *B* ARE BEING SHOWN AS #12 WHEN
 RISER SHOWS #3.
 PLEASE SEE 240.4, 310.16.
  
 18) NOTE: PLEASE SEE THE VALUE WAS STILL NOT ADJUSTED
 ON PERMIT APPLICATION OR EVEN RESPONDED TO. PLEASE SEE
 THE VALUATION FOR THE COMPLETE SCOPE OF WORK IS
 EXTREMELY LOW. ALL VALUE SHALL BE BASED ON LABOR,
 MATERIALS AND ALL PERMANENTLY INSTALLED EQUIPMENT EVEN
 IF OWNER SUPPLIED.
 FBC 108.3
 PLEASE KNOW IF VALUES ARE NOT ADJUSTED, THE ADOPTED
 STANDARDS BY THE FBC MAY BE USED.
  
 19) NOTE: PLEASE SEE THE NOC AS SUBMITTED HAS BECOME
 VOID PER FS 713.13(2). THIS WILL BE NEEDED TO BE
 RE-RECORDED AND SUBMITTED BEFORE PERMIT CAN BE PICKED
 UP. PLEASE KNOW THAT ONCE A NOC HAS BEEN RECORDED, THE
 SCOPE OF WORK MUST COMMENCE WITHIN 90DAYS OR THE NOC
 BECOMES VOID.
  
 20) NOTE: PLEASE SEE ATTACHED FS 553.80(2)(B) WITH
 RESPECT TO REPEAT COMMENTS FOR CODE COMPLIANCE AS
 SEVERAL COMMENTS WERE REPEATED FROM PREVIOUS REVIEW.
 PLEASE KNOW THIS IS ONLY A NOTICE GIVEN AT THIS TIME.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-04-15 Cont ID  
Sent By dpalmer Date 2007-04-15 Time 19:08 Rev Time 0.00
Received By dpalmer Date 2007-04-15 Time 18:18 Sent To  
Notes
2007-04-15 19:08:48** UNSAT **
  
 ** PLEASE KNOW THAT PLANS ARE NOT COMPLETE AT THIS TIME
 FOR A FULL AND COMPLETE REVIEW. THERE MAY VERY WELL BE
 NEW COMMENTS ONCE PLANS ARE COMPLETED FOR REVIEW.
  
 ** PLEASE SEE ANY REFERENCES IN PLAN REVIEW NOTES TO
 CHAPTER 1 OF THE FBC ARE THAT WHICH IS ADOPTED BY THE
 CITY OF WEST PALM BEACH.
  
 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH
 ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS
 UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLANS AT THIS TIME DO NOT INDICATE ANY CODES. PLEASE
 SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO THE 2004
 FBC FOR ALL TRADES AND THE 2005 NFPA-70. PLEASE KNOW
 THERE ARE CHANGES IN THE FBC WHICH MAY AFFECT DESIGNS
 FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 2) NOTE: PLEASE CORRELATE RISER, ELECTRICAL NOTES,
 PANEL SCHEDULE AND PLANS.
 PLEASE SEE THE ELECTRICAL SERVICE IS BEING SHOWN AS A
 400A PANEL IN ONE NOTE, 300AMP IN ANOTHER NOTE, 300A ON
 PANEL SCHEDULE, YET RISER DOES NOT MATCH ANY OF THESE?
 PLEASE SEE THAT COMPLETE INFORMATION FOR THE ENTIRE
 BUILDING NEEDS TO BE PROVIDED AS THIS SEEMS TO BE A
 TENANT SPACE WHICH IS PART OF A LARGER BUILDING. PLEASE
 KNOW THAT ADDITIONAL SERVICE IS NOT BEING GRANTED AS IT
 DOES NOT MEET 230.2. THERE IS NO INDICATION ON PLANS
 WHICH SHOWS COMPLIANCE WITH THE FBC TO CONSIDER THIS A
 *SEPARATE BUILDING BY DEFINITION*.
 PLEASE KNOW THAT THE SERVICE WHICH FEEDS THE BUILDING
 WILL NEED TO UPGRADED IF THE EXISTING SERVICE IS NOT OF
 SUFFICIENT SIZE.
 ** PLEASE SUBMIT A COMPLETED RISER DIAGRAM FOR EXISTING
 SERVICE OR NEW.
 PLEASE INCLUDE GROUNDING ELECTRODE SYSTEM AS REQUIRED
 PER 250.50. (QUOTING THE CODE IS NOT PERMITTED IN LIEU
 OF REQUIRED CODE COMPLIANT DETAIL)
 PLEASE INCLUDE AIC RATINGS FOR ALL NEW SERVICE
 EQUIPMENT.
 PLEASE SEE 215.5, 110.9, 240.4, 310.16, 230.70 ETC A
 REVIEW FOR SERVICE CAN NOT BE DONE AT THIS TIME.
  
 3) NOTE: PLEASE SUBMIT PLANS WHICH ARE COMPLIANT WITH
 THE 2004 FBC W/2006 REVISIONS FOR CHAPTER 13. PLEASE
 SEE 13-413.1ABC.1, 13-415.1.ABC.1.1, .1.2 AND .1.3.
 PLEASE SEE 13-415.1.AB.1.1, 13-415.2.
 PLEASE INDICATE ALL MAXIMUM TIMES ON OVER RIDE DEVICES.
 PLEASE SUBMIT DETAILS ON METHODS WHICH WILL BE
 INSTALLED.
 PLEASE SEE13-415.2.ABC.1.2 (3, 4)
 NO FIXTURE LEGEND WAS SUBMITTED, NO ENERGY
 CALCULATIONS, NO PERFORMANCE CALCULATIONS, ETC
 AS NO INFORMATION FOR CHAPTER 13 WAS SUBMITTED, REVIEW
 FOR THESE ITEMS CAN NOT BE DONE AT THIS TIME.
  
 4) NOTE: PLEASE SUBMIT PLANS DESIGNED FOR COMMERCIAL
 LOAD CALCULATIONS.
 PLEASE SEE 220.12, 220.14, 220.42, 220.44, 220.43
 215.5, 230.42 ETC.
 PLEASE SEE THERE ARE CIRCUITS WHICH ARE OVER LOADED.
 PLEASE SEE NO LOADS ARE SHOWN FOR COMMERCIAL
 APPLICATION.
 PLEASE SEE THAT ALL CONTINUOUS LOADS SHALL BE SHOWN AT
 125% 215.3, 230.42
  
 5) NOTE: PLEASE SHOW AND INDICATE ALL CIRCUITING ON
 PLANS AND CORRELATE WITH THE PANEL SCHEDULE(S) TO BE
 SUBMITTED.
 PLEASE SEE 408.4 OF THE NEC, AND THE FOLLOWING TEXT
 BELOW WHICH IS TAKEN DIRECTLY FROM THE NEC.
 PLEASE KNOW THAT THE PLANS NEED TO LABEL AND PROVIDE
 ROOM AND AREA DESIGNATIONS ON PLANS AND CORRELATE WITH
 THE PANEL SCHEDULES SHOWING ALL ROOMS AND AREAS IN
 WHICH CIRCUITS FEED WILL BE REQUIRED FOR EACH PANEL.
 PLEASE SEE TEXT WHICH IS TAKEN FROM COMMENTARY IN THE
 CODE WHICH STATES THE USE OF *GEN LT* ETC IS NOT
 ACCEPTABLE
  
 *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE
 THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A
 PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE
 THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED.
 CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED
 AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE
 BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN,
 DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE
 CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT
 ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS
 ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR
 RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT
 OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE
 ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT
 PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS
 SECTION.*
 408.4, 310.16, 240.4 ETC
 FBC 106.3.5.4
  
 6) NOTE: PLEASE SEE 700.12E FOR CIRCUITING OF EMERGENCY
 AND EXIT LIGHTS.
  
 7) NOTE: PLEASE SEE FBC 2004 11-4.28.1, .2 AND .3(4)
 AND STATE THE MINIMUM HORN, STROBE LEVELS ON PLANS FOR
 ADA REQUIRED AREAS. DEVICES ARE BEING SHOWN ON
 PLANS/LEGEND.(QUOTING THAT THE DEVICES WILL BE ADA
 COMPLIANT IN LIEU OF INDICATING THE MINIMUM LEVELS
 REQUIRED PER CODE IS NOT PERMITTED)
  
 ** PLEASE KNOW THAT THE FIRE ALARM DEVICES/SYSTEM WILL
 BE UNDER A SEPARATE PERMIT HOWEVER THE BASE LIFE SAFETY
 SYSTEM IS REQUIRED ON BASE PLANS AS SHOWN. DO NOT
 REMOVE FROM SETS.
 FBC 106.3.5.1.2
  
 8) NOTE: PLEASE INDICATE ALL SHUNT TRIP CIRCUITS FOR
 ANY ELECTRICAL UNDER HOOD PER NFPA-96. CHAPTER 9 AND
 10.
  
 9) NOTE: PLEASE SEE 210.8B3 FOR REQUIRED GFCI
 PROTECTION OF ALL 15/20AMP 120V CIRCUITS IN KITCHENS
 WHETHER OR NOT THEY ARE COUNTER SPACE CIRCUITS.
  
 10) NOTE: PLEASE SEE SOME LOADS ON PANEL EXCEED THAT OF
 THE RATED 20AMP CIRCUIT.
 PLEASE SEE SHOW WINDOWS.
 PLEASE INDICATE THE LOADS ON SHOW WINDOWS FOR BRANCH
 CIRCUITS AND FEEDERS/SERVICE PER 220.43
  
 11) NOTE: PLEASE INDICATE LOADS FOR TRACK LIGHTING ON
 SERVICE PER 220.43B.
 THIS IS NOT THE SAME AS THE LOADS FIGURED FOR FBC
 CHAPTER 13 COMPLIANCE. PLEASE SEE THE LOADS FOR CHAPTER
 13 ARE MORE RESTRICTIVE.
  
 12) NOTE: PLEASE SEE 600.5 FOR MISSING SIGN CIRCUIT AND
 LOADS IN CALCULATIONS.
  
 13) NOTE: PLEASE SEE THE VALUATION FOR THE COMPLETE
 SCOPE OF WORK IS EXTREMELY LOW. ALL VALUE SHALL BE
 BASED ON LABOR, MATERIALS AND ALL PERMANENTLY INSTALLED
 EQUIPMENT EVEN IF OWNER SUPPLIED.
 FBC 108.3
 PLEASE KNOW IF VALUES ARE NOT ADJUSTED, THE ADOPTED
 STANDARDS BY THE FBC MAY BE USED.
  
 14) NOTE: PLEASE SEE THE ARCHITECTURAL FIRM IS MISSING
 THE REQUIRED LICENSURE PER FS 481.219 AND FAC
 61G1-16.004.
 PLEASE INCLUDE ON ALL SHEETS AND FOR ALL TRADES WHETHER
 OR NOT COMMENT IS MADE BY OTHER REVIEWERS.
  
 15) NOTE: PLEASE COMPLETE PANEL SCHEDULE(S) WITH ALL
 BREAKER/OCP DEVICES AND CONDUCTOR SIZES.
 408.4.
 310.16, 240.4
 FBC 106.3.5.1.2, 106.1.2
  
 ** PLEASE KNOW DUE TO THE EXTENT OF ELECTRICAL
 COMMENTS, NO LICENSING FOR THE ARCHITECTURAL FIRM, ONE
 SET OF PLANS WILL BE RETAINED BY THIS OFFICE.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2007-12-10 Cont ID  
Sent By mawillia Date 2007-12-10 Time 13:10 Rev Time 0.00
Received By mawillia Date 2007-12-10 Time 12:57 Sent To  
Notes
2007-12-10 13:07:00*****APPROVED REVISION DATED 11/16/07*****
  
  
 REVISED PLAN SHEET A-1 STAMPED, INITIALED, AND DATED.
  
  
 .
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-08-30 Cont ID  
Sent By mawillia Date 2007-08-30 Time 10:15 Rev Time 0.00
Received By mawillia Date 2007-08-30 Time 09:39 Sent To  
Notes
2007-08-30 10:15:11*****APPROVED*****
  
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE
 BEEN ADDRESSED;PLAN SHEET A-1 STAMPED, INITIALED, AND
 DATED.
  
  
 .
  
  
  
  
  
  
  
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-07-10 Cont ID  
Sent By mawillia Date 2007-07-10 Time 13:47 Rev Time 0.00
Received By mawillia Date 2007-07-10 Time 12:31 Sent To  
Notes
2007-07-10 13:46:48*****DENIED*****
  
  
 1.NFPA 101 (2003 EDITION) AND THE FLORIDA FIRE
 PREVENTION CODE (2004 EDITION) SHALL BE REFERENCED.
  
 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL NOT
 INTERFERE OR HINDER EMERGENCY RESPONSE ACCESS TO THE
 PROPERTY OR VICINITY THEREOF (INCLUDING STREETS, ROADS,
 FIRE LANES).
  
 4. COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE DAILY OR MORE FREQUENTLY AS
 NECESSARY FOR SAFE OPERATION.
  
 5.ON THE EXTERIOR ELEVATION WHICH FRONTS SOUTH DIXIE
 HIGHWAY, DISPLAY THE NUMERICAL ADDRESS FOR THIS
 PROJECT.AS PER WEST PALM BEACH CODE, ADDRESS NUMBERS
 SHALL BE NO LESS THAN 6" IN HEIGHT AND NO LESS THAN 1"
 IN WIDTH.
  
 6.PLEASE GIVE THE FOLLOWING INFORMATION:* OCCUPANCY
 TYPE, * OCCUPANT LOAD, * FIRE SPRINKLERED OR NOT, *
 INTERIOR FINISH CLASSIFICATIONS FOR WALLS AND CEILINGS
 MATERIALS
  
 7.COMMERCIAL COOKING EQUIPMENT SHALL BE IN ACCORDANCE
 WITH NFPA 96. SEPARATE PLANS AND PERMIT WILL BE
 REQUIRED.
  
 8.PLEASE BE ADVISED THAT THE SUBMITTED SUB-PERMIT
 PLANS FOR THE COOKING HOOD INSTALLATION AND THE COOKING
 HOOD SUPPRESSION SYSTEM WILL NOT BE REVIEWED UNTIL SUCH
 TIME THAT THE "MASTER" PERMIT HAS BEEN ISSUED.
  
 9.THE ADDRESS NUMBER ON SHEET A-1 & A-2 ARE NOT THE
 SAME AS THE OTHER SUBMITTED PLAN SHEETS.PLEASE
 AMEND.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLANS EACH COMMENT WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-07-10 Cont ID  
Sent By mawillia Date 2007-05-17 Time 13:25 Rev Time 0.00
Received By mawillia Date 2007-05-17 Time 12:42 Sent To  
Notes
2007-05-17 13:25:25*****DENIED*****
  
  
 1.NFPA 101 (2003 EDITION) AND THE FLORIDA FIRE
 PREVENTION CODE (2004 EDITION) SHALL BE REFERENCED.
  
 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL NOT
 INTERFERE OR HINDER EMERGENCY RESPONSE ACCESS TO THE
 PROPERTY OR VICINITY THEREOF (INCLUDING STREETS, ROADS,
 FIRE LANES).
  
 4. COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE DAILY OR MORE FREQUENTLY AS
 NECESSARY FOR SAFE OPERATION.
  
 5.ON THE EXTERIOR ELEVATION WHICH FRONTS SOUTH DIXIE
 HIGHWAY, DISPLAY THE NUMERICAL ADDRESS FOR THIS
 PROJECT.AS PER WEST PALM BEACH CODE, ADDRESS NUMBERS
 SHALL BE NO LESS THAN 6" IN HEIGHT AND NO LESS THAN 1"
 IN WIDTH.
  
 6.PLEASE GIVE THE FOLLOWING INFORMATION:* OCCUPANCY
 TYPE, * OCCUPANT LOAD, * FIRE SPRINKLERED OR NOT, *
 INTERIOR FINISH CLASSIFICATIONS FOR WALLS AND CEILINGS
 MATERIALS
  
 7.COMMERCIAL COOKING EQUIPMENT SHALL BE IN ACCORDANCE
 WITH NFPA 96. SEPARATE PLANS AND PERMIT WILL BE
 REQUIRED.
  
 8.PLEASE BE ADVISED THAT THE SUBMITTED SUB-PERMIT
 PLANS FOR THE COOKING HOOD INSTALLATION AND THE COOKING
 HOOD SUPPRESSION SYSTEM WILL NOT BE REVIEWED UNTIL SUCH
 TIME THAT THE "MASTER" PERMIT HAS BEEN ISSUED.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop G GAS REVIEW
Rev No 5 Status F Date 2007-12-28 Cont ID  
Sent By kstevens Date 2007-12-28 Time 14:54 Rev Time 0.00
Received By kstevens Date 2007-12-28 Time 14:54 Sent To  
Notes
2007-12-28 14:55:26SEE PLUMBING REVISION NOTES FROM 12-28-07

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2007-09-05 Cont ID  
Sent By kstevens Date 2007-09-05 Time 17:44 Rev Time 0.00
Received By kstevens Date 2007-09-05 Time 17:25 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2007-08-31 Cont ID  
Sent By kstevens Date 2007-08-31 Time 07:37 Rev Time 0.00
Received By kstevens Date 2007-08-31 Time 07:37 Sent To  
Notes
2007-08-31 07:38:53DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 ****FROM PREVIOUS REVIEW:
 ******FROM PREVIOUS REVIEWS:
  
 1. THE FOLLOWING ARE GAS PERMIT REQUIREMENTS:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. SOME SECTIONS DO NOT SHOW THE REQUIRED
 LENGTHS. ALSO SHOW ALL VALVES ON THE ISOMETRIC AS WELL
 AS THE SEDIMENT TRAPS REQUIRED IN SECTIONS 408.4 &
 409.5.
 ****RESPONSE NOTED, BUT THE SEDIMENT TRAPS ARE NOT
 SHOWN.
 ******RESPONSE NOTED, BUT NOW "WHITE OUT" IS USED ON
 THE ISOMETRIC, (SEE BTU/HR NUMBERS), AND THIS IS NOT
 APPROVED ON SIGNED & SEALED PLANS PER SECTION 106.1.3.
 - SEPARATE SHUT OFF VALVES ARE REQUIRED FOR EACH GAS
 APPLIANCE. APPLIANCE MARKS 2 & 3 ONLY SHOW ONE SHUT OFF
 VALVE FOR TWO APPLIANCES. INDICATE VALVE SIZE FOR EACH
 APPLIANCE WHICH SHALL BE FULL SIZE PER TABLE 402.4(2).
  
  
 B. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 ****RESPONSE NOTED, BUT THE DISTANCE IS NOT SHOWN.
 ******RESPONSE NOTED, BUT THE TOTAL DISTANCE ADDS UP TO
 111FT, NOT 105FT AS SHOWN.
  
 C. OK
 D. OK
  
 E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESS.
 ******RESPONSE NOTED, BUT THE WATER HEATER, OVEN AND
 COOK TOP STOVE MANUF. SHEETS HAVE NOT BEEN SUBMITTED.
 ALSO THE 36" RANGE INDICATES 203,000 BTU AND IT IS
 INDICATED AS 132,000 BTU. SEE MANUF. SHEET SUBMITTED
 WITH MODEL NUMBER INDICATED. PLEASE CLARIFY.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  
  
  
 .

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2007-07-10 Cont ID  
Sent By kstevens Date 2007-07-10 Time 11:25 Rev Time 0.00
Received By kstevens Date 2007-07-10 Time 11:25 Sent To  
Notes
2007-07-10 11:29:40DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 ******FROM PREVIOUS REVIEW:
  
 1. THE FOLLOWING ARE GAS PERMIT REQUIREMENTS:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. SOME SECTIONS DO NOT SHOW THE REQUIRED
 LENGTHS. ALSO SHOW ALL VALVES ON THE ISOMETRIC AS WELL
 AS THE SEDIMENT TRAPS REQUIRED IN SECTIONS 408.4 &
 409.5.
 ******RESPONSE NOTED, BUT THE SEDIMENT TRAPS ARE NOT
 SHOWN.
  
 B. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 ******RESPONSE NOTED, BUT THE DISTANCE IS NOT SHOWN.
  
 C. OK
 D. OK
  
 E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ******RESPONSE NOTED, BUT COMMENT NOT ADDRESS.
  
 F. N/A
 F. N/A
  
 G. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
 ******RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. SHOW
 VALVES & UNION ON RISER DIAGRAM. (SEE COMMENT #1).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  
  
  
 .

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-07-10 Cont ID  
Sent By kstevens Date 2007-05-14 Time 11:24 Rev Time 0.00
Received By kstevens Date 2007-05-14 Time 11:24 Sent To  
Notes
2007-07-10 11:25:27DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 1. THE FOLLOWING ARE GAS PERMIT REQUIREMENTS:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. SOME SECTIONS DO NOT SHOW THE REQUIRED
 LENGTHS. ALSO SHOW ALL VALVES ON THE ISOMETRIC AS WELL
 AS THE SEDIMENT TRAPS REQUIRED IN SECTIONS 408.4 &
 409.5.
  
 B. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 C. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI. INDICATED ON THE
 PLANS AS 5PSI. PLEASE VERIFY WITH GAS PROVIDER. IF MORE
 THAN 1/2PSI, SHOW THE LOCATION OF ALL GAS REGULATORS
 AND SUBMIT THE MANUF. SPECIFICATION SHEETS INDICATING
 THE MODEL NUMBER OF THE REGULATOR. PLEASE INDICATE IF
 THE REGULATOR SHALL BE VENTED, AND IF SO SHOW THE
 ROUTING OF THE VENTING AND INDICATE THE MATERIAL FOR
 THE VENT. (VENT SHALL BE OF NON-COMBUSTALBE MATERIAL).
 REGULATORS SHALL BE DOWNSTREAM OF THE SOV OF THE GAS
 APPLIANCE.
  
 D. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
  
 E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 F. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 F. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 G. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  
  
  
 .

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-11-27 Cont ID  
Sent By adarroug Date 2007-11-27 Time 10:41 Rev Time 0.00
Received By adarroug Date 2007-11-27 Time 10:41 Sent To  
Notes
2007-11-29 11:08:43TO "BOB"#11
2007-11-27 10:41:49WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-09-05 Cont ID  
Sent By adarroug Date 2007-09-05 Time 14:37 Rev Time 0.00
Received By adarroug Date 2007-09-05 Time 14:37 Sent To P
Notes
2007-09-05 14:37:53TO "P" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-08-06 Cont ID  
Sent By adarroug Date 2007-08-06 Time 14:30 Rev Time 0.00
Received By adarroug Date 2007-08-06 Time 14:30 Sent To  
Notes
2007-08-29 14:39:10TO "COMM" BD#33
2007-08-06 14:31:40WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-06-05 Cont ID  
Sent By adarroug Date 2007-06-05 Time 11:39 Rev Time 0.00
Received By adarroug Date 2007-06-05 Time 11:39 Sent To  
Notes
2007-06-18 09:07:27TO "COMM" BD#24
2007-06-05 11:40:18WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2007-05-31 Time   Rev Time 0.00
Received By dpalmer Date 2007-03-29 Time 18:44 Sent To  
Notes
2007-04-02 17:10:43TO COMM BOARD # 2
2007-03-29 18:43:47WAITING FOR COMM BOARD.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-08-17 Cont ID  
Sent By tgordon Date 2007-08-17 Time 16:00 Rev Time 0.25
Received By tgordon Date 2007-08-17 Time 16:00 Sent To  
Notes
2007-08-20 15:50:15RETURNED TO INCOMING WAITING TO GET ON COMM. BOARD.
2007-08-17 16:01:09*** PROVISO ***
 ADDITIONAL MECHANICAL PERMITS REQUIRED FOR
 (A) WALK-IN-COOLER
 (B) KITCHEN HOOD
 (C) FIRE SUPPRESSION
 (D) MEDICAL GAS OR FUEL
 ** SUBMIT PLANS WITH PERMIT APPLICATION.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-06-20 Cont ID  
Sent By tgordon Date 2007-06-20 Time 09:11 Rev Time 0.30
Received By tgordon Date 2007-06-20 Time 09:11 Sent To  
Notes
2007-06-20 09:14:00*** PROVISO ***
 ADDITIONAL MECHANICAL PERMITS REQUIRED FOR
 (A) WALK-IN-COOLER
 (B) KITCHEN HOOD
 (C) FIRE SUPPRESSION
 (D) MEDICAL GAS OR FUEL
 ** SUBMIT PLANS WITH PERMIT APPLICATION.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-04-17 Cont ID  
Sent By tgordon Date 2007-04-17 Time 08:21 Rev Time 1.00
Received By tgordon Date 2007-04-17 Time 08:21 Sent To  
Notes
2007-04-17 08:46:53*** DENIED ***
 1) PLEASE SUBMITCOOLING LOAD CALCULATIONS, SEE 2004
 FBC 13-607.1.ABC.1 .
  
 2) PLEASE SUBMIT OUTDOOR AIR CALCULATIONS, SEE 2004
 FBC/M 401.2.
  
 3) PLEASE SUBMIT MECHANICAL (A/C) PLANS SHOWING
 EXISTING AND NEW DUCT LAY-OUT WITH AN A/C EQUIPMENT
 SCHEDULE, SEE 2004 FBC 106.3.5.
  
 4) SEE ELECTRICAL REVIEW NOTES 13 AND 14, PLEASE
 CORRECT.
  
 5) PLEASE BE AWARE A MECHANICAL A/C PERMIT WILL BE
 REQUIRED FOR BATHROOM EXHAUST FANS AND ANY OTHER A/C
 WORK TO BE DONE.
  
 6) PLEASE BE AWARE ADDITIONAL MECHANICAL PERMITS WILL
 BE REQUIRED FORWALK-IN-COOLER AND FREEZER. PLANS FOR
 COOLER/FREEZER MAY BE SUBMITTEDWITH APPLICATION WHEN
 APPLYING FOR THAT PERMIT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 6 Status F Date 2007-12-28 Cont ID  
Sent By kstevens Date 2007-12-28 Time 14:43 Rev Time 0.00
Received By kstevens Date 2007-12-28 Time 14:43 Sent To  
Notes
2007-12-28 14:54:07REVISION DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
  
 1. SHT P-1 REVISION DENIED. MOST CLOUDED REVISIONS SHOW
 NO CHANGE.--THERE ARE CLEANOUTS REQUIRED AS THE
 PIPING FOR THE SANITARY EXITS THE BUILDING NEAR THE
 JUNCTION OF THE BUILDING DRAIN AND THE BUILDING SEWER
 AND AS THE PIPING FOR THE GREASE INTERCEPTOR EXITS THE
 INTERCEPTOR. THESE ARE SHOWN TO HAVE BEEN DELETED.
 THESE SHOULD BE SHOWN ON THE PLAIN VIEW ALSO.--
 TOTAL BTU'S AT THE TOTAL GAS CONNECTED LOAD HAS BEEN
 CHANGED FROM 978,000 TO 898,000 TOTAL BTU'S. THE
 ORIGINAL TOTAL WAS CORRECT. THE NEW TOTAL IS DENIED.
 --THE TABLE FOR THE GAS WAS CHANGED FROM 402.4(2) TO
 402.4(1). THIS IS NOT APPROVED. THE ORIGINAL TABLE IS
 CORRECT.--THE NOTE INDICATING THE DISTANCE FROM THE
 POINT OF DELIVERY ETC. ENDS WITH A GAS SIZING TABLE OF
 A.3.1(4). THIS TABLE DOES NOT EXIST IN THE 2004 FUEL
 GAS CODE AND IS NOT CORRECT. THE CORRECT TABLE IS
 402.4(1). PLEASE CHANGE NOTE. PLEASE SUBMIT REVISIONS
 THAT CHANGE FROM THE ORIGINAL STAMPED/REVIEWED PLANS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 5 Status F Date 2007-12-07 Cont ID  
Sent By jleech Date 2007-12-07 Time 15:09 Rev Time 0.00
Received By jleech Date 2007-12-07 Time 15:06 Sent To  
Notes
2007-12-07 15:19:57REVISION DENITED;
 1. MAKE ALL PLUMBING REVISIONS ON "P" PAGES.
 2. FLAT PIPING ON PAGE A-2 DOES NOT MATCH SANITARY
 RISER DIAGRAM ON P-1.
 3. PLANS SHOW A 750 GAL. GREASE TRAP OUTSIDE WITH THE
 ROTISARY, 3-COMPARTMENT SINK AND MOP SINKALL DRAINING
 INTO A GREASE LINE.
 4. THE GREASE TRAP WAS SIZED BY THE UTILITY DEPARTMENT.
 TO CHANGE THE SIZE AND TYPE OF TRAP YOU MUST GET
 APPROVAL FROM UTILITIES BEFORE SUBMITING REVISION TO
 THE BUILDING DEPARTMENT.
 PLUMBING PLAN REVIEW BY
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 4 Status P Date 2007-09-05 Cont ID  
Sent By kstevens Date 2007-09-05 Time 17:25 Rev Time 0.00
Received By kstevens Date 2007-09-05 Time 17:25 Sent To  
Notes
2007-09-05 17:32:11 
  
  
  
  
  
 PASSED/PROVISO
  
 AS INDICATED FROM RESTAURANT OWNER, THE GREASE FROM THE
 ROTISSERIE OVEN SHALL BE COLLECTED AND REMOVED FROM THE
 PROPERTY AND DISPOSED OF PROPERLY.

Review Stop P PLUMBING
Rev No 3 Status F Date 2007-08-31 Cont ID  
Sent By kstevens Date 2007-08-31 Time 06:54 Rev Time 0.00
Received By kstevens Date 2007-08-30 Time 19:10 Sent To  
Notes
2007-08-31 07:36:31DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 CITY WPB MUNICIPAL CODE
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW:
 ******FROM PREVIOUS REVIEWS:
  
 1. OK
 2. OK
  
 3. 2 SETS OF PLANS, STAMPED BY THE DEPT OF BUSINESS
 REGULATION, HOTEL & RESTAURANT DIVISION SHALL BE
 SUBMITTED FOR REVIEW. ONLY ONE SET HAS THE DBPR STAMP.
 ALSO THE TWO PAGE "WORKSHEETS" SHALL BE ATTACHED TO
 EACH SET OF PLANS SUBMITTED FOR REVIEW BY THE CITY
 WPB.
 ****RESPONSE NOTED, BUT THE TWO PAGE "WORKSHEETS" HAVE
 NOT BEEN ATTACHED TO EACH SET OF PLAN.
 ******NO RESPONSE. STAMPED/REVIEWED SHEETS FROM DBPR
 HAVE BEEN DELETED FROM EACH SET. THESE ARE REQUIRED AS
 WELL AS THE TWO PAGE "SPECIFICATION WORKSHEETS". THE
 WORKSHEETS SHALL BE ATTACHED TO THE SHEETS STAMPED &
 REVIEWED BY DBPR AND ONE SHEET SHALL BE INSERTED INTO
 EACH SET OF PLANS AS REQUIRED BY SECTION 102.2.1.
  
 4. THE GREASE INTERCEPTOR SHALL BE SIZED AND LOCATED BY
 THE ENVIRONMENTAL COMPLIANCE DEPT. PLEASE CONTACT
 RODNEY COMPO (561) 822-2272, [email protected], OR CALVIN
 WILLIAMS (561) 822-2284, [email protected]. THEIR FAX
 NUMBER IS (561) 822-2287. ARTICLE III SECTION 90-124.
 --PER ARTICLE III SECTION 90-124(7)(F) A CONCRETE,
 MINIMUM 750 GAL. INTERCEPTOR IS REQUIRED.(SEE
 ATTACHED UTILITY STANDARD FOR GREASE INTERCEPTORS).--
 THE GREASE INTERCEPTORS ARE TO BE INSTALLED OUTSIDE THE
 FOOD PREPARATION AREA WITH THE DISHWASHER DISCHARGING
 VIA A SEPARATE LINE TO THE SANITARY. ARTICLE III
 SECTION 9--124(7)(B).
 ****RESPONSE NOTED, BUT NO INPUT FROM ENVIRONMENTAL
 COMPLIANCE HAS BEEN SUBMITTED. PLEASE SUBMIT WRITTEN
 APPROVAL OF THE SIZE GREASE INTERCEPTOR FROM MR. COMPO
 OR MR. WILLIAMS.
 ******NO RESPONSE, COMMENT NOT ADDRESSED.
  
 5. OK
  
 6. SHT A-2 MORE INFORMATION IS REQUIRED. IS THERE A
 FIXTURE DRAINING INTO THE GREASE TRAP SHOWN ON THE
 FLOOR PLAN AS PLUMBING PLAN KEY ITEM #6. PLEASE
 CLARIFY. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT THE GREASE FROM THE ROTISSERIE
 OVEN CAN NOT DRAIN INTO THE FLOOR SINK. THE GREASE
 SYSTEM IS DESIGNED TO INTERCEPT INCIDENTAL GREASE NOT
 GREASE DRIPPINGS FROM AN OVEN. THE GREASE WILL HAVE TO
 BE CONTAINED AND THEN DISPOSED OF PROPERLY AT A
 RENDERING PLANT, NOT DRAINED INTO THE FLOOR SINK.
 ******NO RESPONSE, COMMENT NOT ADDRESSED.
  
 7. OK
 8. OK
 9. OK
 10. OK
 11. OK
 12. OK
 13. OK
  
 14. SHT A-2 THE ACCESSIBLE TOILET ROOMS SHALL SHOW
 COMPLIANCE WITH THE FOLLOWING:
 ___FOR W/C
 A. 11-4.16.2 CLEAR FLOOR SPACE - ******NO RESPONSE,
 COMMENT NOT ADDRESSED. SHOW IN THE TOILET ROOM TO
 VERIFY COMPLIANCE.
 B. 11-4.16.5 FLUSH CONTROLS - ******NO RESPONSE,
 COMMENT NOT ADDRESSED.
 ___FOR LAV
 A. 11-4.19.3 CLEAR FLOOR SPACE - ******NO RESPONSE,
 COMMENT NOT ADDRESSED. SHOW IN THE TOILET ROOM TO
 VERIFY COMPLIANCE.
 B. 11-4.19.4 EXPOSED PIPES & SURFACES - ******NO
 RESPONSE, COMMENT NOT ADDRESSED.
 C. 11-4.19.5 FAUCETS - ******NO RESPONSE, COMMENT NOT
 ADDRESSED.
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED.
  
 15. THE FOLLOWING ARE GAS PERMIT REQUIREMENTS:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. SOME SECTIONS DO NOT SHOW THE REQUIRED
 LENGTHS. ALSO SHOW ALL VALVES ON THE ISOMETRIC AS WELL
 AS THE SEDIMENT TRAPS REQUIRED IN SECTIONS 408.4 &
 409.5.
 ****RESPONSE NOTED, BUT THE SEDIMENT TRAPS ARE NOT
 SHOWN.
 ******RESPONSE NOTED, BUT NOW "WHITE OUT" IS USED ON
 THE ISOMETRIC, (SEE BTU/HR NUMBERS), AND THIS IS NOT
 APPROVED ON SIGNED & SEALED PLANS PER SECTION 106.1.3.
 - SEPARATE SHUT OFF VALVES ARE REQUIRED FOR EACH GAS
 APPLIANCE. APPLIANCE MARKS 2 & 3 ONLY SHOW ONE SHUT OFF
 VALVE FOR TWO APPLIANCES. INDICATE VALVE SIZE FOR EACH
 APPLIANCE WHICH SHALL BE FULL SIZE PER TABLE 402.4(2).
  
  
 B. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 ****RESPONSE NOTED, BUT THE DISTANCE IS NOT SHOWN.
 ******RESPONSE NOTED, BUT THE TOTAL DISTANCE ADDS UP TO
 111FT, NOT 105 AS SHOWN.
  
 C. OK
 D. OK
  
 E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESS.
 ******RESPONSE NOTED, BUT THE WATER HEATER, OVEN AND
 COOK TOP STOVE MANUF. SHEETS HAVE NOT BEEN SUBMITTED.
 ALSO THE 36" RANGE INDICATES 203,000 BTU AND IT IS
 INDICATED AS 132,000 BTU. SEE MANUF. SHEET SUBMITTED
 WITH MODEL NUMBER INDICATED.
  
 F. N/A
 F. N/A
 G. OK
  
 ************NEW COMMENTS************
  
 1B. OK
 2B. OK
 3B. OK
 4B. OK
 5B. SHT M-1 PLUMBING FIXTURE SCHEDULE INDICATES THE
 GREASE INTERCEPTOR AND THE GAS WATER HEATER BY THE
 GENERAL CONTRACTOR.A SEPARATE GREASE INTERCEPTOR
 PERMIT IS REQUIRED BY THE PROVIDER OF THE GREASE
 INTERCEPTORAND SHALL BE HOOKED UP BY THE PLUMBING
 CONTRACTOR AS WELL AS THE GAS WATER HEATER. FS 489.
 ******NO RESPONSE. PLEASE INDICATE PLUMBING CONTRACTOR
 RESPONSIBILITY FOR THESE INSTALLATIONS.
  
 6B. SEE ATTACHED SHEET CONCERNING THE DESIGN
 PROFESSIONALS AND FS 533.80(2)(B). THIS IS GIVEN AS A
 NOTICE AT THIS TIME.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION. ******SUBMIT ONE SET
 OF VOID SHEETS FOR COMPARISON WHEN RESUBMITTING
 PLANS.******
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  
  
  
 .

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-07-10 Cont ID  
Sent By kstevens Date 2007-07-10 Time 11:33 Rev Time 0.00
Received By kstevens Date 2007-07-09 Time 19:03 Sent To  
Notes
2007-07-10 11:47:21DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 CITY WPB MUNICIPAL CODE
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW:
  
 1. PER ADDRESSING, THE WRONG PCN NUMBER WAS USED DURING
 APPLICATION FOR PERMIT. THE CORRECT ADDRESS IS 3008 S
 DIXIE HWY, NOT 3010 S DIXIE HWY AS INDICATED ON THE
 APPLICATION AND ON THE TITLE BLOCK OF SHEETS A-1 & A-2.
 PLEASE CHANGE THE APPLICATION AND THE TITLE BLOCKS TO
 REFLECT THE CORRECT ADDRESS.
 ****RESPONSE NOTED, BUT THE ADDRESS HAS NOT BEEN
 CHANGED ON THE ARCHITECTURAL SHEETS.
  
 2. SHTS A-2 & A-2 THE BUSINESS NUMBER, (CERTIFICATE OF
 AUTHORIZATION), ADDRESS, AND PHONE NUMBER OF THE
 ARCHITECT'S BUSINESS SHALL BE INDICATED IN THE TITLE
 BLOCK AS WELL AS THE PRINTED NAME OF THE PERSON SEALING
 THE DOCUMENT. FAC 61G1-16.004(1)(2)(6) & FS 481.219,
 481.2055.
 ****RESPONSE NOTED, COMMENT NOT ADDRESSED.
  
 3. 2 SETS OF PLANS, STAMPED BY THE DEPT OF BUSINESS
 REGULATION, HOTEL & RESTAURANT DIVISION SHALL BE
 SUBMITTED FOR REVIEW. ONLY ONE SET HAS THE DBPR STAMP.
 ALSO THE TWO PAGE "WORKSHEETS" SHALL BE ATTACHED TO
 EACH SET OF PLANS SUBMITTED FOR REVIEW BY THE CITY
 WPB.
 ****RESPONSE NOTED, BUT THE TWO PAGE "WORKSHEETS" HAVE
 NOT BEEN ATTACHED TO EACH SET OF PLAN.
  
 4. THE GREASE INTERCEPTOR SHALL BE SIZED AND LOCATED BY
 THE ENVIRONMENTAL COMPLIANCE DEPT. PLEASE CONTACT
 RODNEY COMPO (561) 822-2272, [email protected], OR CALVIN
 WILLIAMS (561) 822-2284, [email protected]. THEIR FAX
 NUMBER IS (561) 822-2287. ARTICLE III SECTION 90-124.
 --PER ARTICLE III SECTION 90-124(7)(F) A CONCRETE,
 MINIMUM 750 GAL. INTERCEPTOR IS REQUIRED.(SEE
 ATTACHED UTILITY STANDARD FOR GREASE INTERCEPTORS).--
 THE GREASE INTERCEPTORS ARE TO BE INSTALLED OUTSIDE THE
 FOOD PREPARATION AREA WITH THE DISHWASHER DISCHARGING
 VIA A SEPARATE LINE TO THE SANITARY. ARTICLE III
 SECTION 9--124(7)(B).
 ****RESPONSE NOTED, BUT NO INPUT FROM ENVIRONMENTAL
 COMPLIANCE HAS BEEN SUBMITTED. PLEASE SUBMIT WRITTEN
 APPROVAL OF THE SIZE GREASE INTERCEPTOR FROM MR. COMPO
 OR MR. WILLIAMS.
  
 5. OK
  
 6. SHT A-2 MORE INFORMATION IS REQUIRED. IS THERE A
 FIXTURE DRAINING INTO THE GREASE TRAP SHOWN ON THE
 FLOOR PLAN AS PLUMBING PLAN KEY ITEM #6. PLEASE
 CLARIFY. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT THE GREASE FROM THE ROTISSERIE
 OVEN CAN NOT DRAIN INTO THE FLOOR SINK. THE GREASE
 SYSTEM IS DESIGNED TO INTERCEPT INCIDENTAL GREASE NOT
 GREASE DRIPPINGS FROM AN OVEN. THE GREASE WILL HAVE TO
 BE CONTAINED AND THEN DISPOSED OF PROPERLY AT A
 RENDERING PLANT, NOT DRAINED INTO THE FLOOR SINK.
  
 7. OK
 8. OK
 9. OK
 10. OK
  
 11. SUBMIT A WATER ISOMETRIC RISER DIAGRAM SHOWING ALL
 PIPE SIZES, VALVES, REQUIRED WATER HAMMER ARRESTORS,
 (LOCATED NEAR THE FIXTURE IN AN "EFFECTIVE RANGE", NOT
 IN THE CEILING). INDICATE THE WATER SERVICE SIZE PER
 TABLE 603.1 AND INDICATE IF THERE IS AN EXISTING RPZV
 BACKFLOW PREVENTER ON THE WATER SERVICE. IF NO
 BACKFLOW, THEN ONE WILL BE REQUIRED PER SECTION
 608.13.2.SECTIONS 106.3.5.1.3(3)(8)(10)(13) & 604.9.
 ****RESPONSE NOTED, BUT A FULL OPEN VALVE IS REQUIRED
 ON THE WATER DISTRIBUTION SUPPLY PIPE AT THE ENTRANCE
 INTO THE STRUCTURE. SECTION 606.1(2).
  
 12. SHT A-2 THERMAL EXPANSION CONTROL IS REQUIRED PER
 SECTION 607.3.2. PLEASE INDICATE METHOD. ****RESPONSE
 NOTED, BUT A CHECK VALVE DOES NOT CONTROL THERMAL
 EXPANSION.PLEASE INDICATE PROPER APPROVED METHOD OF
 CONTROLING THERMAL EXPANSION.
  
 13. OK
  
 14. SHT A-2 THE ACCESSIBLE TOILET ROOMS SHALL SHOW
 COMPLIANCE WITH THE FOLLOWING:
 ___FOR W/C
 A. 11-4.16.2 CLEAR FLOOR SPACE
 B. 11-4.16.5 FLUSH CONTROLS
 ___FOR LAV
 A. 11-4.19.3 CLEAR FLOOR SPACE
 B. 11-4.19.4 EXPOSED PIPES & SURFACES
 C. 11-4.19.5 FAUCETS
 ALSO SHOW THE W/C TO BE 18" OFF THE WALL TO THE
 CENTERLINE OF THE FIXTURE PER FIG. 29. SHOW THE LAV TO
 BE A MINIMUM OF 15" OFF THE WALL TO THE CENTERLINE OF
 THE FIXTURE. (CENTER ON THE 30" OF THE 30"X48" CLEAR
 FLOOR SPACE REQUIRED FOR THE LAV).
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED.
  
 15. THE FOLLOWING ARE GAS PERMIT REQUIREMENTS:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. SOME SECTIONS DO NOT SHOW THE REQUIRED
 LENGTHS. ALSO SHOW ALL VALVES ON THE ISOMETRIC AS WELL
 AS THE SEDIMENT TRAPS REQUIRED IN SECTIONS 408.4 &
 409.5.
 ******RESPONSE NOTED, BUT THE SEDIMENT TRAPS ARE NOT
 SHOWN.
  
 B. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 ******RESPONSE NOTED, BUT THE DISTANCE IS NOT SHOWN.
  
 C. OK
 D. OK
  
 E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ******RESPONSE NOTED, BUT COMMENT NOT ADDRESS.
  
 F. N/A
 F. N/A
  
 G. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
 ******RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. SHOW
 VALVES & UNION ON RISER DIAGRAM. (SEE COMMENT #1).
  
 ************NEW COMMENTS************
  
 1B. (NEW) SHT P-1 INDICATES A WATER FILTER. THE WATER
 FILTER SHALL MEET THE REQUIREMENTS OF NSF 42. SUBMIT
 MANUF. SPECIFICATIONS SHOWING COMPLIANCE. SECTION
 611.1.
  
 2B. SHT P-1 A VENT IS REQUIRED ON THE GREASE SYSTEM.
 SECTION 901.2.
  
 3B. SHT P-1 A SERVICE SINK IS REQUIRED PER TABLE 403.1.
 SINK SHALL BE CONNECTED TO THE GREASE SYSTEM. INDICATE
 THE LOCATION ON THE FLOOR PLAN, GREASE RISER DIAGRAM
 AND THE WATER RISER DIAGRAM.
  
 4B. SHT M-1 GAS WATER HEATER DETAIL. A FLOOR DRAIN IS
 NOT AN APPROVED INDIRECT WASTE RECEPTOR. A FLOOR SINK
 OR HUB DRAIN SHALL BE USED. SECTIONS 802.3 & 802.3.2.
  
 5B. SHT M-1 PLUMBING FIXTURE SCHEDULE INDICATES THE
 GREASE INTERCEPTOR AND THE GAS WATER HEATER BY THE
 GENERAL CONTRACTOR.A SEPARATE GREASE INTERCEPTOR
 PERMIT IS REQUIRED BY THE PROVIDER OF THE GREASE
 INTERCEPTORAND SHALL BE HOOKED UP BY THE PLUMBING
 CONTRACTOR AS WELL AS THE GAS WATER HEATER. FS 489.
  
 6B. SEE ATTACHED SHEET CONCERNING THE DESIGN
 PROFESSIONALS AND FS 533.80(2)(B). THIS IS GIVEN AS A
 NOTICE AT THIS TIME.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  
  
  
 .

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-05-14 Cont ID  
Sent By kstevens Date 2007-05-14 Time 14:11 Rev Time 0.00
Received By kstevens Date 2007-05-14 Time 14:11 Sent To  
Notes
2007-05-14 15:55:28DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 CITY WPB MUNICIPAL CODE
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. PER ADDRESSING, THE WRONG PCN NUMBER WAS USED DURING
 APPLICATION FOR PERMIT. THE CORRECT ADDRESS IS 3008 S
 DIXIE HWY, NOT 3010 S DIXIE HWY AS INDICATED ON THE
 APPLICATION AND ON THE TITLE BLOCK OF SHEETS A-1 & A-2.
 PLEASE CHANGE THE APPLICATION AND THE TITLE BLOCKS TO
 REFLECT THE CORRECT ADDRESS.
  
 2. SHTS A-2 & A-2 THE BUSINESS NUMBER, (CERTIFICATE OF
 AUTHORIZATION), ADDRESS, AND PHONE NUMBER OF THE
 ARCHITECT'S BUSINESS SHALL BE INDICATED IN THE TITLE
 BLOCK AS WELL AS THE PRINTED NAME OF THE PERSON SEALING
 THE DOCUMENT. FAC 61G1-16.004(1)(2)(6) & FS 481.219,
 481.2055.
  
 3. 2 SETS OF PLANS, STAMPED BY THE DEPT OF BUSINESS
 REGULATION, HOTEL & RESTAURANT DIVISION SHALL BE
 SUBMITTED FOR REVIEW. ONLY ONE SET HAS THE DBPR STAMP.
 ALSO THE TWO PAGE "WORKSHEETS" SHALL BE ATTACHED TO
 EACH SET OF PLANS SUBMITTED FOR REVIEW BY THE CITY
 WPB.
  
 4. THE GREASE INTERCEPTOR SHALL BE SIZED AND LOCATED BY
 THE ENVIRONMENTAL COMPLIANCE DEPT. PLEASE CONTACT
 RODNEY COMPO (561) 822-2272, [email protected], OR CALVIN
 WILLIAMS (561) 822-2284, [email protected]. THEIR FAX
 NUMBER IS (561) 822-2287. ARTICLE III SECTION 90-124.
 --PER ARTICLE III SECTION 90-124(7)(F) A CONCRETE,
 MINIMUM 750 GAL. INTERCEPTOR IS REQUIRED.(SEE
 ATTACHED UTILITY STANDARD FOR GREASE INTERCEPTORS).--
 THE GREASE INTERCEPTORS ARE TO BE INSTALLED OUTSIDE THE
 FOOD PREPARATION AREA WITH THE DISHWASHER DISCHARGING
 VIA A SEPARATE LINE TO THE SANITARY. ARTICLE III
 SECTION 9--124(7)(B).
  
 5. SHT A-2 ALL KITCHEN AREA FLOOR DRAINS SHALL CONNECT
 TO THE GREASE WASTE SYSTEM, NOT THE SANITARY AS SHOWN.
 ARTICLE III SECTION 90-124(7).
  
 6. SHT A-2 MORE INFORMATION IS REQUIRED. IS THERE A
 FIXTURE DRAINING INTO THE GREASE TRAP SHOWN ON THE
 FLOOR PLAN AS PLUMBING PLAN KEY ITEM #6. PLEASE
 CLARIFY. SECTION 106.1.1.
  
 7. SHT A-2 THE HAND SINK NEXT TO PLUMBING PLAN KEY ITEM
 #14 SHALL DRAIN INDIRECTLY INTO A FLOOR SINK, AND SHALL
 CONNECT TO THE GREASE WASTE SYSTEM.SECTION802.1.1.
 AS SHOWN THE HAND SINK IS DRAINING THRU THE WET VENT
 FOR THE BATHROOM FIXTURES WHICH IS NOT ALLOWED. SECTION
 909.1.
  
 8. SHT A-2 THE FLOOR DRAIN IN THE ACCESSIBLE TOILET
 ROOM IS NOT VENTED AS SHOWN. THE FLOOR DRAIN SHALL BE
 TAKEN OFF THE VENTED LINE TO THE LAV. SECTION 901.2.1.
  
 9. SHT A-2 THE LAV STACK FOR THE ACCESSIBLE TOILET ROOM
 DOES NOT REFLECT THE PIPING LAYOUT ON THE FLOOR PLAN.
 PLEASE CORRELATE. SECTION 106.1.1.
  
 10. SHT A-2 INDICATE WHERE THE CONDENSATE FROM THE
 WALK-IN FREEZER AND THE WALK-IN REFRIDGERATOR DRAIN. AN
 INDIRECT WASTE RECEPTOR COMPLYING WITH SECTIONS 802.3
 OR 802.3.2 SHALL BE REQUIRED FOR THE DRAINAGE OF THE
 CONDENSATE.
  
 11. SUBMIT A WATER ISOMETRIC RISER DIAGRAM SHOWING ALL
 PIPE SIZES, VALVES, REQUIRED WATER HAMMER ARRESTORS,
 (LOCATED NEAR THE FIXTURE IN AN "EFFECTIVE RANGE", NOT
 IN THE CEILING). INDICATE THE WATER SERVICE SIZE PER
 TABLE 603.1 AND INDICATE IF THERE IS AN EXISTING RPZV
 BACKFLOW PREVENTER ON THE WATER SERVICE. IF NO
 BACKFLOW, THEN ONE WILL BE REQUIRED PER SECTION
 608.13.2.SECTIONS 106.3.5.1.3(3)(8)(10)(13) & 604.9
  
 12. SHT A-2 THERMAL EXPANSION CONTROL IS REQUIRED PER
 SECTION 607.3.2. PLEASE INDICATE METHOD.
  
 13. SHT A-2 PLUMBING PLAN KEY #6 IS NOT APPROVED.
 PLEASE DELETE FROM REFERENCE. ARTICLE III SECTION
 90-124(7)(B)(F).
  
 14. SHT A-2 THE ACCESSIBLE TOILET ROOMS SHALL SHOW
 COMPLIANCE WITH THE FOLLOWING:
 ___FOR W/C
 A. 11-4.16.2 CLEAR FLOOR SPACE
 B. 11-4.16.5 FLUSH CONTROLS
 ___FOR LAV
 A. 11-4.19.3 CLEAR FLOOR SPACE
 B. 11-4.19.4 EXPOSED PIPES & SURFACES
 C. 11-4.19.5 FAUCETS
 ALSO SHOW THE W/C TO BE 18" OFF THE WALL TO THE
 CENTERLINE OF THE FIXTURE PER FIG. 29. SHOW THE LAV TO
 BE A MINIMUM OF 15" OFF THE WALL TO THE CENTERLINE OF
 THE FIXTURE. (CENTER ON THE 30" OF THE 30"X48" CLEAR
 FLOOR SPACE REQUIRED FOR THE LAV).
  
 15. THE FOLLOWING ARE GAS PERMIT REQUIREMENTS:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. SOME SECTIONS DO NOT SHOW THE REQUIRED
 LENGTHS. ALSO SHOW ALL VALVES ON THE ISOMETRIC AS WELL
 AS THE SEDIMENT TRAPS REQUIRED IN SECTIONS 408.4 &
 409.5.
  
 B. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 C. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI. INDICATED ON THE
 PLANS AS 5PSI. PLEASE VERIFY WITH GAS PROVIDER. IF MORE
 THAN 1/2PSI, SHOW THE LOCATION OF ALL GAS REGULATORS
 AND SUBMIT THE MANUF. SPECIFICATION SHEETS INDICATING
 THE MODEL NUMBER OF THE REGULATOR. PLEASE INDICATE IF
 THE REGULATOR SHALL BE VENTED, AND IF SO SHOW THE
 ROUTING OF THE VENTING AND INDICATE THE MATERIAL FOR
 THE VENT. (VENT SHALL BE OF NON-COMBUSTALBE MATERIAL).
 REGULATORS SHALL BE DOWNSTREAM OF THE SOV OF THE GAS
 APPLIANCE.
  
 D. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
  
 E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 F. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 F. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 G. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  
  
  
 .

Review Stop Z ZONING
Rev No 1 Status N Date 2007-04-10 Cont ID  
Sent By jroach Date 2007-04-10 Time 13:33 Rev Time 0.00
Received By jroach Date 2007-04-10 Time 13:33 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved