 |
Plan Review Details - Permit 07031011
Plan Review Stops For Permit 07031011 |
Review Stop |
AD |
ADDRESSING |
Rev No |
1 |
Status |
P |
Date |
2007-05-29 |
|
|
Cont ID |
|
Sent By |
lursu |
Date |
2007-05-29 |
Time |
11:16 |
Rev Time |
0.00 |
Received By |
lursu |
Date |
2007-04-16 |
Time |
16:22 |
Sent To |
|
|
Notes |
2007-04-17 15:50:47 | THE SITE ADDRESS ON THE APPLICATION IS 3010 S DIXIE | | HWY.THE ADDRESS WAS FIELD VERIFIED AND BELONGS TO | | PARCEL CONTROL NUMBER = 74 43 43 34 16 000 0010 AND NOT | | PCN = 74 43 43 34 04 002 0010 AS ON THE APPLICATION.THE | | OWNER INFO ON THE PAPA WEBSITE IS THE SAME FOR BOTH | | PARCELS.HOWEVER PERMIT IS APPLIED TO THE CORRECT PCN. | | | | LACRAMIOARA URSU | | MIS - GIS SUPPORT SPECIALIST | | CITY OF WEST PALM BEACH | | OFFICE:822-1239 | | FAX: 822-1249 | | E-MAIL:[email protected] |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2007-12-01 |
|
|
Cont ID |
|
Sent By |
mjacobs |
Date |
2007-12-01 |
Time |
06:12 |
Rev Time |
0.00 |
Received By |
mjacobs |
Date |
2007-12-01 |
Time |
05:45 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2007-08-30 |
|
|
Cont ID |
|
Sent By |
mjacobs |
Date |
2007-08-30 |
Time |
07:13 |
Rev Time |
0.00 |
Received By |
mjacobs |
Date |
2007-08-30 |
Time |
06:07 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2007-06-21 |
|
|
Cont ID |
|
Sent By |
mjacobs |
Date |
2007-06-21 |
Time |
14:29 |
Rev Time |
0.00 |
Received By |
mjacobs |
Date |
2007-06-21 |
Time |
12:30 |
Sent To |
|
|
Notes |
2007-06-21 14:28:29 | BUILDING PLAN REVIEW | | PERMIT: 07031011 | | ADD: 3010 S. DIXIE HWY | | CONT: MIKE MOORE CONSTRUCTION | | TEL: (561)748-7000 | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | W/ 2006 FBC REVISIONS | | * WEST PALM BEACH AMENDMENTS | | | | REVIEW 2ND | | ACTION: DENIED | | | | **************NO RESPONSE WERE GIVEN*************** | | | | 1)--- VERY IMPORTANT STATEMENT --- | | PLEASE DO NOT IGNORE! | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | BER, WITH A DESCRIPTION OF THE REVISION | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | 2)61G1-16.004 TITLE BLOCK. | | A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR | | INTERIOR DESIGN DRAWINGS AND SPECIFICATION | | IDENTIFICATION SHEETS. THE TITLE BLOCK MUST, AT A | | MINIMUM, CONTAIN THE FOLLOWING INFORMATION: | | (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER. | | (2) FIRM LICENSE NUMBER. | | (3) NAME OR IDENTIFICATION OF PROJECT. | | (4) DATE PREPARED. | | (5) A SPACE FOR THE SIGNATURE AND DATED SEAL. | | (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING | | THE DOCUMENT. | | | | 3)108.3* THE CLAIMED VALUATION ON THE PERMIT | | APPLICATION IS LOW.IF, IN THE OPINION OF THE BUILDING | | OFFICIAL, THE CLAIMED VALUATION OF BUILDING, | | ALTERATION, STRUCTURE, ELECTRUCAL, GAS, MECHANICAL OR | | PLUMBING SYSTEMS APPEARS TO BE UNDERESTIMATED ON THE | | APPLICATION, THE PERMIT SHALL BE DENIED. FOR PERMITTING | | PURPOSES, VALUATION SHALL BE THE TOTAL REPLACEMENT | | VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, | | MECHANICAL, INTERIOR FINISH ARCHITECTURAL AND DESIGN | | FEES, MARKETING COST, AND OVERHEAD AND PROFIT EXCLUDING | | LAND VALUE. | | | | 4)110.2* W. P. B. ADMINISTRATIVE | | CODE, INFORMATION THAT IS REQUIRED FOR | | RECORD KEEPING. | | A) THE EDITION OFTHE CODE UNDER WHICH | | THE PROJECT WAS DESIGNED. | | B) THE USE AND OCCUPANCY, IN ACCORDANCE | | WITH THE PROVISIONS OF CHAPTER 3. | | C) THE DESIGN OCCUPANT LOAD, SEE 1004. | | D) IF AN AUTOMATIC SPRINKLER SYSTEM IS | | PROVIDED, WHETHER THE SPRINKLER SYSTEM | | IS REQUIRED. | | E) SQ. FT. FOOTPRINT | | F) SQ. FT. UNDER ROOF (TOTAL) | | G) OCCUPANT LOAD | | | | 5)11-4.32.2 SEATING. | | IF SEATING SPACES FOR PEOPLE IN WHEELCHAIRS ARE | | PROVIDED AT FIXED TABLES OR COUNTERS, CLEAR FLOOR SPACE | | COMPLYING WITH SECTION 11-4.2.4 SHALL BE PROVIDED. SUCH | | CLEAR FLOOR SPACE SHALL NOT OVERLAP KNEE SPACE BY MORE | | THAN 19 INCHES (485 MM) (SEE FIGURE 45 ). 11-4.32.3 | | KNEE CLEARANCES.IF SEATING FOR PEOPLE IN WHEELCHAIRS IS | | PROVIDED AT TABLES OR COUNTERS, KNEE SPACES AT LEAST 27 | | INCHES (685 MM) HIGH, 30 INCHES (760 MM) WIDE, AND 19 | | INCHES (485 MM) DEEP SHALL BE PROVIDED (SEE FIGURE 45 | | ). SHOW HOW THE TABLES ON SHEET A-1 WILL MEET THE | | REQUIREMENTS OF FIG 45 BY INDICATING THE DIMENTIONS OF | | THE TABLEAND SHOWING THE CLEAR FLOOR SPACE ON THE | | PLANS. | | | | 6)INDICATE THE TYPE OF ALTERATION OF THE PROJECT IN | | ACCORDANCE WITH CH 3 OF THE 2004 FLORIDA EXISTING | | BUILDING CODE. | | | | 7)FBC.1210.1 FLOORS. IN OTHER THAN DWELLING UNITS, | | TOILET AND BATHING ROOM FLOORS SHALL HAVE A SMOOTH, | | HARD, NONABSORBENT SURFACE THAT EXTENDS UPWARD ONTO THE | | WALLS AT LEAST 6 INCHES (152 MM). | | | | 8)FBC.1210.2WALLS WITHIN 2 FEET (610 MM) OF URINALS | | AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD, | | NONABSORBENT SURFACE, TO A HEIGHT OF 4 FEET (1219 MM) | | ABOVE THE FLOOR, AND EXCEPT FOR STRUCTURAL ELEMENTS, | | THE MATERIALS USED IN SUCH WALLS SHALL BE OF A TYPE | | THAT IS NOT ADVERSELY AFFECTED BY MOISTURE. | | | | MYRON JACOBS | | BUILDING PLAN REVIEWER | | 805-6726 | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2007-05-31 |
|
|
Cont ID |
|
Sent By |
mjacobs |
Date |
2007-05-31 |
Time |
14:59 |
Rev Time |
0.00 |
Received By |
mjacobs |
Date |
2007-05-31 |
Time |
11:09 |
Sent To |
PC |
|
Notes |
2007-05-31 14:59:03 | | | | | | | | | | | BUILDING PLAN REVIEW | | PERMIT: 07031011 | | ADD: 3010 S. DIXIE HWY | | CONT: MIKE MOORE CONSTRUCTION | | TEL: (561)748-7000 | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | W/ 2006 FBC REVISIONS | | * WEST PALM BEACH AMENDMENTS | | | | REVIEW 1ST | | ACTION: DENIED | | | | 1)--- VERY IMPORTANT STATEMENT --- | | PLEASE DO NOT IGNORE! | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | BER, WITH A DESCRIPTION OF THE REVISION | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | 2)61G1-16.004 TITLE BLOCK. | | A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR | | INTERIOR DESIGN DRAWINGS AND SPECIFICATION | | IDENTIFICATION SHEETS. THE TITLE BLOCK MUST, AT A | | MINIMUM, CONTAIN THE FOLLOWING INFORMATION: | | (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER. | | (2) FIRM LICENSE NUMBER. | | (3) NAME OR IDENTIFICATION OF PROJECT. | | (4) DATE PREPARED. | | (5) A SPACE FOR THE SIGNATURE AND DATED SEAL. | | (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING | | THE DOCUMENT. | | | | 3)108.3* THE CLAIMED VALUATION ON THE PERMIT | | APPLICATION IS LOW.IF, IN THE OPINION OF THE BUILDING | | OFFICIAL, THE CLAIMED VALUATION OF BUILDING, | | ALTERATION, STRUCTURE, ELECTRUCAL, GAS, MECHANICAL OR | | PLUMBING SYSTEMS APPEARS TO BE UNDERESTIMATED ON THE | | APPLICATION, THE PERMIT SHALL BE DENIED. FOR PERMITTING | | PURPOSES, VALUATION SHALL BE THE TOTAL REPLACEMENT | | VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, | | MECHANICAL, INTERIOR FINISH ARCHITECTURAL AND DESIGN | | FEES, MARKETING COST, AND OVERHEAD AND PROFIT EXCLUDING | | LAND VALUE. | | | | 4)110.2* W. P. B. ADMINISTRATIVE | | CODE, INFORMATION THAT IS REQUIRED FOR | | RECORD KEEPING. | | A) THE EDITION OFTHE CODE UNDER WHICH | | THE PROJECT WAS DESIGNED. | | B) THE USE AND OCCUPANCY, IN ACCORDANCE | | WITH THE PROVISIONS OF CHAPTER 3. | | C) THE DESIGN OCCUPANT LOAD, SEE 1004. | | D) IF AN AUTOMATIC SPRINKLER SYSTEM IS | | PROVIDED, WHETHER THE SPRINKLER SYSTEM | | IS REQUIRED. | | E) SQ. FT. FOOTPRINT | | F) SQ. FT. UNDER ROOF (TOTAL) | | G) OCCUPANT LOAD | | | | 5)11-4.32.2 SEATING. | | IF SEATING SPACES FOR PEOPLE IN WHEELCHAIRS ARE | | PROVIDED AT FIXED TABLES OR COUNTERS, CLEAR FLOOR SPACE | | COMPLYING WITH SECTION 11-4.2.4 SHALL BE PROVIDED. SUCH | | CLEAR FLOOR SPACE SHALL NOT OVERLAP KNEE SPACE BY MORE | | THAN 19 INCHES (485 MM) (SEE FIGURE 45 ). 11-4.32.3 | | KNEE CLEARANCES.IF SEATING FOR PEOPLE IN WHEELCHAIRS IS | | PROVIDED AT TABLES OR COUNTERS, KNEE SPACES AT LEAST 27 | | INCHES (685 MM) HIGH, 30 INCHES (760 MM) WIDE, AND 19 | | INCHES (485 MM) DEEP SHALL BE PROVIDED (SEE FIGURE 45 | | ). SHOW HOW THE TABLES ON SHEET A-1 WILL MEET THE | | REQUIREMENTS OF FIG 45 BY INDICATING THE DIMENTIONS OF | | THE TABLEAND SHOWING THE CLEAR FLOOR SPACE ON THE | | PLANS. | | | | 6)INDICATE THE TYPE OF ALTERATION OF THE PROJECT IN | | ACCORDANCE WITH CH 3 OF THE 2004 FLORIDA EXISTING | | BUILDING CODE. | | | | 7)FBC. 1210.1 FLOORS. IN OTHER THAN DWELLING UNITS, | | TOILET AND BATHING ROOM FLOORS SHALL HAVE A SMOOTH, | | HARD, NONABSORBENT SURFACE THAT EXTENDS UPWARD ONTO THE | | WALLS AT LEAST 6 INCHES (152 MM). | | | | 8)FBC. 1210.2WALLS WITHIN 2 FEET (610 MM) OF | | URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD, | | NONABSORBENT SURFACE, TO A HEIGHT OF 4 FEET (1219 MM) | | ABOVE THE FLOOR, AND EXCEPT FOR STRUCTURAL ELEMENTS, | | THE MATERIALS USED IN SUCH WALLS SHALL BE OF A TYPE | | THAT IS NOT ADVERSELY AFFECTED BY MOISTURE. | | | | MYRON JACOBS | | BUILDING PLAN REVIEWER | | 805-6726 | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
P |
Date |
2007-11-29 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-11-29 |
Time |
15:05 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-11-29 |
Time |
15:05 |
Sent To |
|
|
Notes |
2007-11-29 15:06:03 | REV FOR DEVICE AND LOCATION CHANGES. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2007-08-14 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-08-14 |
Time |
10:58 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-08-14 |
Time |
10:58 |
Sent To |
I |
|
Notes |
2007-08-14 11:18:44 | PLANS REMOVED FROM INCOMING , REVIEW OK, STAMPED FOR | | ELECTRICAL SHEETS AND SENT BACK TO INCOMING TABLE | | WAITING FOR COMM BOARD. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2007-06-22 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-06-22 |
Time |
09:03 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-06-22 |
Time |
07:01 |
Sent To |
|
|
Notes |
2007-06-22 09:03:45 | *** UNSAT 2ND REVIEW *** | | | | *** PLEASE SEE MANY ITEMS FROM PREVIOUS REVIEW HAVE NOT | | BEEN ADDRESSED AND THERE ARE SOME NEW COMMENTS DUE TO | | CHANGES IN PLANS. PLEASE SEE THAT MOST OF THE ITEMS ARE | | FROM PREVIOUS REVIEW. | | | | ** ONCE AGAIN, DUE TO THE AMOUNT OF COMMENTS AND | | UN-LICENSED INFORMATION, ONE SET OF PLANS ARE BEING | | RETAINED BY THIS OFFICE. | | | | 1) NOTE:PLEASE SEE THE TITLE BLOCKS FOR ARCHITECTURAL | | FIRM. AS STATED ON PREVIOUS REVIEW NOT CERTIFICATE OF | | AUTHORIZATION NUMBER IS ON PLANS AND NOT INFORMATION ON | | THE DEPARTMENT OF BUSINESS AND PROFESSIONAL REGULATION | | FROM THE STATE COULD BE LOCATED. PLANS ARE BEING | | RETAINED AND INFORMATION TO THE STATE BOARD OF | | ARCHITECTS AND STATE LEGAL COUNSEL TO THE BOARD WILL BE | | NOTIFIED. | | PLEASE SEE THE ARCHITECTURAL FIRM IS MISSING THE | | REQUIRED LICENSURE PER FS 481.219 AND FAC 61G1-16.004. | | PLEASE INCLUDE ON ALL SHEETS AND FOR ALL TRADES WHETHER | | OR NOT COMMENT IS MADE BY OTHER REVIEWERS. | | | | 2) NOTE: PLEASE CORRELATE RISER, ELECTRICAL NOTES, | | PANEL SCHEDULE AND PLANS. | | PLEASE SEE THE ELECTRICAL RISER IS STILL SHOWING A NEW | | SERVICE WHICH IS NOT PERMITTED AND IS NOT GRANTED BY | | THIS OFFICE. PLEASE SEE THE PREVIOUS NOTES ON PLANS HAD | | SOME DIFFERENCES IN THE SIZE OF SERVICE AND NOW THEY | | HAVE BEEN CHANGED BUT HOWEVER ARE STILL NOT CORRECT. | | PLEASE SEE THE ELECTRICAL SERVICE IS BEING SHOWN AS A | | 300A PANEL IN ONE NOTE, 200AMP IN ANOTHER NOTE. | | THIS LOCATION HAS BEEN LOOKED AT BY THIS OFFICE AND THE | | TENANT SPACE DOES NOT FALL UNDER THE DEFINITION OF A | | *BUILDING*. PLEASE SEE THAT COMPLETE INFORMATION FOR | | THE ENTIRE BUILDING NEEDS TO BE PROVIDED AS THIS SEEMS | | TO BE A TENANT SPACE WHICH IS PART OF A LARGER | | BUILDING. PLEASE KNOW THAT ADDITIONAL SERVICE IS NOT | | BEING GRANTED AS IT DOES NOT MEET 230.2. THERE IS NO | | INDICATION ON PLANS WHICH SHOWS COMPLIANCE WITH THE FBC | | TO CONSIDER THIS A *SEPARATE BUILDING BY DEFINITION*. | | PLEASE KNOW THAT THE SERVICE WHICH FEEDS THE BUILDING | | WILL NEED TO UP-GRADED IF THE EXISTING SERVICE IS NOT | | OF SUFFICIENT SIZE. | | ** PLEASE SUBMIT A COMPLETED RISER DIAGRAM FOR EXISTING | | SERVICE OR NEW. AS THE SERVICE AS PERMITTED HAS NOT | | BEEN SHOWN A REVIEW OF SERVICE CAN NOT BE DONE AT THIS | | TIME. | | | | 3) NOTE: PLEASE SEE THE PREVIOUS NOTES REQUESTED A | | COMPLETED RISER HOWEVER SOME OF THE INFORMATION IS | | STILL NOT ON PLANS. PLEASE SEE THE GROUNDING ELECTRODE | | SYSTEM AS REQUIRED PER 250.50 IS NOW SHOWING THE | | BUILDING/FOOTER STEEL? THIS IS AN EXISTING BUILDING AND | | THE EXISTING FOOTER STEEL IS NOT REQUIRED TO BE | | UNCOVERED IF THE ATTACHMENT IS NOT ALREADY MADE. THIS | | WOULD INDEED AFFECT THE STRUCTURAL INTEGRITY OF THE | | EXISTING FOOTER | | PLEASE INCLUDE AIC RATINGS FOR ALL NEW SERVICE | | EQUIPMENT. | | PLEASE SEE 215.5, 110.9, 240.4, 310.16, 230.70 | | | | 4) NOTE: PLEASE SUBMIT PLANS WHICH ARE COMPLIANT WITH | | THE 2004 FBC W/2006 REVISIONS FOR CHAPTER 13 AS | | PREVIOUSLY REQUESTED. PLEASE SEE 13-413.1ABC.1, | | 13-415.1.ABC.1.1, .1.2 AND .1.3. PLEASE SEE | | 13-415.1.AB.1.1, 13-415.2. | | PLEASE SEE A LIGHTING CONTROL PANEL IS NOW NOTED BUT | | THE NO INFORMATION WAS SHOWN FOR THE LIGHTING CONTROL | | PANEL OR SYSTEM. | | PLEASE SEE NOT TIMED SCHEDULING WAS SUBMITTED. | | PLEASE SEE NO TIMES WERE INDICATED FOR OVER RIDES. | | PLEASE SEE NO SPECIFIC TYPES OF DEVICES ARE INDICATED. | | PLEASE SEE ALL LOCATIONS FOR OVER RIDES ARE NOT SHOWN | | AS REQUIRED PER SECTIONS ABOVE. | | PLEASE SEE NOT ALL SEPARATE SPACES ARE SHOWING REQUIRED | | DEVICES. | | PLEASE SEE THE LIGHTING POWER DENSITIES ARE NOT | | CORRECT. | | PLEASE SEE TRACK LIGHTING PER 13-415.2.ABC.1.2 WAS NOT | | SHOWN OR CORRECT. | | PLEASE SEE13-415.2.ABC.1.2 (3, 4) | | NO FIXTURE LEGEND WAS SUBMITTED WHICH INDICATES THE | | FIXTURES AS NOTED ON PLANS, NO WATTAGE ON FIXTURES ETC | | NO ENERGY CALCULATIONS/PERFORMANCE CALCULATIONS, ETC | | AS THERE IS MUCH INFORMATION FOR CHAPTER 13 WHICH WAS | | NOT SUBMITTED, REVIEW FOR MANY OF THESE ITEMS CAN NOT | | BE DONE AT THIS TIME. | | | | 5) NOTE: PLEASE SUBMIT PLANS DESIGNED FOR COMMERCIAL | | LOAD CALCULATIONS. THIS WAS NOT DONE, IN FACT NO LOAD | | CALCULATIONS WERE SUBMITTED AND ONLY LOADS ON | | CIRCUITING ON PANEL SCHEDULES WAS SHOWN. | | PLEASE SEE 220.12, 220.14, 220.42, 220.44, 220.43 | | 215.5, 230.42 ETC. | | PLEASE SEE THAT ALL CONTINUOUS LOADS SHALL BE SHOWN AT | | 125% 215.3, 230.42. THIS WAS SHOWN, HOWEVER PLEASE BE | | SURE TO FIGURE INTO SERVICE. | | ** PLEASE KNOW DEPENDING ON SERVICE, LOAD CALCULATIONS | | FOR THE EXISTING SERVICE OR NEW PROPOSED *BUILDING* | | SERVICE MAY BE NEEDED. AS NO INFORMATION FOR THE | | *BUILDINGS* SERVICE WAS GIVEN WE CAN NOT DETERMINE MANY | | THINGS. | | | | 6) NOTE: PLEASE SHOW AND INDICATE ALL CIRCUITING ON | | PLANS AND CORRELATE WITH THE PANEL SCHEDULE(S) TO BE | | SUBMITTED. THIS NOTE REMAINS FROM PREVIOUS REVIEW AS | | SOME ITEMS ARE MISSING FROM PLANS. | | | | 7) NOTE:PLEASE SEE NEW HORN/STROBES ARE SHOWN ON | | PLANS HOWEVER NO MINIMUM LEVELS FOR ADA COMPLIANCE WAS | | SHOWN.PLEASE SEE FBC 2004 11-4.28.1, .2 AND .3(4) AND | | STATE THE MINIMUM HORN, STROBE LEVELS ON PLANS FOR ADA | | REQUIRED AREAS. DEVICES ARE BEING SHOWN ON | | PLANS/LEGEND.(QUOTING THAT THE DEVICES WILL BE ADA | | COMPLIANT IN LIEU OF INDICATING THE MINIMUM LEVELS | | REQUIRED PER CODE IS NOT PERMITTED) | | | | ** PLEASE KNOW THAT THE FIRE ALARM DEVICES/SYSTEM WILL | | BE UNDER A SEPARATE PERMIT HOWEVER THE BASE LIFE SAFETY | | SYSTEM IS REQUIRED ON BASE PLANS AS SHOWN. DO NOT | | REMOVE FROM SETS. | | FBC 106.3.5.1.2 | | | | 8) NOTE:SAME NOTE FROM PREVIOUS REVIEW. NOTES WERE | | PLACED ON PLANS HOWEVER THE INDICATE OF THESE BREAKERS | | ON PANEL SCHEDULES COULD NOT BE LOCATED. PLEASE | | INDICATE ALL SHUNT TRIP CIRCUITS FOR ANY ELECTRICAL | | UNDER HOOD PER NFPA-96. CHAPTER 9 AND 10. | | | | 9) NOTE: PLEASE SEE 210.8B3 FOR REQUIRED GFCI | | PROTECTION OF ALL 15/20AMP 120V CIRCUITS IN KITCHENS | | WHETHER OR NOT THEY ARE COUNTER SPACE CIRCUITS. PLEASE | | SEE NOTES WERE ADDED AND MOST ARE SHOWN HOWEVER NOT | | ALL. | | | | 10) NOTE: PLEASE INDICATE LOADS FOR TRACK LIGHTING ON | | SERVICE PER 220.43B. | | THIS IS NOT THE SAME AS THE LOADS FIGURED FOR FBC | | CHAPTER 13 COMPLIANCE. PLEASE SEE THE LOADS FOR CHAPTER | | 13 ARE MORE RESTRICTIVE FOR LPD. | | PLEASE SEE THIS IS THE SAME AS PREVIOUS REVIEW. | | | | 12) NOTE: PLEASE SEE THE SIGN CIRCUIT AND WINDOW | | RECEPTACLES WERE ADDED TO PLANS HOWEVER PLEASE VERIFY | | THE NEW LIGHTING SWITCHES BEING ADDED TO PLANS ARE | | BEING SHOWN OUTSIDE THE FRONT OF THE STORE AS SHOWN ON | | PLANS? | | | | 13) NOTE: PLEASE SEE MISSING DISCONNECT FOR WATER | | HEATER PER 422.30,.31 | | MAY NOT QUOTE REQUIREMENT OR CODE. | | | | 14) NOTE: PLEASE SEE MISSING DISCONNECT FOR A/C CU PER | | 440.11. | | MAY NOT QUOTE REQUIREMENT OR CODE IN LIEU OF DETAIL. | | | | 15) NOTE: PLEASE SEE MISSING GFI RECEPTACLE FOR CU. | | 210.63,210.8B | | | | 16) NOTE: PLEASE SEE NOTE ON PLANS MENTIONS NEW | | HARD-WIRED SMOKE DETECTORS WHICH TO BE INSTALLED | | HOWEVER NONE OF THESE COULD BE LOCATED ON PLANS ALONG | | WITH CIRCUITING. IF A FA SYSTEM IS GOING TO BE | | INSTALLED AS SHOWN ON PLANS, PLEASE SHOW HOW THESE SDS | | WILL BE CONNECTED. | | | | 17) NOTE: PLEASE SEE THE CONDUCTORS ON PANEL SCHEDULE | | FOR FEEDERS TO PANEL *B* ARE BEING SHOWN AS #12 WHEN | | RISER SHOWS #3. | | PLEASE SEE 240.4, 310.16. | | | | 18) NOTE: PLEASE SEE THE VALUE WAS STILL NOT ADJUSTED | | ON PERMIT APPLICATION OR EVEN RESPONDED TO. PLEASE SEE | | THE VALUATION FOR THE COMPLETE SCOPE OF WORK IS | | EXTREMELY LOW. ALL VALUE SHALL BE BASED ON LABOR, | | MATERIALS AND ALL PERMANENTLY INSTALLED EQUIPMENT EVEN | | IF OWNER SUPPLIED. | | FBC 108.3 | | PLEASE KNOW IF VALUES ARE NOT ADJUSTED, THE ADOPTED | | STANDARDS BY THE FBC MAY BE USED. | | | | 19) NOTE: PLEASE SEE THE NOC AS SUBMITTED HAS BECOME | | VOID PER FS 713.13(2). THIS WILL BE NEEDED TO BE | | RE-RECORDED AND SUBMITTED BEFORE PERMIT CAN BE PICKED | | UP. PLEASE KNOW THAT ONCE A NOC HAS BEEN RECORDED, THE | | SCOPE OF WORK MUST COMMENCE WITHIN 90DAYS OR THE NOC | | BECOMES VOID. | | | | 20) NOTE: PLEASE SEE ATTACHED FS 553.80(2)(B) WITH | | RESPECT TO REPEAT COMMENTS FOR CODE COMPLIANCE AS | | SEVERAL COMMENTS WERE REPEATED FROM PREVIOUS REVIEW. | | PLEASE KNOW THIS IS ONLY A NOTICE GIVEN AT THIS TIME. | | | | * ** IMPORTANT** | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | PICKED UP FOR CORRECTIONS, PLEASE BE | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | AND STAMPING. DO NOT LEAVE ANY | | OLD/VOIDED SHEETS IN SETS. | | PLEASE KNOW ONLY ONE SET OF THE | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | FOR REFERENCE. | | THIS WILL HELP IN THE REVIEW PROCESS AND | | AVOID ANY DELAYS. | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2007-04-15 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-04-15 |
Time |
19:08 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-04-15 |
Time |
18:18 |
Sent To |
|
|
Notes |
2007-04-15 19:08:48 | ** UNSAT ** | | | | ** PLEASE KNOW THAT PLANS ARE NOT COMPLETE AT THIS TIME | | FOR A FULL AND COMPLETE REVIEW. THERE MAY VERY WELL BE | | NEW COMMENTS ONCE PLANS ARE COMPLETED FOR REVIEW. | | | | ** PLEASE SEE ANY REFERENCES IN PLAN REVIEW NOTES TO | | CHAPTER 1 OF THE FBC ARE THAT WHICH IS ADOPTED BY THE | | CITY OF WEST PALM BEACH. | | | | 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH | | ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS | | UNDER THE NEW CODES ADOPTED BY THE STATE. | | PLANS AT THIS TIME DO NOT INDICATE ANY CODES. PLEASE | | SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO THE 2004 | | FBC FOR ALL TRADES AND THE 2005 NFPA-70. PLEASE KNOW | | THERE ARE CHANGES IN THE FBC WHICH MAY AFFECT DESIGNS | | FOR ALL TRADES. | | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS | | REVIEWER AT A MINIMUM. | | 2004 FBC W/ 2006 REVISIONS | | 2005 NFPA-70 | | 2002 NFPA-72 | | 2003 NFPA-101 | | | | 2) NOTE: PLEASE CORRELATE RISER, ELECTRICAL NOTES, | | PANEL SCHEDULE AND PLANS. | | PLEASE SEE THE ELECTRICAL SERVICE IS BEING SHOWN AS A | | 400A PANEL IN ONE NOTE, 300AMP IN ANOTHER NOTE, 300A ON | | PANEL SCHEDULE, YET RISER DOES NOT MATCH ANY OF THESE? | | PLEASE SEE THAT COMPLETE INFORMATION FOR THE ENTIRE | | BUILDING NEEDS TO BE PROVIDED AS THIS SEEMS TO BE A | | TENANT SPACE WHICH IS PART OF A LARGER BUILDING. PLEASE | | KNOW THAT ADDITIONAL SERVICE IS NOT BEING GRANTED AS IT | | DOES NOT MEET 230.2. THERE IS NO INDICATION ON PLANS | | WHICH SHOWS COMPLIANCE WITH THE FBC TO CONSIDER THIS A | | *SEPARATE BUILDING BY DEFINITION*. | | PLEASE KNOW THAT THE SERVICE WHICH FEEDS THE BUILDING | | WILL NEED TO UPGRADED IF THE EXISTING SERVICE IS NOT OF | | SUFFICIENT SIZE. | | ** PLEASE SUBMIT A COMPLETED RISER DIAGRAM FOR EXISTING | | SERVICE OR NEW. | | PLEASE INCLUDE GROUNDING ELECTRODE SYSTEM AS REQUIRED | | PER 250.50. (QUOTING THE CODE IS NOT PERMITTED IN LIEU | | OF REQUIRED CODE COMPLIANT DETAIL) | | PLEASE INCLUDE AIC RATINGS FOR ALL NEW SERVICE | | EQUIPMENT. | | PLEASE SEE 215.5, 110.9, 240.4, 310.16, 230.70 ETC A | | REVIEW FOR SERVICE CAN NOT BE DONE AT THIS TIME. | | | | 3) NOTE: PLEASE SUBMIT PLANS WHICH ARE COMPLIANT WITH | | THE 2004 FBC W/2006 REVISIONS FOR CHAPTER 13. PLEASE | | SEE 13-413.1ABC.1, 13-415.1.ABC.1.1, .1.2 AND .1.3. | | PLEASE SEE 13-415.1.AB.1.1, 13-415.2. | | PLEASE INDICATE ALL MAXIMUM TIMES ON OVER RIDE DEVICES. | | PLEASE SUBMIT DETAILS ON METHODS WHICH WILL BE | | INSTALLED. | | PLEASE SEE13-415.2.ABC.1.2 (3, 4) | | NO FIXTURE LEGEND WAS SUBMITTED, NO ENERGY | | CALCULATIONS, NO PERFORMANCE CALCULATIONS, ETC | | AS NO INFORMATION FOR CHAPTER 13 WAS SUBMITTED, REVIEW | | FOR THESE ITEMS CAN NOT BE DONE AT THIS TIME. | | | | 4) NOTE: PLEASE SUBMIT PLANS DESIGNED FOR COMMERCIAL | | LOAD CALCULATIONS. | | PLEASE SEE 220.12, 220.14, 220.42, 220.44, 220.43 | | 215.5, 230.42 ETC. | | PLEASE SEE THERE ARE CIRCUITS WHICH ARE OVER LOADED. | | PLEASE SEE NO LOADS ARE SHOWN FOR COMMERCIAL | | APPLICATION. | | PLEASE SEE THAT ALL CONTINUOUS LOADS SHALL BE SHOWN AT | | 125% 215.3, 230.42 | | | | 5) NOTE: PLEASE SHOW AND INDICATE ALL CIRCUITING ON | | PLANS AND CORRELATE WITH THE PANEL SCHEDULE(S) TO BE | | SUBMITTED. | | PLEASE SEE 408.4 OF THE NEC, AND THE FOLLOWING TEXT | | BELOW WHICH IS TAKEN DIRECTLY FROM THE NEC. | | PLEASE KNOW THAT THE PLANS NEED TO LABEL AND PROVIDE | | ROOM AND AREA DESIGNATIONS ON PLANS AND CORRELATE WITH | | THE PANEL SCHEDULES SHOWING ALL ROOMS AND AREAS IN | | WHICH CIRCUITS FEED WILL BE REQUIRED FOR EACH PANEL. | | PLEASE SEE TEXT WHICH IS TAKEN FROM COMMENTARY IN THE | | CODE WHICH STATES THE USE OF *GEN LT* ETC IS NOT | | ACCEPTABLE | | | | *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE | | THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A | | PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE | | THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED. | | CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED | | AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE | | BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN, | | DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE | | CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT | | ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS | | ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR | | RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT | | OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE | | ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT | | PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS | | SECTION.* | | 408.4, 310.16, 240.4 ETC | | FBC 106.3.5.4 | | | | 6) NOTE: PLEASE SEE 700.12E FOR CIRCUITING OF EMERGENCY | | AND EXIT LIGHTS. | | | | 7) NOTE: PLEASE SEE FBC 2004 11-4.28.1, .2 AND .3(4) | | AND STATE THE MINIMUM HORN, STROBE LEVELS ON PLANS FOR | | ADA REQUIRED AREAS. DEVICES ARE BEING SHOWN ON | | PLANS/LEGEND.(QUOTING THAT THE DEVICES WILL BE ADA | | COMPLIANT IN LIEU OF INDICATING THE MINIMUM LEVELS | | REQUIRED PER CODE IS NOT PERMITTED) | | | | ** PLEASE KNOW THAT THE FIRE ALARM DEVICES/SYSTEM WILL | | BE UNDER A SEPARATE PERMIT HOWEVER THE BASE LIFE SAFETY | | SYSTEM IS REQUIRED ON BASE PLANS AS SHOWN. DO NOT | | REMOVE FROM SETS. | | FBC 106.3.5.1.2 | | | | 8) NOTE: PLEASE INDICATE ALL SHUNT TRIP CIRCUITS FOR | | ANY ELECTRICAL UNDER HOOD PER NFPA-96. CHAPTER 9 AND | | 10. | | | | 9) NOTE: PLEASE SEE 210.8B3 FOR REQUIRED GFCI | | PROTECTION OF ALL 15/20AMP 120V CIRCUITS IN KITCHENS | | WHETHER OR NOT THEY ARE COUNTER SPACE CIRCUITS. | | | | 10) NOTE: PLEASE SEE SOME LOADS ON PANEL EXCEED THAT OF | | THE RATED 20AMP CIRCUIT. | | PLEASE SEE SHOW WINDOWS. | | PLEASE INDICATE THE LOADS ON SHOW WINDOWS FOR BRANCH | | CIRCUITS AND FEEDERS/SERVICE PER 220.43 | | | | 11) NOTE: PLEASE INDICATE LOADS FOR TRACK LIGHTING ON | | SERVICE PER 220.43B. | | THIS IS NOT THE SAME AS THE LOADS FIGURED FOR FBC | | CHAPTER 13 COMPLIANCE. PLEASE SEE THE LOADS FOR CHAPTER | | 13 ARE MORE RESTRICTIVE. | | | | 12) NOTE: PLEASE SEE 600.5 FOR MISSING SIGN CIRCUIT AND | | LOADS IN CALCULATIONS. | | | | 13) NOTE: PLEASE SEE THE VALUATION FOR THE COMPLETE | | SCOPE OF WORK IS EXTREMELY LOW. ALL VALUE SHALL BE | | BASED ON LABOR, MATERIALS AND ALL PERMANENTLY INSTALLED | | EQUIPMENT EVEN IF OWNER SUPPLIED. | | FBC 108.3 | | PLEASE KNOW IF VALUES ARE NOT ADJUSTED, THE ADOPTED | | STANDARDS BY THE FBC MAY BE USED. | | | | 14) NOTE: PLEASE SEE THE ARCHITECTURAL FIRM IS MISSING | | THE REQUIRED LICENSURE PER FS 481.219 AND FAC | | 61G1-16.004. | | PLEASE INCLUDE ON ALL SHEETS AND FOR ALL TRADES WHETHER | | OR NOT COMMENT IS MADE BY OTHER REVIEWERS. | | | | 15) NOTE: PLEASE COMPLETE PANEL SCHEDULE(S) WITH ALL | | BREAKER/OCP DEVICES AND CONDUCTOR SIZES. | | 408.4. | | 310.16, 240.4 | | FBC 106.3.5.1.2, 106.1.2 | | | | ** PLEASE KNOW DUE TO THE EXTENT OF ELECTRICAL | | COMMENTS, NO LICENSING FOR THE ARCHITECTURAL FIRM, ONE | | SET OF PLANS WILL BE RETAINED BY THIS OFFICE. | | | | * ** IMPORTANT** | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | PICKED UP FOR CORRECTIONS, PLEASE BE | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | AND STAMPING. DO NOT LEAVE ANY | | OLD/VOIDED SHEETS IN SETS. | | PLEASE KNOW ONLY ONE SET OF THE | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | FOR REFERENCE. | | THIS WILL HELP IN THE REVIEW PROCESS AND | | AVOID ANY DELAYS. | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
4 |
Status |
P |
Date |
2007-12-10 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2007-12-10 |
Time |
13:10 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2007-12-10 |
Time |
12:57 |
Sent To |
|
|
Notes |
2007-12-10 13:07:00 | *****APPROVED REVISION DATED 11/16/07***** | | | | | | REVISED PLAN SHEET A-1 STAMPED, INITIALED, AND DATED. | | | | | | . | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2007-08-30 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2007-08-30 |
Time |
10:15 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2007-08-30 |
Time |
09:39 |
Sent To |
|
|
Notes |
2007-08-30 10:15:11 | *****APPROVED***** | | | | | | THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE | | BEEN ADDRESSED;PLAN SHEET A-1 STAMPED, INITIALED, AND | | DATED. | | | | | | . | | | | | | | | | | | | | | | | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
F |
Date |
2007-07-10 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2007-07-10 |
Time |
13:47 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2007-07-10 |
Time |
12:31 |
Sent To |
|
|
Notes |
2007-07-10 13:46:48 | *****DENIED***** | | | | | | 1.NFPA 101 (2003 EDITION) AND THE FLORIDA FIRE | | PREVENTION CODE (2004 EDITION) SHALL BE REFERENCED. | | | | 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | 3.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL NOT | | INTERFERE OR HINDER EMERGENCY RESPONSE ACCESS TO THE | | PROPERTY OR VICINITY THEREOF (INCLUDING STREETS, ROADS, | | FIRE LANES). | | | | 4. COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL | | BE REMOVED FROM THE SITE DAILY OR MORE FREQUENTLY AS | | NECESSARY FOR SAFE OPERATION. | | | | 5.ON THE EXTERIOR ELEVATION WHICH FRONTS SOUTH DIXIE | | HIGHWAY, DISPLAY THE NUMERICAL ADDRESS FOR THIS | | PROJECT.AS PER WEST PALM BEACH CODE, ADDRESS NUMBERS | | SHALL BE NO LESS THAN 6" IN HEIGHT AND NO LESS THAN 1" | | IN WIDTH. | | | | 6.PLEASE GIVE THE FOLLOWING INFORMATION:* OCCUPANCY | | TYPE, * OCCUPANT LOAD, * FIRE SPRINKLERED OR NOT, * | | INTERIOR FINISH CLASSIFICATIONS FOR WALLS AND CEILINGS | | MATERIALS | | | | 7.COMMERCIAL COOKING EQUIPMENT SHALL BE IN ACCORDANCE | | WITH NFPA 96. SEPARATE PLANS AND PERMIT WILL BE | | REQUIRED. | | | | 8.PLEASE BE ADVISED THAT THE SUBMITTED SUB-PERMIT | | PLANS FOR THE COOKING HOOD INSTALLATION AND THE COOKING | | HOOD SUPPRESSION SYSTEM WILL NOT BE REVIEWED UNTIL SUCH | | TIME THAT THE "MASTER" PERMIT HAS BEEN ISSUED. | | | | 9.THE ADDRESS NUMBER ON SHEET A-1 & A-2 ARE NOT THE | | SAME AS THE OTHER SUBMITTED PLAN SHEETS.PLEASE | | AMEND. | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | LETTER INDICATING WHERE ON THE PLANS EACH COMMENT WAS | | ADDRESSED | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2007-07-10 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2007-05-17 |
Time |
13:25 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2007-05-17 |
Time |
12:42 |
Sent To |
|
|
Notes |
2007-05-17 13:25:25 | *****DENIED***** | | | | | | 1.NFPA 101 (2003 EDITION) AND THE FLORIDA FIRE | | PREVENTION CODE (2004 EDITION) SHALL BE REFERENCED. | | | | 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | 3.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL NOT | | INTERFERE OR HINDER EMERGENCY RESPONSE ACCESS TO THE | | PROPERTY OR VICINITY THEREOF (INCLUDING STREETS, ROADS, | | FIRE LANES). | | | | 4. COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL | | BE REMOVED FROM THE SITE DAILY OR MORE FREQUENTLY AS | | NECESSARY FOR SAFE OPERATION. | | | | 5.ON THE EXTERIOR ELEVATION WHICH FRONTS SOUTH DIXIE | | HIGHWAY, DISPLAY THE NUMERICAL ADDRESS FOR THIS | | PROJECT.AS PER WEST PALM BEACH CODE, ADDRESS NUMBERS | | SHALL BE NO LESS THAN 6" IN HEIGHT AND NO LESS THAN 1" | | IN WIDTH. | | | | 6.PLEASE GIVE THE FOLLOWING INFORMATION:* OCCUPANCY | | TYPE, * OCCUPANT LOAD, * FIRE SPRINKLERED OR NOT, * | | INTERIOR FINISH CLASSIFICATIONS FOR WALLS AND CEILINGS | | MATERIALS | | | | 7.COMMERCIAL COOKING EQUIPMENT SHALL BE IN ACCORDANCE | | WITH NFPA 96. SEPARATE PLANS AND PERMIT WILL BE | | REQUIRED. | | | | 8.PLEASE BE ADVISED THAT THE SUBMITTED SUB-PERMIT | | PLANS FOR THE COOKING HOOD INSTALLATION AND THE COOKING | | HOOD SUPPRESSION SYSTEM WILL NOT BE REVIEWED UNTIL SUCH | | TIME THAT THE "MASTER" PERMIT HAS BEEN ISSUED. | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
5 |
Status |
F |
Date |
2007-12-28 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2007-12-28 |
Time |
14:54 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2007-12-28 |
Time |
14:54 |
Sent To |
|
|
Notes |
2007-12-28 14:55:26 | SEE PLUMBING REVISION NOTES FROM 12-28-07 |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
4 |
Status |
P |
Date |
2007-09-05 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2007-09-05 |
Time |
17:44 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2007-09-05 |
Time |
17:25 |
Sent To |
|
|
Notes |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
3 |
Status |
F |
Date |
2007-08-31 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2007-08-31 |
Time |
07:37 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2007-08-31 |
Time |
07:37 |
Sent To |
|
|
Notes |
2007-08-31 07:38:53 | DENIED | | REFERENCE: FBC-2004 FUEL GAS | | | | ****FROM PREVIOUS REVIEW: | | ******FROM PREVIOUS REVIEWS: | | | | 1. THE FOLLOWING ARE GAS PERMIT REQUIREMENTS: | | | | A. SUBMIT AN ISOMETRIC DRAWING THAT | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | AND CORRESPONDING LENGTHS PER FBC-2004 | | FUEL GAS CODE. SOME SECTIONS DO NOT SHOW THE REQUIRED | | LENGTHS. ALSO SHOW ALL VALVES ON THE ISOMETRIC AS WELL | | AS THE SEDIMENT TRAPS REQUIRED IN SECTIONS 408.4 & | | 409.5. | | ****RESPONSE NOTED, BUT THE SEDIMENT TRAPS ARE NOT | | SHOWN. | | ******RESPONSE NOTED, BUT NOW "WHITE OUT" IS USED ON | | THE ISOMETRIC, (SEE BTU/HR NUMBERS), AND THIS IS NOT | | APPROVED ON SIGNED & SEALED PLANS PER SECTION 106.1.3. | | - SEPARATE SHUT OFF VALVES ARE REQUIRED FOR EACH GAS | | APPLIANCE. APPLIANCE MARKS 2 & 3 ONLY SHOW ONE SHUT OFF | | VALVE FOR TWO APPLIANCES. INDICATE VALVE SIZE FOR EACH | | APPLIANCE WHICH SHALL BE FULL SIZE PER TABLE 402.4(2). | | | | | | B. SHOW THE DISTANCE FROM THE POINT OF | | DELIVERY, (METER), TO THE MOST REMOTE | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | FBC-2004 FUEL GAS CODE APPENDIX A - USE | | OF CAPACITY TABLES A.3.1(4). | | ****RESPONSE NOTED, BUT THE DISTANCE IS NOT SHOWN. | | ******RESPONSE NOTED, BUT THE TOTAL DISTANCE ADDS UP TO | | 111FT, NOT 105FT AS SHOWN. | | | | C. OK | | D. OK | | | | E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | STANDARDS NFPA 54, NFPA 58, AND THE | | FBC-2004 FUEL GAS CODE SEC 402.2. | | ****RESPONSE NOTED, BUT COMMENT NOT ADDRESS. | | ******RESPONSE NOTED, BUT THE WATER HEATER, OVEN AND | | COOK TOP STOVE MANUF. SHEETS HAVE NOT BEEN SUBMITTED. | | ALSO THE 36" RANGE INDICATES 203,000 BTU AND IT IS | | INDICATED AS 132,000 BTU. SEE MANUF. SHEET SUBMITTED | | WITH MODEL NUMBER INDICATED. PLEASE CLARIFY. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | WITH A DESCRIPTION OF THE REVISION | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID | | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY | | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU | | FOR YOUR ANTICIPATED COOPERATION. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] | | | | | | | | | | | | . |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
2 |
Status |
F |
Date |
2007-07-10 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2007-07-10 |
Time |
11:25 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2007-07-10 |
Time |
11:25 |
Sent To |
|
|
Notes |
2007-07-10 11:29:40 | DENIED | | REFERENCE: FBC-2004 FUEL GAS | | | | ******FROM PREVIOUS REVIEW: | | | | 1. THE FOLLOWING ARE GAS PERMIT REQUIREMENTS: | | | | A. SUBMIT AN ISOMETRIC DRAWING THAT | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | AND CORRESPONDING LENGTHS PER FBC-2004 | | FUEL GAS CODE. SOME SECTIONS DO NOT SHOW THE REQUIRED | | LENGTHS. ALSO SHOW ALL VALVES ON THE ISOMETRIC AS WELL | | AS THE SEDIMENT TRAPS REQUIRED IN SECTIONS 408.4 & | | 409.5. | | ******RESPONSE NOTED, BUT THE SEDIMENT TRAPS ARE NOT | | SHOWN. | | | | B. SHOW THE DISTANCE FROM THE POINT OF | | DELIVERY, (METER), TO THE MOST REMOTE | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | FBC-2004 FUEL GAS CODE APPENDIX A - USE | | OF CAPACITY TABLES A.3.1(4). | | ******RESPONSE NOTED, BUT THE DISTANCE IS NOT SHOWN. | | | | C. OK | | D. OK | | | | E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | STANDARDS NFPA 54, NFPA 58, AND THE | | FBC-2004 FUEL GAS CODE SEC 402.2. | | ******RESPONSE NOTED, BUT COMMENT NOT ADDRESS. | | | | F. N/A | | F. N/A | | | | G. EMERGENCY HOOD SHUT DOWN SHUT OFF | | VALVE TO BE BELOW CEILING. MANUAL SHUT | | OFF VALVE TO BE UPSTREAM. UNION TO BE | | DOWN STREAM OF MANUAL VALVE. | | ******RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. SHOW | | VALVES & UNION ON RISER DIAGRAM. (SEE COMMENT #1). | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | WITH A DESCRIPTION OF THE REVISION | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID | | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY | | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU | | FOR YOUR ANTICIPATED COOPERATION. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] | | | | | | | | | | | | . |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
F |
Date |
2007-07-10 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2007-05-14 |
Time |
11:24 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2007-05-14 |
Time |
11:24 |
Sent To |
|
|
Notes |
2007-07-10 11:25:27 | DENIED | | REFERENCE: FBC-2004 FUEL GAS | | | | 1. THE FOLLOWING ARE GAS PERMIT REQUIREMENTS: | | | | A. SUBMIT AN ISOMETRIC DRAWING THAT | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | AND CORRESPONDING LENGTHS PER FBC-2004 | | FUEL GAS CODE. SOME SECTIONS DO NOT SHOW THE REQUIRED | | LENGTHS. ALSO SHOW ALL VALVES ON THE ISOMETRIC AS WELL | | AS THE SEDIMENT TRAPS REQUIRED IN SECTIONS 408.4 & | | 409.5. | | | | B. SHOW THE DISTANCE FROM THE POINT OF | | DELIVERY, (METER), TO THE MOST REMOTE | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | FBC-2004 FUEL GAS CODE APPENDIX A - USE | | OF CAPACITY TABLES A.3.1(4). | | | | C. INDICATE THE DELIVERY PRESSURE (PSI) | | PER FBC-2004 FUEL GAS CODE SEC. 402.2. | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. INDICATED ON THE | | PLANS AS 5PSI. PLEASE VERIFY WITH GAS PROVIDER. IF MORE | | THAN 1/2PSI, SHOW THE LOCATION OF ALL GAS REGULATORS | | AND SUBMIT THE MANUF. SPECIFICATION SHEETS INDICATING | | THE MODEL NUMBER OF THE REGULATOR. PLEASE INDICATE IF | | THE REGULATOR SHALL BE VENTED, AND IF SO SHOW THE | | ROUTING OF THE VENTING AND INDICATE THE MATERIAL FOR | | THE VENT. (VENT SHALL BE OF NON-COMBUSTALBE MATERIAL). | | REGULATORS SHALL BE DOWNSTREAM OF THE SOV OF THE GAS | | APPLIANCE. | | | | D. SUBMIT A DETAIL SHOWING THE TYPE, | | LOCATION, SIZE AND TERMINATION OF THE | | GAS VENTS PER FBC-2004 FUEL GAS CODE | | SECS. 502 THRU 505. | | | | E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | STANDARDS NFPA 54, NFPA 58, AND THE | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | | F. CLEARLY SHOW THE LOCATION AND CAP- | | ACITY OF LP TANK(S), TYPE OF TANK (DOT | | OR ASME), THE DISTANCE OF THE TANK FROM | | THE BUILDING AND ADJACENT PROPERTY LINES | | THE DISTANCE OF THE TANK FROM ALL SOUR- | | CES OF IGNITION, OTHER CONTAINERS, BUILD | | INGS, AND THE LOCATION OF ANY BUILDING | | OPENINGS BELOW THE RELIEF VALVE OF THE | | TANK PER NFPA 58, TABLE 3-2.2.2. | | | | F. CLEARLY INDICATE ON THE PLAN IF THE | | LP TANK IS ABOVE OR BELOW GROUND, AND | | SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES | | PER NFPA 58. IF THE TANK | | IS BELOW GROUND THE CONTAINER SHALL BE | | SECURILY ANCHORED PER NFPA 58 SECTION | | 3-2.2.7(H). | | | | G. EMERGENCY HOOD SHUT DOWN SHUT OFF | | VALVE TO BE BELOW CEILING. MANUAL SHUT | | OFF VALVE TO BE UPSTREAM. UNION TO BE | | DOWN STREAM OF MANUAL VALVE. | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | WITH A DESCRIPTION OF THE REVISION | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID | | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY | | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU | | FOR YOUR ANTICIPATED COOPERATION. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] | | | | | | | | | | | | . |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2007-11-27 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-11-27 |
Time |
10:41 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-11-27 |
Time |
10:41 |
Sent To |
|
|
Notes |
2007-11-29 11:08:43 | TO "BOB"#11 | 2007-11-27 10:41:49 | WAITING FOR "BOB" |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2007-09-05 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-09-05 |
Time |
14:37 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-09-05 |
Time |
14:37 |
Sent To |
P |
|
Notes |
2007-09-05 14:37:53 | TO "P" BOX/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2007-08-06 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-08-06 |
Time |
14:30 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-08-06 |
Time |
14:30 |
Sent To |
|
|
Notes |
2007-08-29 14:39:10 | TO "COMM" BD#33 | 2007-08-06 14:31:40 | WAITING FOR "COMM" BD |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2007-06-05 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-06-05 |
Time |
11:39 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-06-05 |
Time |
11:39 |
Sent To |
|
|
Notes |
2007-06-18 09:07:27 | TO "COMM" BD#24 | 2007-06-05 11:40:18 | WAITING FOR "COMM" BD |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2007-05-31 |
Time |
|
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-03-29 |
Time |
18:44 |
Sent To |
|
|
Notes |
2007-04-02 17:10:43 | TO COMM BOARD # 2 | 2007-03-29 18:43:47 | WAITING FOR COMM BOARD. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2007-08-17 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2007-08-17 |
Time |
16:00 |
Rev Time |
0.25 |
Received By |
tgordon |
Date |
2007-08-17 |
Time |
16:00 |
Sent To |
|
|
Notes |
2007-08-20 15:50:15 | RETURNED TO INCOMING WAITING TO GET ON COMM. BOARD. | 2007-08-17 16:01:09 | *** PROVISO *** | | ADDITIONAL MECHANICAL PERMITS REQUIRED FOR | | (A) WALK-IN-COOLER | | (B) KITCHEN HOOD | | (C) FIRE SUPPRESSION | | (D) MEDICAL GAS OR FUEL | | ** SUBMIT PLANS WITH PERMIT APPLICATION. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2007-06-20 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2007-06-20 |
Time |
09:11 |
Rev Time |
0.30 |
Received By |
tgordon |
Date |
2007-06-20 |
Time |
09:11 |
Sent To |
|
|
Notes |
2007-06-20 09:14:00 | *** PROVISO *** | | ADDITIONAL MECHANICAL PERMITS REQUIRED FOR | | (A) WALK-IN-COOLER | | (B) KITCHEN HOOD | | (C) FIRE SUPPRESSION | | (D) MEDICAL GAS OR FUEL | | ** SUBMIT PLANS WITH PERMIT APPLICATION. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2007-04-17 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2007-04-17 |
Time |
08:21 |
Rev Time |
1.00 |
Received By |
tgordon |
Date |
2007-04-17 |
Time |
08:21 |
Sent To |
|
|
Notes |
2007-04-17 08:46:53 | *** DENIED *** | | 1) PLEASE SUBMITCOOLING LOAD CALCULATIONS, SEE 2004 | | FBC 13-607.1.ABC.1 . | | | | 2) PLEASE SUBMIT OUTDOOR AIR CALCULATIONS, SEE 2004 | | FBC/M 401.2. | | | | 3) PLEASE SUBMIT MECHANICAL (A/C) PLANS SHOWING | | EXISTING AND NEW DUCT LAY-OUT WITH AN A/C EQUIPMENT | | SCHEDULE, SEE 2004 FBC 106.3.5. | | | | 4) SEE ELECTRICAL REVIEW NOTES 13 AND 14, PLEASE | | CORRECT. | | | | 5) PLEASE BE AWARE A MECHANICAL A/C PERMIT WILL BE | | REQUIRED FOR BATHROOM EXHAUST FANS AND ANY OTHER A/C | | WORK TO BE DONE. | | | | 6) PLEASE BE AWARE ADDITIONAL MECHANICAL PERMITS WILL | | BE REQUIRED FORWALK-IN-COOLER AND FREEZER. PLANS FOR | | COOLER/FREEZER MAY BE SUBMITTEDWITH APPLICATION WHEN | | APPLYING FOR THAT PERMIT. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
6 |
Status |
F |
Date |
2007-12-28 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2007-12-28 |
Time |
14:43 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2007-12-28 |
Time |
14:43 |
Sent To |
|
|
Notes |
2007-12-28 14:54:07 | REVISION DENIED | | REFERENCE: FBC-2004 PLUMBING | | FBC-2004 FUEL GAS | | | | 1. SHT P-1 REVISION DENIED. MOST CLOUDED REVISIONS SHOW | | NO CHANGE.--THERE ARE CLEANOUTS REQUIRED AS THE | | PIPING FOR THE SANITARY EXITS THE BUILDING NEAR THE | | JUNCTION OF THE BUILDING DRAIN AND THE BUILDING SEWER | | AND AS THE PIPING FOR THE GREASE INTERCEPTOR EXITS THE | | INTERCEPTOR. THESE ARE SHOWN TO HAVE BEEN DELETED. | | THESE SHOULD BE SHOWN ON THE PLAIN VIEW ALSO.-- | | TOTAL BTU'S AT THE TOTAL GAS CONNECTED LOAD HAS BEEN | | CHANGED FROM 978,000 TO 898,000 TOTAL BTU'S. THE | | ORIGINAL TOTAL WAS CORRECT. THE NEW TOTAL IS DENIED. | | --THE TABLE FOR THE GAS WAS CHANGED FROM 402.4(2) TO | | 402.4(1). THIS IS NOT APPROVED. THE ORIGINAL TABLE IS | | CORRECT.--THE NOTE INDICATING THE DISTANCE FROM THE | | POINT OF DELIVERY ETC. ENDS WITH A GAS SIZING TABLE OF | | A.3.1(4). THIS TABLE DOES NOT EXIST IN THE 2004 FUEL | | GAS CODE AND IS NOT CORRECT. THE CORRECT TABLE IS | | 402.4(1). PLEASE CHANGE NOTE. PLEASE SUBMIT REVISIONS | | THAT CHANGE FROM THE ORIGINAL STAMPED/REVIEWED PLANS. | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | WITH A DESCRIPTION OF THE REVISION MADE, | | IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | ONE SET OF THEM LOOSELY ON TOP OF THE | | COLLATED PLANS TO BE REVIEWED. | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
5 |
Status |
F |
Date |
2007-12-07 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2007-12-07 |
Time |
15:09 |
Rev Time |
0.00 |
Received By |
jleech |
Date |
2007-12-07 |
Time |
15:06 |
Sent To |
|
|
Notes |
2007-12-07 15:19:57 | REVISION DENITED; | | 1. MAKE ALL PLUMBING REVISIONS ON "P" PAGES. | | 2. FLAT PIPING ON PAGE A-2 DOES NOT MATCH SANITARY | | RISER DIAGRAM ON P-1. | | 3. PLANS SHOW A 750 GAL. GREASE TRAP OUTSIDE WITH THE | | ROTISARY, 3-COMPARTMENT SINK AND MOP SINKALL DRAINING | | INTO A GREASE LINE. | | 4. THE GREASE TRAP WAS SIZED BY THE UTILITY DEPARTMENT. | | TO CHANGE THE SIZE AND TYPE OF TRAP YOU MUST GET | | APPROVAL FROM UTILITIES BEFORE SUBMITING REVISION TO | | THE BUILDING DEPARTMENT. | | PLUMBING PLAN REVIEW BY | | JOHN LEECH | | 805-6695 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
4 |
Status |
P |
Date |
2007-09-05 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2007-09-05 |
Time |
17:25 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2007-09-05 |
Time |
17:25 |
Sent To |
|
|
Notes |
2007-09-05 17:32:11 | | | | | | | | | | | | | PASSED/PROVISO | | | | AS INDICATED FROM RESTAURANT OWNER, THE GREASE FROM THE | | ROTISSERIE OVEN SHALL BE COLLECTED AND REMOVED FROM THE | | PROPERTY AND DISPOSED OF PROPERLY. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
F |
Date |
2007-08-31 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2007-08-31 |
Time |
06:54 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2007-08-30 |
Time |
19:10 |
Sent To |
|
|
Notes |
2007-08-31 07:36:31 | DENIED | | REFERENCE: FBC-2004 PLUMBING | | FBC-2004 FUEL GAS | | FBC-2004 CHAPTER 1 | | FBC-2004 CHAPTER 11 | | CITY WPB MUNICIPAL CODE | | FLORIDA ADMINISTRATIVE CODE | | FLORIDA STATUTES | | | | ****FROM PREVIOUS REVIEW: | | ******FROM PREVIOUS REVIEWS: | | | | 1. OK | | 2. OK | | | | 3. 2 SETS OF PLANS, STAMPED BY THE DEPT OF BUSINESS | | REGULATION, HOTEL & RESTAURANT DIVISION SHALL BE | | SUBMITTED FOR REVIEW. ONLY ONE SET HAS THE DBPR STAMP. | | ALSO THE TWO PAGE "WORKSHEETS" SHALL BE ATTACHED TO | | EACH SET OF PLANS SUBMITTED FOR REVIEW BY THE CITY | | WPB. | | ****RESPONSE NOTED, BUT THE TWO PAGE "WORKSHEETS" HAVE | | NOT BEEN ATTACHED TO EACH SET OF PLAN. | | ******NO RESPONSE. STAMPED/REVIEWED SHEETS FROM DBPR | | HAVE BEEN DELETED FROM EACH SET. THESE ARE REQUIRED AS | | WELL AS THE TWO PAGE "SPECIFICATION WORKSHEETS". THE | | WORKSHEETS SHALL BE ATTACHED TO THE SHEETS STAMPED & | | REVIEWED BY DBPR AND ONE SHEET SHALL BE INSERTED INTO | | EACH SET OF PLANS AS REQUIRED BY SECTION 102.2.1. | | | | 4. THE GREASE INTERCEPTOR SHALL BE SIZED AND LOCATED BY | | THE ENVIRONMENTAL COMPLIANCE DEPT. PLEASE CONTACT | | RODNEY COMPO (561) 822-2272, [email protected], OR CALVIN | | WILLIAMS (561) 822-2284, [email protected]. THEIR FAX | | NUMBER IS (561) 822-2287. ARTICLE III SECTION 90-124. | | --PER ARTICLE III SECTION 90-124(7)(F) A CONCRETE, | | MINIMUM 750 GAL. INTERCEPTOR IS REQUIRED.(SEE | | ATTACHED UTILITY STANDARD FOR GREASE INTERCEPTORS).-- | | THE GREASE INTERCEPTORS ARE TO BE INSTALLED OUTSIDE THE | | FOOD PREPARATION AREA WITH THE DISHWASHER DISCHARGING | | VIA A SEPARATE LINE TO THE SANITARY. ARTICLE III | | SECTION 9--124(7)(B). | | ****RESPONSE NOTED, BUT NO INPUT FROM ENVIRONMENTAL | | COMPLIANCE HAS BEEN SUBMITTED. PLEASE SUBMIT WRITTEN | | APPROVAL OF THE SIZE GREASE INTERCEPTOR FROM MR. COMPO | | OR MR. WILLIAMS. | | ******NO RESPONSE, COMMENT NOT ADDRESSED. | | | | 5. OK | | | | 6. SHT A-2 MORE INFORMATION IS REQUIRED. IS THERE A | | FIXTURE DRAINING INTO THE GREASE TRAP SHOWN ON THE | | FLOOR PLAN AS PLUMBING PLAN KEY ITEM #6. PLEASE | | CLARIFY. SECTION 106.1.1. | | ****RESPONSE NOTED, BUT THE GREASE FROM THE ROTISSERIE | | OVEN CAN NOT DRAIN INTO THE FLOOR SINK. THE GREASE | | SYSTEM IS DESIGNED TO INTERCEPT INCIDENTAL GREASE NOT | | GREASE DRIPPINGS FROM AN OVEN. THE GREASE WILL HAVE TO | | BE CONTAINED AND THEN DISPOSED OF PROPERLY AT A | | RENDERING PLANT, NOT DRAINED INTO THE FLOOR SINK. | | ******NO RESPONSE, COMMENT NOT ADDRESSED. | | | | 7. OK | | 8. OK | | 9. OK | | 10. OK | | 11. OK | | 12. OK | | 13. OK | | | | 14. SHT A-2 THE ACCESSIBLE TOILET ROOMS SHALL SHOW | | COMPLIANCE WITH THE FOLLOWING: | | ___FOR W/C | | A. 11-4.16.2 CLEAR FLOOR SPACE - ******NO RESPONSE, | | COMMENT NOT ADDRESSED. SHOW IN THE TOILET ROOM TO | | VERIFY COMPLIANCE. | | B. 11-4.16.5 FLUSH CONTROLS - ******NO RESPONSE, | | COMMENT NOT ADDRESSED. | | ___FOR LAV | | A. 11-4.19.3 CLEAR FLOOR SPACE - ******NO RESPONSE, | | COMMENT NOT ADDRESSED. SHOW IN THE TOILET ROOM TO | | VERIFY COMPLIANCE. | | B. 11-4.19.4 EXPOSED PIPES & SURFACES - ******NO | | RESPONSE, COMMENT NOT ADDRESSED. | | C. 11-4.19.5 FAUCETS - ******NO RESPONSE, COMMENT NOT | | ADDRESSED. | | ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. | | | | 15. THE FOLLOWING ARE GAS PERMIT REQUIREMENTS: | | | | A. SUBMIT AN ISOMETRIC DRAWING THAT | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | AND CORRESPONDING LENGTHS PER FBC-2004 | | FUEL GAS CODE. SOME SECTIONS DO NOT SHOW THE REQUIRED | | LENGTHS. ALSO SHOW ALL VALVES ON THE ISOMETRIC AS WELL | | AS THE SEDIMENT TRAPS REQUIRED IN SECTIONS 408.4 & | | 409.5. | | ****RESPONSE NOTED, BUT THE SEDIMENT TRAPS ARE NOT | | SHOWN. | | ******RESPONSE NOTED, BUT NOW "WHITE OUT" IS USED ON | | THE ISOMETRIC, (SEE BTU/HR NUMBERS), AND THIS IS NOT | | APPROVED ON SIGNED & SEALED PLANS PER SECTION 106.1.3. | | - SEPARATE SHUT OFF VALVES ARE REQUIRED FOR EACH GAS | | APPLIANCE. APPLIANCE MARKS 2 & 3 ONLY SHOW ONE SHUT OFF | | VALVE FOR TWO APPLIANCES. INDICATE VALVE SIZE FOR EACH | | APPLIANCE WHICH SHALL BE FULL SIZE PER TABLE 402.4(2). | | | | | | B. SHOW THE DISTANCE FROM THE POINT OF | | DELIVERY, (METER), TO THE MOST REMOTE | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | FBC-2004 FUEL GAS CODE APPENDIX A - USE | | OF CAPACITY TABLES A.3.1(4). | | ****RESPONSE NOTED, BUT THE DISTANCE IS NOT SHOWN. | | ******RESPONSE NOTED, BUT THE TOTAL DISTANCE ADDS UP TO | | 111FT, NOT 105 AS SHOWN. | | | | C. OK | | D. OK | | | | E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | STANDARDS NFPA 54, NFPA 58, AND THE | | FBC-2004 FUEL GAS CODE SEC 402.2. | | ****RESPONSE NOTED, BUT COMMENT NOT ADDRESS. | | ******RESPONSE NOTED, BUT THE WATER HEATER, OVEN AND | | COOK TOP STOVE MANUF. SHEETS HAVE NOT BEEN SUBMITTED. | | ALSO THE 36" RANGE INDICATES 203,000 BTU AND IT IS | | INDICATED AS 132,000 BTU. SEE MANUF. SHEET SUBMITTED | | WITH MODEL NUMBER INDICATED. | | | | F. N/A | | F. N/A | | G. OK | | | | ************NEW COMMENTS************ | | | | 1B. OK | | 2B. OK | | 3B. OK | | 4B. OK | | 5B. SHT M-1 PLUMBING FIXTURE SCHEDULE INDICATES THE | | GREASE INTERCEPTOR AND THE GAS WATER HEATER BY THE | | GENERAL CONTRACTOR.A SEPARATE GREASE INTERCEPTOR | | PERMIT IS REQUIRED BY THE PROVIDER OF THE GREASE | | INTERCEPTORAND SHALL BE HOOKED UP BY THE PLUMBING | | CONTRACTOR AS WELL AS THE GAS WATER HEATER. FS 489. | | ******NO RESPONSE. PLEASE INDICATE PLUMBING CONTRACTOR | | RESPONSIBILITY FOR THESE INSTALLATIONS. | | | | 6B. SEE ATTACHED SHEET CONCERNING THE DESIGN | | PROFESSIONALS AND FS 533.80(2)(B). THIS IS GIVEN AS A | | NOTICE AT THIS TIME. | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | WITH A DESCRIPTION OF THE REVISION | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID | | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY | | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU | | FOR YOUR ANTICIPATED COOPERATION. ******SUBMIT ONE SET | | OF VOID SHEETS FOR COMPARISON WHEN RESUBMITTING | | PLANS.****** | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] | | | | | | | | | | | | . |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2007-07-10 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2007-07-10 |
Time |
11:33 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2007-07-09 |
Time |
19:03 |
Sent To |
|
|
Notes |
2007-07-10 11:47:21 | DENIED | | REFERENCE: FBC-2004 PLUMBING | | FBC-2004 FUEL GAS | | FBC-2004 CHAPTER 1 | | FBC-2004 CHAPTER 11 | | CITY WPB MUNICIPAL CODE | | FLORIDA ADMINISTRATIVE CODE | | FLORIDA STATUTES | | | | ****FROM PREVIOUS REVIEW: | | | | 1. PER ADDRESSING, THE WRONG PCN NUMBER WAS USED DURING | | APPLICATION FOR PERMIT. THE CORRECT ADDRESS IS 3008 S | | DIXIE HWY, NOT 3010 S DIXIE HWY AS INDICATED ON THE | | APPLICATION AND ON THE TITLE BLOCK OF SHEETS A-1 & A-2. | | PLEASE CHANGE THE APPLICATION AND THE TITLE BLOCKS TO | | REFLECT THE CORRECT ADDRESS. | | ****RESPONSE NOTED, BUT THE ADDRESS HAS NOT BEEN | | CHANGED ON THE ARCHITECTURAL SHEETS. | | | | 2. SHTS A-2 & A-2 THE BUSINESS NUMBER, (CERTIFICATE OF | | AUTHORIZATION), ADDRESS, AND PHONE NUMBER OF THE | | ARCHITECT'S BUSINESS SHALL BE INDICATED IN THE TITLE | | BLOCK AS WELL AS THE PRINTED NAME OF THE PERSON SEALING | | THE DOCUMENT. FAC 61G1-16.004(1)(2)(6) & FS 481.219, | | 481.2055. | | ****RESPONSE NOTED, COMMENT NOT ADDRESSED. | | | | 3. 2 SETS OF PLANS, STAMPED BY THE DEPT OF BUSINESS | | REGULATION, HOTEL & RESTAURANT DIVISION SHALL BE | | SUBMITTED FOR REVIEW. ONLY ONE SET HAS THE DBPR STAMP. | | ALSO THE TWO PAGE "WORKSHEETS" SHALL BE ATTACHED TO | | EACH SET OF PLANS SUBMITTED FOR REVIEW BY THE CITY | | WPB. | | ****RESPONSE NOTED, BUT THE TWO PAGE "WORKSHEETS" HAVE | | NOT BEEN ATTACHED TO EACH SET OF PLAN. | | | | 4. THE GREASE INTERCEPTOR SHALL BE SIZED AND LOCATED BY | | THE ENVIRONMENTAL COMPLIANCE DEPT. PLEASE CONTACT | | RODNEY COMPO (561) 822-2272, [email protected], OR CALVIN | | WILLIAMS (561) 822-2284, [email protected]. THEIR FAX | | NUMBER IS (561) 822-2287. ARTICLE III SECTION 90-124. | | --PER ARTICLE III SECTION 90-124(7)(F) A CONCRETE, | | MINIMUM 750 GAL. INTERCEPTOR IS REQUIRED.(SEE | | ATTACHED UTILITY STANDARD FOR GREASE INTERCEPTORS).-- | | THE GREASE INTERCEPTORS ARE TO BE INSTALLED OUTSIDE THE | | FOOD PREPARATION AREA WITH THE DISHWASHER DISCHARGING | | VIA A SEPARATE LINE TO THE SANITARY. ARTICLE III | | SECTION 9--124(7)(B). | | ****RESPONSE NOTED, BUT NO INPUT FROM ENVIRONMENTAL | | COMPLIANCE HAS BEEN SUBMITTED. PLEASE SUBMIT WRITTEN | | APPROVAL OF THE SIZE GREASE INTERCEPTOR FROM MR. COMPO | | OR MR. WILLIAMS. | | | | 5. OK | | | | 6. SHT A-2 MORE INFORMATION IS REQUIRED. IS THERE A | | FIXTURE DRAINING INTO THE GREASE TRAP SHOWN ON THE | | FLOOR PLAN AS PLUMBING PLAN KEY ITEM #6. PLEASE | | CLARIFY. SECTION 106.1.1. | | ****RESPONSE NOTED, BUT THE GREASE FROM THE ROTISSERIE | | OVEN CAN NOT DRAIN INTO THE FLOOR SINK. THE GREASE | | SYSTEM IS DESIGNED TO INTERCEPT INCIDENTAL GREASE NOT | | GREASE DRIPPINGS FROM AN OVEN. THE GREASE WILL HAVE TO | | BE CONTAINED AND THEN DISPOSED OF PROPERLY AT A | | RENDERING PLANT, NOT DRAINED INTO THE FLOOR SINK. | | | | 7. OK | | 8. OK | | 9. OK | | 10. OK | | | | 11. SUBMIT A WATER ISOMETRIC RISER DIAGRAM SHOWING ALL | | PIPE SIZES, VALVES, REQUIRED WATER HAMMER ARRESTORS, | | (LOCATED NEAR THE FIXTURE IN AN "EFFECTIVE RANGE", NOT | | IN THE CEILING). INDICATE THE WATER SERVICE SIZE PER | | TABLE 603.1 AND INDICATE IF THERE IS AN EXISTING RPZV | | BACKFLOW PREVENTER ON THE WATER SERVICE. IF NO | | BACKFLOW, THEN ONE WILL BE REQUIRED PER SECTION | | 608.13.2.SECTIONS 106.3.5.1.3(3)(8)(10)(13) & 604.9. | | ****RESPONSE NOTED, BUT A FULL OPEN VALVE IS REQUIRED | | ON THE WATER DISTRIBUTION SUPPLY PIPE AT THE ENTRANCE | | INTO THE STRUCTURE. SECTION 606.1(2). | | | | 12. SHT A-2 THERMAL EXPANSION CONTROL IS REQUIRED PER | | SECTION 607.3.2. PLEASE INDICATE METHOD. ****RESPONSE | | NOTED, BUT A CHECK VALVE DOES NOT CONTROL THERMAL | | EXPANSION.PLEASE INDICATE PROPER APPROVED METHOD OF | | CONTROLING THERMAL EXPANSION. | | | | 13. OK | | | | 14. SHT A-2 THE ACCESSIBLE TOILET ROOMS SHALL SHOW | | COMPLIANCE WITH THE FOLLOWING: | | ___FOR W/C | | A. 11-4.16.2 CLEAR FLOOR SPACE | | B. 11-4.16.5 FLUSH CONTROLS | | ___FOR LAV | | A. 11-4.19.3 CLEAR FLOOR SPACE | | B. 11-4.19.4 EXPOSED PIPES & SURFACES | | C. 11-4.19.5 FAUCETS | | ALSO SHOW THE W/C TO BE 18" OFF THE WALL TO THE | | CENTERLINE OF THE FIXTURE PER FIG. 29. SHOW THE LAV TO | | BE A MINIMUM OF 15" OFF THE WALL TO THE CENTERLINE OF | | THE FIXTURE. (CENTER ON THE 30" OF THE 30"X48" CLEAR | | FLOOR SPACE REQUIRED FOR THE LAV). | | ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. | | | | 15. THE FOLLOWING ARE GAS PERMIT REQUIREMENTS: | | | | A. SUBMIT AN ISOMETRIC DRAWING THAT | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | AND CORRESPONDING LENGTHS PER FBC-2004 | | FUEL GAS CODE. SOME SECTIONS DO NOT SHOW THE REQUIRED | | LENGTHS. ALSO SHOW ALL VALVES ON THE ISOMETRIC AS WELL | | AS THE SEDIMENT TRAPS REQUIRED IN SECTIONS 408.4 & | | 409.5. | | ******RESPONSE NOTED, BUT THE SEDIMENT TRAPS ARE NOT | | SHOWN. | | | | B. SHOW THE DISTANCE FROM THE POINT OF | | DELIVERY, (METER), TO THE MOST REMOTE | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | FBC-2004 FUEL GAS CODE APPENDIX A - USE | | OF CAPACITY TABLES A.3.1(4). | | ******RESPONSE NOTED, BUT THE DISTANCE IS NOT SHOWN. | | | | C. OK | | D. OK | | | | E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | STANDARDS NFPA 54, NFPA 58, AND THE | | FBC-2004 FUEL GAS CODE SEC 402.2. | | ******RESPONSE NOTED, BUT COMMENT NOT ADDRESS. | | | | F. N/A | | F. N/A | | | | G. EMERGENCY HOOD SHUT DOWN SHUT OFF | | VALVE TO BE BELOW CEILING. MANUAL SHUT | | OFF VALVE TO BE UPSTREAM. UNION TO BE | | DOWN STREAM OF MANUAL VALVE. | | ******RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. SHOW | | VALVES & UNION ON RISER DIAGRAM. (SEE COMMENT #1). | | | | ************NEW COMMENTS************ | | | | 1B. (NEW) SHT P-1 INDICATES A WATER FILTER. THE WATER | | FILTER SHALL MEET THE REQUIREMENTS OF NSF 42. SUBMIT | | MANUF. SPECIFICATIONS SHOWING COMPLIANCE. SECTION | | 611.1. | | | | 2B. SHT P-1 A VENT IS REQUIRED ON THE GREASE SYSTEM. | | SECTION 901.2. | | | | 3B. SHT P-1 A SERVICE SINK IS REQUIRED PER TABLE 403.1. | | SINK SHALL BE CONNECTED TO THE GREASE SYSTEM. INDICATE | | THE LOCATION ON THE FLOOR PLAN, GREASE RISER DIAGRAM | | AND THE WATER RISER DIAGRAM. | | | | 4B. SHT M-1 GAS WATER HEATER DETAIL. A FLOOR DRAIN IS | | NOT AN APPROVED INDIRECT WASTE RECEPTOR. A FLOOR SINK | | OR HUB DRAIN SHALL BE USED. SECTIONS 802.3 & 802.3.2. | | | | 5B. SHT M-1 PLUMBING FIXTURE SCHEDULE INDICATES THE | | GREASE INTERCEPTOR AND THE GAS WATER HEATER BY THE | | GENERAL CONTRACTOR.A SEPARATE GREASE INTERCEPTOR | | PERMIT IS REQUIRED BY THE PROVIDER OF THE GREASE | | INTERCEPTORAND SHALL BE HOOKED UP BY THE PLUMBING | | CONTRACTOR AS WELL AS THE GAS WATER HEATER. FS 489. | | | | 6B. SEE ATTACHED SHEET CONCERNING THE DESIGN | | PROFESSIONALS AND FS 533.80(2)(B). THIS IS GIVEN AS A | | NOTICE AT THIS TIME. | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | WITH A DESCRIPTION OF THE REVISION | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID | | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY | | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU | | FOR YOUR ANTICIPATED COOPERATION. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] | | | | | | | | | | | | . |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2007-05-14 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2007-05-14 |
Time |
14:11 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2007-05-14 |
Time |
14:11 |
Sent To |
|
|
Notes |
2007-05-14 15:55:28 | DENIED | | REFERENCE: FBC-2004 PLUMBING | | FBC-2004 FUEL GAS | | FBC-2004 CHAPTER 1 | | FBC-2004 CHAPTER 11 | | CITY WPB MUNICIPAL CODE | | FLORIDA ADMINISTRATIVE CODE | | FLORIDA STATUTES | | | | 1. PER ADDRESSING, THE WRONG PCN NUMBER WAS USED DURING | | APPLICATION FOR PERMIT. THE CORRECT ADDRESS IS 3008 S | | DIXIE HWY, NOT 3010 S DIXIE HWY AS INDICATED ON THE | | APPLICATION AND ON THE TITLE BLOCK OF SHEETS A-1 & A-2. | | PLEASE CHANGE THE APPLICATION AND THE TITLE BLOCKS TO | | REFLECT THE CORRECT ADDRESS. | | | | 2. SHTS A-2 & A-2 THE BUSINESS NUMBER, (CERTIFICATE OF | | AUTHORIZATION), ADDRESS, AND PHONE NUMBER OF THE | | ARCHITECT'S BUSINESS SHALL BE INDICATED IN THE TITLE | | BLOCK AS WELL AS THE PRINTED NAME OF THE PERSON SEALING | | THE DOCUMENT. FAC 61G1-16.004(1)(2)(6) & FS 481.219, | | 481.2055. | | | | 3. 2 SETS OF PLANS, STAMPED BY THE DEPT OF BUSINESS | | REGULATION, HOTEL & RESTAURANT DIVISION SHALL BE | | SUBMITTED FOR REVIEW. ONLY ONE SET HAS THE DBPR STAMP. | | ALSO THE TWO PAGE "WORKSHEETS" SHALL BE ATTACHED TO | | EACH SET OF PLANS SUBMITTED FOR REVIEW BY THE CITY | | WPB. | | | | 4. THE GREASE INTERCEPTOR SHALL BE SIZED AND LOCATED BY | | THE ENVIRONMENTAL COMPLIANCE DEPT. PLEASE CONTACT | | RODNEY COMPO (561) 822-2272, [email protected], OR CALVIN | | WILLIAMS (561) 822-2284, [email protected]. THEIR FAX | | NUMBER IS (561) 822-2287. ARTICLE III SECTION 90-124. | | --PER ARTICLE III SECTION 90-124(7)(F) A CONCRETE, | | MINIMUM 750 GAL. INTERCEPTOR IS REQUIRED.(SEE | | ATTACHED UTILITY STANDARD FOR GREASE INTERCEPTORS).-- | | THE GREASE INTERCEPTORS ARE TO BE INSTALLED OUTSIDE THE | | FOOD PREPARATION AREA WITH THE DISHWASHER DISCHARGING | | VIA A SEPARATE LINE TO THE SANITARY. ARTICLE III | | SECTION 9--124(7)(B). | | | | 5. SHT A-2 ALL KITCHEN AREA FLOOR DRAINS SHALL CONNECT | | TO THE GREASE WASTE SYSTEM, NOT THE SANITARY AS SHOWN. | | ARTICLE III SECTION 90-124(7). | | | | 6. SHT A-2 MORE INFORMATION IS REQUIRED. IS THERE A | | FIXTURE DRAINING INTO THE GREASE TRAP SHOWN ON THE | | FLOOR PLAN AS PLUMBING PLAN KEY ITEM #6. PLEASE | | CLARIFY. SECTION 106.1.1. | | | | 7. SHT A-2 THE HAND SINK NEXT TO PLUMBING PLAN KEY ITEM | | #14 SHALL DRAIN INDIRECTLY INTO A FLOOR SINK, AND SHALL | | CONNECT TO THE GREASE WASTE SYSTEM.SECTION802.1.1. | | AS SHOWN THE HAND SINK IS DRAINING THRU THE WET VENT | | FOR THE BATHROOM FIXTURES WHICH IS NOT ALLOWED. SECTION | | 909.1. | | | | 8. SHT A-2 THE FLOOR DRAIN IN THE ACCESSIBLE TOILET | | ROOM IS NOT VENTED AS SHOWN. THE FLOOR DRAIN SHALL BE | | TAKEN OFF THE VENTED LINE TO THE LAV. SECTION 901.2.1. | | | | 9. SHT A-2 THE LAV STACK FOR THE ACCESSIBLE TOILET ROOM | | DOES NOT REFLECT THE PIPING LAYOUT ON THE FLOOR PLAN. | | PLEASE CORRELATE. SECTION 106.1.1. | | | | 10. SHT A-2 INDICATE WHERE THE CONDENSATE FROM THE | | WALK-IN FREEZER AND THE WALK-IN REFRIDGERATOR DRAIN. AN | | INDIRECT WASTE RECEPTOR COMPLYING WITH SECTIONS 802.3 | | OR 802.3.2 SHALL BE REQUIRED FOR THE DRAINAGE OF THE | | CONDENSATE. | | | | 11. SUBMIT A WATER ISOMETRIC RISER DIAGRAM SHOWING ALL | | PIPE SIZES, VALVES, REQUIRED WATER HAMMER ARRESTORS, | | (LOCATED NEAR THE FIXTURE IN AN "EFFECTIVE RANGE", NOT | | IN THE CEILING). INDICATE THE WATER SERVICE SIZE PER | | TABLE 603.1 AND INDICATE IF THERE IS AN EXISTING RPZV | | BACKFLOW PREVENTER ON THE WATER SERVICE. IF NO | | BACKFLOW, THEN ONE WILL BE REQUIRED PER SECTION | | 608.13.2.SECTIONS 106.3.5.1.3(3)(8)(10)(13) & 604.9 | | | | 12. SHT A-2 THERMAL EXPANSION CONTROL IS REQUIRED PER | | SECTION 607.3.2. PLEASE INDICATE METHOD. | | | | 13. SHT A-2 PLUMBING PLAN KEY #6 IS NOT APPROVED. | | PLEASE DELETE FROM REFERENCE. ARTICLE III SECTION | | 90-124(7)(B)(F). | | | | 14. SHT A-2 THE ACCESSIBLE TOILET ROOMS SHALL SHOW | | COMPLIANCE WITH THE FOLLOWING: | | ___FOR W/C | | A. 11-4.16.2 CLEAR FLOOR SPACE | | B. 11-4.16.5 FLUSH CONTROLS | | ___FOR LAV | | A. 11-4.19.3 CLEAR FLOOR SPACE | | B. 11-4.19.4 EXPOSED PIPES & SURFACES | | C. 11-4.19.5 FAUCETS | | ALSO SHOW THE W/C TO BE 18" OFF THE WALL TO THE | | CENTERLINE OF THE FIXTURE PER FIG. 29. SHOW THE LAV TO | | BE A MINIMUM OF 15" OFF THE WALL TO THE CENTERLINE OF | | THE FIXTURE. (CENTER ON THE 30" OF THE 30"X48" CLEAR | | FLOOR SPACE REQUIRED FOR THE LAV). | | | | 15. THE FOLLOWING ARE GAS PERMIT REQUIREMENTS: | | | | A. SUBMIT AN ISOMETRIC DRAWING THAT | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | AND CORRESPONDING LENGTHS PER FBC-2004 | | FUEL GAS CODE. SOME SECTIONS DO NOT SHOW THE REQUIRED | | LENGTHS. ALSO SHOW ALL VALVES ON THE ISOMETRIC AS WELL | | AS THE SEDIMENT TRAPS REQUIRED IN SECTIONS 408.4 & | | 409.5. | | | | B. SHOW THE DISTANCE FROM THE POINT OF | | DELIVERY, (METER), TO THE MOST REMOTE | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | FBC-2004 FUEL GAS CODE APPENDIX A - USE | | OF CAPACITY TABLES A.3.1(4). | | | | C. INDICATE THE DELIVERY PRESSURE (PSI) | | PER FBC-2004 FUEL GAS CODE SEC. 402.2. | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. INDICATED ON THE | | PLANS AS 5PSI. PLEASE VERIFY WITH GAS PROVIDER. IF MORE | | THAN 1/2PSI, SHOW THE LOCATION OF ALL GAS REGULATORS | | AND SUBMIT THE MANUF. SPECIFICATION SHEETS INDICATING | | THE MODEL NUMBER OF THE REGULATOR. PLEASE INDICATE IF | | THE REGULATOR SHALL BE VENTED, AND IF SO SHOW THE | | ROUTING OF THE VENTING AND INDICATE THE MATERIAL FOR | | THE VENT. (VENT SHALL BE OF NON-COMBUSTALBE MATERIAL). | | REGULATORS SHALL BE DOWNSTREAM OF THE SOV OF THE GAS | | APPLIANCE. | | | | D. SUBMIT A DETAIL SHOWING THE TYPE, | | LOCATION, SIZE AND TERMINATION OF THE | | GAS VENTS PER FBC-2004 FUEL GAS CODE | | SECS. 502 THRU 505. | | | | E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | STANDARDS NFPA 54, NFPA 58, AND THE | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | | F. CLEARLY SHOW THE LOCATION AND CAP- | | ACITY OF LP TANK(S), TYPE OF TANK (DOT | | OR ASME), THE DISTANCE OF THE TANK FROM | | THE BUILDING AND ADJACENT PROPERTY LINES | | THE DISTANCE OF THE TANK FROM ALL SOUR- | | CES OF IGNITION, OTHER CONTAINERS, BUILD | | INGS, AND THE LOCATION OF ANY BUILDING | | OPENINGS BELOW THE RELIEF VALVE OF THE | | TANK PER NFPA 58, TABLE 3-2.2.2. | | | | F. CLEARLY INDICATE ON THE PLAN IF THE | | LP TANK IS ABOVE OR BELOW GROUND, AND | | SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES | | PER NFPA 58. IF THE TANK | | IS BELOW GROUND THE CONTAINER SHALL BE | | SECURILY ANCHORED PER NFPA 58 SECTION | | 3-2.2.7(H). | | | | G. EMERGENCY HOOD SHUT DOWN SHUT OFF | | VALVE TO BE BELOW CEILING. MANUAL SHUT | | OFF VALVE TO BE UPSTREAM. UNION TO BE | | DOWN STREAM OF MANUAL VALVE. | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | WITH A DESCRIPTION OF THE REVISION | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID | | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY | | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU | | FOR YOUR ANTICIPATED COOPERATION. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] | | | | | | | | | | | | . |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
N |
Date |
2007-04-10 |
|
|
Cont ID |
|
Sent By |
jroach |
Date |
2007-04-10 |
Time |
13:33 |
Rev Time |
0.00 |
Received By |
jroach |
Date |
2007-04-10 |
Time |
13:33 |
Sent To |
|
|
Notes |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |