Plan Review Details - Permit 07030996
Plan Review Stops For Permit 07030996
Review Stop AD ADDRESSING
Rev No 3 Status P Date 2007-12-18 Cont ID  
Sent By lursu Date 2007-12-18 Time 14:09 Rev Time 0.00
Received By lursu Date 2007-12-18 Time 14:09 Sent To  
Notes
2007-12-18 14:11:51CONVERSATION WITH THE PROPERTY OWNER , THE JOB LOCATION
 IS FOR THE ENTIRE BUILDING AND THE MAIN ADDRESS USED BY
 THE OWNER IS 6905 S DIXIE HWY ,REVISED PLANS AND PERMIT
 APPLICATION MUST REFLECT THE ADDRESS OF 6905 WITH A
 PARENTHESIS OF UNITS INCLUDED STARTING AT 6901 TO 6905
 S DIXIE HWY .
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected].

Review Stop AD ADDRESSING
Rev No 2 Status F Date 2007-06-01 Cont ID  
Sent By lursu Date 2007-06-01 Time 10:15 Rev Time 0.00
Received By jwitmer Date 2007-06-04 Time 16:45 Sent To  
Notes
2007-06-01 10:17:08JOB LOCATION IS NOT SPECIFIED ON THE SITE PLAN ,IS THE
 PERMIT APPLIED ONLY TO UNIT 1 OR TO THE ENTIRE BUILDING
 FOR RENOVATION?PLEASE SPECIFY.IF THE PERMIT IMPLIES THE
 ENTIRE BUILDING THEN THE MAIN ADDRESS 6901 S DIXIE HWY
 SHOULD BE USED .HOWEVER ALL FOUR UNITS MUST HAVE A
 INDIVIDUAL SITE ADDRESS ( NUMBER) ,PLEASE CONTACT THIS
 OFFICE TO REQUEST THE ADDRESSES OF THESE FOUR UNITS.
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]

Review Stop AD ADDRESSING
Rev No 1 Status P Date 2007-04-17 Cont ID  
Sent By lursu Date 2007-04-17 Time 10:53 Rev Time 0.00
Received By lursu Date 2007-04-17 Time 10:42 Sent To  
Notes
2007-04-17 11:09:56THE SITE ADDRESS, 6901 S DIXIE HWY, USED ON THE PERMIT
 IS CORRECT. THIS PARCEL CONTROL NUMBER = 74 43 44 09 05
 000 1770 HAS THREE UNITS DESCRIBED AS :6901, 6903 &
 6905 S DIXIE HWY.THE LOWEST ADDRESS 6901 S DIXIE HWY
 WILL BE USED AS THE MAIN ADDRESS FOR THE BUILDING.
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2009-03-02 Cont ID  
Sent By mjacobs Date 2009-03-02 Time 11:48 Rev Time 0.00
Received By mjacobs Date 2009-03-02 Time 11:04 Sent To PC
Notes
2009-03-02 11:48:343/2/09 REVISED SHEETS A-2 / A-3 AND A-4 REMOVING ALL
 ARCHITECTURAL TRIM WORK ON THE EXTERIOR OF THE
 BUILDING.

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status N Date 2009-01-27 Cont ID  
Sent By mjacobs Date 2009-01-27 Time 11:33 Rev Time 0.00
Received By mjacobs Date 2009-01-27 Time 11:29 Sent To  
Notes
2009-01-27 11:33:15SUBMITTAL OF THE ORIGINAL LETTER FROM TOMMY TAVERAS, PE
 REQUIRED A SHOP REVIEW STAMP FROM THE ORIGINAL DESIGN
 TEAM RAR ARCHITECT. THE REVIEW STAMP WAS DONE ON
 1-27-09 BY RAFAEL A. RODRIGUEZ. MJ
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2009-01-16 Cont ID  
Sent By mjacobs Date 2009-01-16 Time 10:40 Rev Time 0.00
Received By mjacobs Date 2009-01-16 Time 10:39 Sent To PC
Notes
2009-01-16 10:40:00SUBMITTAL LETTER FOR WALL BRACING DETAIL FROM ENGINEER
 .

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-04-08 Cont ID  
Sent By mjacobs Date 2008-04-08 Time 08:12 Rev Time 0.00
Received By mjacobs Date 2008-04-08 Time 07:24 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-02-23 Cont ID  
Sent By mjacobs Date 2008-02-23 Time 07:46 Rev Time 0.00
Received By mjacobs Date 2008-02-23 Time 06:06 Sent To  
Notes
2008-02-23 07:46:41BUILDING PLAN REVIEW
 PERMIT: 07030996
 ADD: 6905 S. DIXIE HWY
 CONT: JHAMTEC CONST.
 TEL: (561)602-0009
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 3RD 2-23-08
 ACTION: DENIED
  
 1)OK
  
 2)FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3)OK
  
 4)SEMI-CORRECT: THE DRAWINGS NOW SHOW THE CORRECT
 SITE ADDRESS ON EACH SHEET. SHEET SP-1 SHOWS THE
 DIFFERENT UNIT/SUITE NUMBERS FOR EACH UNIT WHICH RANGE
 FROM 6901 THRU 6905. SHEETS D-1 AND A-1 SHOW UNIT #1
 AND UNIT #4 HAVE THE SAME NUMBER 6901. PLEASE CLARIFY
 AND CHANGE THE PAGES ACCORDINGLY.
  
 5-10) OK
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 FAX (561) 805-6676
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-12-14 Cont ID  
Sent By jwitmer Date 2007-12-14 Time 08:50 Rev Time 1.22
Received By jwitmer Date 2007-12-14 Time 08:50 Sent To  
Notes
2007-12-14 09:00:35BUILDING PLAN REVIEW
 PERMIT: 07030996
 ADD: 6901-05 S DIXIE HWY
 CONT: JHAMTEC
 TEL: (561)512-9341
  
  
  
 12-14-07
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2 ) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY
 COMMENCED WITHIN 90 DAYS AFTER THE RECORDING THEREOF,
 SUCH NOTICE IS NULL & VOID. NOTE:
 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT
 THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) COMPLIED.
  
 4) 2ND REQUEST,PLEASE CONTACT LILY URSA AT 822-1239
 FOR ADDRESSING THE CITY HAS A SITE ADDRESS OF 6901 S.
 DIXIE HWY FOR THE PROPERTY BUT EACH UNIT REQUIRES
 TENANT ADDRESSES, BEFORE THIS PERMIT CAN BE ISSUED
 CONTACT MUST BE MADE WITH OUR ADDRESSING PERSONEL FOR
 TENANT ADDRESSES. THIS PERMIT WILL NOT BE ISSUED UNTIL
 THIS ISSUE HAS BEEN RESOLVED, THANK YOU FOR YOUR
 COOPERATION IN THIS MATTER.
  
 5)110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A)SEMI- COMPLIED.
 NOTE 2006 FBC EXISTING BUILDING CODE ALSO PROVIDE LEVEL
 OF ALTERATION.
 B-G) COMPLIED.
  
 6) COMPLIED.
  
 7-10) COMPLIED.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-06-04 Cont ID  
Sent By jwitmer Date 2007-06-04 Time 16:45 Rev Time 0.75
Received By jwitmer Date 2007-06-04 Time 16:45 Sent To PC
Notes
2007-12-14 08:50:06BUILDING PLAN REVIEW
 PERMIT: 07030996
 ADD: 6901-05 S DIXIE HWY
 CONT: JHAMTEC
 TEL: (561)512-9341
  
  
  
 12-14-07
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2 ) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY
 COMMENCED WITHIN 90 DAYS AFTER THE RECORDING THEREOF,
 SUCH NOTICE IS NULL & VOID. NOTE:
 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT
 THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) COMPLIED.
  
 4) 2ND REQUEST,PLEASE CONTACT LILY URSA AT 822-1239
 FOR ADDRESSING THE CITY HAS A SITE ADDRESS OF 6901 S.
 DIXIE HWY FOR THE PROPERTY BUT EACH UNIT REQUIRES
 TENANT ADDRESSES, BEFORE THIS PERMIT CAN BE ISSUED
 CONTACT MUST BE MADE WITH OUR ADDRESSING PERSONEL FOR
 TENANT ADDRESSES. THIS PERMIT WILL NOT BE ISSUED UNTIL
 THIS ISSUE HAS BEEN RESOLVED, THANK YOU FOR YOUR
 COOPERATION IN THIS MATTER.
  
 5)110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A)SEMI- COMPLIED.
 NOTE 2006 FBC EXISTING BUILDING CODE ALSO PROVIDE LEVEL
 OF ALTERATION.
 B-G) COMPLIED.
  
 6) COMPLIED.
  
 7-10) COMPLIED.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
2007-12-14 08:46:23BUILDING PLAN REVIEW
 PERMIT: 07030996
 ADD: 6901-05 S DIXIE HWY
 CONT: JHAMTEC
 TEL: (561)512-9341
  
  
  
 12-14-07
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2 ) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY
 COMMENCED WITHIN 90 DAYS AFTER THE RECORDING THEREOF,
 SUCH NOTICE IS NULL & VOID. NOTE:
 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT
 THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) COMPLIED.
  
 4) 2ND REQUEST,PLEASE CONTACT LILY URSA AT 822-1239
 FOR ADDRESSING THE CITY HAS A SITE ADDRESS OF 6901 S.
 DIXIE HWY FOR THE PROPERTY BUT EACH UNIT REQUIRES
 TENANT ADDRESSES, BEFORE THIS PERMIT CAN BE ISSUED
 CONTACT MUST BE MADE WITH OUR ADDRESSING PERSONEL FOR
 TENANT ADDRESSES. THIS PERMIT WILL NOT BE ISSUED UNTIL
 THIS ISSUE HAS BEEN RESOLVED, THANK YOU FOR YOUR
 COOPERATION IN THIS MATTER.
  
 5)110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A)SEMI- COMPLIED.
 NOTE 2006 FBC EXISTING BUILDING CODE ALSO PROVIDE LEVEL
 OF ALTERATION.
 B-G) COMPLIED.
  
 6) COMPLIED.
  
 7-10) COMPLIED.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
2007-06-04 17:04:37BUILDING PLAN REVIEW
 PERMIT: 07030996
 ADD: 6901-05 S DIXIE HWY
 CONT: JHAMTEC
 TEL: (561)512-9341
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2 ) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY
 COMMENCED WITHIN 90 DAYS AFTER THE RECORDING THEREOF,
 SUCH NOTICE IS NULL & VOID. NOTE:
 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT
 THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) PLEASE SEE ELECTRICAL COMMENT ABOUT A RESIDENTIAL
 DESIGNER AND SCOPE OF WORK. SEE FL SS 481.229 FOR
 REQUIREMENTS OF DESIGN PROFESSIONAL FOR COMMERCIAL
 WORK.
  
 4) PLEASE CONTACT LILY URSA AT 822-1239 FOR ADDRESSING
 EITHER THIS NEEDS TO BE ADDES AS A UNIT OR A LOT SPLIT
 HAS OCCURED THE PCN OESN'T MATCH WITH THE ONE LISTED ON
 THE PERMIT APPLICATION.
  
 5)110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PROJECT WILL BE PERMITED.
 NOTE 2006 FBC EXISTING BUILDING CODE ALSO PROVIDE LEVEL
 OF ALTERATION.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
 G) NUMBER OF UNITS
  
 6)2004 FL. BLD CODE 1603.1.4 THE
 FOLLOWING INFORMATION RELATED TO WIND
 SHALL BE SHOWN ON THE CONSTRUCTION
 DRAWINGS,
 2)- WIND IMPORTANCE FACTOR, & BUILDING CATEGORY THIS
 STATEMENT ALSO INDICATES A R-3 OCCUPANCY?
  
 7) PLAANS DO NOT PROVIDE INFORMATION TO BREAKAREA SINK?
 SINKS:
 11-4.24.2 SINKS, HEIGHT. SINKS SHALL
 BE MOUNTED WITH THE COUNTER NO HIGHER
 THAN 34" ABOVE THE FINISH FLOOR.
 11-4.24.3 KNEE CLEARANCE THAT IS AT
 LEAST 27" HIGH 30" WIDE, AND 19" DEEP
 SHALL BE PROVIDED UNDERNEATH SINKS.
 11-4.24.5 CLEAR FLOOR SPACE.
 A CLEAR FLOOR SPACE AT LEAST 30 INCHES BY 48 INCHES
 (760 MM BY 1219 MM) COMPLYING WITH SECTION 11-4.2.4
 SHALL BE PROVIDED IN FRONT OF A SINK TO ALLOW FORWARD
 APPROACH. THE CLEAR FLOOR SPACE SHALL BE ON AN
 ACCESSIBLE ROUTE AND SHALL EXTEND A MAXIMUM OF 19
 INCHES (485 MM) UNDERNEATH THE SINK
  
 8)FL BLD CODE 1609.1.4: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) WINDOWS
 B) SWING DOORS EXTERIOR
  
 9)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 10)WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2008-04-02 Cont ID  
Sent By dpalmer Date 2008-04-02 Time 11:40 Rev Time 0.00
Received By dpalmer Date 2008-04-02 Time 11:40 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-02-09 Cont ID  
Sent By dpalmer Date 2008-02-09 Time 08:46 Rev Time 0.00
Received By dpalmer Date 2008-02-09 Time 08:46 Sent To  
Notes
2008-02-11 08:46:50** DENIED REVIEW ***
  
 1) NOTE: PLEASE SEE COMMENTS FROM PREVIOUS REVIEW #2
 WHICH REQUESTED THE SUBMITTAL OF INTERIOR AND EXTERIOR
 LIGHTING PERFORMANCE CALCULATIONS PER 13-415.2 AND
 13-415.2.ABC.1.3.
 IN MEETING HELD BEFORE PLANS WERE SUBMITTED THE
 QUESTIONS BROUGHT UP ABOUT THE REVIEW WERE BASED ON THE
 ELECTRICAL SERVICE AND THE COMMENT WAS ALL OTHER NOTES
 WERE UNDERSTOOD AND WOULD BE ADDRESSED.
 PLEASE SEE THE PLANS DO INDICATE THE FIXTURES, THE
 TYPES AND THE WATTAGES HOWEVER NO CALCULATIONS PER THE
 SECTIONS ABOVE WERE SHOWN ON PLANS.
  
 **THERE WERE RESPONSE COMMENTS FROM ARCHITECT FOR OTHER
 TRADE REVIEWS HOWEVER COULD NOT LOCATE ANY FOR
 ELECTRICAL. THESE ARE NOT REQUIRED HOWEVER WILL HELP IN
 THE REVIEW PROCESS.
  
 **ONCE AGAIN, IF THERE ARE ANY QUESTIONS ON THIS AND
 HOW THESE NEEDS TO BE ACCOMPLISHED PLEASE DO NOT
 HESITATE IN CONTACTING THIS REVIEWER TO GO OVER
 COMMENTS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 [email protected]
 561-805-6717

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-12-03 Cont ID  
Sent By dpalmer Date 2007-12-03 Time 13:33 Rev Time 0.00
Received By dpalmer Date 2007-12-03 Time 13:33 Sent To  
Notes
2007-12-03 13:33:56 
 ** DENIED 2NDD REVIEW **
  
 ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEWS ARE
 STILL IN NEED OF ADDRESSING ALONG WITH SOME NEW
 COMMENTS BASED ON REVISED AND NEW PLANS SUBMITTED.
  
 1) NOTE: PLEASE KNOW THE ADDRESS SITUATION HAS NOT YET
 BEEN DETERMINED FOR PROJECT. THE PERMIT APPLICATION AND
 RE-SUBMITTAL SHEET STILL INDICATES 6901-6905 YET PLANS
 CALLS FOR 6903. THE APPLIED LOCATION IN OUR SYSTEM AS
 OF THIS REVIEW IS 6901.
 THE ADDRESSING AND BUILDING REVIEW WILL BE ADDRESSING
 THESE COMMENTS HOWEVER THIS WILL AFFECT ALL SHEETS
 INCLUDING ELECTRICAL.
 PLEASE UPDATE ONCE ALL HAS BEEN DETERMINED. FBC
 106.1.2, 106.3.5, FAC61G1-16.004
  
 2) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE
 CALCULATIONS PER 13-415.2.
 THIS IS TO INCLUDE OUTSIDE LIGHTING ALSO PER
 13-415.2.ABC.1.3
 THIS IS A NEW NOTE AS SCOPE ON ORIGINAL PLANS WAS NOT
 CLEAR.
  
 3) NOTE: PLEASE SEE THAT THE NEW ELECTRICAL SERVICE AS
 SHOWN IS NOT PERMITTED. PLEASE KNOW AS THIS IS ONE
 BUILDING BY DEFINITION ONLY ONE ELECTRICAL SERVICE IS
 PERMITTED PER 230.2.
 PLEASE SUBMIT THE EXISTING RISER FOR NEW TENANT SPACE
 TO BE FED FROM THE EXISTING SERVICE OR THE EXISTING
 SERVICE WILL NEED TO BE UPGRADED FOR THE WHOLE
 BUILDING.
  
 4) NOTE: PLEASE SEE THE LOAD CALCULATIONS INDICATE THE
 SIGN CIRCUIT AT 2500VA WHICH EXCEEDS THAT OF A 20AMP
 CIRCUIT. THE PANEL SCHEDULE INDICATES 15AMPS HOWEVER
 THIS DOES NOT CORRELATE WITH THE VA ON LOAD
 CALCULATIONS.
 PLEASE KNOW THE MINIMUM THAT IS REQUIRED BY THE NEC IS
 1200 VA AT 125% FOR CONTINUOUS LOADS ON FEEDERS ETC.
 600.5, 215.3, 230.42
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-04-15 Cont ID  
Sent By dpalmer Date 2007-04-15 Time 19:52 Rev Time 0.00
Received By dpalmer Date 2007-04-15 Time 19:37 Sent To  
Notes
2007-04-15 19:53:29** UNSAT **
  
 ** PLEASE SEE ANY REFERENCES IN PLAN REVIEW NOTES TO
 CHAPTER 1 OF THE FBC ARE THAT WHICH IS ADOPTED BY THE
 CITY OF WEST PALM BEACH.
  
 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH
 ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS
 UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLANS AT THIS TIME DO NOT INDICATE ANY CODES.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2003 NFPA-101
  
 2) NOTE: PLEASE SEE FS 481.229 AS PLANS MUST BE DONE BY
 AND ARCHITECT AT A MINIMUM. PLANS FOR COMMERCIAL
 OCCUPANCY MAY NOT BE DONE BY A *RESIDENTIAL DESIGNER*.
 IF THERE ARE ANY QUESTIONS, PLEASE CONTACT THIS OFFICE
 OR STATE PROSECUTING ATTORNEY MR. DAVID MINACCI LEGAL
 COUNSEL TO THE BOARD OF ARCHITECTS.
  
 3) NOTE: PLEASE COORDINATE THE ADDRESS FOR WORK BEING
 DONE. THE PALM BEACH COUNTY PROPERTY APPRAISER?S OFFICE
 INDICATES 6903, YET PERMIT APPLICATION INDICATE
 6901-6905.
 IF THE PRIMARY ADDRESS IS 6903, SUITE OR UNIT NUMBERS
 MAY BE ASSIGNED AND SHALL ALSO BE INDICATED ON
 PLANS/TITLE BLOCKS.
 DOCUMENTS HAVE BEEN FORWARDED TO THE ADDRESSING
 REVIEWER.
  
 4) NOTE: PLEASE CLARIFY IF WORK IS IN ONCE TENANT SPACE
 OR MORE THAN ONE?
 PLANS ARE NOT CLEAR AT THIS TIME FOR COMPLETE SCOPE OF
 WORK.
 PLEASE SUBMIT COMPLETE ELECTRICAL FOR NEW OR EXISTING
 FOR THIS SPACE.
 PLEASE INCLUDE NEW CIRCUITING ON PLANS AND CORRELATE
 WITH A PANEL SCHEDULE WHICH IS TO BE SUBMITTED.
 PLEASE INDICATE THE SIZE OF THE PANEL, SERVICE ETC.
 PLEASE SUBMIT LOADS, LOAD CALCULATIONS FOR SERVICE
 ETC.
 PLEASE SEE MISSING SIGN CIRCUITS.
 PLEASE SEE MISSING SHOW WINDOW RECEPTACLES.
 PLEASE SEE MISSING MINIMUM LIGHTING ON PLANS
 PLEASE SEE IF THESE ARE MULTIPLE TENANTS, NEED TO SHOW
 THE PANELS, OR HOUSE PANEL WHICH IS FEEDING NEW OUTSIDE
 LIGHTS.
 ETC ETC,
 215.5, 408.4, 220.43, 600.5, 210.62, 240.4, 310.16 ETC
 PLEASE SEE THE 2005 NEC AS PLANS ARE NOT COMPLETE FOR
 SUFFICIENT ELECTRICAL REVIEW AT THIS TIME.
 AS THERE ARE MANY ITEMS MISSING, THERE MAY BE NEW
 COMMENTS WHEN PLANS ARE COMPLETED.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2008-04-07 Cont ID  
Sent By mawillia Date 2008-04-07 Time 13:51 Rev Time 0.00
Received By mawillia Date 2008-04-07 Time 13:28 Sent To  
Notes
2008-04-07 13:39:25*****APPROVED*****
  
  
 PLAN SHEETS A-1, A-2, AND E-1 WERE STAMPED, INITIALED,
 AND DATED.
  
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2008-03-04 Cont ID  
Sent By mawillia Date 2008-03-04 Time 16:11 Rev Time 0.00
Received By mawillia Date 2008-03-04 Time 15:16 Sent To  
Notes
2008-03-04 16:06:51*****UNSAT*****
  
 PLEASE ACKNOWLEDGE THE FOLLOWING COMMENT TAKEN FROM THE
 PREVIOUS FIRE PLAN REVIEW:
  
 1.THE SCOPE OF WORK SITE SHALL BE IN THE TITLE BLOCK
 OF EACH SUBMITTED PLAN SHEET.(1) PLEASE BE
 ADVISED THAT THE PLAN SHEETS INDICATES 6905 AS THE
 NUMERICAL ADDRESS WHEREAS THE ADDRESS NOTED IN THE
 CITY'S PERMITTING SYSTEM AND ACCORDING TO THE SUBMITTED
 PLAN INDICATES THE SCOPE OF WORK TO BE CONDUCTED AT
 6901.(2) DRAWING NO. 1 SHOWS UNIT 1 ADDRESSED AS 6901
 COMPARED TO DRAWING NO.2 (PROPOSED FRONT/EAST
 ELEVATION) SHOWS UNIT 1 AS 6905.
  
 IF ASSISTANCE IS NEEDED TO RECTIFY AN ADDRESSING
 MATTER, FEEL FREE TO CONTACT LILI URSU AT 561-822-1239
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-12-06 Cont ID  
Sent By mawillia Date 2007-12-06 Time 16:13 Rev Time 0.00
Received By mawillia Date 2007-12-06 Time 15:31 Sent To  
Notes
2007-12-06 16:10:19*****DENIED*****
  
 PLEASE ACKNOWLEDGE THE FOLLOWING COMMENTS TAKEN FROM
 THE PREVIOUS FIRE PLAN REVIEW:
  
 1.THE ACTUAL ADDRESS SHALL BE IN THE TITLE BLOCK OF
 EACH SUBMITTED PLAN SHEET.PLEASE BE ADVISED THAT THE
 PLAN SHEET INDICATES 6903 AS THE NUMERICAL ADDRESS
 WHEREAS THE ADDRESS NOTED IN THE CITY'S PERMIT SYSTEM
 INDICATES 6901.
  
 3.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 4.THE REMOVAL AND (OR) REPLACEMENT OF BUILDING
 MATERIALS & SUPPLIES SHALL NOT HINDER OR INTERFERE WITH
 EMERGENCY RESPONSE ACCESS TO THE PROPERTY OR VICINITY
 THEREOF (INCLUDING STREETS, ROADS, FIRE LANES).
  
 6.DISPLAY EXIT LIGHTS, EMERGENCY LIGHTS, AND THE
 LOCATION OF THE 2A:10BC FIRE RATED FIRE EXTINGUISHER(S)
 IN THIS OFFICE SPACE.
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-06-01 Cont ID  
Sent By mawillia Date 2007-06-01 Time 11:05 Rev Time 0.00
Received By mawillia Date 2007-06-01 Time 09:50 Sent To  
Notes
2007-06-01 10:09:03*****DENIED*****
  
  
 1.THE ACTUAL ADDRESS SHALL BE IN THE TITLE BLOCK OF
 EACH SUBMITTED PLAN SHEET.PLEASE BE ADVISED THAT THE
 PLAN SHEET INDICATES 6903 AS THE NUMERICAL ADDRESS
 WHEREAS THE ADDRESS NOTED IN THE CITY'S PERMIT SYSTEM
 INDICATES 6901.
  
 2.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 3.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 4.THE REMOVAL AND (OR) REPLACEMENT OF BUILDING
 MATERIALS & SUPPLIES SHALL NOT HINDER OR INTERFERE WITH
 EMERGENCY RESPONSE ACCESS TO THE PROPERTY OR VICINITY
 THEREOF (INCLUDING STREETS, ROADS, FIRE LANES).
  
 5.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR
 MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 6.DISPLAY EXIT LIGHTS, EMERGENCY LIGHTS, AND THE
 LOCATION OF THE 2A:10BC FIRE RATED FIRE EXTINGUISHER(S)
 IN THIS OFFICE SPACE.
  
 7.DOES THE PROPOSED STRUCTURE HAVE A FIRE ALARM
 AND/OR FIRE SPRINKLER SYSTEM IN ITS MAKEUP?
  
 8.SHOW/DISPLAY THE NUMERICAL ADDRESS ON THE EXTERIOR
 ELEVATION SO THAT IT IS DISTINGUISHABLE FROM THE OTHER
 SUITES.AS PER WEST PALM BEACH CODE,THOSE NUMBERS
 SHALL BE NO LESS THAN 6" IN HEIGHT AND NO LESS THAN 1"
 IN WIDTH.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2009-02-27 Cont ID  
Sent By adarroug Date 2009-02-27 Time 08:35 Rev Time 0.00
Received By adarroug Date 2009-02-27 Time 08:35 Sent To  
Notes
2009-02-27 08:42:20TO "MJACOBS" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2009-01-26 Cont ID  
Sent By adarroug Date 2009-01-26 Time 10:24 Rev Time 0.00
Received By adarroug Date 2009-01-26 Time 10:24 Sent To B
Notes
2009-01-26 10:24:54TO "MJACOBS" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-03-31 Cont ID  
Sent By adarroug Date 2008-03-31 Time 15:54 Rev Time 0.00
Received By adarroug Date 2008-03-31 Time 15:54 Sent To  
Notes
2008-03-31 15:57:08TO "COMM" BD#44

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-02-08 Cont ID  
Sent By adarroug Date 2008-02-08 Time 11:21 Rev Time 0.00
Received By adarroug Date 2008-02-08 Time 11:21 Sent To  
Notes
2008-02-08 11:23:51TO "COMM" BD#30--NEW SHEETS ALL TRADES

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-11-08 Cont ID  
Sent By adarroug Date 2007-11-08 Time 15:00 Rev Time 0.00
Received By adarroug Date 2007-11-08 Time 15:00 Sent To  
Notes
2007-11-27 14:04:23TO "COMM" BD#3
2007-11-08 15:00:46WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-06-04 Cont ID  
Sent By jwitmer Date 2007-06-04 Time 17:05 Rev Time 0.00
Received By jwitmer Date 2007-04-05 Time 17:22 Sent To  
Notes
2007-04-05 17:22:52TO COMM BOARD # 21

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-02-13 Cont ID  
Sent By tgordon Date 2008-02-13 Time 10:50 Rev Time 0.30
Received By tgordon Date 2008-02-13 Time 10:50 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-11-29 Cont ID  
Sent By tgordon Date 2007-11-29 Time 15:57 Rev Time 0.30
Received By tgordon Date 2007-11-29 Time 15:57 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-05-02 Cont ID  
Sent By tgordon Date 2007-05-02 Time 13:31 Rev Time 0.00
Received By tgordon Date 2007-05-02 Time 12:43 Sent To  
Notes
2007-05-02 13:44:10*** DENIED ***
 1) MECHANICAL PERMIT #07040155 HAS BEEN APPLIED FOR BUT
 NO MECHANICAL PLANS WERE SUBMITTED FOR REVIEW. PLEASE
 SUBMIT MECHANICAL PLANS FOR REVIEW, PER 2004 FBC CITY
 OF WPB AMEND. 106.3.5.4 (10).
  
 2) PERMIT APPLICATION STATES ADDRESS AS 6901 - 05,
 PLEASE STATE ON PLANS IF FIVE UNITS ARE BEING RENOVATED
 OR JUST ONE.
  
 3) MECHANICAL INFORMATION NEED, A/C EQUIPMENT SCHEDULE,
 AND LOCATION OF MINI SPLIT SYSTEM (A/H & C/U)
  
 4) AS NO WINDOW INFORMATION HAS BEEN PROVIDED BATHROOM
 MAY NEED AN EXHAUST FAN, SEE 2004 FBC/M 403, PLEASE
 CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-03-11 Cont ID  
Sent By jleech Date 2008-03-11 Time 09:34 Rev Time 0.00
Received By jleech Date 2008-03-11 Time 08:43 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-12-13 Cont ID  
Sent By kstevens Date 2007-12-13 Time 11:09 Rev Time 0.00
Received By kstevens Date 2007-12-13 Time 11:09 Sent To  
Notes
2007-12-13 11:26:22DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW: (FIRST REVIEW FOR THE DESIGN
 PROFESSIONL)
  
 1. OK
  
 2. ADDRESS ON THE APPLICATION DOES NOT REFLECT THE
 ADDRESS SHOWN ON THE PLANS, SEE THE PALM BEACH COUNTY
 PROPERTY APPRAISER'S WEB-SITE. PLEASE CORRELATE THE
 INFORMATION AND INDICATE UNIT NUMBER AFFECTED BY THE
 APPLICATION. SECTION 106.1.1.
 ****NO RESPONSE, NOT ADDRESSED. THE ADDRESS ON OUR
 SYSTEM IS 6901 S DIXIE HWY. THE APPLICATION & PLANS
 SHALL SHOW THE CORRECT ADDRESS ON THE TITLE BLOCK ONCE
 THE CORRECT ADDRESS, INCLUDING SPACE, SUITE OR UNIT
 DESIGNATION, HAS BEEN DETERMINED BY THE ADDRESSING
 REVIEWER.
  
 3. SHT A1 SHOW COMPLIANCE WITH THE FOLLOWING: ___FOR
 W/C:
 A. 11-4.16.5 FLUSH CONTROLS
 ****NO RESPONSE, NOT ADDRESSED
 ___FOR LAV:
 A. 11-4.19.2 HEIGHT - SHOWS 2'10" FROM THE BOTTOM OF
 THE SLAB ON ONE SIDE OF THE DETAIL AND 2'11-1/2" FROM
 FINISHED FLOOR ON THE OTHER SIDE OF THE DETAIL. PLEASE
 COMPLY WITH SECTION 11-4.19.2.
 ****RESPONSE NOTED, BUT THE CLEARANCE IS NOT INDICATED.
 (29" REQUIRED).
 B. 11-4.19.5 FAUCETS
 ****NO RESPONSE, NOT ADDRESSED
 C. 11-4.29.6 MIRRORS
 ****NO RESPONSE, NOT ADDRESSED
 ___TOILET ROOM
 A. OK
  
 4. NOT APPLICABLE
  
 5. PER TABLE 403.1 A DRINKING FOUNTAIN IS REQUIRED.
 PLEASE INDICATE THE LOCATION OF THE DRINKING FOUNTAIN.
 ****NO RESPONSE, NOT ADDRESSED
  
 6. SUBMIT A SANITARY ISOMETRIC RISER DIAGRAM SHOWING
 ALL PIPE SIZES, VENTS, TRAPS ETC. SECTION
 106.3.5.1.3(4)(13). --THE SINK IS NOT SHOWN ON THE
 RISER DIAGRAM SUBMITTED, AND THE DRINKING FOUNTAIN
 SHALL BE SHOWN ALSO. IF THE RISER DIAGRAM IS NOT
 DESIGNED BY A DESIGN PROFESSIONAL, THE DESIGNER SHALL
 SIGN HIS OR HER NAME TO THE RISER DIAGRAM AND SHALL
 HAVE HIS OR HER NAME PRINTED ON THE RISER DIAGRAM.
 ****RESPONSE NOTED, BUT THE DRINKING FOUNTAIN SHALL BE
 INCLUDED.
  
 7. SUBMIT A WATER ISOMETRIC RISER DIAGRAM SHOWING ALL
 PIPE SIZES, VALVES, WATER HAMMER ARRESTORS REQUIRED BY
 SECTION 604.9 & LOCATED NEAR THE FIXTURES, (NOT IN THE
 CEILING), ETC. SECTION 106.3.5.1.3(3)(10)(13).
 ****RESPONSE NOTED, BUT THE DRINKING FOUNTAIN SHALL BE
 INCLUDED.
  
 8. AN RPZV BACKFLOW IS REQUIRED ON THE WATER SERVICE TO
 THE SPACE. PLEASE INDICATE IF THE BACKFLOW IS EXISTING,
 OR IF NOT INDICATE ON THE WATER SUPPLY RISER DIAGRAM.
 SECTIONS 106.3.5.1.3(8) & 607.3.2.
 ****NO RESPONSE, NOT ADDRESSED.
  
 **********NEW COMMENTS**********
  
 1B. THE APPLICATION REQUIRES THAT THE PROJECT IS
 DESCRIBED IN DETAIL. NO MENTION OF THE NEW ACCESSIBLE
 TOILET ROOM IS IN THE DESCRIPTION OF WORK. PLEASE
 DESCRIBE THE PROJECT IN DETAIL AS REQUIRED.
  
 2B. SUBMIT A DETAIL FOR THE DRINKING FOUNTAIN SHOWING
 COMPLIANCE WITH SECTION 11-4.15 WITH ALL SUBSECTIONS AS
 WELL AS SECTION 11-4.1.3(10)(A) PROVISIONS FOR THOSE
 WHO HAVE DIFFICULTY BENDING OR STOOPING.
  
 3B. SHT A-3 DETAIL D SHOWS THE W/C 1'9" OFF THE WALL TO
 THE CENTER OF THE FIXTURE. 1'8" REQUIRED PER FIG. 28.
 (SEE DETAIL D-1). PLEASE CORRELATE.
  
 4B. SHT A-3 DETAIL D NOTE FOR LAV PIPING INSULATION IS
 NOT COMPLETE AND LEGIBLE. PLEASE CLARIFY. SECTIONS
 106.1.1 & 11-4.19.4.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE ONE
 SET OF THEM LOOSELY ON TOP OF THE COLLATED
 PLANS TO BE REVIEWED. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-05-29 Cont ID  
Sent By kstevens Date 2007-05-29 Time 09:06 Rev Time 0.00
Received By kstevens Date 2007-05-29 Time 09:06 Sent To  
Notes
2007-05-29 10:23:31DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. PLANS SHALL BE DRAWN BY AN ARCHITECT PER FS 481.229
 & SECTION 106.1.
  
 2. ADDRESS ON THE APPLICATION DOES NOT REFLECT THE
 ADDRESS SHOWN ON THE PLANS, SEE THE PALM BEACH COUNTY
 PROPERTY APPRAISER'S WEB-SITE. PLEASE CORRELATE THE
 INFORMATION AND INDICATE UNIT NUMBER AFFECTED BY THE
 APPLICATION. SECTION 106.1.1.
  
 3. SHT A1 SHOW COMPLIANCE WITH THE FOLLOWING: ___FOR
 W/C:
 A. 11-4.16.5 FLUSH CONTROLS
 ___FOR LAV:
 A. 11-4.19.2 HEIGHT - SHOWS 2'10" FROM THE BOTTOM OF
 THE SLAB ON ONE SIDE OF THE DETAIL AND 2'11-1/2" FROM
 FINISHED FLOOR ON THE OTHER SIDE OF THE DETAIL. PLEASE
 COMPLY WITH SECTION 11-4.19.2.
 B. 11-4.19.5 FAUCETS
 C. 11-4.29.6 MIRRORS
 ___TOILET ROOM
 A. 11-4.22.3 AN UNOBSTRUCTED TURNING AREA
  
 4. SHT A1 THE SINK SHALL BE ACCESSIBLE. SHOW COMPLIANCE
 WITH SECTION 11-4.24 AND ALL SUBSECTIONS. (FORWARD
 APPROACH REQUIRED AND NO CABINET DOORS ALLOWED).
  
 5. PER TABLE 403.1 A DRINKING FOUNTAIN IS REQUIRED.
 PLEASE INDICATE THE LOCATION OF THE DRINKING FOUNTAIN.
  
 6. SUBMIT A SANITARY ISOMETRIC RISER DIAGRAM SHOWING
 ALL PIPE SIZES, VENTS, TRAPS ETC. SECTION
 106.3.5.1.3(4)(13). --THE SINK IS NOT SHOWN ON THE
 RISER DIAGRAM SUBMITTED, AND THE DRINKING FOUNTAIN
 SHALL BE SHOWN ALSO. IF THE RISER DIAGRAM IS NOT
 DESIGNED BY A DESIGN PROFESSIONAL, THE DESIGNER SHALL
 SIGN HIS OR HER NAME TO THE RISER DIAGRAM AND SHALL
 HAVE HIS OR HER NAME PRINTED ON THE RISER DIAGRAM.
  
 7. SUBMIT A WATER ISOMETRIC RISER DIAGRAM SHOWING ALL
 PIPE SIZES, VALVES, WATER HAMMER ARRESTORS REQUIRED BY
 SECTION 604.9 & LOCATED NEAR THE FIXTURES, (NOT IN THE
 CEILING), ETC. SECTION 106.3.5.1.3(3)(10)(13).
  
 8. AN RPZV BACKFLOW IS REQUIRED ON THE WATER SERVICE TO
 THE SPACE. PLEASE INDICATE IF THE BACKFLOW IS EXISTING,
 OR IF NOT INDICATE ON THE WATER SUPPLY RISER DIAGRAM.
 SECTIONS 106.3.5.1.3(8) & 607.3.2.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE ONE
 SET OF THEM LOOSELY ON TOP OF THE COLLATED
 PLANS TO BE REVIEWED. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 3 Status P Date 2008-04-01 Cont ID  
Sent By choops Date 2008-04-01 Time 08:52 Rev Time 0.00
Received By choops Date 2008-04-01 Time 08:52 Sent To  
Notes
2008-04-01 08:52:59***APPROVED - RESUB #3 - (RESTAMPED PLANS)***
  
 PROVISOS: 1)NEW A/C EQUIPMENT MAY NOT PROJECT MORE
 THAN 4' INTO A REQUIRED SETBACK.2)PURSUANT TO
 SECTION 94-513(A)(2) OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS: NONCONFORMING STRUCTURES OR BUILDINGS
 SHALL NOT BE IMPROVED, CONSTRUCTED, ENLARGED, OR
 ALTERED IN ANY MANNER TO CREATE A NEW NONCONFORMITY OR
 TO INCREASE AN EXISTING NONCONFORMITY, BUT MAY BE
 IMPROVED, CONSTRUCTED, ENLARGED, OR ALTERED AS LONG AS
 NO NEW NONCONFORMITY IS CREATED OR AN EXISTING
 NONCONFORMITY INCREASED.

Review Stop Z ZONING
Rev No 2 Status P Date 2008-02-19 Cont ID  
Sent By choops Date 2008-02-19 Time 10:16 Rev Time 0.00
Received By choops Date 2008-02-19 Time 10:16 Sent To  
Notes
2008-02-19 10:16:42***APPROVED - RESUB #2 - (RESTAMPED PLANS)***
  
 PROVISOS: 1)NEW A/C EQUIPMENT MAY NOT PROJECT MORE
 THAN 4' INTO A REQUIRED SETBACK.2)PURSUANT TO
 SECTION 94-513(A)(2) OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS: NONCONFORMING STRUCTURES OR BUILDINGS
 SHALL NOT BE IMPROVED, CONSTRUCTED, ENLARGED, OR
 ALTERED IN ANY MANNER TO CREATE A NEW NONCONFORMITY OR
 TO INCREASE AN EXISTING NONCONFORMITY, BUT MAY BE
 IMPROVED, CONSTRUCTED, ENLARGED, OR ALTERED AS LONG AS
 NO NEW NONCONFORMITY IS CREATED OR AN EXISTING
 NONCONFORMITY INCREASED.

Review Stop Z ZONING
Rev No 1 Status P Date 2007-12-04 Cont ID  
Sent By choops Date 2007-12-04 Time 10:31 Rev Time 0.00
Received By choops Date 2007-12-04 Time 10:31 Sent To  
Notes
2007-12-14 08:58:53BUILDING PLAN REVIEW
 PERMIT: 07030996
 ADD: 6901-05 S DIXIE HWY
 CONT: JHAMTEC
 TEL: (561)512-9341
  
  
  
 12-14-07
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2 ) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY
 COMMENCED WITHIN 90 DAYS AFTER THE RECORDING THEREOF,
 SUCH NOTICE IS NULL & VOID. NOTE:
 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT
 THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) COMPLIED.
  
 4) 2ND REQUEST,PLEASE CONTACT LILY URSA AT 822-1239
 FOR ADDRESSING THE CITY HAS A SITE ADDRESS OF 6901 S.
 DIXIE HWY FOR THE PROPERTY BUT EACH UNIT REQUIRES
 TENANT ADDRESSES, BEFORE THIS PERMIT CAN BE ISSUED
 CONTACT MUST BE MADE WITH OUR ADDRESSING PERSONEL FOR
 TENANT ADDRESSES. THIS PERMIT WILL NOT BE ISSUED UNTIL
 THIS ISSUE HAS BEEN RESOLVED, THANK YOU FOR YOUR
 COOPERATION IN THIS MATTER.
  
 5)110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A)SEMI- COMPLIED.
 NOTE 2006 FBC EXISTING BUILDING CODE ALSO PROVIDE LEVEL
 OF ALTERATION.
 B-G) COMPLIED.
  
 6) COMPLIED.
  
 7-10) COMPLIED.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
2007-12-14 08:52:16BUILDING PLAN REVIEW
 PERMIT: 07030996
 ADD: 6901-05 S DIXIE HWY
 CONT: JHAMTEC
 TEL: (561)512-9341
  
  
  
 12-14-07
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2 ) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY
 COMMENCED WITHIN 90 DAYS AFTER THE RECORDING THEREOF,
 SUCH NOTICE IS NULL & VOID. NOTE:
 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT
 THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) COMPLIED.
  
 4) 2ND REQUEST,PLEASE CONTACT LILY URSA AT 822-1239
 FOR ADDRESSING THE CITY HAS A SITE ADDRESS OF 6901 S.
 DIXIE HWY FOR THE PROPERTY BUT EACH UNIT REQUIRES
 TENANT ADDRESSES, BEFORE THIS PERMIT CAN BE ISSUED
 CONTACT MUST BE MADE WITH OUR ADDRESSING PERSONEL FOR
 TENANT ADDRESSES. THIS PERMIT WILL NOT BE ISSUED UNTIL
 THIS ISSUE HAS BEEN RESOLVED, THANK YOU FOR YOUR
 COOPERATION IN THIS MATTER.
  
 5)110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A)SEMI- COMPLIED.
 NOTE 2006 FBC EXISTING BUILDING CODE ALSO PROVIDE LEVEL
 OF ALTERATION.
 B-G) COMPLIED.
  
 6) COMPLIED.
  
 7-10) COMPLIED.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
2007-12-04 10:35:38***APPROVED - RESUB #1 - (1ST ZONING REVIEW)***
  
 PROVISOS: 1)NEW A/C EQUIPMENT MAY NOT PROJECT MORE
 THAN 4' INTO A REQUIRED SETBACK.2)PURSUANT TO
 SECTION 94-513(A)(2) OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS: NONCONFORMING STRUCTURES OR BUILDINGS
 SHALL NOT BE IMPROVED, CONSTRUCTED, ENLARGED, OR
 ALTERED IN ANY MANNER TO CREATE A NEW NONCONFORMITY OR
 TO INCREASE AN EXISTING NONCONFORMITY, BUT MAY BE
 IMPROVED, CONSTRUCTED, ENLARGED, OR ALTERED AS LONG AS
 NO NEW NONCONFORMITY IS CREATED OR AN EXISTING
 NONCONFORMITY INCREASED.