Plan Review Details - Permit 07030973
Plan Review Stops For Permit 07030973
Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-11-02 Cont ID  
Sent By btrobaug Date 2007-11-02 Time 16:53 Rev Time 0.00
Received By btrobaug Date 2007-11-02 Time 16:13 Sent To Z
Notes
2007-11-02 16:53:01 
  
  
 PROVISO
  
 PRIOR TO A PERMIT BEING ISSUED THE CONTRACTOR MUST
 CHANGE THE DESCRIPTION AREA ON THE APPLICATION
 TOREFLECT THE SCOPE OF WORK NOW BEING DONE. TAKE THE
 APPLICATION TO THE CLERK TO CHANGE PERMIT TYPE FROM
 "SERVICE CHANE" TO "LOW VOLTAGE".
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-10-23 Cont ID  
Sent By btrobaug Date 2007-07-27 Time 15:22 Rev Time 0.00
Received By btrobaug Date 2007-07-27 Time 13:31 Sent To PC
Notes
2007-10-23 15:22:32 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} AN ATS AND GENERATOR WERE PERMITTED UNDER #06040674
 AND REMAINS OPEN. INDICATE IF THIS IS A SECOND
 GENERATOR AND SERVICE BEING ADDED. SEE 230.2 FOR NUMBER
 OF SERVICES ALLOWED.
  
 2} PROVIDE A SITE PLAN LOCATING ALL SERVICE LOCATIONS
 ON THE BUILDING. 106.1.2 FBC.
  
 3} PAL GROUP IS REPRESENTING ITSELF AS THE DESIGNER OF
 RECORD. THEIR TITLE BLOCK REQUIRES A CERTIFICATE OF
 AUTHORIZATION PER 471.023 FS.
  
 4} THE ARCHITECT WHO SEALED THE PLANS MUST PROVIDE A
 TITLE BLOCK PER 61G1-16.004 FAC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-06-04 Cont ID  
Sent By btrobaug Date 2007-06-04 Time 16:29 Rev Time 0.33
Received By btrobaug Date 2007-06-04 Time 16:09 Sent To PC
Notes
2007-06-04 16:18:41 
  
  
 DENIED/INCOMPLETE INFORMATION
  
 1} PROVIDE SPECIFICATIONS FOR THE TRANSFER SWITCH.
  
 2} THE TITLE BLOCK FOR THE DESIGNER OF RECORD MUST
 CONTAIN A CERTIFICATE OF AUTHORIZATION PER F.A.C.
  
 3} INDICATE IF PANELS "A" AND "B" ARE ARE NEW OR
 EXISTING. IF NEW PROVIDE FEEDER AND PANEL INFORMATION.
  
 4} CHANGE THE DESCRIPTION OF THE PROJECT ON THE
 APPLICATION TO MATCH THE WORK INTENDED.IF ONLY ADDING
 A TRANSFER SWITCH, STATE SAME. "TIE INTO EXISTING
 ELECTRIC" IS NOT INDICATING WHAT IS TO BE "TIED IN"
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-04-03 Cont ID  
Sent By btrobaug Date 2007-04-03 Time 12:00 Rev Time 0.50
Received By btrobaug Date 2007-04-03 Time 11:31 Sent To I
Notes
2007-04-03 12:00:47 
  
  
 NONCOMPLIANT
  
 1} THE ARHCHITECTS SEAL ON THE PLANS SUBMITTED IS NOT
 AN "IMPRESSION TYPE" AS REQUIRED BY ARTICLE
 481.221FLORIDA STATUTES.
  
 2} THE TITLE BLOCK FOR THE DESIGNER OF RECORD MUST
 CONTAIN A CERTIFICATE OF AUTHORIZATION PER F.A.C.
  
 3} THE DISCONNECTS MUST BE GROUPED PER 230.72. IN THIS
 CASE ALL IN THE SAME ROOM. A METER OUTSIDE WITH THE
 EXISTING ONE AND A NIPPLE TO A NEW 200 AMP DISCONNECT
 WOULD MEET THIS REQUIREMENT. PLEASE INDICATE COMPLIANCE
 ON THE PLANS.
  
 4} CHANGE THE DESCRIPTION OF THE PROJECT ON THE
 APPLICATION TO MATCH THE WORK INTENDED. SEE " SERVICE
 UPGRADE-----", THIS IS ADDING TO SERVICE.
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-10-26 Cont ID  
Sent By adarroug Date 2007-10-26 Time 14:39 Rev Time 0.00
Received By adarroug Date 2007-10-26 Time 14:39 Sent To E
Notes
2007-10-26 14:39:30TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-07-25 Cont ID  
Sent By btrobaug Date 2007-07-25 Time 17:28 Rev Time 0.00
Received By btrobaug Date 2007-07-25 Time 17:28 Sent To E
Notes
2007-07-25 17:29:14TO BT'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-05-24 Cont ID  
Sent By adarroug Date 2007-05-24 Time 13:21 Rev Time 0.00
Received By adarroug Date 2007-05-24 Time 13:21 Sent To E
Notes
2007-05-24 13:22:08TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-04-03 Cont ID  
Sent By btrobaug Date 2007-04-03 Time 12:01 Rev Time 0.00
Received By btrobaug Date 2007-03-28 Time 17:45 Sent To PC
Notes
2007-03-28 17:45:14SENT TO ELECTRICAL INBOX MMILLER

Review Stop Z ZONING
Rev No 1 Status F Date 2007-11-06 Cont ID  
Sent By choops Date 2007-11-06 Time 11:38 Rev Time 0.00
Received By choops Date 2007-11-06 Time 11:38 Sent To  
Notes
2007-11-06 11:40:57***FAILED - 1ST ZONING REVIEW***
  
  
 1)ANY NEW ANTENNAS/MECHANICAL EQUIPMENT WILL REQUIRE
 AN INFORMAL SITE PLAN REVIEW SUBMITTED TO AND APPROVED
 BY THE CITY'S PLANNING AND ZONING DEPARTMENT.
 561-822-1435
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720