Plan Review Stops For Permit 07030973 |
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
P |
Date |
2007-11-02 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2007-11-02 |
Time |
16:53 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2007-11-02 |
Time |
16:13 |
Sent To |
Z |
|
Notes |
2007-11-02 16:53:01 | | | | | | | PROVISO | | | | PRIOR TO A PERMIT BEING ISSUED THE CONTRACTOR MUST | | CHANGE THE DESCRIPTION AREA ON THE APPLICATION | | TOREFLECT THE SCOPE OF WORK NOW BEING DONE. TAKE THE | | APPLICATION TO THE CLERK TO CHANGE PERMIT TYPE FROM | | "SERVICE CHANE" TO "LOW VOLTAGE". | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
F |
Date |
2007-10-23 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2007-07-27 |
Time |
15:22 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2007-07-27 |
Time |
13:31 |
Sent To |
PC |
|
Notes |
2007-10-23 15:22:32 | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 | | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, | | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND | | NONCOMPLIANT WITH THE FOLLOWING: | | | | 1} AN ATS AND GENERATOR WERE PERMITTED UNDER #06040674 | | AND REMAINS OPEN. INDICATE IF THIS IS A SECOND | | GENERATOR AND SERVICE BEING ADDED. SEE 230.2 FOR NUMBER | | OF SERVICES ALLOWED. | | | | 2} PROVIDE A SITE PLAN LOCATING ALL SERVICE LOCATIONS | | ON THE BUILDING. 106.1.2 FBC. | | | | 3} PAL GROUP IS REPRESENTING ITSELF AS THE DESIGNER OF | | RECORD. THEIR TITLE BLOCK REQUIRES A CERTIFICATE OF | | AUTHORIZATION PER 471.023 FS. | | | | 4} THE ARCHITECT WHO SEALED THE PLANS MUST PROVIDE A | | TITLE BLOCK PER 61G1-16.004 FAC. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 | | [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2007-06-04 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2007-06-04 |
Time |
16:29 |
Rev Time |
0.33 |
Received By |
btrobaug |
Date |
2007-06-04 |
Time |
16:09 |
Sent To |
PC |
|
Notes |
2007-06-04 16:18:41 | | | | | | | DENIED/INCOMPLETE INFORMATION | | | | 1} PROVIDE SPECIFICATIONS FOR THE TRANSFER SWITCH. | | | | 2} THE TITLE BLOCK FOR THE DESIGNER OF RECORD MUST | | CONTAIN A CERTIFICATE OF AUTHORIZATION PER F.A.C. | | | | 3} INDICATE IF PANELS "A" AND "B" ARE ARE NEW OR | | EXISTING. IF NEW PROVIDE FEEDER AND PANEL INFORMATION. | | | | 4} CHANGE THE DESCRIPTION OF THE PROJECT ON THE | | APPLICATION TO MATCH THE WORK INTENDED.IF ONLY ADDING | | A TRANSFER SWITCH, STATE SAME. "TIE INTO EXISTING | | ELECTRIC" IS NOT INDICATING WHAT IS TO BE "TIED IN" | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2007-04-03 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2007-04-03 |
Time |
12:00 |
Rev Time |
0.50 |
Received By |
btrobaug |
Date |
2007-04-03 |
Time |
11:31 |
Sent To |
I |
|
Notes |
2007-04-03 12:00:47 | | | | | | | NONCOMPLIANT | | | | 1} THE ARHCHITECTS SEAL ON THE PLANS SUBMITTED IS NOT | | AN "IMPRESSION TYPE" AS REQUIRED BY ARTICLE | | 481.221FLORIDA STATUTES. | | | | 2} THE TITLE BLOCK FOR THE DESIGNER OF RECORD MUST | | CONTAIN A CERTIFICATE OF AUTHORIZATION PER F.A.C. | | | | 3} THE DISCONNECTS MUST BE GROUPED PER 230.72. IN THIS | | CASE ALL IN THE SAME ROOM. A METER OUTSIDE WITH THE | | EXISTING ONE AND A NIPPLE TO A NEW 200 AMP DISCONNECT | | WOULD MEET THIS REQUIREMENT. PLEASE INDICATE COMPLIANCE | | ON THE PLANS. | | | | 4} CHANGE THE DESCRIPTION OF THE PROJECT ON THE | | APPLICATION TO MATCH THE WORK INTENDED. SEE " SERVICE | | UPGRADE-----", THIS IS ADDING TO SERVICE. | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 | | [email protected] |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2007-10-26 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-10-26 |
Time |
14:39 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-10-26 |
Time |
14:39 |
Sent To |
E |
|
Notes |
2007-10-26 14:39:30 | TO "BTROBAUG" DESK/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2007-07-25 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2007-07-25 |
Time |
17:28 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2007-07-25 |
Time |
17:28 |
Sent To |
E |
|
Notes |
2007-07-25 17:29:14 | TO BT'S DESK |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2007-05-24 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-05-24 |
Time |
13:21 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-05-24 |
Time |
13:21 |
Sent To |
E |
|
Notes |
2007-05-24 13:22:08 | TO "BTROBAUG" DESK/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2007-04-03 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2007-04-03 |
Time |
12:01 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2007-03-28 |
Time |
17:45 |
Sent To |
PC |
|
Notes |
2007-03-28 17:45:14 | SENT TO ELECTRICAL INBOX MMILLER |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2007-11-06 |
|
|
Cont ID |
|
Sent By |
choops |
Date |
2007-11-06 |
Time |
11:38 |
Rev Time |
0.00 |
Received By |
choops |
Date |
2007-11-06 |
Time |
11:38 |
Sent To |
|
|
Notes |
2007-11-06 11:40:57 | ***FAILED - 1ST ZONING REVIEW*** | | | | | | 1)ANY NEW ANTENNAS/MECHANICAL EQUIPMENT WILL REQUIRE | | AN INFORMAL SITE PLAN REVIEW SUBMITTED TO AND APPROVED | | BY THE CITY'S PLANNING AND ZONING DEPARTMENT. | | 561-822-1435 | | | | | | QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, | | ZONING TECHNICIAN (561)805-6720 |
|
|