2007-08-15 08:49:03BUILDING PLAN REVIEW
 PERMIT: 07030949
 ADD: 422 SUNSET ROAD
 CONT: BURKHARDT
 TEL: (561)718-2602
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVISION: DENIED
 REFERENCE: STRUCTURAL OPENINGS IN MASONARY WALLS
  
 IN EITHER CASE, EMPERICAL DESIGN OR REINFORCED MASONRY
 LINTELS CAN NOT BE SUPPORTED BY WOOD HEADERS AND JACK
 STUDS OR FULLLENGTH STUDS. PLEASE SEE ACI 530-02.
 2109.1 GENERAL.
 EMPIRICALLY DESIGNED MASONRY SHALL CONFORM TO THIS
 CHAPTER OR CHAPTER 5 OF ACI 530-02 /ASCE 5/TMS 402.
 2101.2.4 EMPIRICAL DESIGN.
 MASONRY DESIGNED BY THE EMPIRICAL DESIGN METHOD SHALL
 COMPLY WITH THE PROVISIONS OF SECTIONS 2106 AND 2109 OR
 CHAPTER 5 OF ACI 530-02/ASCE 5/TMS 402
 5.6.1 DEFLECTION OF BEAMS AND LINTELS DUE TO DEAD PLUS
 LIVE LOADS SHALL NOT EXCEED L/600 NOR 0.3 IN. WHEN
 PROVIDING VERTICAL SYPPORT TO MASONRY ELEMENTS DESIGNED
 IN ACCORDANCE WITH CHAPTER 6 OR CHAPTER 9.
 ACI 530-02: 9.9.3 SUPPORTS ON WOOD- NO MASONRY SHALL BE
 SUPPORTED ON WOOD GIRDERS OR OTHER FORM OF WOOD
 CONSTRUCTION.
  
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-07-06 Cont ID  
Sent By jwitmer Date 2007-07-06 Time 11:57 Rev Time 0.77
Received By jwitmer Date 2007-07-06 Time 11:57 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-06-04 Cont ID  
Sent By lmartine Date 2007-06-04 Time 13:09 Rev Time 0.00
Received By lmartine Date 2007-06-04 Time 13:09 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-05-03 Cont ID  
Sent By jwitmer Date 2007-05-03 Time 13:45 Rev Time 2.22
Received By jwitmer Date 2007-05-03 Time 13:45 Sent To FIRE
Notes
2007-05-03 15:13:52BUILDING PLAN REVIEW
 PERMIT:07030949
 ADD: 422 SUNSET RD
 CONT: BURKHARDT COST
 TEL: (561718-2602
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2 ) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLYCOMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6)THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION. THE SUBMITED NOC IS OVER 90 OLD, NO
 COMMENCEMENT OF WORK UNDER THIS PERMIT. PERMIT
 REFRENECD
 IS 06010452.
  
 3)PLEASE PROVIDE THE DORMA PRODUCT INFORMAITON FOR A
 WINDOW WALL SYSTEM HOW IT WILL INTERGRATE INTO THE NEW
 STEEL FRAMEWORK.
  
 4) PROVIDE PRODUCT INFORMATION ON THE DORMA SYSTEM FOR
 SAFEY GLA'HAZARDOUS LOCATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-07-06 Cont ID  
Sent By btrobaug Date 2007-07-06 Time 14:16 Rev Time 0.00
Received By btrobaug Date 2007-07-06 Time 12:34 Sent To PC
Notes
2007-07-06 14:16:04 
  
 PROVISO
  
 WITH FIXTURE TYPES BEING ADDED, THE INPUT DATA REPORT
 FOR LIGHTING IN THE ENERGY CALCULATION , PAGES 2 AND 3,
 MUST BE REVISED TO REFLECT THOSE CHANGES. 13.103.3 FBC
  
 SUBMIT SAME TO THIS OFFICE FOR REVIEW PRIOR TO FINAL
 INSPECTION. REVIEWED SET TO BE ON THE JOB SITE AND WITH
 THE FILE SET.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
 FAX/:561/805-6676

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-05-24 Cont ID  
Sent By btrobaug Date 2007-05-24 Time 12:51 Rev Time 1.00
Received By btrobaug Date 2007-05-24 Time 12:22 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-04-16 Cont ID  
Sent By btrobaug Date 2007-04-16 Time 14:22 Rev Time 1.00
Received By btrobaug Date 2007-04-16 Time 06:55 Sent To  
Notes
2007-04-16 07:51:04 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW
  
 1} ELECTRICAL NOTE #1 INCORRECTLY LISTS THE 2002 NEC,
 THE 2005 NEC WAS ADOPTED 8 DECEMBER 2006, ALSO THE 2006
 REVISIONS TO THE FBC. PLEASE CORRECT NOTE.
  
 1} PANEL "P2" IS SHOWN IN ROOM 116 AND ROOM 101. PLEASE
 CORRECT THE NUMBERS.
  
 2} PROVIDE A PANEL SCHEDULE PER 408.4. PLEASE SEE NEW
 VERBAGE FOR 2005 NEC: "THE IDENTIFICATION SHALL INCLUDE
 SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE
 DISTINGUISHED FROM ALL OTHERS." NEW INTENT IN THE 2005
 NEC.
  
 3} THE MOTION SENSORS INDICATED ON E-2.1 FLOOR PLAN AND
 NOTE, DO NOT INDICATE WHEN THEY TIME OFF, SEE
 13-415.ABC.1.2A(FOR 30 MINUTES).
  
 4} THE INPUT DATA REPORT, PAGES 2 & 3 IN THE ENERGY
 CALCS SUBMITTED, DOES NOT CORRELATE TO THE DENSITY
 CALCULATIONS ON SHEET E-1.1 OF THE PLAN. IT LISTS ONE
 LUMINAIR WITH A MANUAL ON OFF, FOR ALL AREAS.
 ALSO THE FIXTURES LISTED DO NOT MATCH THE FIXTURE
 SCHEDULE ON THE PLAN.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-05-29 Cont ID  
Sent By mawillia Date 2007-05-29 Time 17:25 Rev Time 0.00
Received By mawillia Date 2007-05-29 Time 16:52 Sent To  
Notes
2007-05-29 17:22:24*****APPROVED*****
  
 ALL COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN ADDRESSED;PLAN SHEETS LS-1, A-3, AND E-1.1 WERE
 STAMPED, INITIALED, AND DATED.
  
  
  
 .
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-05-03 Cont ID  
Sent By mawillia Date 2007-05-03 Time 18:14 Rev Time 0.00
Received By mawillia Date 2007-05-03 Time 17:17 Sent To  
Notes
2007-05-03 18:14:24*****DENIED*****
  
  
  
 1.IS THE BUILDING CLASSIFIED AS A COMBINED BUSINESS
 OCCUPANCY AND PARKING STRUCTURE COMPLYING WITH 38.1.2
 OF NFPA 101, LIFE SAFETY CODE, 2003 EDITION?
  
 2.PROVIDE THE LOCATION OF THE 2A:10BC RATED FIRE
 EXTINGUISHER(S) WHICH SATISFY THE 75' TRAVEL DISTANCE.
  
 3.INTERIOR WALL AND CEILING FINISH MATERIALS SHALL BE
 CLASS A OR CLASS B IN EXITS AND IN EXIT ACESS
 CORRIDORS, AND CLASS A, CLASS B, OR CLASS C IN ALL
 OTHER SPACES.
  
 4.IT IS SHOWN ON SHEET E1-1 THAT THERE IS AN EXIT
 DOOR LEADING TO THE STORAGE/WAREHOUSE/PARKING AREA.IS
 THIS AREA CONSIDERED TO BE MORE HAZARDOUS THAN THE
 BUSINESS AREA FROM WHENCE THEY'RE EXITING?
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2007-09-11 Cont ID  
Sent By adarroug Date 2007-09-11 Time 12:29 Rev Time 0.00
Received By adarroug Date 2007-09-11 Time 12:29 Sent To B
Notes
2007-09-11 12:29:45TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2007-09-10 Cont ID  
Sent By adarroug Date 2007-09-10 Time 10:11 Rev Time 0.00
Received By adarroug Date 2007-09-10 Time 10:11 Sent To M
Notes
2007-09-10 10:11:41TO "M" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2007-08-06 Cont ID  
Sent By adarroug Date 2007-08-06 Time 13:25 Rev Time 0.00
Received By adarroug Date 2007-08-06 Time 13:25 Sent To B
Notes
2007-08-06 13:25:59TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2007-07-27 Cont ID  
Sent By adarroug Date 2007-07-27 Time 14:39 Rev Time 0.00
Received By adarroug Date 2007-07-27 Time 14:39 Sent To M
Notes
2007-07-27 14:40:03TO "M" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2007-07-12 Cont ID  
Sent By adarroug Date 2007-07-12 Time 08:51 Rev Time 0.00
Received By adarroug Date 2007-07-12 Time 08:51 Sent To M
Notes
2007-07-12 08:51:57TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-07-02 Cont ID  
Sent By adarroug Date 2007-07-02 Time 11:31 Rev Time 0.00
Received By adarroug Date 2007-07-02 Time 11:31 Sent To P
Notes
2007-07-02 11:31:56TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-07-02 Cont ID  
Sent By adarroug Date 2007-07-02 Time 11:29 Rev Time 0.00
Received By adarroug Date 2007-07-02 Time 11:29 Sent To E
Notes
2007-07-02 11:30:02TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-06-24 Cont ID  
Sent By adarroug Date 2007-06-24 Time 12:27 Rev Time 0.00
Received By adarroug Date 2007-06-24 Time 12:27 Sent To B
Notes
2007-06-24 12:28:01TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-05-15 Cont ID  
Sent By adarroug Date 2007-05-15 Time 15:04 Rev Time 0.00
Received By adarroug Date 2007-05-15 Time 15:04 Sent To  
Notes
2007-05-15 15:04:15TO "BOB"#8

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-05-03 Cont ID  
Sent By jbabcock Date 2007-04-10 Time 11:24 Rev Time 0.00
Received By mawillia Date   Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-05-03 Cont ID  
Sent By mawillia Date 2007-05-03 Time 17:18 Rev Time 0.00
Received By mawillia Date 2007-03-27 Time 19:07 Sent To  
Notes
2007-04-13 10:10:54PLANS REMOVED FROM "COMM" BD#1, AND MOVED TO "BOB"#3
2007-03-30 17:47:04TO COMM BOARD # 1
2007-03-27 19:07:17WAITING FOR COMM BOARD

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2007-09-12 Cont ID  
Sent By tgordon Date 2007-09-12 Time 15:35 Rev Time 0.25
Received By tgordon Date 2007-09-12 Time 15:35 Sent To  
Notes
2007-09-12 15:39:03SUBMITTAL FOR FOUR SUPPLY AIR DROPS.
 *** PROVISO ***
 1) IF OTHER MECHANICAL CHANGES ARE MADE THEN MECHANICAL
 PLANS WILL NEED TO BE REVISED.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2007-07-30 Cont ID  
Sent By tgordon Date 2007-07-30 Time 08:37 Rev Time 0.20
Received By tgordon Date 2007-07-30 Time 08:37 Sent To  
Notes
2007-07-30 08:38:31SUBMITTAL FOR BATHROOM EXHAUST FAN DUCTS.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-07-16 Cont ID  
Sent By tgordon Date 2007-07-16 Time 14:13 Rev Time 0.30
Received By tgordon Date 2007-07-16 Time 14:13 Sent To  
Notes
2007-07-16 14:14:17REVISION TO MECH. PLANS PAGES M-0.1 AND M-1.1.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-05-22 Cont ID  
Sent By tgordon Date 2007-05-22 Time 11:28 Rev Time 0.45
Received By tgordon Date 2007-05-22 Time 11:28 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-05-02 Cont ID  
Sent By tgordon Date 2007-05-02 Time 11:31 Rev Time 2.00
Received By tgordon Date 2007-05-02 Time 11:31 Sent To  
Notes
2007-05-02 11:37:28*** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-400.3.ABC.2.
  
 2) SEE PLANS PAGE M-0.1 MECHANICAL NOTES #3, NEED TO
 STATE 2004 FBC & MECHANICAL (NOT LATEST EDITION),
 PLEASE CORRECT.
  
 3) SEE PAGE M-0.1 SLAB HUNG A/H UNIT DETAIL, PRIMARY
 CONDENSATE DRAIN LINE AND AUXILIARY DRAIN LINE ARE TIED
 INTO THE SAME LINE, NOT PERMITTED, SEE 2004 FBC M 307.
 ALSO THE DETAIL SHOWS A CHECK VALVE IN THE DRAIN LINE,
 AS THIS LINE IS NOT UNDER PRESSURE THE VALVE WOULD BE A
 BLOCKAGE, PLEASE CORRECT.
  
 4) PLEASE SHOW ON PLANS PAGE M-1.1, THE CONDENSATE
 DRAIN LINES AND WERE THEY WILL TERMINATE.
  
 5) SEE PAGE M-1.1 KEY NOTE #8 89"X28" LOUVER, PLEASE
 STATE IF THE LOUVER IS OPEN TO THE OFFICE SPACES, OPEN
 PLENUM SPACE, OR ABOVE PLATFORM DECK.
  
 6) THE OPEN RETURN AIR PLENUM WILL NEED TO BE
 INSULATED, SEE 2004 FBC 13-410.1.ABC.2.2, PLEASE
 CORRECT.
  
 7) PLEASE ADD NOTE TO MECHANICAL PLANS, NO COMBUSTIBLE
 MATERIALS PERMITTED IN PLENUM, PER 2004 FBC/M 602.2.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-07-11 Cont ID  
Sent By jleech Date 2007-07-11 Time 11:11 Rev Time 0.00
Received By jleech Date 2007-07-11 Time 11:10 Sent To  
Notes
2007-07-11 11:11:54REVISED WATER AND SANITARY RISER DIAGRAMS OK

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-06-05 Cont ID  
Sent By jleech Date 2007-06-05 Time 08:31 Rev Time 0.00
Received By jleech Date 2007-06-05 Time 08:31 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-04-18 Cont ID  
Sent By jleech Date 2007-04-18 Time 12:37 Rev Time 0.00
Received By jleech Date 2007-04-18 Time 12:37 Sent To  
Notes
2007-04-18 13:24:56DENIED;
  
 1.PAGE LS-1 (APPLICABLE CODES) THE BUILDING IS
 SEPERATED INTO TWO OCCUPANCY CLASSIFICATIONS, EACH
 OCCUPANCY MUST MEET FBC- 2004 PLUMBING CODE TABLE
 403.1. A DRINKING FOUNTAIN IS REQUIRED IN THE OFFICE
 AREA.
 2. PAGE P-1.1 ( WATER RISER DIAGRAM) WATER HAMMER
 ARRESTORS ARE REQUIRED IN KITCHEN, PER SECTION 604.9.
 PLEASE SHOW ON PLANS AND SPEC OUT TYPE TO BE USED.
 3. PAGE P-1.1 PLUMBING FIXTURES, SK-2 KITCHEN SINK MUST
 MEET THE HANDICAP CODE SECTION 11-4.24.4 DEPTH OF SINK
 TO BE NO DEEPER THAN 6 1/2 INCH. THE FAUSET MUST BE
 LEVER TYPE, SECTION 11-4.24.7. GARBAGE DISPOSER CAN NOT
 INTERFERE WITH THE KNEE SPACE REQUIRED PER SECTION
 11-4.24.3. A INTERIOR DESIGNER MAY NOT COMPLY WITH THE
 HANDICAP CODE, THIS WOULD CAUSE NON-COMPLIANCE TO THE
 CODE REQUIREMENTS.
 4. THE BATHROOMS ARE NOT PRIVATE. MORE THAN ONE PERSON
 WILL BE USING THE BATHROOMS. SEE SECTION 11-4.1.3(11).
 PAGE A-5 DETAIL 17, MISSING TOTLE WIDTH OF BATHROOM
 SHOW TOILET AT 18" OF SIDE WALL SEE FIGURE 28 IN H/C
 CODE. GRAB BARS ARE REQUIRED.
 5. WALL AND FLOOR FINISHES NOT FOUND ON PLANS FOR
 BATHROOM WALLS AND FLOOR.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 2 Status P Date 2007-06-13 Cont ID  
Sent By lmartine Date 2007-06-13 Time 17:13 Rev Time 0.00
Received By lmartine Date 2007-06-12 Time 15:25 Sent To  
Notes
2007-06-13 17:14:52SEE PLANS FOR JULIA'S APPROVAL LM
2007-06-12 15:25:33PLANNING AND ZONING***APPROVED WITH PROVISO***
  
  
 ***PROVISO***
 APPROVAL IS CONTINGENT UPON THE FOLLOWING:
 LANDSCAPE PERMIT # 07050913 SHALL BE APPROVED PRIOR TO
 THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY FOR ALL
 PERMITS.
 MASTER PERMIT# 06010452
 PERMIT# 06110667 (PAINT BOOTH AND MIXING ROOM)

Review Stop Z ZONING
Rev No 1 Status F Date 2007-04-10 Cont ID  
Sent By jbabcock Date 2007-04-13 Time 10:55 Rev Time 0.00
Received By jbabcock Date 2007-04-13 Time 13:43 Sent To I
Notes
2007-04-13 10:55:41 
 PLANNING AND ZONING-***FAILED***
  
 1. PROVIDE RESPONSES TO COMMENTS IN WRITING.
  
 2. PURSUANT TO SECTION 94-444, PROVIDE A TRASH
 RECEPTACLE.REFERENCE FIGURE XIV-3 FOR DIMENSIONAL
 REQUIREMENTS AND SPECIFICATIONS FOR TRASH RECEPTACLES.
 IF THE PROPOSED TRASH RECEPTACLE DOES NOT MEET THE
 DIMENSIONAL REQUIREMENTS, A
 DEVIATION FROM THE DIMENSIONAL STANDARD
 MAY BE PERMITTED.IF A DEVIATION IS REQUESTED, A SIGN
 OFF FROM SANITATION IS REQUIRED ON THE SITE PLAN
 ILLUSTRATING THE DEVIATION FROM THE STANDARD.
  
 3. PROVIDE DETAILS THAT ILLUSTRATE ADA COMPLIANCE.
 SPECIFICALLY, SHOW THE HANDICAP ACCESS DETAIL FROM THE
 PARKING AREA TO THE BUILDING ENTRANCE ON THE SOUTH EAST
 SIDE OF THE PROPERTY.
  
 4. PURSUANT TO SECTION 94-441(C) THE LANDSCAPING, TREE
 PROTECTION, AND SCREENING REQUIREMENTS OF THIS SECTION
 SHALL APPLY TO ALL DEVELOPMENT WITHIN THE CITY, EXCEPT
 THOSE DEVELOPMENTS EXEMPTED IN SUBSECTION (C) OF THIS
 SECTION. REFER TO SECTION 94-441 (C) IN THIS CASE TO
 SHOW THAT THE (2) RENOVATIONS, REPAIR, ALTERATION, OR
 REDVELOPMENT DOES NOT EXCEED 50 PERCENT OF THE VALUE OF
 THE STRUCTURE. PROVIDE VALUE OF STRUCTURE TO SHOW
 COMPLIANCE WITH CODE.
  
 5.PROVIDE DETAILED INFORMATION ABOUT THE
 PROPOSED USES ON SITE INCLUDING THE MOTOR VEHICLE
 SERVICE USE AND THE NEW PROPOSED OFFICE USE.
  
  
  
 FOR ANY ADDITIONAL INFORMATION OR QUESTIONS YOU MAY
 CONTACT:
  
 JULIA BABCOCK
 PLANNER
 OFFICE: (561) 822-1442
 EMAIL: [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved