Plan Review Details - Permit 07030833
Plan Review Stops For Permit 07030833
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-06-04 Cont ID  
Sent By shill Date 2007-06-04 Time 08:19 Rev Time 0.00
Received By shill Date 2007-06-04 Time 08:19 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-05-30 Cont ID  
Sent By shill Date 2007-05-30 Time 11:38 Rev Time 0.00
Received By shill Date 2007-05-30 Time 11:38 Sent To  
Notes
2007-05-30 11:57:27****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* CITY
 OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 1.)THERE ARE TWO WIND LOAD DESIGN SPECIFICATIONS IN
 THE PERMIT PACKAGE.ONE WAS PRODUCED WITH SOFTWARE,
 THE OTHER WAS PROVIDED BY A STRUCTURAL ENGINEER.
 ENGINEERING IN ACCORDANCE WITH ASCE7-02 IS REQUIRED FOR
 DESIGN PRESSURES FOR BUILDINGS OVER 60' IN HEIGHT,
 FBC1609.1.1.THEREFORE, YOU CANNOT USE THE PRESSURES
 PRODUCED BY THE WIND LOAD SOFTWARE.PLEASE REMOVE THE
 "DESIGN PRESSURE CALCULATION" FROM THE PACKAGE AND USE
 THE PRESSURES SPECIFIED BY THE ENGINEER (WHICH ARE
 HIGHER) FOR THIS PROJECT.
  
 2.)TWO DIFFERENT INSTALLATION SCHEDULES WERE
 PROVIDED.ONE STATES THAT THE SUBSTRATE IS CONCRETE
 BLOCK, THE OTHER STATES POURED CONCRETE.SUBMIT ONLY
 ONE INSTALLATION SCHEDULE, TWO COPIES.TWO SETS
 SUBMITTED OF THE CONCRETE BLOCK SCHEDULE, ONLY ONE FOR
 THE INSTALLATION SCHEDULE WITH THE POURED CONCRETE
 SUBSTRATE.TWO IDENTICAL COMPLETE SETS, COLLATED,
 SHOULD ALWAYS BE SUBMITTED FOR PERMITTING.
  
 3.)THE INSTALLATION SCHEDULES USE THE DESIGN
 PRESSURES PRODUCED BY THE SOFTWARE.YOU MUST USE THE
 DESIGN PRESSURES SPECIFIED BY THE STRUCTURAL ENGINEER,
 WHICH ARE HIGHER.REVISE THE INSTALLATION SCHEDULE
 ACCORDINGLY.
  
 4.)THE INSTALLATION SCHEDULE STATES THAT SHUTTER SPAN
 IS 9'.ON THE PRODUCT APPROVAL, YOU HAVE CIRCLED
 ANCHOR SPACING FOR AN 8'0" SPAN, -60PSF DESIGN
 PRESSURE.THE ENGINEER SPECIFIES -62.27 FOR ONE OF THE
 OPENINGS, SO YOU MUST USE THE -75PSF COLUMN FOR THAT
 OPENING.IF THE SPAN (WHICH SHOULD BE THE BLADE
 LENGTH) IS OVER 8', USE THE 9' COLUMN.PLEASE CLARIFY
 THE SPAN AS THE MOUNTING DETAIL TO BE USED IS NOT
 CLEAR.
  
 5.)THE COLUMN ON THE INSTALLATION SCHEDULE MARKED
 "SHUTTER MOUNTING:CONNECTION TYPE PER PRODUCT
 APPROVAL" IS TO INDICATE WHICH MOUNTING DETAIL YOU ARE
 USING.ON THIS PRODUCT APPROVAL, IT WOULD BE DETAILS A
 THROUGH L.IT IS NOT CLEAR WHICH MOUNTING DETAIL YOU
 ARE USING AS SEVERAL HAVE BEEN CIRCLED ON THE PRODUCT
 APPROVAL.
  
 6.)THE PRODUCT APPROVAL HAS H, FLOOR MOUNTING
 CIRCLED, WITH 8.5 ANCHORING ALSO CIRCLED.THE
 INSTALLATION SCHEDULE DOES NOT SPECIFY 8.5 ANCHOR
 SPACING.ANYTHING CIRCLED ON THE PRODUCT APPROVAL
 SHOULD CORRELATE WITH THE JOB AND INSTALLATION
 SCHEDULE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-05-04 Cont ID  
Sent By shill Date 2007-05-04 Time 11:41 Rev Time 0.00
Received By shill Date 2007-05-04 Time 11:41 Sent To  
Notes
2007-05-04 11:43:39****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)INSTALLATION SCHEDULE REQUIRED, SEE ATTACHED
 SAMPLE.I BELIEVE THIS WAS IN THE APPLICATION PACKAGE
 ON FIRST REVIEW, BUT IS NOT IN THE RESUBMITTAL.THIS
 INFORMATION IS ALWAYS REQUIRED FOR SHUTTER PERMITS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-04-02 Cont ID  
Sent By shill Date 2007-04-02 Time 10:01 Rev Time 0.00
Received By shill Date 2007-04-02 Time 10:01 Sent To  
Notes
2007-04-02 10:02:16****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 SHUTTER PERMIT APPLICATION, ONLY CHECKED ITEMS APPLY
  
 ____1.A NOTICE OF COMMENCEMENT MUST BE FILED WITH
 THE CLERK OF COURTS BEFORE A PERMIT CAN BE ISSUED,
 FS713.13.
  
 _XX_2.ENGINEER'S LETTER REQUIRED CERTIFYING
 BUILDING HEIGHT OF 60' AS DECLARED BY CONTRACTOR.
 DESIGN PRESSURES FOR BUILDINGS OVER 60FEET ARE REQUIRED
 TO BE DESIGNED USING ASCE7, FBC1609.1.1 AND MUST BE
 DONE BY A DESIGN PROFESSIONAL. DOCUMENTS PREPARED BY AN
 ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 SIGNED SEALED ORIGINALS FAC61G15-23.002.
  
 ____3.PROVIDE A COPY OF THE CONDO ASSOCIATION
 APPROVAL.
  
 ____4.COMPLETE THE ATTACHED INSTALLATION SCHEDULE
 OR PROVIDE ALL INFORMATION TO SHOW CODE COMPLIANCE IN
 ANOTHER FORMAT.
  
 ____5.FLORIDA STATE OR LOCAL PRODUCT APPROVAL
 REQUIRED, FAC9B72, WWW.FLORIDABUILDING.ORG.
  
 ____6.ON THE PRODUCT APPROVAL, MARK WHICH DETAILS
 APPLY TO THIS JOB.PLEASE USE INK RATHER THAN A
 HIGHLIGHTER.
  
 ____7.SHOW THE EMERGENCY MEANS OF ESCAPE, FBC
 R310.
  
 ____8.PROVIDE A FLOOR PLAN SHOWING WHERE THE
 SHUTTERS WILL BE INSTALLED AND PANEL SIZES WHICH
 CORRELATES WITH THE INSTALLATION SCHEDULE, ITEM 4
 ABOVE.
  
 ____9.REVISE EXPOSURE CATEGORY FBC1609.6.2.1(2),
 FBC R301.2.1.4.NOTE THAT THE DEFINITION FOR EXPOSURE
 C HAS CHANGED EFFECTIVE DECEMBER 8, 2006 FBC1609.4, FBC
 R301.2.1.4.
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-06-01 Cont ID  
Sent By adarroug Date 2007-06-01 Time 08:56 Rev Time 0.00
Received By adarroug Date 2007-06-01 Time 08:56 Sent To B
Notes
2007-06-01 08:56:22TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-05-21 Cont ID  
Sent By adarroug Date 2007-05-21 Time 09:58 Rev Time 0.00
Received By adarroug Date 2007-05-21 Time 09:58 Sent To B
Notes
2007-05-21 09:58:32TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-05-03 Cont ID  
Sent By adarroug Date 2007-05-03 Time 09:29 Rev Time 0.00
Received By adarroug Date 2007-05-03 Time 09:29 Sent To B
Notes
2007-05-03 09:29:46TO "SHILL' DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-04-02 Cont ID  
Sent By shill Date 2007-04-02 Time 10:02 Rev Time 0.00
Received By shill Date 2007-03-25 Time 11:40 Sent To  
Notes
2007-03-25 11:40:50TO "MISC" BOX#1