Plan Review Details - Permit 07030795
Plan Review Stops For Permit 07030795
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-05-09 Cont ID  
Sent By shill Date 2007-05-09 Time 10:26 Rev Time 0.00
Received By shill Date 2007-05-09 Time 10:26 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-05-03 Cont ID  
Sent By shill Date 2007-05-03 Time 15:27 Rev Time 0.00
Received By shill Date 2007-05-03 Time 15:27 Sent To  
Notes
2007-05-03 15:29:18****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 1.)PLEASE SEE THE REDLINED ANCHOR SCHEDULE AND THE
 PRODUCT APPROVAL.I CANNOT UNDERSTAND THE CONNECTION
 TYPE FOR OPENING 3.IF YOU DO NOT UNDERSTAND THE
 REDLINE CORRECTIONS, PLEASE CONTACT ME.PLEASE CHECK
 ALL OPENINGS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-04-21 Cont ID  
Sent By shill Date 2007-04-21 Time 11:50 Rev Time 0.00
Received By shill Date 2007-04-21 Time 11:50 Sent To  
Notes
2007-04-21 11:53:40****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FACFLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.)YOU HAVE REDUCED THE PRESSURE TO -47.2.THIS IS
 "WORST CASE" FOR ZONE 5, EXPOSURE B.THIS JOB IS
 EXPOSURE C; SEE FBC1609.6.2.1(2), FBC R301.2.1.4.
 OPENING 9 REQUIRES A -53.24PSF.SEE FBC TABLE R
 301.2(2) AND FBC R301.2.(3).REVISE PRESSURE AND CHECK
 ANCHOR SPACING FOR ALL OPENINGS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-03-30 Cont ID  
Sent By shill Date 2007-03-30 Time 13:54 Rev Time 0.00
Received By shill Date 2007-03-30 Time 13:54 Sent To  
Notes
2007-03-30 13:55:17****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC*CITY OF WEST PALM BEACH AMENDMENTS TO THE
 FBC2004
 FACFLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)OPENING 14, C5 CONNECTION, YOU SPECIFY 10"
 SPACING.YOUR PRESSURE OF -49.5 REQUIRES USE OF THE
 -77PSF CHART, 4 INCH REQUIRED.CHECK ALL OPENINGS.
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-05-07 Cont ID  
Sent By adarroug Date 2007-05-07 Time 14:38 Rev Time 0.00
Received By adarroug Date 2007-05-07 Time 14:38 Sent To B
Notes
2007-05-07 14:38:43TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-04-30 Cont ID  
Sent By adarroug Date 2007-04-30 Time 16:17 Rev Time 0.00
Received By adarroug Date 2007-04-30 Time 16:17 Sent To B
Notes
2007-04-30 16:18:05TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-04-18 Cont ID  
Sent By adarroug Date 2007-04-18 Time 11:02 Rev Time 0.00
Received By adarroug Date 2007-04-18 Time 11:02 Sent To B
Notes
2007-04-18 11:02:44TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-03-30 Cont ID  
Sent By shill Date 2007-03-30 Time 13:55 Rev Time 0.00
Received By shill Date 2007-03-24 Time 15:05 Sent To  
Notes
2007-03-24 15:05:32TO "MISC" BOX#1