Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-05-21 Cont ID  
Sent By mcarsill Date 2007-05-21 Time 15:46 Rev Time 0.00
Received By mcarsill Date 2007-05-21 Time 15:39 Sent To  
Notes
2007-05-21 15:45:541. NOTE # 2 ON PAGE FP-1 IS INCORRECT. "STANDPIPE
 SYSTEM SHALL COMPLY WITH NFPA 24". SHOULD READ
 STANDPIPE SYSTEM SHALL COMPLY WITH NFPA 14.
  
 2. PARKING GARAGE FIRE SPRINKLER SYSTEM TO COMPLY WITH
 NFPA 13.
  
 3. ANY FIRE SPRINKLER HEADS DUE TO THEIR INSTALLATION
 HEIGHT OR INSTALLED IN AN AREA WHERE THEY ARE SUBJECT
 TO MECHANICAL DAMAGE SHALL BE PROVIDED WITH HEAD
 GUARDS.
  
 4. NOTE # 3 ON PAGE FP-2 IS NOT COMPLETE.
  
 5. THE ENTIRE FIRE SPRINKLER SYSTEM SHALL BE INSTALLED
 IN AN APPROVED AND WORKMANSHIP MANNER.
  
 6. FIRE SPRINKLER SYSTEM SUBJECT TO FIELD INSPECTION
 AND APPROVAL.
  
 7. SPEC BOOKS DO NOT DECLARE ANY UL LISTING FOR THE 120
 GALLON DIESEL FUEL TANK BEING PROPOSED. PLEASE PROVIDE
 LISTING INFORMATION.
  
 APPROVED PROVISO:
  
 MIKE CARSILLO, BATTALION CHIEF OF FIRE PREVENTION
 804-4709 PHONE
 804-4774 FAX

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-04-12 Cont ID  
Sent By mcarsill Date 2007-04-12 Time 08:33 Rev Time 0.00
Received By mcarsill Date 2007-04-12 Time 08:33 Sent To  
Notes
2007-04-12 08:45:021. ENTIRE PARKING GARAGE IS TO BE COMPLETELY FIRE
 SPRINKLER PROTECTED EXCEPT FOR THE FPL VAULT.
  
 2. THE FIRST FLOOR MECHANICAL ROOM MUST ALSO BE FIRE
 SPRINKLER PROTECTED. PLANS DO NOT ILLUSTRATE FIRE
 SPRINKLER HEADS IN THIS ROOM OR ELECTRICAL ROOM B1.111.
 PRE-ACTION FIRE SPRINKLER SYSTEM NOTED TO BE PLANNED IN
 THE MAIN ELECTRICAL ROOM ACCORDING TO THE NOTES.
  
 3. STANDPIPE SYSTEM FIRE HOSE VALVES SHALL BE EQUIPPED
 WITH 2 1/2 TO 1 1/2 REDUCERS.
  
 4. SPARE SPRINKLER HEADS AND A WRENCH SHALL BE PROVIDED
 FOR THE FIRE SPRINKLER SYSTEM.
  
 5. FIRE DEPARTMENT CONNECTIONS SHALL BE PROVIDED WITH
 KNOX-BOX LOCKING CAPRS.
  
 6. FIRE SPRINKLER SYSTEM TO BE INSTALLED IN ACCORDANCE
 WITH NFPA 13.
  
 7. STANDPIPE SYSTEM SHALL BE INSTALLED IN ACCORDANCE
 WITH NFPA 14.
  
 8. FIRE PUMP TO BE INSTALLED IN ACCORDANCE WITH NFPA
 20.
  
 9. FIRE SPRINKLER HEADS THAT ARE INSTALLED OUTSIDE
 SHALL BE WAX COATED OR CORROSION RESISTANT.
  
 10. CUT SHEETS NEEDED FOR THE FIRE PUMP, BACKFLOW
 PREVENTION DEVICE, FIRE SPRINKLER HEADS, AND ALL OTHER
 APPURTENANT EQUIPMENT.
  
 11. TEMPORARY STANDPIPE SYSTEMS SHALL BE REQUIRED WHEN
 EACH BUILDING REACHES THREE STORIES OR THIRTY FEET IN
 HEIGHT.
  
 MIKE CARSILLO, BATTALION CHIEF OF FIRE PREVENTION
 804-4709 PHONE
 804-4774 FAX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-05-10 Cont ID  
Sent By adarroug Date 2007-05-10 Time 16:35 Rev Time 0.00
Received By adarroug Date 2007-05-10 Time 16:35 Sent To FIRE
Notes
2007-05-10 16:35:37TO "F" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-04-12 Cont ID  
Sent By mawillia Date 2007-04-12 Time 13:55 Rev Time 0.00
Received By mawillia Date 2007-03-24 Time 16:34 Sent To  
Notes
2007-03-24 16:34:09TO "F" BOX


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved