Plan Review Details - Permit 07030789
Plan Review Stops For Permit 07030789 |
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2007-05-21 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2007-05-21 |
Time |
15:46 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2007-05-21 |
Time |
15:39 |
Sent To |
|
|
Notes |
2007-05-21 15:45:54 | 1. NOTE # 2 ON PAGE FP-1 IS INCORRECT. "STANDPIPE | | SYSTEM SHALL COMPLY WITH NFPA 24". SHOULD READ | | STANDPIPE SYSTEM SHALL COMPLY WITH NFPA 14. | | | | 2. PARKING GARAGE FIRE SPRINKLER SYSTEM TO COMPLY WITH | | NFPA 13. | | | | 3. ANY FIRE SPRINKLER HEADS DUE TO THEIR INSTALLATION | | HEIGHT OR INSTALLED IN AN AREA WHERE THEY ARE SUBJECT | | TO MECHANICAL DAMAGE SHALL BE PROVIDED WITH HEAD | | GUARDS. | | | | 4. NOTE # 3 ON PAGE FP-2 IS NOT COMPLETE. | | | | 5. THE ENTIRE FIRE SPRINKLER SYSTEM SHALL BE INSTALLED | | IN AN APPROVED AND WORKMANSHIP MANNER. | | | | 6. FIRE SPRINKLER SYSTEM SUBJECT TO FIELD INSPECTION | | AND APPROVAL. | | | | 7. SPEC BOOKS DO NOT DECLARE ANY UL LISTING FOR THE 120 | | GALLON DIESEL FUEL TANK BEING PROPOSED. PLEASE PROVIDE | | LISTING INFORMATION. | | | | APPROVED PROVISO: | | | | MIKE CARSILLO, BATTALION CHIEF OF FIRE PREVENTION | | 804-4709 PHONE | | 804-4774 FAX |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2007-04-12 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2007-04-12 |
Time |
08:33 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2007-04-12 |
Time |
08:33 |
Sent To |
|
|
Notes |
2007-04-12 08:45:02 | 1. ENTIRE PARKING GARAGE IS TO BE COMPLETELY FIRE | | SPRINKLER PROTECTED EXCEPT FOR THE FPL VAULT. | | | | 2. THE FIRST FLOOR MECHANICAL ROOM MUST ALSO BE FIRE | | SPRINKLER PROTECTED. PLANS DO NOT ILLUSTRATE FIRE | | SPRINKLER HEADS IN THIS ROOM OR ELECTRICAL ROOM B1.111. | | PRE-ACTION FIRE SPRINKLER SYSTEM NOTED TO BE PLANNED IN | | THE MAIN ELECTRICAL ROOM ACCORDING TO THE NOTES. | | | | 3. STANDPIPE SYSTEM FIRE HOSE VALVES SHALL BE EQUIPPED | | WITH 2 1/2 TO 1 1/2 REDUCERS. | | | | 4. SPARE SPRINKLER HEADS AND A WRENCH SHALL BE PROVIDED | | FOR THE FIRE SPRINKLER SYSTEM. | | | | 5. FIRE DEPARTMENT CONNECTIONS SHALL BE PROVIDED WITH | | KNOX-BOX LOCKING CAPRS. | | | | 6. FIRE SPRINKLER SYSTEM TO BE INSTALLED IN ACCORDANCE | | WITH NFPA 13. | | | | 7. STANDPIPE SYSTEM SHALL BE INSTALLED IN ACCORDANCE | | WITH NFPA 14. | | | | 8. FIRE PUMP TO BE INSTALLED IN ACCORDANCE WITH NFPA | | 20. | | | | 9. FIRE SPRINKLER HEADS THAT ARE INSTALLED OUTSIDE | | SHALL BE WAX COATED OR CORROSION RESISTANT. | | | | 10. CUT SHEETS NEEDED FOR THE FIRE PUMP, BACKFLOW | | PREVENTION DEVICE, FIRE SPRINKLER HEADS, AND ALL OTHER | | APPURTENANT EQUIPMENT. | | | | 11. TEMPORARY STANDPIPE SYSTEMS SHALL BE REQUIRED WHEN | | EACH BUILDING REACHES THREE STORIES OR THIRTY FEET IN | | HEIGHT. | | | | MIKE CARSILLO, BATTALION CHIEF OF FIRE PREVENTION | | 804-4709 PHONE | | 804-4774 FAX |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2007-05-10 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-05-10 |
Time |
16:35 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-05-10 |
Time |
16:35 |
Sent To |
FIRE |
|
Notes |
2007-05-10 16:35:37 | TO "F" BOX/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2007-04-12 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2007-04-12 |
Time |
13:55 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2007-03-24 |
Time |
16:34 |
Sent To |
|
|
Notes |
2007-03-24 16:34:09 | TO "F" BOX |
|
|
|