Plan Review Details - Permit 07030768
Plan Review Stops For Permit 07030768
Review Stop G GAS REVIEW
Rev No 3 Status P Date 2007-06-12 Cont ID  
Sent By mperson Date 2007-06-12 Time 10:01 Rev Time 0.33
Received By mperson Date 2007-06-12 Time 10:01 Sent To PC
Notes
2007-06-12 10:06:59REVISION: CHANGE DELIVERY PRESSURE FROM 0.5 PSI TO 2
 PSI AND PIPE SIZE.
  
 NOTE: POOL PERMIT APPROVED ON POOL PERMIT #06090554.
  
 ****************PROVISO***************
 A} PER FBC-2004 FUEL GAS, SECTION 409.4 MP REGULATOR
 VALVES: A LISTED SHUTOFF VALVE SHALL BE INSTALLED
 IMMEDIATELY AHEAD OF EACH MP REGULATOR.

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2007-04-25 Cont ID  
Sent By mperson Date 2007-04-25 Time 14:02 Rev Time 0.45
Received By mperson Date 2007-04-25 Time 14:02 Sent To PC
Notes
2007-04-25 14:04:58NOTE: POOL HEATER APPROVED ON POOL PERMIT #06090554

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-04-05 Cont ID  
Sent By mperson Date 2007-04-05 Time 10:22 Rev Time 0.33
Received By mperson Date 2007-04-05 Time 10:22 Sent To PC
Notes
2007-04-05 10:47:37DENIED
 REFERENCE:
 ** FBC-2004 FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
  
 MORE INFORMATION REQUIRED ON GAS ISOMETRIC FOR GAS PLAN
 REVIEW TO MEET CODE COMPLIANCE:
  
 1.SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 NOTE: THIS INCLUDES THE EXISTING GAS SYSTEM AS WELL AS
 THE PROPOSED GAS SYSTEM. CLEARLY INDICATE ON THE
 RESUBMITTED DRAWING THE EXISTING AND THE NEW PIPING.
 PLEASE REFERENCE THE ATTACHED PERMIT INFORMATION TO THE
 GAS COMMENTS INDICATING SAID ADDRESS HAS EXISTING GAS
 APPLIANCES.
  
 2.SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 NOTE: THIS INCLUDES THE EXISTING AS WELL AS THE
 PROPOSED.
  
 3.BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 NOTE: THIS INCLUDES THE EXISTING AS WELL AS THE
 PROPOSED.
  
 4.SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 5.INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 6.FBC-2004 CHAPTER 1,SECTION 106.3.4.2:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME, AND ALSO DATE DRAWING. PLEASE DO
 THIS PRIOR TO RESUBMITTING.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: PLEASE REFERENCE THE CITY OF WEST PALM BEACH GAS
 PERMIT APPLICATION REQUIREMENTS ATTACHED TO THE GAS
 COMMENTS FOR FUTURE PERMIT APPLICATIONS.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-06-04 Cont ID  
Sent By adarroug Date 2007-06-04 Time 11:40 Rev Time 0.00
Received By adarroug Date 2007-06-04 Time 11:40 Sent To G
Notes
2007-06-04 11:40:46TO "G" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-04-13 Cont ID  
Sent By adarroug Date 2007-04-13 Time 15:20 Rev Time 0.00
Received By adarroug Date 2007-04-13 Time 15:20 Sent To G
Notes
2007-04-13 15:21:03TO "G" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-04-05 Cont ID  
Sent By mperson Date 2007-04-05 Time 10:48 Rev Time 0.00
Received By mperson Date 2007-03-23 Time 11:15 Sent To  
Notes
2007-03-23 11:15:49TO "G" BOX