Plan Review Details - Permit 07030642
Plan Review Stops For Permit 07030642
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-08-17 Cont ID  
Sent By shill Date 2007-08-17 Time 17:28 Rev Time 0.00
Received By shill Date 2007-08-17 Time 17:28 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-05-07 Cont ID  
Sent By shill Date 2007-05-07 Time 14:57 Rev Time 0.00
Received By shill Date 2007-08-17 Time 17:28 Sent To  
Notes
2007-05-07 14:56:47****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED
 FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED,DATED
 ORIGINALS FS471.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-04-19 Cont ID  
Sent By shill Date 2007-04-19 Time 18:03 Rev Time 0.00
Received By shill Date 2007-04-19 Time 18:03 Sent To  
Notes
2007-04-19 18:04:21****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
  
 1.)PROVIDE ANCHORING INFORMATION TO
 COMPLY WITH FBC1609.1.3, FBC R310; STRUCTURAL
 MEMBERS AND SYSTEMS, AND COMPONENTS AND CLADDING IN A
 BUILDING OR STRUCTURE SHALL BE ANCHORED TO RESIST
 WIND-INDUCED OVERTURNING, UPLIFT AND SLIDING AND TO
 PROVIDE CONTINUOUS LOAD PATHS FOR THESE FORCES TO THE
 FOUNDATION.WHERE A PORTION OF THE RESISTANCE TO THESE
 FORCES IS PROVIDED BY DEAD LOAD, THE MINIMUM DEAD LOAD
 LIKELY TO BE IN PLACE DURING A DESIGN WIND EVENT SHALL
 BE USED.
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-08-13 Cont ID  
Sent By btrobaug Date 2007-08-13 Time 15:00 Rev Time 0.00
Received By btrobaug Date 2007-08-13 Time 14:37 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-05-07 Cont ID  
Sent By btrobaug Date 2007-05-07 Time 11:50 Rev Time 0.50
Received By btrobaug Date 2007-05-07 Time 11:03 Sent To M
Notes
2007-05-07 11:50:12 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE 3/0 CONDUCTORS FROM THE GENERATORS 300 AMP
 BREAKER DO NOT COMPLY WITH 310.16. THEY NEED TO BE 300
 MCM MINIMUM. ALSO THOSE FEEDER CONDUCTORS WOULD BE
 REQUIRED THE ENTIRE LENGTH OF THE GENERATOR FEED TO THE
 200 AMP INDOOR PANEL IF THE CURRENT IS NOT LIMITED TO
 200 AMPS AT THE GENERATOR OR THE 300 AMP DISCONNECT
 SHOWN OUTSIDE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-03-28 Cont ID  
Sent By btrobaug Date 2007-03-28 Time 07:38 Rev Time 0.33
Received By btrobaug Date 2007-03-28 Time 07:04 Sent To M
Notes
2007-03-28 07:37:10 
  
 DENIED/INCOMPLETE INFORMATION
  
 1}PROVIDE SPECIFICATIONS FOR THE TRANSFER SWITCH. AS
 FIRST MEANS OF DISCONNECT IT MUST BE SERVICE RATED,
 CAPABLE OF DISCONNECTING ALL SOURCES OF POWER AND HAVE
 AN AIC RATING FOR THE SERVICE.
  
 2} PLEASE SUBMIT A SITE PLAN AND LOCATE ALL
 THE SERVICE AND GENERATOR GEAR ON SAME
 SO THAT COMPLIANCE WITH
 230.72(GROUPING), 225.31-39 FOR THE
 DISCONNECTING MEANS REQUIREMENTS AND
 250.32 FOR GROUNDING CAN BE REVIEWED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2007-04-10 Cont ID  
Sent By mperson Date 2007-04-10 Time 15:19 Rev Time 0.55
Received By mperson Date 2007-04-10 Time 15:19 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-08-06 Cont ID  
Sent By adarroug Date 2007-08-06 Time 18:39 Rev Time 0.00
Received By adarroug Date 2007-08-06 Time 18:39 Sent To E
Notes
2007-08-06 18:39:52TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-05-04 Cont ID  
Sent By adarroug Date 2007-05-04 Time 14:48 Rev Time 0.00
Received By adarroug Date 2007-05-04 Time 14:35 Sent To E
Notes
2007-05-04 14:48:50TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-05-02 Cont ID  
Sent By adarroug Date 2007-05-02 Time 11:24 Rev Time 0.00
Received By adarroug Date 2007-05-02 Time 11:24 Sent To Z
Notes
2007-05-02 11:24:51TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-04-19 Cont ID  
Sent By shill Date 2007-04-19 Time 18:04 Rev Time 0.00
Received By shill Date 2007-03-24 Time 13:21 Sent To  
Notes
2007-03-24 13:22:12TO "GEN-RES" "E"

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-05-07 Cont ID  
Sent By tgordon Date 2007-05-07 Time 14:42 Rev Time 0.20
Received By tgordon Date 2007-05-07 Time 14:42 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2007-03-29 Cont ID  
Sent By tgordon Date 2007-03-29 Time 08:06 Rev Time 0.20
Received By tgordon Date 2007-03-29 Time 08:06 Sent To G
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2007-05-02 Cont ID  
Sent By adavila Date 2007-05-02 Time 14:42 Rev Time 0.00
Received By adavila Date 2007-05-02 Time 14:42 Sent To I
Notes
2007-05-02 14:42:43PER ERIC SCHNEIDER, PRINCIPAL PLANNER.

Review Stop Z ZONING
Rev No 1 Status P Date 2007-03-22 Cont ID  
Sent By adavila Date 2007-03-22 Time 11:10 Rev Time 0.00
Received By adavila Date 2007-03-22 Time 10:13 Sent To I
Notes
2007-03-22 11:10:26PER ERIC SCHNEIDER, PRINCIPAL PLANNER.