Plan Review Details - Permit 07030592
Plan Review Stops For Permit 07030592
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2008-01-23 Cont ID  
Sent By jwitmer Date 2008-01-23 Time 16:32 Rev Time 55.00
Received By jwitmer Date 2008-01-23 Time 16:32 Sent To PC
Notes
2008-01-23 16:41:52SUBMITTALS:
 TOWER # 6 CAST IN PLACE ROOF SLAB SHORING INSPECTION
 REPORT
 STAIR TOWER# 1 4-5, 5-6 STAIR SHORING LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 19 Status P Date 2008-04-23 Cont ID  
Sent By jwitmer Date 2008-04-23 Time 16:14 Rev Time 1.22
Received By jwitmer Date 2008-04-23 Time 16:14 Sent To  
Notes
2008-04-23 16:15:01REVISION# 2 3/21/08 REMOVAL OF PARKING CONTROL SYSTEM

Review Stop B BUILDING (STRUCTURAL)
Rev No 18 Status P Date 2008-04-03 Cont ID  
Sent By jwitmer Date 2008-04-03 Time 14:24 Rev Time 0.77
Received By jwitmer Date 2008-04-03 Time 14:24 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 17 Status P Date 2008-03-10 Cont ID  
Sent By jwitmer Date 2008-03-10 Time 13:20 Rev Time 0.55
Received By jwitmer Date 2008-03-10 Time 13:20 Sent To PC
Notes
2008-03-10 13:21:26REVISION: YKK AP STOREFRONT FL 5845

Review Stop B BUILDING (STRUCTURAL)
Rev No 16 Status P Date 2008-03-10 Cont ID  
Sent By jwitmer Date 2008-03-10 Time 13:09 Rev Time 0.55
Received By jwitmer Date 2008-03-10 Time 13:09 Sent To PC
Notes
2008-03-10 13:10:46STAIR TOWER # 3 & 6, AREA OF REFUGE SHORING PLAN

Review Stop B BUILDING (STRUCTURAL)
Rev No 15 Status F Date 2008-01-23 Cont ID  
Sent By jwitmer Date 2008-01-23 Time 16:22 Rev Time 0.77
Received By jwitmer Date 2008-01-23 Time 16:22 Sent To PC
Notes
2008-01-23 16:29:22BUILDING PLAN REVIEW
 PERMIT: 07030592
 ADD: 505 BANYAN BLVD
 CONT: THE WEITZ CO
 TEL: (561)722-8837
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVISIONREVIEW
 ACTION: DENIED
  
 1)THRESHOLD BUILDING THREE SETS OF ALL DOCUMENTS ARE
 REQUIRED. 106.1.2
  
 2)PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO
 COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE
 APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER
 SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL,
 SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR
 SITE SPECIFIC FORM PER RULE 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG 2004 FBC - FL 5845
  
 3)WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 PLEASE PROVIDE TECHNICAL SHEETS.PLEASE HIGHLIGHT
 WHIGH TYPE OF GLAZING WILL BE INSTALLED WITH ASSOCIATED
 PRESSURES.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 14 Status P Date 2008-01-23 Cont ID  
Sent By jwitmer Date 2008-01-23 Time 16:10 Rev Time 0.77
Received By jwitmer Date 2008-01-23 Time 16:10 Sent To PC
Notes
2008-01-23 16:13:01REVISIONS:
 SKETCH SSK-301-14-08
 A4.0.0 DETAIL # 301-15-08
 A5.7.6 DETAIL# 501-15-08

Review Stop B BUILDING (STRUCTURAL)
Rev No 13 Status P Date 2007-12-26 Cont ID  
Sent By jwitmer Date 2007-12-26 Time 10:20 Rev Time 0.77
Received By jwitmer Date 2007-12-26 Time 10:20 Sent To  
Notes
2007-12-26 10:43:0707030592:
 TOWER# 2 5TH & 6TH LEVEL STAIR INSPECTION REPORTS
 TOWER# 1 LOBBY SLAB LEVEL 5TH & 6TH SHORING
 INSPECTION REPORT
 TOWER# 5 LEVELS LEVELS 5TH & 6TH STAIR SHORING
 INSPECTIONSREPORT
 TOWER# 3, ROOF SLABAREA OF REFUGE SHORING INSPECTION
 REPORT
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 12 Status P Date 2007-11-20 Cont ID  
Sent By jwitmer Date 2007-11-20 Time 15:34 Rev Time 0.77
Received By jwitmer Date 2007-11-20 Time 15:34 Sent To  
Notes
2007-11-20 15:49:17SUBMITTAL: STAIR TOWER# 2 STAIR SHORING LEVEL 4-5
 STAIR TOWER# 3 STAIR SHORING LEVEL 5-6
 STAIR TOWER# 4 STAIR SHORING LEVEL 5-6
 STAIR TOWER# 5 STAIR SHORING LEVEL 4-5
 STAIR TOWER# 6 STAIR SHORING LEVEL 5-6
 ELEVATED SLAB @ 5TH & 6TH LEVEL TOWER#
 2.

Review Stop B BUILDING (STRUCTURAL)
Rev No 11 Status P Date 2007-11-13 Cont ID  
Sent By jwitmer Date 2007-11-13 Time 16:28 Rev Time 1.11
Received By jwitmer Date 2007-11-13 Time 16:28 Sent To PC
Notes
2007-11-13 16:29:34CAST IN PLACE STAIR AND LANDINGS SHORING DRAWINGS. 0K

Review Stop B BUILDING (STRUCTURAL)
Rev No 10 Status P Date 2007-10-30 Cont ID  
Sent By jwitmer Date 2007-10-30 Time 08:24 Rev Time 0.55
Received By jwitmer Date 2007-10-30 Time 08:24 Sent To PC
Notes
2007-10-30 08:32:16SUBMITTALS: SHORING LETTERS
 STAIR TOWER 2 & 3 ROOF SLAB.
 STAIR TOWER 4 & 5 5TH FLOOR
 STAIR TOWER 5 4TH # 5TH FLOORS
 STAIR TOWER# 6 4TH & 5TH FLOORS
 ELEVATED CAST IN PLACE SHORING DRAWINGS

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status P Date 2007-09-28 Cont ID  
Sent By jwitmer Date 2007-09-28 Time 07:35 Rev Time 1.22
Received By jwitmer Date 2007-09-28 Time 07:35 Sent To PC
Notes
2007-09-28 07:53:14505 BANYAN BLVD
 TOWERS 3& 4 ROOF SLAB SHORING INSPECTION REPORTS HECTOR
 F. VERGARA P.E.
 TOWER # 5 ROOF SLAB INSPECTION REPORT HECTOR F. VERGARA
 P.E.
 TOWER # 6 ROOF SLAB SHORING DRAWINGSHECTOR F. VERGARA
 P.E.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2007-09-17 Cont ID  
Sent By jwitmer Date 2007-09-17 Time 07:59 Rev Time 0.55
Received By jwitmer Date 2007-09-17 Time 07:59 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2007-09-17 Cont ID  
Sent By jwitmer Date 2007-09-17 Time 07:51 Rev Time 0.55
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2007-08-03 Cont ID  
Sent By jwitmer Date 2007-08-03 Time 11:36 Rev Time 0.55
Received By jwitmer Date 2007-08-03 Time 11:36 Sent To PC
Notes
2007-08-03 11:42:40 
 *** ISSUED PERMIT***
 -PLAN REVIEW HISTORY-
  
 PERMIT#07030592
 ADDRESS: 505 BANYAN BLVD
 CONT: THE WEITZ CO
 TELL # (561) 722-8837
  
 THE ATTACHED COMMENTS ARE PART OF THE
 PERMIT AND PLAN REVIEW PACKAGE AND ARE
 NOT TO BE REMOVED FROM THE ISSUED SET
 OF PLANS.106.1.1 ADMINISTRATIVE CODE/ 06.
  
 BUILDING PROVISOS, ITEMS 1& 2 SHALL SUBMIT INFORMATION
 WITHIN 30DAYS OR THE PERMIT SHALL BE REVOKED:
  
 1)LIGHT POLE PROVISO, TO BE REVIEWED BY THE DESIGNER
 OF RECORD BEFORE SUBMITTAL TO THE BUILDING
 DEPARTMENT..
  
 2)THE ARCHITECTURAL SHEETS & STRUCTURAL SHEETS SHALL
 PROVIDE DETAILS FOR SLAB & ANCHOR REQUIREMENT PLEASE
 PROVIDE SIZE OF LP GAS TANK (WXL),PLUS PROVIDE PLANS
 WITH THE INFORMATION DEPICTING HOLD DOWN BRACKETS, TYPE
 OF FASTENER, AND THE MINIMUM EDGE DISTANCE THE DEVICE
 REQUIRES WITHOUT LOAD REDUCTION.SECOND, PROVIDE
 INFORMATION ON THE SLAB, THICKNESS, WIDTH AND LENGTH,
 IF WIRE MESH, FIBER MESH OR IF STEEL REBAR WILL BE
 USED. THE NEW SLAB AND HOLD DOWN DETAILS: 104.2.1*
 ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN.2004 FL. BLDG CODE 1603.1.4 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE SHOWN ON THE
 CONSTRUCTION DRAWINGS:
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING CATEGORY
 3)- WIND EXPOSURE
 4)- COMPONENTS & CLADDING, THE DESIGN WIND PRESSURES IN
 TERMS OF PSF.
  
 NOTE INFORMATIONAL ONLY:
  
 3) 109.3.10* IMPACT OF CONSTRUCTION. ALL CONSTRUCTION
 ACTIVITY REGULATED BY THIS CODE SHALL BE PERFORMED IN A
 MANNER SO AS NOT TO ADVERSELY IMPACT THE CONDITION OF
 ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS PERMITTED TO
 AFFECT SAID PROPERTY PURSUANT TO A CONSENT BY
 THE APPLICABLE PROPERTY OWNER, UNDER TERMS & CONDITIONS
 AGREEABLE TO THE APPLICABLE PROPERTY OWNER.
 THIS INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF
 DUST, NOISE, WATER OR DRAINAGE RUN-OFF,
 DEBRIS, AND THE STORAGE OF CONSTRUCTION MATERIALS. NEW
 CONSTRUCTION ACTIVITY SHALL NOT ADVERSELY IMPACT
 HISTORIC SURFACE WATER DRAINAGE FLOWS SERVING ADJACENT
 PROPERTIES, & MAY REQUIRE SPECIAL DRAINAGE DESIGN
 COMPLYING WITH ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY,
 DEVELOPERS, CONTRACTORS, AND OWNERS OF ALL NEW
 RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ
 FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPONCOMPLETION OF THE IMPROVEMENT, A
 CERTIFICATE FROM A LICENSED ENGINEER SHALL BE SUBMITTED
 TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL OF THE
 FINAL INSPECTION.
  
 4) 109.3.10.1 HURRICANE PROTECTION. IT SHALL BE
 UNLAWFUL FOR ANY PERSON TO ALLOWCONSTRUCTION RELATED
 MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24 HRS.
 AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS SHALL BE
 EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN
 SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY
 PERSONS WHO FAILS TO COMPLY TO REMOVE OR SECURE THE
 CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS WITHIN 24
 HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED SHALL BE
 SUBJECT TO A FINE NOT TO EXCEED $500.00. IN ADDITION
 TO THE ABOVE, A LICENSED CONTRACTOR WHO VIOLATES THIS
 SECTION SHALL BE SUBJECT TO DISCIPLINE PURSUANT TO
 SECTION 113 OF THIS CHAPTER.
  
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2007-07-30 Cont ID  
Sent By jwitmer Date 2007-07-30 Time 13:22 Rev Time 0.33
Received By jwitmer Date 2007-07-30 Time 13:22 Sent To PC
Notes
2007-07-30 13:26:30BUILDING PLAN REVIEW
 PERMIT: 07030592
 ADD: 505 BANYAN BLVD
 CONT: THE WEITZ CO
 TEL: (561)722-8837 KEITH VAN DRUFF
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) SHORING OR SHOP DRAWINGS SHALL BE REVIEWED BY THE
 DESIGNER OF RECORD AND HAVE THEIR SHOP DRAWING STAMP
 AFFIXED.
  
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2007-07-30 Cont ID  
Sent By jwitmer Date 2007-07-30 Time 13:09 Rev Time 2.22
Received By jwitmer Date 2007-07-30 Time 11:06 Sent To  
Notes
2007-07-30 13:15:12BUILDING PLAN REVIEW
 PERMIT: 07030592
 ADD: 505 BANYAN BLVD
 CONT: THE WEITZ CO
 TEL: (561)722-8837
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 4THREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) LIGHT POLE PROVISO, REMOVED. CALCULATIONS WERE
 SUBMITTED THIS REVIEWWITHOUT THE REVIEW OF THE
 DESIGNER OF RECORD.
  
 3) THE ELECTRICAL SHEET E2.11 NOW SHOWS A NEW 500 ABOVE
 GROUND LP GAS TANK. THE ARCHITECTURAL SHEETS NOR THE
 STRUCTURAL SHEETS PROVIDE ANY DETAILS. PLEASE PROVIDE
 THE SLAB & ANCHOR REQUIREMENT PLEASE PROVIDE SIZE OF LP
 GAS TANK (WXL),
 PLUS PROVIDE PLANS WITH THE INFORMATION
 DEPICTING HOLD DOWN BRACKETS, TYPE OF
 FASTENER, AND THE MINIMUM EDGE DISTANCE
 THE DEVICE REQUIRES WITHOUT LOAD
 REDUCTION.
 SECOND, PROVIDE INFORMATION ON THE
 SLAB, THICKNESS, WIDTH AND LENGTH, IF
 WIREMESH, FIBER MESH OR IF STEEL REBAR
 WILL BEUSED.
 THE NEW SLAB AND HOLD DOWN DETAILS:
 104.2.1* ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN.
  
 4)2004 FL. BLD CODE 1603.1.4 THE
 FOLLOWING INFORMATION RELATED TO WIND
 SHALL BE SHOWN ON THE CONSTRUCTION
 DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-07-03 Cont ID  
Sent By jwitmer Date 2007-07-03 Time 12:31 Rev Time 0.77
Received By jwitmer Date 2007-07-03 Time 12:31 Sent To  
Notes
2007-07-03 12:49:26BUILDING PROVISO:
 1) ROOFING TO BE PULLED AND UNDER A SEPERATE PERMIT
 FEES AND REVIEW.
 2) LIGHT POLES ON ROOD DECK TO BE DESIGNED UNDER THE
 ASCE 7-02 WILL BE GIVEN 30 DAYS TO UPDATE CALCS AND
 SUBMIT TO THE CITY.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-06-28 Cont ID  
Sent By jwitmer Date 2007-06-28 Time 16:48 Rev Time 3.33
Received By jwitmer Date 2007-06-30 Time 11:45 Sent To  
Notes
2007-06-28 16:50:46BUILDING PLAN REVIEW
 PERMIT: 07030592
 ADD: 505 BANYAN BLVD
 CONT: THE WEITZ CO
 TEL: (561)722-8837
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 2NDREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) COMPLIED.
  
 3) 2ND REQUEST, FOR THE THRESHOLD INSPECTOR TO SIGN AN
 ORIGINAL AGREEMENT, NOT A PHOT-COPY, HAROLD PISKURA HAS
 PUT A LOCK ON THE PERMIT UNTIL THIS MATTER IS RESOLVED.
 WPB AMENDMENT 105.13.6. W.P.B. CONSTRUCTION SERVICES
 DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL
 INSPECTOR AS REQUIRED BY S.
 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS
 REQUIRED BY THIS CODE. CONTACT HAROLD PISKURA MANAGER
 OF THE SPECIAL INSPECTOR PROGRAM AT (561)
 805-6711 FOR FURTHER INFORMATION BEFORE THE PERMIT MAY
 BE ISSUED.
  
 4-6) COMPLIED.
  
 7) PARTIALLY COMPLIED, FL BLD CODE 1609.1.4:
 COMPONENTS & CLADDING, PROVIDE 2 COPIES(3 IF THRESHOLD
 OR RESIDENT INSPECTOR) OF PRODUCT TESTING REPORTS
 ,I(NCOMPLETE) REPORTS ARE AS FOLLOWS:
 ROOFING ASSEMBLIES, JOHN MANVILLE MODIFIED BITUMEN
 OVER CONCRETE ,
 THIS ROOF IS MISSING OR NOT IN COMPLIANCE WITH THE
 FOLLOW ITEMS:
 ___ CONTRACTOR DID NOT PROVIDE THE MEAN ROOF HEIGHT.
  
 ___ CONTRACTOR DID NOT INDICATE THE ROOF PITCH.
  
 _XX__ CONTRACTOR FAILED TO INDICATE WHICH SYSTEM TO BE
 USED.
  
 _XX__ THE SYSTEM PROVIDED HAS A LOWPRESSURE FOR ZONE
 _2&3__ .
  
 _XX__ THE SYSTEM PROVIDED STATESLIMITATION# 7,
 SHOULD THE FASTENER RESISTANCE BE LESS THAN THAT
 REQUIRED, AS DETERMINED BY THEBUILDING OFFICIAL, A
 REVISED
 FASTENER SPACING, PREPARED , SIGNED AND SEALED BY A
 FLORIDA REGISTERED PROFESSIONAL ENGINEER, REGISTERED
 ARCHITECT OR REGISTERED ROOF CONSULTANT MAY BE
 SUBMITTED.
  
 ___THE SYSTEM PROVIDED INDICATESLIMITATION# 9, NO
 ENHANCEDFASTENING ALLOWED.
  
 8) COMPLIED.
  
 9) SECOND REQUEST," JOHN MANVILLE MODIFIED BITUMEN"
 PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 10-11) COMPLIED.
  
 12) NEW COMMENT, SUBMITTAL FOR ALUMINUM LIGHT POLE FOR
 TOP OF ROOF DECK DESIGN BY HAPCO ALUMINUM LIGHT POLES
 DESIGNED TO THE ASCE 7-98
 NOT THE CURRENT ASCE 7-02. PLEASE SEE SUBMITTALS, ONLY
 TWO SEALED DOCUMENTS WERE LOCATED, REQUIRES THREE.
  
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-04-11 Cont ID  
Sent By jwitmer Date 2007-04-11 Time 14:31 Rev Time 6.66
Received By jwitmer Date 2007-04-11 Time 14:31 Sent To FIRE
Notes
2007-04-11 16:12:55BUILDING PLAN REVIEW
 PERMIT: 07030592
 ADD: 505 BANYAN BLVD
 CONT: THE WEITZ CO
 TEL: (561)722-8837
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)FL S. S. 553.71(7) " THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN
 HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPAN
 CY CLASSIFICATION AS DEINED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS
 5,000 SQ FT IN AREA AND AN OCCUPANT
 CONTENT OF GREATER THAN 500 PERSONS.
 105.13.1 THE ENFORCING AGENCY SHALL
 REQUIRE A SPECIAL INSPECTOR TO PERFORM
 STRUCTURAL INSPECTIONS ON A THRESHOLD
 BUILDING PURSUANT TO A STRUCTURAL
 INSPECTION PLAN PREPARED BY THE
 ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE
 ENFORCING AGENCY PRIOR TO THE ISSUANCE
 OF A BUILDING PERMIT FOR THE
 CONSTRUCTION OF A THRESHOLD BUILDING.
 THE PURPOSE OF THE STRUCTURL INSPECTION
 PLAN IS TO PROVIDE SPECIFIC INSPECTION
 PROCEDURES AND SCHEDULES SO THAT THE
 BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 3)WPB AMENDMENT 105.13.6. W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A
 SPECIAL INSPECTOR AS REQUIRED BY S.
 553.79(5) FLORIDA STATUTES TO THE MIN-
 IMUM INSPECTIONS REQUIRED BY THIS CODE.
 CONTACT HAROLD PISKURA MANAGER OF THE
 SPECIAL INSPECTOR PROGRAM AT (561)
 805-6711 FOR FURTHER INFORMATION BEFORE
 THE PERMIT MAY BE ISSUED.
  
 4)W.P.B. AMENDMENT 105.13.4.4 ALL
 PLANS FOR THE BUILDING WHICH ARE
 REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CON-
 TAIN A STATEMENT THAT, TO THE BEST OF
 THE ARCHITECT'S PR ENGINEER'S KNOWLEDGE,
 THE PLANS AND SPECIFICATIONS COMPLY WITH
 THE APPLICABLE FIRE-SAFETY STANDARDS AS
 DETERMINED BY THE LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 5) SHEET LS!.0.0
  
 5A) APPLICABLE CODES PLANS SUBMITTED AFTER DEC.8/ 2006
 SHALL REVIEWED UNDER THE 2004 BASE FBC WITH 2006
 AMENDMENTS.
  
 5B) BUILDING TYPE & FIRE RESISTANCE, NOTE # 1 USES
 TABLE 600 AS A REFRENCE, THIS IS FROM THE FBC 2001
 CODE, PLEASE CORRECT.
  
 5C) BUILDING TYPE & FIRE RESISTANCE, NOTE # 3, USES A
 CODE SECTION TABLE 705.2.1 IN REFRENCE TO SHAFTS, THIS
 ALSO IS A REFRENCE TO THE 2001 FBC BASE CODE, PLEASE
 CORRECT.
  
 5D)PLANS INDICATE THE OPEN AREA CALCULATIONS LISTED
 UNDER 406.3.3.1.PLEASE PROVIDE THE INTERIOR WALL PER
 CENTAGES OF OPEN AREAS WITH UNIFORMLY DISTRIBUTED
 OPENINGS.
  
 5E) OCCUPANCY CLASSIFICATION: PLANS INDICATE A MIXED
 USE BUILDING, S2, OFFICE AND INDUSTRIAL USAGE.
 PLANS ALSO INDICATE BELOW THE AREA OF REFUGE THIS
 BUILDING IS NOT FIRE SPRINKLERED!
 2004 EXISTING BUILDING CODE CHAPTER NINE
 ADDITIONS 901.2 CREATION OREXTENTION OF
 NONCONFORMITY. AN ADDITION SHALL NOT CREATE OR EXTEND
 ANY NONCONFORMITY IN THE EXISTING BUILDING TO WHICH THE
 ADDITION IS BEING MADE WITH
 REGARDS TO ACCESSIBILITY, STRUCTURAL STRENGTH,
 FIRE SAFETY, MEANS OF EGRESS, OR THE CAPACITY OF
 MECHANICAL, PLUMBING, OR ELECTRICAL SYSTEMS.
  
 LS1.0.0 CLEARLY INDICATES THIS IS A MIXED USE
 BUILDING AND NOT ONLY TO BE USED FOR S-2 OPEN AIR
 PARKING. SINCE THIS IS A MIXED USE BUILDING OVER THREE
 STORIES THE EXEMPTION FOUND UNDER 903.6(2) ELIMINATING
 THE FIRE SPRINKLERS NO
 LONGER STANDS.
 SINGLE USE 406.3.5.1
 WHEN THE OPEN PARKING GARAGE IS USED EXCLUSIVELY
 FOR THE PARKING OR STORAGE OF PRIVATE MOTOR VEHICLES,
 WITH NO OTHER USES IN THE BUILDING, THE AREA AND HEIGHT
 SHALL BE PERMITTED TO COMPLY WITH TABLE 406.3.5 , ALONG
 WITH
 INCREASES ALLOWED BY SECTION 406.3.6 .
 EXCEPTION: THE GRADE-LEVEL TIER IS PERMITTED TO
 CONTAIN AN OFFICE, WAITING AND TOILET ROOMS HAVING A
 TOTAL COMBINED AREA OF NOT MORE THAN 1,000 SQUARE FEET
 (93 M 2 ). SUCH AREA NEED NOT BE SEPARATED FROM THE
 OPEN PARKING
 GARAGE.
 THE OFFICE AREA ON THE FIRST FLOOR IS 1,425 SQ
 FT.
 903.6.1
 ANY BUILDING WHICH IS OF THREE STORIES OR MORE IN
 HEIGHT SHALL BE EQUIPPED WITH AN APPROVED AUTOMATIC
 SPRINKLER SYSTEM INSTALLED IN ACCORDANCE WITH SECTION
 903.1 .
 EXCEPTIONS:
 (2)A STAND-ALONE PARKING GARAGE CONSTRUCTED
 WITH NONCOMBUSTIBLE MATERIALS, THE DESIGN OF WHICH IS
 SUCH THAT ALL LEVELS OF THE GARAGE ARE UNIFORMLY OPEN
 TO THE ATMOSPHERE ON ALL SIDES WITH THE PERCENTAGES OF
 OPENINGS
 EQUAL TO OR GREATER THAN THOSE SPECIFIED IN SECTION
 406.3 . SUCH GARAGES SHALL BE SEPARATED FROM ANY OTHER
 STRUCTURE BY NOT LESS THAN 20 FEET (6096 MM). A
 STAND-ALONE PARKING GARAGE IS ONE THAT IS SOLELY FOR
 THE PARKING OF
 VEHICLES AND DOES NOT HAVE ANY OTHER OCCUPANCY
 GROUP IN THE BUILDING.
 THIS BUILDING SHALL REQUIRE FIRE SPRINKLERS
 903.6.1.
 ANY BUILDING WHICH IS OF THREE STORIES OR MORE IN
 HEIGHT SHALL BE EQUIPPED WITH AN APPROVED AUTOMATIC
 SPRINKLER SYSTEM INSTALLED IN ACCORDANCE WITH SECTION
 903.1 .
  
 6)FP1.00 NOTE# 1 INDICATES FIRE SPRINKLER HEADS TO
 BE INSTALLED IN ACCORDANCE WITH NFPA 14, THIS IS FOR
 STAND PIPES, NFPA 13 IS FOR FIRE SPRIKLERS.
  
 7)FL BLD CODE 1609.1.4: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT
 INSPECTOR) OF PRODUCT
 TESTING REPORTS, MISSING REPORTS ARE AS FOLLOWS:
 7A) WINDOWS
 7B) EXTERIOR HOLLOW METAL DOORS
 7C) LOUVERS
 7D) ROOFING ASSEMBLIES
  
 8)WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 9)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 10)A.8.0.0 THE DOOR SCHEDULEINDICATES THE USE OF
 GLAZED PANELS IN THE 1 1/2 HR RATED DOORS, PLEASE
 PROVIDE THE SIZE OF PANELS AND TYPE OF GLAZING TO BE
 USED INT THESE PANELS?
 TABLE 715.4& TABLE 715.4.3.
  
 11) SHEET A4.0.2 TYPICAL ROOF DETAIL INDICATES O.S.
 TAKEN TO MEAN OVERFLOW SCUPPERS IF THIS IS CORRECT THE
 RAINWATER COLLECTION HEAD IS DRAWN OFF TO THE SIDE NOT
 IN LINE WITH THE OVERFLOW SCUPPERS.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 9 Status P Date 2009-06-02 Cont ID  
Sent By dwise Date 2009-06-02 Time 21:01 Rev Time 0.00
Received By dwise Date 2009-05-28 Time 21:01 Sent To FIRE
Notes
2009-06-02 21:01:54SENT TO FIRE FOR RESTAMP.

Review Stop E ELECTRICAL
Rev No 8 Status P Date 2008-04-10 Cont ID  
Sent By dpalmer Date 2008-04-10 Time 08:16 Rev Time 0.00
Received By dpalmer Date 2008-04-10 Time 08:16 Sent To  
Notes
2008-04-10 08:19:04REV #7 ONLY. DELETION OFPARKING SYSTEMS DEVICES.
 IF OK WITH FIRE WILL NEED TO RETAIN FILE SET.

Review Stop E ELECTRICAL
Rev No 7 Status F Date 2008-03-31 Cont ID  
Sent By dpalmer Date 2008-03-31 Time 18:13 Rev Time 0.00
Received By dpalmer Date 2008-03-31 Time 18:12 Sent To PC
Notes
2008-03-31 18:13:12** DENIEDREVIEW **
  
 ** REVISIONS SUBMITTED TO FIRE DATED 3/14/ AND
 REVISIONS SUBMIT TO ELECTRICAL DATED 3/27
  
 1) NOTE: PLEASE SEE ELECTRICAL RISER HAS NOW CHANGED
 THE GENERATOR FROM PROPANE ON-SITE FUEL TO NATURAL GAS.
 THIS WAS NOT LABELED AS A REVISION NOR DOES ANY OTHER
 ITEM ON THE RISER SHEET SHOW THIS BEING CHANGED. THE
 REV #4 WHICH IS NEXT TO GENERATOR WAS ALREADY SUBMITTED
 ON PREVIOUS REVISIONS AND DOES NOT CONTAIN THE SAME
 WORDING.
 THE PREVIOUS CLEARLY INDICATED *PROPANE/ON-SITE FUEL*.
 IF THIS GENERATOR IS GOING TO BE *OPTIONAL STAND-BY*
 THEN IT IS NOT REQUIRED TO CONTAIN ON-SITE FUEL. ALL
 EMERGENCY AND EXIT LIGHTS SHALL CONTAIN BATTERY BACK UP
 POWER SOURCE OR OTHER ACCEPTABLE MEANS.
 PLEASE SEE LS CODE 101 7.8.2.1, 7.8.2.2 ALONG WITH NEC
 700.12F., 700.12B3, 701.11B3
 PLEASE ADJUST.
  
 ** SHEETS WHICH CONTAINED STAMPED FROM FIRE REVIEW HAVE
 BEEN VOIDED.
 MUST RE-SUBMITTED OTHER SHEETS STAMPED BY FIRE MARSHAL
 WHEN RESUBMITTING CORRECTED REVISIONS.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2007-12-13 Cont ID  
Sent By dpalmer Date 2007-12-13 Time 09:01 Rev Time 0.00
Received By dpalmer Date 2007-12-13 Time 09:01 Sent To PC
Notes
2007-12-13 09:01:45REV AND NEW SHEET 2.30,5.00

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2007-08-03 Cont ID  
Sent By dpalmer Date 2007-08-03 Time 11:08 Rev Time 0.00
Received By dpalmer Date 2007-08-03 Time 11:08 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2007-08-01 Cont ID  
Sent By dpalmer Date 2007-08-01 Time 14:51 Rev Time 0.00
Received By dpalmer Date 2007-08-01 Time 14:47 Sent To  
Notes
2007-08-01 14:51:31** TEMP UNSAT STATUS**
  
 1) NOTE: PLEASE SEE ARE STATED ON PREVIOUS REVIEW. THE
 SEAL IN USE FOR THE LANDSCAPE ARCHITECT ON L AND IRR
 PLANS IS NO LONGER VALID WITH THE STATE OF FLORIDA,
 FLORIDA ADMINISTRATIVE CODE.
 A TIME CAN BE SET UP FOR THE DESIGNER OF RECORD TO COME
 IN AND RE-SEAL, SIGN AND DATE PLANS.
 FAC 61G1-16.002
 61G1-16.004
  
 **NOTE ** PLEASE SEE THE PLANS HAVE NOW BEEN REVISED TO
 SHOW A ON-SITE TANK HOWEVER ONLY THE ELECTRICAL AND
 PLUMBING SHEETS SHOW THIS.
 ** PLEASE SEE OTHER POSSIBLE NOTES FROM OTHER TRADES AS
 THIS NEW TANK WAS NOT ADDED TO OTHER SHEETS. NFPA-110
 CHAPTER 4
  
 **NOTED** PLEASE SEE PREVIOUS REVIEW REQUESTED THE
 ADDRESS BE ADDED FOR TITLE BLOCKS. THIS WAS ONLY DONE
 ON SOME OF THE NEW SHEETS WHERE MOST OF THE PREVIOUS
 SHEETS FOR ALL TRADES WERE NOT DONE.
 PLEASE SEE THE ADDRESS FOR THE PROJECT IS REQUIRED TO
 BE ON PLANS. PLEASE SEE THE ADDRESS OF 505 BANYAN BLVD
 SHOULD BE ON PLANS. PLEASE KNOW THAT ANY SHEETS WHICH
 MAY ALREADY BE PASSED AND CONTAINS CITY STAMPS MAY
 *PRINT, STAMP OR BY OTHER PERMANENT MEANS* THE ADDRESS
 ON TITLE BLOCKS.
 FAC 61G1-16.004
 THIS WAS CORRECTED IN MEETING WITH THE ENGINEER ON E,
 AND P SHEETS ON 7/27/07
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-07-27 Cont ID  
Sent By dpalmer Date 2007-07-27 Time 08:37 Rev Time 2.22
Received By dpalmer Date 2007-07-26 Time 11:54 Sent To  
Notes
2007-07-27 08:37:36 
 *** UNSAT 3RD REVIEW ***
  
 ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW STILL
 REMAIN.
  
  
 1) NOTE: PLEASE SEE ARE STATED ON PREVIOUS REVIEW. THE
 SEAL IN USE FOR THE LANDSCAPE ARCHITECT ON L AND IRR
 PLANS IS NO LONGER VALID WITH THE STATE OF FLORIDA,
 FLORIDA ADMINISTRATIVE CODE.
 A TIME CAN BE SET UP FOR THE DESIGNER OF RECORD TO COME
 IN AND RE-SEAL, SIGN AND DATE PLANS.
 FAC 61G1-16.002
 61G1-16.004
  
 2) NOTE: PLEASE SEE PREVIOUS REVIEW COMMENTS WITH
 RESPECT TO THE GENERATOR AND MINIMUM FUEL REQUIRED.
 PLEASE SEE THE USE OF FUEL AND TIME OF SUPPLY CAN NOT
 BE FOUND ON PLANS.
 PLEASE STATE THE CONSUMPTION AT THE FULL LOAD BASED ON
 THE LOAD CALCULATIONS PROVIDED.
 PLEASE SEE THE PLANS HAVE NOW BEEN REVISED TO SHOW A
 ON-SITE TANK HOWEVER ONLY THE ELECTRICAL AND PLUMBING
 SHEETS SHOW THIS.
 ** PLEASE SEE OTHER POSSIBLE NOTES FROM OTHER TRADES AS
 THIS NEW TANK WAS NOT ADDED TO OTHER SHEETS. NFPA-110
 CHAPTER 4
  
 3) NOTE:PLEASE SEE PREVIOUS REVIEW REQUESTED THE
 ADDRESS BE ADDED FOR TITLE BLOCKS. THIS WAS ONLY DONE
 ON SOME OF THE NEW SHEETS WHERE MOST OF THE PREVIOUS
 SHEETS FOR ALL TRADES WERE NOT DONE.
 PLEASE SEE THE ADDRESS FOR THE PROJECT IS REQUIRED TO
 BE ON PLANS. PLEASE SEE THE ADDRESS OF 505 BANYAN BLVD
 SHOULD BE ON PLANS. PLEASE KNOW THAT ANY SHEETS WHICH
 MAY ALREADY BE PASSED AND CONTAINS CITY STAMPS MAY
 *PRINT, STAMP OR BY OTHER PERMANENT MEANS* THE ADDRESS
 ON TITLE BLOCKS.
 FAC 61G1-16.004
  
 4) NOTE: PLEASE KNOW THE ENGINEER OF RECORD FOR
 ELECTRICAL WILL BE REQUIRED TO MEET IN THIS OFFICE TO
 SIGN AND SEAL SHEETS E 101, 2.51, 2.61 AND 5.10 AS THE
 SIGNATURES ON THOSE SHEETS DO NOT SEEM TO MATCH THAT OF
 THE NEW SHEETS AND PLANS ON FILE FROM THE DESIGNER OF
 RECORD.
 FS471.025
  
 *** MOST OF THE ABOVE COMMENTS CAN BE ADDRESSED BY
 SETTING UP MEETING TIMES FOR DESIGNERS TO COME IN AND
 CORRECT PLANS.
 PLEASE SEE THAT THE ADDRESS CAN BE ADDED BY ANYONE ON
 THE PROJECT.
 PLEASE KNOW THAT THE FUEL CONSUMPTION INFORMATION CAN
 BE DONE ON A SEPARATE SHEET, SIGNED, DATED, SEALED WITH
 TITLE BLOCK INFORMATION WHICH CAN BE ATTACHED TO
 SHEETS.
 ** IMPORTANT**
 AS OTHER REVIEWS HAVE NOT YET TAKEN PLACE, PLEASE KNOW
 IF PLANS ARE RETURNED FOR ANY OTHER TRADE COMMENTS
 PLEASE MAKE THE ABOVE CORRECTIONS AT THAT TIME.
  
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-06-22 Cont ID  
Sent By dpalmer Date 2007-06-22 Time 18:32 Rev Time 0.00
Received By dpalmer Date 2007-06-20 Time 21:07 Sent To  
Notes
2007-06-22 18:32:46*** UNSAT2ND REVIEW ***
  
 ** PLEASE SEE THERE ARE STILL SOME NOTES FROM PREVIOUS
 REVIEW WHICH ARE STILL IN NEED OF ADDRESSING.
  
  
 1) NOTE: PLEASE SEE MOST OF THE CODES WERE ADDRESSED
 AND ADJUSTED ON PLANS HOWEVER PLEASE SEE SHEET FA WHICH
 STILL INDICATES THE SFBC.
 ** PLEASE SEE COMMENT WITH RESPECT TO FA SYSTEMS. **
 SOME OF THESE CODES MAY BE PRESENT ON PLANS HOWEVER
 PLEASE VERIFY THE CODES AND SEE COMMENTS FROM OTHER
 TRADES WHICH MAY AFFECT THIS NOTE.
 ** PLEASE SEE COMMENTS IN REVIEW WITH RESPECT TO SOME
 AREAS OF PLANS WHICH REFLECT THE SOUTH FLORIDA BUILDING
 CODE SFBC. THIS HAS NOT BEEN IN EFFECT SINCE 3/1/02.
  
 2) NOTE:PLEASE SEE MISSING INFORMATION ON TITLE
 BLOCKS FOR L AND IRR SHEETS. PLEASE SEE MISSING THE
 PRINTED NAME AND PRINTED LICENSE NUMBER OF THE DESIGNER
 OF RECORD. PLEASE ALSO SEE THE SEAL IS NOT VALID UNDER
 THE FAC 61G1-16.002
 61G1-16.004
  
 3) NOTE:PLEASE SEE THE STAIRS AS PREVIOUSLY NOTED
 WILL BE REQUIRED TO HAVE BATTERY BACK UP FIXTURES OF
 SOME TYPE FOR MINIMUM LIGHTING LEVELS. PLEASE KNOW THE
 SINGLE TRIPPING OF THE OCP WILL PLACE THE EGRESS OF
 STAIRS IN DARKNESS. PLEASE PROVIDE FURTHER INFORMATION
 ON START OF GENERATOR. IF THE GEN UNIT ONLY STARTS
 UNDER POWER FAILURE OF MAIN, THEN THE BATTERY BACK UP
 LIGHTS ARE REQUIRED. IF THE UNIT START UP IS TRIGGERED
 BY THE FAILURES OF THE EMERGENCY DISCONNECT THEN THE
 MULTI-CIRCUITS WILL BE OK. PLEASE SEE THE NOTE FROM
 PREVIOUS REVIEW BELOW WILL REMAIN. PLEASE CALL TO GO
 OVER.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE PROVIDE PHOTO-METRICS FOR STAIR TOWERS WHICH
 INDICATE THE MINIMUM OF 10FT CANDLES UNDER NORMAL AND
 1FT CANDLE UNDER EMERGENCY CONDITIONS.
 PLEASE ALSO SEE THE FIXTURES AS SHOWN DO NOT PROVIDE
 ENOUGH INFORMATION FOR TYPE OF FIXTURE. PLEASE SEE A
 BATTERY BACK UP FIXTURE WILL BE REQUIRED FOR THE
 MINIMUM LEVELS FOR EGRESS UNDER EMERGENCY CONDITIONS.
 PLEASE SEE LS 101 7.8, 7.9, 7.8.1.3, 7.9.2.2. PLEASE
 SEE THAT THE FAILING OF A SINGLE DEVICE, OCP, SWITCH
 ETC SHALL NOT LEAVE ANY ONE EGRESS AREA IN TOTAL
 DARKNESS.
 PLEASE INDICATE ON PLANS IF THE EXISTING GENERATOR
 ROOM, FIRE PUMP ROOM AND MAIN ELECTRICAL ROOM CONTAIN
 EMERGENCY BATTERY BACK UP FIXTURES OF SOME TYPE. IF
 EXISTING PLEASE SHOW, IF NOT, PLEASE KNOW THESE WILL BE
 REQUIRED.
 NEC 700.12E, 700.16, NFPA-101101 7.8, 7.9, NFPA-110
 7.3.1
  
 4) NOTE: THIS IS THE SAME NOTE. PLEASE SEE THE MINIMUM
 LEVELS ARE REQUIRED ON PLANS FOR THE SYSTEM AS SHOWN.
 THIS IS REQUIRED UNDER THE FBC FOR ADA COMPLIANCE WHICH
 IS MORE RESTRICTIVE THAN NFPA-72.
 PLEASE SEE PLANS DO INDICATE A FA SYSTEM.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE SEE THE FA SHEETS AS THESE INDICATE THE HORN
 AND STROBE DEVICES FROM THE SFBC AND OTHER CODES WHICH
 ARE NO LONGER IN EFFECT.
 PLEASE SEE THE MINIMUM LEVELS FOR THESE DEVICES SHALL
 BE STATED PER FBC 2004 11-4.28.1,.2 AND .3(4).
  
 5) NOTE: THIS IS THE SAME NOTE: THE LPD WHICH ARE SHOWN
 ON PLANS WERE VIEWED, HOWEVER THE NEED OF A FIXTURE
 LEGEND WHICH COORDINATES WITH THE IDENTIFICATION OF
 PLANS IS NEEDED. PLEASE SEE SOME FIXTURES ARE
 IDENTIFIED ON PLANS ARE NOT FOUND ON THE *LEGEND* AS
 SUBMITTED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SUBMIT A COMPLETE FIXTURE LEGEND OF ALL
 FIXTURES AND CORRELATE WITH PLANS.
 PLEASE ALSO SEE THE 2004 FBC W/ 2006 REVISIONS TO
 CHAPTER 13 FOR THE POWER ALLOWANCES PERMITTED AND
 PERFORMANCE CALCULATIONS PER 13-415.2.
 PLEASE PROVIDE WORST CASE VOLTAGE DROP PER
 13-413.1ABC.1 FOR BRANCH CIRCUITS INSTALLED AS NEW.
 PLEASE SEE ALL OF CHAPTER 13 FOR LIGHTING AND
 CONTROLS.
 PLEASE SEE THAT NOT ENOUGH INFORMATION IS PROVIDED FOR
 LIGHTING CONTROLS, PANELS, SCHEDULING ETC.
 FBC 106.1.2
  
 6) NOTE: THIS COULD NOT BE LOCATED IN PACKAGE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SUBMIT WIND LOADS FOR ROOF TOP LIGHTING POLES
 SHOWING THE MINIMUM LOADS FOR POLES AND FIXTURES WITH
 THEIR EFFECTIVE PROJECTED AREAS (EFA) TO MEET THE
 MINIMUM OF THE FBC 140 MPH WIND LOADS.
 THIS INFORMATION WILL BE REVIEWED BY THE STRUCTURAL
 PLANS EXAMINER.
 FBC 106.1.2
  
 7) NOTE: PLEASE SEE THE GENERATOR IS NOW BEING SHOWN AS
 EXISTING AND IS NOW SHOWN AS NATURAL GAS, HOWEVER AS
 THE LOADS HAVE BEEN INCREASED THE AMOUNT OF ON-SITE
 FUEL NEEDS TO BE VERIFIED. PLEASE SEE THE MINIMUM FUEL
 REQUIRED AS STATED IN PREVIOUS REVIEW STILL NEEDS TO BE
 SHOWN AND IDENTIFIED ON PLANS. PLEASE SEE AS THERE ARE
 SEVERAL ITEMS WHICH IS NEEDED FOR ALL TRADES, THERE MAY
 BE NEW COMMENTS FROM OTHER TRADES IF NEW LARGER ON-SITE
 TANK IS NEEDED. ** AS STATED IN THE CODE, THE LEGALLY
 REQUIRED OR EMERGENCY SYSTEMS SHALL NOT RELY ON
 UTILITY.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THAT IT IS UNCLEAR WHAT IS BEING DONE WITH
 THE GENERATOR. IS THIS UNIT GOING TO BE NEW OR EXISTING
 TO REMAIN?
 PLEASE SEE THE RISER SEEMS TO SHOW UNIT AS GAS AND
 DIESEL? PLEASE CLARIFY IS THIS NATURAL GAS? OR
 GASOLINE? PLEASE VERIFY.
 PLEASE SUBMIT THE FUEL CONSUMPTION RATE FOR THE
 GENERATOR AT FULL LOAD INCLUDING THE LOAD OF THE FIRE
 PUMP AT 100%.
 PLEASE SEE NFPA-20 9.6.2.2.
 PLEASE SEE 701.11B3
  
 8) NOTE: THIS NOTE REMAINS AS NO LOCKED ROTOR CURRENT
 INFORMATION COULD BE LOCATED FOR THE MAIN FIRE PUMP
 CONTROLLER. PLEASE SEE THE RISER WAS REVISED TO SHOW A
 1200AMP BREAKER WHICH DOES NOT SEEM TO BE CORRECT.
 PLEASE SEE THE REQUIRED OCP ON THE MAG-TRIP IS
 TYPICALLY THE SIZE OF THE BREAKER HOWEVER ONLY A
 MAG-TRIP WITH SETTINGS. THIS IS NOT ACTUALLY GOING TO
 BE A 1200AMP BREAKER?
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE BE SURE INFORMATION IS PROVIDED ON PLANS FOR
 THE LOCKED ROTOR OVER CURRENT PROTECTION ON THE PRIMARY
 SIDE OF THE FIRE PUMP.
 PLEASE SEE 695.4B1, NFPA-20 9.3.2.2.3.2
 PLEASE ALSO SEE OTHER SECTIONS UNDER 9.3 FOR THE FPC.
  
 9) NOTE: PLEASE SEE THE ADDRESS FOR THE PROJECT IS
 REQUIRED TO BE ON PLANS. PLEASE SEE THE ADDRESS OF 505
 BANYAN BLVD SHOULD BE ON PLANS. PLEASE KNOW THAT ANY
 SHEETS WHICH MAY ALREADY BE PASSED AND CONTAINS CITY
 STAMPS MAY *PRINT, STAMP OR BY OTHER PERMANENT MEANS*
 THE ADDRESS ON TITLE BLOCKS.
 FAC 61G1-16.004
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
 ** PLEASE SEE ANY POSSIBLE COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS.
2007-06-21 06:59:452007-02-21 06:59:45
 REVIEW IN PROGRESS
2007-06-20 21:07:422007-06-20 21:07:42
 IN ELEC FOR REVIEW.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-03-23 Cont ID  
Sent By dpalmer Date 2007-03-23 Time 19:03 Rev Time 0.00
Received By dpalmer Date 2007-03-23 Time 07:50 Sent To  
Notes
2007-03-23 19:07:13****** UNSAT ******
  
 ** PLEASE KNOW THAT AS SOME INFORMATION HAS NOTYET
 BEEN SUBMITTED FOR REVIEW YET THERE MAY VERY WELL BE
 NEW COMMENTS ON THE NEXT REVIEW.
  
 ** PLEASE KNOW THAT ANY REFERENCE TO THE FBC CHAPTER 1
 IN THE PLAN REVIEW COMMENTS CAN BE FOUND IN THE
 ADMINISTRATIVE SECTION OF THE 2004 FBC AS ADOPTED BY
 THE CITY OF WEST PALM BEACH.
  
  
 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH
 ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS
 UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS.
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
 2003 NFPA-20
 2002 NFPA-110
 ** SOME OF THESE CODES MAY BE PRESENT ON PLANS HOWEVER
 PLEASE VERIFY THE CODES AND SEE COMMENTS FROM OTHER
 TRADES WHICH MAY AFFECT THIS NOTE.
 ** PLEASE SEE COMMENTS IN REVIEW WITH RESPECT TO SOME
 AREAS OF PLANS WHICH REFLECT THE SOUTH FLORIDA BUILDING
 CODE SFBC. THIS HAS NOT BEEN IN EFFECT SINCE 3/1/02.
  
 2) NOTE: PLEASE SEE THE *S* SHEETS WHICH IS MISSING
 INFORMATION ON TITLE BLOCKS FOR FIRM. PLEASE SEE
 MISSING THE CERTIFICATE OF AUTHORIZATION NUMBER AS
 REQUIRED PER FAC 61G15-23.002, AND FS 471.023. THIS IS
 REQUIRED WHETHER OR NOT COMMENT IS MADE BY OTHER
 REVIEWER(S).
  
 3) NOTE: PLEASE SEE TITLE BLOCK FOR GARTEK ENGINEERING
 IS SMALL AND INFORMATION IS NOT CLEAR. PLEASE SEE TITLE
 BLOCK AND ADJUST FONT/PRINTING.
  
 4) NOTE: PLEASE PROVIDE PHOTO-METRICS FOR STAIR TOWERS
 WHICH INDICATE THE MINIMUM OF 10FT CANDLES UNDER NORMAL
 AND 1FT CANDLE UNDER EMERGENCY CONDITIONS.
 PLEASE ALSO SEE THE FIXTURES AS SHOWN DO NOT PROVIDE
 ENOUGH INFORMATION FOR TYPE OF FIXTURE. PLEASE SEE A
 BATTERY BACK UP FIXTURE WILL BE REQUIRED FOR THE
 MINIMUM LEVELS FOR EGRESS UNDER EMERGENCY CONDITIONS.
 PLEASE SEE LS 101 7.8, 7.9, 7.8.1.3, 7.9.2.2. PLEASE
 SEE THAT THE FAILING OF A SINGLE DEVICE, OCP, SWITCH
 ETC SHALL NOT LEAVE ANY ONE EGRESS AREA IN TOTAL
 DARKNESS.
 PLEASE INDICATE ON PLANS IF THE EXISTING GENERATOR
 ROOM, FIRE PUMP ROOM AND MAIN ELECTRICAL ROOM CONTAIN
 EMERGENCY BATTERY BACK UP FIXTURES OF SOME TYPE. IF
 EXISTING PLEASE SHOW, IF NOT, PLEASE KNOW THESE WILL BE
 REQUIRED.
 NEC 700.12E, 700.16, NFPA-101101 7.8, 7.9, NFPA-110
 7.3.1
  
 5) NOTE: PLEASE SEE THE FA SHEETS AS THESE INDICATE THE
 HORN AND STROBE DEVICES FROM THE SFBC AND OTHER CODES
 WHICH ARE NO LONGER IN EFFECT.
 PLEASE SEE THE MINIMUM LEVELS FOR THESE DEVICES SHALL
 BE STATED PER FBC 2004 11-4.28.1,.2 AND .3(4).
  
 6) NOTE: PLEASE SEE THE *CODED NOTES* FOR THE PARKING
 BOOTHS DO NOT PROVIDE THE MINIMUM CIRCUITING FOR THE
 NEW ELECTRICAL WHICH IS BEING INSTALLED AT BOOTHS. DO
 THEY INCREASE IN LOAD? ARE THESE GOING TO BE NEW UNITS
 WHICH WILL CONTAIN ALL NEW ELECTRICAL AND PANELS?
 PLEASE PROVIDE MORE INFORMATION.
 FBC 106.1.2
  
 7) NOTE: PLEASE SUBMIT A COMPLETE FIXTURE LEGEND OF ALL
 FIXTURES AND CORRELATE WITH PLANS.
 PLEASE ALSO SEE THE 2004 FBC W/ 2006 REVISIONS TO
 CHAPTER 13 FOR THE POWER ALLOWANCES PERMITTED AND
 PERFORMANCE CALCULATIONS PER 13-415.2.
 PLEASE PROVIDE WORST CASE VOLTAGE DROP PER
 13-413.1ABC.1 FOR BRANCH CIRCUITS INSTALLED AS NEW.
 PLEASE SEE ALL OF CHAPTER 13 FOR LIGHTING AND
 CONTROLS.
 PLEASE SEE THAT NOT ENOUGH INFORMATION IS PROVIDED FOR
 LIGHTING CONTROLS, PANELS, SCHEDULING ETC.
 FBC 106.1.2
  
 8) NOTE: PLEASE SUBMIT WIND LOADS FOR ROOF TOP LIGHTING
 POLES SHOWING THE MINIMUM LOADS FOR POLES AND FIXTURES
 WITH THEIR EFFECTIVE PROJECTED AREAS (EFA) TO MEET THE
 MINIMUM OF THE FBC 140 MPH WIND LOADS.
 THIS INFORMATION WILL BE REVIEWED BY THE STRUCTURAL
 PLANS EXAMINER.
 FBC 106.1.2
  
 9) NOTE: PLEASE SUBMIT COMPLETE MANUFACTURE'S SPECS/CUT
 SHEETS FOR ALL NEW EQUIPMENT BEING INSTALLED FOR THE
 GENERATOR, FIRE PUMP, FIRE PUMP CONTROLLER, AND ATS(S)
 .
 PLEASE SEE THERE ARE SEVERAL ITEMS WHICH NEED TO BE
 REVIEWED FOR CODE COMPLIANCE WHICH CAN NOT BE DONE AT
 THIS TIME.
 PLEASE ALSO BE SURE ALL INFORMATION SUBMITTED CONTAINS
 LISTINGS FROM ANRTL.
 110.3, 90.7.
  
 10) NOTE: PLEASE PROVIDE NOTES ON RISER FOR SIGNAGE AS
 REQUIRED PER 230.2E, 700.8, 701.9 ETC.
  
 11) NOTE: PLEASE SEE THAT IT IS UNCLEAR WHAT IS BEING
 DONE WITH THE GENERATOR. IS THIS UNIT GOING TO BE NEW
 OR EXISTING TO REMAIN?
 PLEASE SEE THE RISER SEEMS TO SHOW UNIT AS GAS AND
 DIESEL? PLEASE CLARIFY IS THIS NATURAL GAS? OR
 GASOLINE? PLEASE VERIFY.
 PLEASE SUBMIT THE FUEL CONSUMPTION RATE FOR THE
 GENERATOR AT FULL LOAD INCLUDING THE LOAD OF THE FIRE
 PUMP AT 100%.
 PLEASE SEE NFPA-20 9.6.2.2.
 PLEASE SEE 701.11B3
  
 12) NOTE: PLEASE SUBMIT ONLY ONE ELECTRICAL RISER WHICH
 WILL BE ON THE PERMITTED RECORD SET OF PLANS. IF THE
 OTHER OPTION (1 OR 2) IS DONE INSTEAD THEN REVISED
 PLANS WILL BE REQUIRED THAT TIME. THE RECORD SET OF
 PLANS MUST CONTAIN ONE OPTION.
 PLEASE KNOW THE REVIEW WILL BE DONE ON THE ONE
 SUBMITTED.
  
 13) NOTE: PLEASE SEE RISER AS IT APPEARS TO SHOW THE
 SERVICE ENTRANCE CONDUCTORS BEING RUN OVER HEAD TO THE
 FIRE PUMP/FPC.
 PLEASE SEE NFPA-70 695.6A AS THESE WILL BE REQUIRE DOT
 BE RUN OVER HEAD IF THIS IS THE CASE.
 PLEASE ALSO SEE NFPA-20 9.3.1*
  
 14) NOTE: PLEASE BE SURE INFORMATION IS PROVIDED ON
 PLANS FOR THE LOCKED ROTOR OVER CURRENT PROTECTION ON
 THE PRIMARY SIDE OF THE FIRE PUMP.
 PLEASE SEE 695.4B1, NFPA-20 9.3.2.2.3.2
 PLEASE ALSO SEE OTHER SECTIONS UNDER 9.3 FOR THE FPC.
  
 15) NOTE: PLEASE SEE THE CONDUCTORS TO THE FPC FROM FPL
 AS THESE ARE NOT SHOWING A NEUTRAL CONDUCTOR TO THE
 FIRST MEANS OF DISCONNECT WHICH IS REQUIRED. THIS
 CONDUCTOR IS REQUIRED TO TERMINATE IN THIS FPC. PLEASE
 ALSO KNOW THAT THERE MAY VERY WELL BE THE NEED FOR THE
 NEUTRAL IN THE FPC. THE MANUFACTURE MAY REQUIRE FOR
 CONTROLS.
 PLEASE SEE THAT THE GENERATOR IS BEING NOTED AS A
 SEPARATELY DERIVED SYSTEM AS REQUIRED, PLEASE VERIFY IF
 THE NEUTRAL WILL BEBROUGHT FROM THE GENERATOR AS IF
 THIS IS A SD GENERATOR THEN THIS FPC WILL CONTAIN A
 FOUR POLE ATS.
 PLEASE SEE THE FOLLOWING COMMENT.
 PLEASE SEE RISER IS CURRENTLY SHOWING *EQUIPMENT
 GROUNDING CONDUCTOR* FROM THE FPL TRANSFORMER ETC.
 PLEASE SEE 250.6 FOR OBJECTIONABLE CURRENTS AS THE
 NEUTRAL IS REQUIRED TO BE BONDED AT THE FIRST MEANS OF
 DISCONNECT. 250.24.
 250.30, 250.20 ETC.
 PLEASE SEE THE FPC SEEMS TO SHOW A GROUNDING ELECTRODE
 BY ITSELF WITHOUT ANY CONNECTIONTO A MINIMUM
 SYSTEM(S) PER 250.50 OR BONDING TO THE OTHER SERVICES?
 PLEASE VERIFY THIS.
 250.92, 250.94, 250.66
 PLEASE PROVIDE MORE INFORMATION.
 FBC 106.1.2
  
 16) NOTE: PLEASE SEE ALTHOUGH GF PROTECTION IS NOT
 REQUIRED ON THE EMERGENCY SIDE OF THE EMERGENCY SYSTEM
 AND LEGALLY REQUIRED SYSTEMS, PROPER GROUND FAULT
 SENSING IS REQUIRED.
 PLEASE SEE NFPA-110 6.2.15** ISOLATION OF NEUTRAL
 CONDUCTORS. PROVISIONS SHALL BE INCLUDED FOR ENSURING
 CONTINUITY, TRANSFER, AND ISOLATION OF THE PRIMARY AND
 THE EPS NEUTRAL CONDUCTORS WHEREVER THEY ARE SEPARATELY
 GROUNDED TO ACHIEVE GROUND-FAULT SENSING.
 PLEASE SEE AN ATTACHED BRIEF EXPLANATION FROM *ASCO*
 WHITE PAPER: WHERE GROUND FAULT PROTECTION IS TRIGGERED
 BY THE CODE AND AN ALTERNATE POWER SUPPLY IS INCLUDED,
 SWITCHING OF THE NEUTRAL BECOMES NECESSARY. THE CIRCUIT
 SHOWN ABOVE ILLUSTRATES SUCH A CIRCUMSTANCE. THE
 SERVICE IS LARGER THAN 1,000 AMPS. CONSEQUENTLY, GROUND
 FAULT PROTECTION IS REQUIRED AT THE MAIN SERVICE
 DISCONNECT AT A MINIMUM. IF IT IS INSTALLED THERE AND
 THE GENERATOR NEUTRAL GROUNDING WAS THROUGH A SOLID
 CONNECTION TO THE MAIN SERVICE NEUTRAL, A GROUND FAULT
 WHEN THE GENERATOR IS FEEDING THE LOAD WILL CAUSE THE
 MAIN SERVICE DISCONNECT TO OPEN. THIS WILL NOT
 DISCONNECT THE ARCING FAULT FROM THE GENERATOR.
 COORDINATION IS THUS LOST."
 PLEASE KNOW BASED ON THE INFORMATION FROM SEVERAL OTHER
 MANUFACTURES ALSO AND THE CODE PLEASE BE SURE THE
 MANUFACTURES SPECS TO BE SUBMITTED ARE INDEED 4POLE ATS
 DEVICES AS NOTED FOR EACH RISER MENTIONS.
 PLEASE VERIFY THE FPC/ATS.
 PLEASE ALSO SEE GENERATOR GROUNDING DETAIL WILL BE
 REQUIRED TO BE REVISED.
 PLEASE SEE 250.20, 250.30, 250.66, 240.13, 230.95,
 700.7D, 700.26
  
 17) NOTE: PLEASE CORRELATE PLANS AS THE ELECTRICAL
 PLANS INDICATE A 150HP 480V FIRE PUMP AND THE FIRE
 PROTECTION SHEETS INDICATE A 125HP 480V PUMP. PLEASE
 KNOW AT THIS TIME REVIEW OF THE RISER CONDUCTORS CAN
 NOT BE DONE AS IT IS NOT KNOWN WHICH ONE IS BEING
 INSTALLED.
 FBC 106.1.2
  
 18) NOTE: PLEASE SHOW ALL CONTINUOUS LOADS AT 125%.
 PLEASE INCLUDE LOAD CALCULATIONS FOR INCREASED LOADS IN
 A LOAD SUMMARY.
 215.5,215.3, 230.42. AND 220.
 FBC 106.3.5.1.2
  
 19) NOTE: PLEASE SEE OPTION #2 AS IT STILL INDICATES
 400AMP OCP ON THE 400AMP FEEDERS TO THE 200AMP ATS??
 AND 200AMP DISCONNECT ETC.
 PLEASE VERIFY AND COORDINATE.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2007-07-06 Cont ID  
Sent By rchokshi Date 2007-07-06 Time 11:49 Rev Time 0.00
Received By rchokshi Date 2007-07-06 Time 11:49 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2007-06-27 Cont ID  
Sent By rchokshi Date 2007-06-27 Time 14:14 Rev Time 0.00
Received By rchokshi Date 2007-06-27 Time 14:03 Sent To  
Notes
2007-06-27 14:13:49PLEASE PROVIDE THE FOLLOWING INFO:
  
 1. PLEASE SHOW STANDARDS NOTES OF CITY OF WPB ON
 DRAWINGSFOR SIDEWALK WIDTH , ITS SLOPE, DRIVEWAY,
 PARKING, HANDICAP PARKING, PAINTING DETAILS FOR PARKING
 PER CITY CODES ETC.,, MUST MEET PER ADA,,ETC.,YOU CAN
 GET STANDARD NOTES OF CITY OFWPB INA C.D.
 FROM 1000 45TH STREET. ENG DEPT.WE SHOULD HAVE THOSE
 NOTES ON YOUR DRAWINGS.
 2. PLEASE SHOW ON DRAWINGSDUMPSTER & ITS ENCLOSURE
 DETAILS PER CITY OF WPB, &LOCATION ON DWG, LOCATION
 MUST BE ACCESSIBLE FOR PICKUP TRUCK.
 3. POLLUTION PREVENTION DETAILS,CLOTHES USED FOR SILT
 ETC., PLANS SHOWING SILT FENCE AROUND THE SITE & CATCH
 BASINS.HEIGHT OF FENCE SHOULD BE HIGH ENOUGH PER FDEP
 TO STOP DUST & PARTICLES.
 4. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH
 STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVED
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2007-04-12 Cont ID  
Sent By rchokshi Date 2007-04-12 Time 13:50 Rev Time 0.00
Received By rchokshi Date 2007-04-12 Time 13:40 Sent To  
Notes
2007-04-12 13:49:52FAILED FOR FOLLOWING REASONS:
  
 1. NO CIVIL DRAINAGE, STORM WATER PLANS FOUND IN YOUR
 PACKAGE.
 2. PLEASE ALSO SUBMITWATER QUALITY CALCULATION, A
 COPY OF SFWMD PERMIT, & GEO-TECH REPORT
  
 RASIK CHOKSHI805-6723

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status P Date 2009-06-05 Cont ID  
Sent By mwennerg Date 2009-06-05 Time 09:04 Rev Time 0.00
Received By mwennerg Date 2009-06-05 Time 09:03 Sent To B
Notes
2009-06-05 09:05:09REVISION DATED 3/26/08 STAMPED SHEETS E2.30, E2.40 AND
 E2.50.

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2008-05-07 Cont ID  
Sent By mawillia Date 2008-05-07 Time 14:57 Rev Time 0.00
Received By mawillia Date 2008-05-07 Time 14:33 Sent To B
Notes
2008-05-07 14:57:48*****REVISION , DELETION OF NEW PARKING SYSTEM,
 APPROVED*****
  
 REVISED PLAN SHEETS A1.0.0, A2.1.4, A2.4.0, A2.4.2,
 E1.01, E2.41, E5.00, E5.10, AND PK0.03 & PK0.04 WERE
 REVIEWED;PLAN SHEET E2.41 STAMPED, INTITIALED, AND
 DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2008-03-26 Cont ID  
Sent By mawillia Date 2008-03-26 Time 17:20 Rev Time 0.00
Received By mawillia Date 2008-03-26 Time 17:06 Sent To E
Notes
2008-03-26 17:08:08*****REVISION #6, DATED 3/11/08, APPROVED*****
  
 REVISED PLAN SHEETS E1.00, E4.00, E5.00, AND E7.00 WERE
 STAMPED, INTITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-08-01 Cont ID  
Sent By mwennerg Date 2007-08-01 Time 15:09 Rev Time 0.00
Received By mwennerg Date 2007-08-01 Time 15:09 Sent To  
Notes
2007-08-01 15:28:48***PROVISO***
  
 1) PLEASE NOTE THAT THE NEW (500) GALLON LP TANK IS
 ONLY ILLUSTRATED ON ELECTRICAL AND PLUMBING SHEETS.
 LIFE SAFETY SHEETS WERE SUBMITTED WITH NO CHANGE FROM
 PREVIOUS FIRE REVIEW.
  
 2) SAFEGUARDS AGAINST POTENTIAL MECHANICAL DAMAGE TO LP
 TANK MAY BE REQUIRED TO INCLUDE BOLLARDS IF NECESSARY.
  
 3) REQUIRED MEANS OF EGRESS AND WALKWAYS SHALL NOT BE
 OBSTRUCTED BY ASSOCIATED EQUIPMENT. PLEASE NOTE THAT
 THIS CAN'T BE VERIFIED AT THIS TIME.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-07-05 Cont ID  
Sent By mcarsill Date 2007-07-05 Time 15:02 Rev Time 0.00
Received By mcarsill Date 2007-07-05 Time 14:58 Sent To  
Notes
2007-07-05 15:01:48APPROVED PROVISO
  
 1. ALL PLAN REVIEW COMMENTS FROM OTHER BUILDING,
 MECHANICAL, ELECTRICAL, AND PLUMBING REVIEWERS ARE TO
 BE ADEQUATELY ADDRESSED.
 2. PREVIOUS PLAN REVIEW COMMENTS BY FIRE RESCUE APPEAR
 TO HAVE BEEN ADDRESSES BY WAY OF REVISIONS TO THE
 PLANS.
  
 MIKE CARSILLO, BATTALION CHIEF OF FIRE PREVENTION
 804-4709 PHONE
 804-4774 FAX

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-05-03 Cont ID  
Sent By mcarsill Date 2007-05-03 Time 08:48 Rev Time 0.00
Received By mcarsill Date 2007-04-30 Time 18:26 Sent To  
Notes
2007-05-03 09:25:181. IT HAS BEEN DECLARED ON THE PLANS, PAGE LS1.0.0 THAT
 THE BUILDING IS A MIXED OCCUPANCY BUILDING INSTEAD OF
 JUST AN OPEN PARKING GARAGE.
  
 2. NFPA 88A, THE STANDARTD FOR PARKING STRUCTURES
 DEFINES A PARKING STRUCTURE AS "A BUILDING, STRUCTURE,
 OR PORTION THEREOF USED FOR THE PARKING, STORAGE, OR
 BOTH OF MOTOR VEHICLES".
  
 3. THIS STANDARD FURTHER REQUIRES THAT INTERNAL AREAS
 NOT USED FOR PARKING SHALL BE PROVIDED WITH SMOKE
 RESISTANT WALLS WHICH DOES NOT APPEAR TO BE DECLARED ON
 THE PLANS.
  
 4. THE FLORIDA FIRE PREVENTION CODE REQUIRES THAT
 "ADDITIONS SHALL CONFORM TO THE PROVISIONS OF NEW
 CONSTRUCTION".
  
 5. THE MEANS OF EGRESS CHART ON PAGE LS1.0.0 APPEARS TO
 BE INCORRECT. THE TOTAL EGRESS CAPACITY OF 972 PERSONS
 APPEARS TO BE INCORRECT. PLEASE VERIFY INFORMATION ON
 THE PLANS.
  
 6. NOTE 16 ON PAGE LS1.0.0 IS INCORRECT. ALL CUTTING
 AND WELDING OPERATIONS TO COMPLY WITH NFPA 51B.
  
 7. NFPA 88A, FURTHER DEFINES AN OPEN PARKING STRUCTURE
 "IS A PARKING STRUCTURE THAT EACH PARKING LEVEL HAS
 WALL OPENINGS OPEN TO THE ATMOSPHERE FOR AN AREA NOT
 LESS THAN 0.4 FOR EACH LINEAR METER (1.4 FT.2 FOR EACH
 LINEAR FOOT ) OF ITS EXTERIOR PERIMETER. SUCH OPENINGS
 ARE DISTRIBUTED OVER 40 PERCENT OF THE BUILDING
 PERIMETER OR UNIFORMLY OVER TWO OPPOSING SIDES.
 INTERIOR WALL LINES AND COLUMN LINES ARE AT LEAST 20
 PERCENT OPEN, WITH OPENINGS DISTRIBUTED TO PROVIDE
 VENTIALTION".
  
 8. TACTILE SIGNAGE REQUIRED REQUIRED AT ALL EXIT
 DOORS.
  
 9. PLEASE DECLARE THE USES OF ALL ROOMS WITHIN THE
 GARAGE OFFICE AREA ON PAGE A2.1.0.
  
 10. PLEASE EXPLAIN PURPOSE OF JERSEY BARRIERS
 ILLUSTRATED ON THE PLANS. WHAT IMPACT IF ANY WILL THEY
 HAVE ON EXITING.
  
 11. STAIRWELL IDENTIFICATION SIGNS WILL BE REQUIRED.
 THESE SIGNS SHALL INDICATE FLOOR LLEVEL, STAIR
 IDENTITY, TERMINUS TOP AND BOTTOM.
  
 12. DOES THE EXISTING BUILDING HAVE THE ADDRESS AFFIXED
 TO IT. ON ONE ELEVATION IT APPEARS THAT THE ADDRESS
 EXISTS.
  
 13. PLEASE PROVIDE PRESCRIPTIVE STRENGTH REQUIREMENTS
 FOR THE NEW CABLE RAILING SYSTEM BEING PROPOSED AS
 SHOWN ON PAGE A2..5.1.
  
 14. PLEASE PROVIDE PRESCRIPTIVE STRENGTH REQUIREMENTS
 FOR THE NEW GUARDRAILS TO BE INSTALLED SHOWN ON PAGE
 A.2.5.1.
  
 15. SEPARATE PLANS AND PERMIT REQUIRED FOR NEW FIRE
 ALARM CONTROL PABEL NOTED ON PAGE E1.00.
  
 16. DEMOLITION OF EXISTING ELECTRICAL WIRING, FIXTURES,
 AND APPURTENANT EQUIPMENT SHALL COMPLY WITH NFPA 70 AND
 NFPA 70E.
  
 17. NOTE 19 ON PAGE FP1.00 SHALL INCLUDE DOCUMENTATION
 OF INSPECTIONS TO THE BUREAU OF FIRE PREVENTION.
  
 18. SUBMIT MORE INFORMATION ON NEW FIRE PUMP AND
 AUTOMATIC TRANSFER SWITCH.
  
 19. PLEASE PROVIDE MORE DETAILS ON PRESSURE REDUCING
 VALVES. WILL THEY BE FACTORY OR FIELD ADJUSTABLE.
  
 20. ON PAGE FP2.60 THE FIRE DEPARTMENT OUTLET
 CONNECTIONS SHOULD BE CHANGED TO ROOF MANIFOLDS.
  
 21. ALL EMPLOYEES NEED TO BE TRAINED AND DOCUMENTED IN
 THE USE OF PORTABLE FIRE EQUIPMENT AND THE TRANSMISSION
 OF ALARMS.
  
 22. NFPA 88A THE STANDARD FOR PARKING STRUCTURES DOES
 NOT REQUIRE AUTOMATIC FIRE SPRINKLER SYSTEMS IN OPEN
 PARKING STRUCTURES. OTHER CODES MAY REQUIRE BE REQUIRE
 FIRE SPRINKLER PROTECTION.
  
 MIKE CARSILLO, BATTALION CHIEF
 804-4709 PHONE
 804-4774 FAX
  
 MIKE WILLIAMS, FIRE PREVENTION CAPTAIN
 805-6722 PHONE

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2007-08-02 Cont ID  
Sent By jleech Date 2007-08-02 Time 08:08 Rev Time 0.00
Received By jleech Date 2007-08-02 Time 08:08 Sent To  
Notes
2007-08-02 08:32:02PROVISO;
 THE GAS PLAN, PAGE P3.10 MUST BE REVISED WITHIN 30 DAYS
 THE FOLLOWING INFORMATION NEEDS TO BE CHANGED ARE ADDED
 TO PLAN;
 A) DEVELOPED LENGHT FROM TANK TO
 GENERATOR.
 B) PIPE SIZE, WELDED OR SCREW PIPE.
 C) SUBMIT REGUATOR SPEC SHEETS. (MOST LP
 SYSTEMS HAVE A FIRST AND SECOND STAGE REGULATOR)
 D) SLEAVE PIPE THRU WALL.
 E) DETAIL REQUIRED FOR TANK PAD AND TIE
 DOWN.
 F) SHUT OFF VALVES REQUIRED DOWN STREAM OF
 REGULATORS AND UNIONS. ( SHOW ON RISER DIAGRAM)
 G) IF TANK REQUIRES PROTECTION FROM DAMAGE
 SHOW AND SPEC. ON DRAWINGS.

Review Stop I INCOMING/PROCESSING
Rev No 24 Status N Date 2008-04-08 Cont ID  
Sent By adarroug Date 2008-04-08 Time 09:46 Rev Time 0.00
Received By adarroug Date 2008-04-08 Time 09:46 Sent To  
Notes
2008-04-08 09:49:10TO "COMM" BD#15

Review Stop I INCOMING/PROCESSING
Rev No 23 Status N Date 2008-03-27 Cont ID  
Sent By adarroug Date 2008-03-27 Time 14:55 Rev Time 0.00
Received By adarroug Date 2008-03-27 Time 14:55 Sent To E
Notes
2008-03-27 14:56:04TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 22 Status N Date 2008-03-17 Cont ID  
Sent By adarroug Date 2008-03-17 Time 11:46 Rev Time 0.00
Received By adarroug Date 2008-03-17 Time 11:46 Sent To FIRE
Notes
2008-03-17 11:47:28TO "F" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 21 Status N Date 2008-03-17 Cont ID  
Sent By adarroug Date 2008-03-17 Time 11:43 Rev Time 0.00
Received By adarroug Date 2008-03-17 Time 11:43 Sent To B
Notes
2008-03-17 11:44:25TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 20 Status N Date 2008-02-29 Cont ID  
Sent By adarroug Date 2008-02-29 Time 16:39 Rev Time 0.00
Received By adarroug Date 2008-02-29 Time 16:39 Sent To B
Notes
2008-02-29 16:40:00TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 19 Status N Date 2008-02-29 Cont ID  
Sent By adarroug Date 2008-02-29 Time 08:17 Rev Time 0.00
Received By adarroug Date 2008-02-29 Time 08:17 Sent To B
Notes
2008-02-29 08:18:15TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 18 Status N Date 2008-02-28 Cont ID  
Sent By adarroug Date 2008-02-28 Time 16:53 Rev Time 0.00
Received By adarroug Date 2008-02-28 Time 16:53 Sent To B
Notes
2008-02-28 16:53:42TO "RBROWN" DESK/SUBMITAL

Review Stop I INCOMING/PROCESSING
Rev No 17 Status N Date 2008-01-18 Cont ID  
Sent By adarroug Date 2008-01-18 Time 12:18 Rev Time 0.00
Received By adarroug Date 2008-01-18 Time 12:18 Sent To B
Notes
2008-01-18 12:18:35TO "JWITMER" DESK/2 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 16 Status N Date 2008-01-18 Cont ID  
Sent By adarroug Date 2008-01-18 Time 12:14 Rev Time 0.00
Received By adarroug Date 2008-01-18 Time 12:14 Sent To B
Notes
2008-01-18 12:15:12TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 15 Status N Date 2008-01-18 Cont ID  
Sent By adarroug Date 2008-01-18 Time 12:13 Rev Time 0.00
Received By adarroug Date 2008-01-18 Time 12:13 Sent To B
Notes
2008-01-18 12:14:10TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2007-12-21 Cont ID  
Sent By spalmer Date 2007-12-21 Time 16:23 Rev Time 0.00
Received By spalmer Date 2007-12-21 Time 16:23 Sent To B
Notes
2007-12-21 16:23:29TO JIM WITMER

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2007-12-21 Cont ID  
Sent By spalmer Date 2007-12-21 Time 16:22 Rev Time 0.00
Received By spalmer Date 2007-12-21 Time 16:22 Sent To B
Notes
2007-12-21 16:22:50TO JIM WITMER

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2007-12-07 Cont ID  
Sent By adarroug Date 2007-12-07 Time 14:44 Rev Time 0.00
Received By adarroug Date 2007-12-07 Time 14:44 Sent To E
Notes
2007-12-07 14:44:40TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2007-12-07 Cont ID  
Sent By adarroug Date 2007-12-07 Time 14:38 Rev Time 0.00
Received By adarroug Date 2007-12-07 Time 14:38 Sent To B
Notes
2007-12-07 14:38:40TO "JWITMER" DESK/2 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2007-11-16 Cont ID  
Sent By adarroug Date 2007-11-16 Time 11:32 Rev Time 0.00
Received By adarroug Date 2007-11-16 Time 11:32 Sent To B
Notes
2007-11-16 11:32:47TO "JWITMER" DESK/6 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2007-11-02 Cont ID  
Sent By adarroug Date 2007-11-02 Time 11:56 Rev Time 0.00
Received By adarroug Date 2007-11-02 Time 11:55 Sent To B
Notes
2007-11-02 11:56:21TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2007-10-26 Cont ID  
Sent By shill Date 2007-10-26 Time 11:06 Rev Time 0.00
Received By shill Date 2007-10-26 Time 11:06 Sent To B
Notes
2007-10-26 11:07:04TO "JWITMER" DESK/4 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-10-25 Cont ID  
Sent By adarroug Date 2007-10-25 Time 16:49 Rev Time 0.00
Received By adarroug Date 2007-10-25 Time 16:47 Sent To B
Notes
2007-10-25 16:51:49TO "JWITME" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-10-25 Cont ID  
Sent By adarroug Date 2007-10-25 Time 16:32 Rev Time 0.00
Received By adarroug Date 2007-10-25 Time 16:32 Sent To ENG
Notes
2007-10-25 16:32:30TO "ENG' BOX/3 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-09-27 Cont ID  
Sent By adarroug Date 2007-09-27 Time 10:38 Rev Time 0.00
Received By adarroug Date 2007-09-27 Time 10:38 Sent To B
Notes
2007-09-27 10:38:52TO "JWITMER" DESK/3 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-08-28 Cont ID  
Sent By adarroug Date 2007-08-28 Time 11:35 Rev Time 0.00
Received By adarroug Date 2007-08-28 Time 11:35 Sent To B
Notes
2007-08-28 11:35:37TO "JWITMER" DESK/3 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-07-24 Cont ID  
Sent By adarroug Date 2007-07-24 Time 11:50 Rev Time 0.00
Received By adarroug Date 2007-07-24 Time 11:50 Sent To  
Notes
2007-07-24 11:51:23TO "COMM" BD#43/PLANS ON RACK--FOLDED PLANS AND SMALL
 ROLLED PLAN

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-05-23 Cont ID  
Sent By adarroug Date 2007-05-23 Time 10:10 Rev Time 0.00
Received By adarroug Date 2007-05-23 Time 10:10 Sent To  
Notes
2007-06-12 12:08:07TO "COMM" BD#7/ PLANS ON RACK--3 LARGE FOLDED AND 1
 ROLL
2007-05-23 10:10:52WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-04-30 Cont ID  
Sent By mawillia Date 2007-04-30 Time 18:26 Rev Time 0.00
Received By mawillia Date 2007-03-19 Time 14:36 Sent To  
Notes
2007-03-19 14:36:30TO "COMM" BD#28/PLANS ON RACK, 3 ROLLS

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-08-01 Cont ID  
Sent By rregueir Date 2007-08-01 Time 11:46 Rev Time 0.00
Received By rregueir Date 2007-08-01 Time 11:46 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-06-20 Cont ID  
Sent By rregueir Date 2007-06-20 Time 13:29 Rev Time 0.00
Received By rregueir Date 2007-06-19 Time 19:36 Sent To  
Notes
2007-06-20 13:28:24-----------DENIED--------------
  
 FBC 2004 CODE FAMILY W/ 2006 REVISIONS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 PG LS2.1.4: PLEASE PROVIDE SPECIFIC LOCATION, SIZE AND
 INSTALLATION DETAIL FOR THE FIRE DAMPER IN OFFICE
 STORAGE AREA PER FBC,M 607.8. ALSO, SEE FBC,M 607.2
 REGARDING FIRE DAMPER INSTALLATION INSTRUCTIONS.
 CONSULT FIRE DAMPER MANUFACTURER'S INSTALLATION
 INSTRUCTIONS FOR FRAMED WALL OPENING REQUIREMENTS AND
 INCLUDE WALL OPENING FRAMING DETAIL ON PLANS. FBC
 106.1.2
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J REGUEIRO
 561.805.6719

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2007-04-10 Cont ID  
Sent By rregueir Date 2007-04-10 Time 12:59 Rev Time 0.00
Received By rregueir Date 2007-04-04 Time 14:24 Sent To  
Notes
2007-04-10 12:59:11NO MECHANICAL REVIEW REQUIRED AT THIS TIME. THIS
 CONDITION COULD CHANGE IF ANY CHANGES ARE MADE TO THE
 GENERATOR RELATED TO FUEL TYPE, FUEL STORAGE AND/OR
 ONSITE REFUELING CAPABILITIES.
  
 RONALD J REGUEIRO
 561-805-6719
 [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-08-02 Cont ID  
Sent By jleech Date 2007-08-02 Time 08:36 Rev Time 0.00
Received By jleech Date 2007-08-02 Time 08:35 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-06-25 Cont ID  
Sent By kstevens Date 2007-06-25 Time 16:32 Rev Time 0.00
Received By kstevens Date 2007-06-25 Time 16:32 Sent To  
Notes
2007-06-25 17:28:03DENIED
 REFERENCE: FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW:
  
 1.
 2. OK
 3. OK
 4. OK
 5. OK
  
 6. SHTS LP-1, LP-2, LD-1, IRR-1 & IRR-2. THE ADDRESS
 SUBMITTED TO THE STATE OF FLORIDA DBPR WEBSITE SHALL
 ALSO BE ADDED TO THE TITLE BLOCK OF THE LANDSCAPE
 ARCHITECTS. (SEE ATTACHED SHEET FROM DBPR WEBSITE).
 ****RESPONSE NOTED, BUT NOW THE PRINTED NAME OF THE
 PERSON SEALING THE DOCUMENT IS NOT SHOWN AS WELL AS THE
 DATE THE SIGNATURE AND SEAL WERE AFFIXED TO THE PLANS
 IS NOT INDICATED BELOW THE SIGNATURE AS REQUIRED BY FAC
 61G1-16.004(5)(6).
  
 7. OK
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-04-26 Cont ID  
Sent By kstevens Date 2007-04-26 Time 10:52 Rev Time 0.00
Received By kstevens Date 2007-04-25 Time 18:56 Sent To  
Notes
2007-04-26 11:23:56DENIED
 REFERENCE: FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SURVEY SHEETS 2, 3 & 4 OF 4. ALL FINAL DRAWINGS,
 PLANS, SPECIFICATIONS, PLATS, OR REPORTS PREPARED ON
 ISSUED BY THE REGISTRANT SHALL BE SIGNED, DATED AND
 SEALED. FS 472.025.
  
 2. SHTS P2.50 & 2.60 MORE INFORMATION IS REQUIRED.
 INDICATE WHAT THE ABBREVIATION WDP STANDS FOR. THERE
 ARE 4 2" WDP'S SHOWN ON EACH FLOOR. PLEASE CLARIFY.
 SECTION 106.1.1.
  
 3. SHT P2.60 SUBMIT A RISER DIAGRAM SHOWING THE TYPICAL
 PLANTER BOX DRAIN PIPING. SHOW PIPE SIZES AND INDICATE
 THE TERMINATION POINT.SECTION 106.3.5.1.3(7)(13).
  
 4. SHT P2.80 STORM RISER DIAGRAM. SHOW ALL DRAINS
 CONNECTING TO THE RISER DIAGRAMS FOR EACH ADDED LEVEL.
 SHOW ALL PIPE SIZES TO EACH DRAIN. SECTION
 106.3.5.1.3(7)(13) AND TABLE 1106.3.
  
 5. ALL SHEETS WITH THE GARTEK ENGINEERING TITLE BLOCK.
 SOME OF THE INFORMATION IS NOT LEGIBLE. PLEASE CHECK
 TITLE BLOCK AND MAKE SURE ALL INFORMATION CAN BE READ.
 SECTION 106.1.1.
  
 6. SHTS LP-1, LP-2, LD-1, IRR-1 & IRR-2. THE ADDRESS
 SUBMITTED TO THE STATE OF FLORIDA DBPR WEBSITE SHALL
 ALSO BE ADDED TO THE TITLE BLOCK OF THE LANDSCAPE
 ARCHITECTS. (SEE ATTACHED SHEET FROM DBPR WEBSITE).
  
 7. SHTS IRR-1 & IRR-2 SHOW THE LOCATION OF THE
 CONTROLLER & THE RAIN SENSOR. SECTION 106.3.5.1.3(9). -
 THE PLUMBING PLANS INDICATE 11 3/4" IRRIGATION RISERS,
 BUT THE IRRIGATION PLANS ONLY SHOW 1. PLEASE CLARIFY.
 SECTION 106.1.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 3 Status P Date 2007-08-02 Cont ID  
Sent By astelly Date 2007-08-02 Time 16:03 Rev Time 0.00
Received By astelly Date 2007-08-02 Time 18:46 Sent To  
Notes
2007-08-02 18:02:42AMY F. STELLY
 URBAN DESIGN
 822-1440
  
 **PROVISO**
  
 1. PLEASE SUBMIT A SITE PLAN SHOWING THE LOCATION OF
 THE PROPOSED FUEL TANK.
 2. THE PROPOSED FUEL TANK MUST BE ENCLOSED AND SCREENED
 AS PER SECTION 94-444 OF THE ZONING CODE. THE MATERIAL
 AND ARTICULATION OF THE ENCLOSURE MUST BE COMPATIBLE
 WITH THE ARCHITECTURE OF THE PRINCIPAL STRUCTURE.
 ELEVATIONS SHOWING THE INTEGRATION OF THE SCREENING AND
 PRINCIPAL STRUCTURE MUST BE SUBMITTED.
 3. THESE CONDITIONS MUST BE SATISFIED WITHIN 30 DAYS OR
 THE PERMIT WILL BE REVOKED AS PER ROBERT BROWN.

Review Stop Z ZONING
Rev No 2 Status P Date 2007-06-30 Cont ID  
Sent By astelly Date 2007-06-30 Time 11:45 Rev Time 0.00
Received By astelly Date 2007-06-30 Time 12:21 Sent To  
Notes
2007-06-30 12:21:07AMY F. STELLY
 URBAN DESIGN
 822-1440
 APPROVED NEWLY SUBMITTED PARKING PLAN SHEETS.

Review Stop Z ZONING
Rev No 1 Status P Date 2007-04-05 Cont ID  
Sent By astelly Date 2007-04-05 Time 17:20 Rev Time 0.00
Received By astelly Date 2007-04-05 Time 17:20 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy