Plan Review Details - Permit 07030589
Plan Review Stops For Permit 07030589
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2007-03-19 Cont ID  
Sent By kstevens Date 2007-03-19 Time 18:29 Rev Time 0.00
Received By kstevens Date 2007-03-19 Time 18:29 Sent To  
Notes
2007-03-19 18:32:09********PASSED/PROVISO********
  
 A SHUT OFF VALVE IS REQUIRED UPSTREAM OF EACH
 REGULATOR.--BOTH VENT LINES FROM THE REGULATORS
 SHALL BE OF NON COMBUSTABLE MATERIAL.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-03-17 Cont ID  
Sent By kstevens Date 2007-03-17 Time 16:58 Rev Time 0.00
Received By kstevens Date 2007-03-17 Time 16:58 Sent To  
Notes
2007-03-17 17:12:09DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 A. THE FOLLOWING INFORMATION IS REQUIRED:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. NOT ALL CUT SECTIONS SHOWN.
  
 2. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 3. SUBMIT MANUFACTURE SHEET FOR ALL GAS REGULATORS.
 INDICATE THE MODEL NUMBER OF EACH REGULATOR.
  
 4. CPVC IS NOT AN APPROVED MATERIAL FOR THE REGULATOR
 VENTS. VENTS SHALL BE OF A NON-COMBUSTABLE MATERIAL.
 SECTION 410.3.
  
 5. A SHUT OFF VALVE IS REQUIRED UPSTREAM OF THE
 REGULATORS. SECTION 409.4.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-03-20 Cont ID  
Sent By lmartine Date 2007-03-16 Time 14:57 Rev Time 0.00
Received By spalmer Date 2007-03-20 Time 10:09 Sent To P
Notes
2007-03-16 15:01:47GAVE TO KENNY FOR SATURDAY REVIEW.
2007-03-16 10:43:02TO "G" BOX