Plan Review Details - Permit 07030577
Plan Review Stops For Permit 07030577
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-03-16 Cont ID  
Sent By rmcdouga Date 2007-03-16 Time 10:26 Rev Time 0.00
Received By rmcdouga Date 2007-03-15 Time 19:05 Sent To  
Notes
2007-03-16 10:26:21DENIED BY BUILDING
  
 1)THE STATE HAS NOT GIVEN FINAL APPROVAL TO THE
 PROTECTO WRAP UNDERLAYMENT. THE STATUS IS LISTED AS
 APPLIED FOR,AT THIS TIME. IN ORDER TO USE THIS
 PRODUCT IN THIS JURISDICTION, THE MANUFACTURER OR
 DISTRIBUTOR IS REQUIRED TO APPLY FOR LOCAL PRODUCT
 APPROVAL IN ACCORDANCE WITH FLORIDA BUILDING COMMISSION
 RULE 9B-72. SEE ATTACHED APPLICATION.
  
 2) THE PRODUCT INFORMATION SUBMITTED FOR THE ALTUSA
 CLAY TILE IS OUTDATED. THE NOA HAS BEEN SUPERCEEDED BY
 NOA 05-0901.06 AND THE NEW STATE NUMBER IS FL# 5559.
 PLEASE SUBMIT THE CURRENT PRODUCT APPROVALS.
  
 3) SPECIFY THE ATTACHMENT METHOD THAT WILL BE USED TO
 INSTALL THE CLAY ROOF TILE. CIRCLE THE APPROPRIATE ITEM
 ON THE NOA.
  
 4) THE NOA SUBMITTED FOR THE GAF MODIFIED ROOF SYSTEM
 HAS TWO DIFFERENT APPROVED ASSEMBLIES FOR SBS OVER AN
 INSULATED WOOD DECK. SPECIFY WHICH ONE WILL BE
 INSTALLED AND SPECIFY THE FASTENING OPTION AND MAXIMUM
 DESIGN PRESSURE THAT WILL BE USED. CIRCLE THE
 APPROPRIATE ITEMS ON THE NOA. SUBMIT RAS 117
 CALCULATIONS AS REQUIRED BY GENERAL LIMITATION #7 ON
 PAGE 32 FOR ROOF ZONES THAT REQUIRE ENHANCED FASTENING
 DUE TO HIGHER UPLIFT PRESSURES.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714