Plan Review Details - Permit 07030569
Plan Review Stops For Permit 07030569
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2008-04-17 Cont ID  
Sent By jgomez Date 2008-04-17 Time 13:16 Rev Time 0.00
Received By jgomez Date 2008-04-17 Time 12:38 Sent To PC
Notes
2008-04-17 13:16:40REVISED ENERGY CALCULATIONS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2008-04-02 Cont ID  
Sent By jgomez Date 2008-04-02 Time 14:37 Rev Time 0.00
Received By jgomez Date 2008-04-02 Time 14:30 Sent To M
Notes
2008-04-02 14:55:10ENERGY CALCULATIONS BUILDING REVIEW CHECKLIST:
  
 1- ENGINEER WHO PREPARED,SIGNED AND SEALEDTHE
 ENERGY CALCULATIONS NEEDS TO PROVIDE HIS INFORMATION AS
 REQUIRED BY CHAPTER 471 AND SEC. 61G15-23.002 FLORIDA
 ADMINISTRATIVE CODE.
  
 2-COORDINATE UNDER ATTIC AREA ITEM # 10A WITH
 ARCHITECTURAL PLANS.SEE ARCHITECTURAL PLANS FOR
 SPECIFIED INSULATION R VALUE.
  
 3- CEILING FAN CREDIT WAS TAKEN ON ITEM #15.THEN,
 NEED TO REVISE ELECTRICAL PLAN SHOWINGCEILING FAN
 SIZES TO BE INSTALLED IN ALL ROOMS AS REQUIRED BY TABLE
 13-607.1.A.1 FBC 2004.
  
 4- OWNER AGENT TO SIGN AND DATE BOTTOM OF FORM.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-01-28 Cont ID  
Sent By jgomez Date 2008-01-28 Time 14:19 Rev Time 0.00
Received By jgomez Date 2008-01-28 Time 14:19 Sent To  
Notes
2008-01-28 14:22:07MET WITH MR.POPP.LEGACY REPORT FOR ICYNENE WAS NOT
 USED.ONLY USING THE MANUFACTURER SPECIFICATIONS WHICH
 DOESN'T HAVE THE THICKNESS LIMITATIONS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-12-07 Cont ID  
Sent By jgomez Date 2007-12-07 Time 17:12 Rev Time 0.00
Received By jgomez Date 2007-12-07 Time 16:58 Sent To PC
Notes
2007-12-07 17:24:36BUILDING REVIEW APPROVED WITH PROVISO:
 1- REVISE ICYNENE R-VALUE INSULATION ON CEILING. SEE
 SEC. 7.4 OF LEGACY REPORT NER-420 SUBMITTEDFOR
 MAXIMUMALLOWED THICKNESS. REVISE ARCHITECTURAL
 DRAWINGS AS REQUIRED.
 2- REVISE ENERGY CALCULATIONS TO MATCHARCHITECTURAL
 DRAWINGS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-10-03 Cont ID  
Sent By jgomez Date 2007-10-03 Time 07:39 Rev Time 0.00
Received By jgomez Date 2007-10-02 Time 18:32 Sent To PC
Notes
2007-10-03 09:53:25RESIDENTIAL ADDITION BUILDING REVIEW SECOND CHECKLIST.
 REVIEW DONE UNDER 2004 FLORIDA RESIDENTIAL CODE AND
 2004 FBC.
  
 1- ONLY ONE SET OF PLANS WAS SIGNED AND SEALED.BOTH
 SETS NEED TO BE SIGNED AND SEALED BY THE ARCHITECT.
  
 2- OLD TITLE BLOCK WITH AA0002284 NUMBER WAS
 RESUBMITTED WITH REVISED DRAWINGS.REVISE TITLE BLOCK
 SHOWING ONLY THE NAME OF THE ARCHITECT AND HISFLORIDA
 LICENSE NUMBER AS REQUIRED BY SEC. 61G1-16.004 OF
 FLORIDA ADMINISTRATIVE CODE.
  
 3- AFTER ALL DRAWINGS ARE REVISED, BRING THEM TO PALM
 BEACH COUNTY (2300 N. JOG RD (561)233-5115.BRING
 BACK STAMPED PLANS AND COPY OF PAID RECEIPT.
 NOTE: THIS MIGHT BE DONE LATER ON TIME OF PERMIT PICK
 UP.
  
 4- PROVIDE COMPLETE INFORMATION SHOWING COMPLIANCE WITH
 CRAWL SPACESEC. R408 OF 2004 FLORIDA RESIDENTIAL
 CODE.PLANS DON'T COMPLY WITH VENTILATION LOCATION
 SEC. R408.1 AND SEC. R408.2 OF 2004 FLORIDA RESIDENTIAL
 CODE.ALSO,NEED TO PROVIDE ACCESS AS REQUIRED BY
 SEC. R408.3 OF 2004 FLORIDA RESIDENTIAL CODE.
 ***NOTE: PLEASE MAKE SURE THIS INFORMATION IS
 COORDINATED WITH ALL ARCHITECTURAL AND STRUCTURAL PLANS
 AND ELEVATIONS TO AVOID CONFLICTS AND DELAYS IN THE
 REVIEW PROCESS.
  
 5- PROVIDE COMPLETE SPECS SHOWING HOW COMPLYING WITH
 SEC. R319.1 OF 2004 FLORIDA RESIDENTIAL CODE REGARDING
 PROTECTION OF WOOD AGAINST DECAY.COPYING THIS CODE
 SECTION IN THE PLANS DOESN'T ANSWER THE QUESTION.
 CLEARLY SPECIFY HOW PROTECTING THE WOOD TO COMPLY WITH
 THIS SECTION.SEC. 106.1.2 CITY AMENDMENTS TO FBC
 2004.
  
 6- SPECIFY ROOF TILE FASTENING AS REQUIRED BY SEC.
 106.1.1.2 CITY AMENDMENTS TO FBC 2004.DESIGNER OF
 RECORD NEEDS TO SPECIFY FASTENING. PRODUCT APPROVAL IS
 JUST TO DEMONSTRATE THAT IT MEETS THE DESIGNER OF
 RECORD SPECIFICATIONS.REPEAT COMMENT. THIS COMMENT
 WAS NOT ADDRESSED AT ALL.
  
 7- A) PLANS WERE REVISED TO HAVE ICYNENE INSULATION.
 NEED TO PROVIDE COMPLETE SPECS FOR YCENENE INSULATION
 INSTALLATION TO VERIFY THAT INSULATION VALUES SHOWN ON
 THE ENERGY CALCULATIONS ARE MET. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 B) SPECIFY ICYNENE R VALUE IN ALL PLANS AND BUILDING
 SECTIONS TO SHOW COMPLIANCE WITH ENERGY CALCULATIONS.
 SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 8- SHEETS A-6 AND A-7:
 A) PLEASE MAKE SURE THAT FLOOR JOIST SIZE AND
 SPACINGSHOWN ON ALL ARCHITECTURAL SECTIONSMATCH
 STRUCTURAL DRAWINGS.
  
 B) CLARIFY IF EXTERIOR WALLS ARE GOING TO BE 2X4'S
 OR 2X6'S TO VERIFY COMPLIANCE WITH INSULATION VALUES
 SPECIFIED ON ENERGY CALCULATIONS. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 C) SPECIFY CLEARANCE FROMGRADE TO BOTTOM OF FLOOR
 JOIST TO VERIFY COMPLIANCE WITH SEC. R319 OF 2004
 FLORIDA RESIDENTIAL CODE.
  
 9- SOIL TEST REPORT:
 A) BOTH COPIES NEED TO HAVE ENGINEER'S ORIGINAL
 SEAL, SIGNATURE AND DATE AS REQUIRED BY SEC.
 61G15-23.002FLORIDA ADMINISTRATIVE CODE.
  
 B) ENGINEERING FIRM NEEDS TO WRITE IN ALL SHEETS THE
 FIRM'S CERTIFICATE OF AUTHORIZATIONNUMBER AS REQUIRED
 BY SEC. 61G15-23.002(2) OF FLORIDA STATUTE.
  
 C) THERE IS A TYPO ON THE ADDRESS. REVISE HOUSE
 NUMBER ASREQUIRED.
  
 10- PROPERTY IS LOCATED ON HISTORICAL SITE.PLEASE
 BRING ALL PLANS FOR HISTORICAL APPROVAL PRIOR TO
 SUBMITTAL TO THIS OFFICE.
  
 11- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCARULE
 9B-72 FOR:
 A) CLAY TILE.NOA #02-1115.02 SUBMITTED WAS
 SUPERSEDED. SEE ATTACHED COPY OF MIAMI DADE PRODUCT
 APPROVAL DIVISION. NEED TO PROVIDE CURRENT PRODUCT
 APPROVAL.
  
 12- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING)ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3CITY AMENDMENTS TO FBC 2004.
 REPEAT COMMENT. NOT ADDRESSED ON PREVIOUS CHECKLIST.
  
 13- ENERGY CALCULATIONS:
 A) PROVIDE COMPLETE INFORMATION ON TOP OF FORM
 (REPEAT COMMENT, NOT ADDRESSED).
  
 B) THERE IS NOT SLAB ON GRADE.SEE PLANS AND REVISE
 AS REQUIRED. (REPEAT COMMENT, NOT ADDRESSED).
  
 C) COORDINATE R VALUE WITH YCENENE INSULATION.
  
 D) ENGINEER WHO PREPARED CALCULATIONS NEEDS TO
 PROVIDE ALL HIS INFORMATION AS REQUIRED BY CHAPTER 471
 FLORIDA STATUTE AND FLORIDA ADMINISTRATIVE CODE.
 (REPEAT COMMENT, NOT ADDRESSED).
  
 E) OVERHANG LENGTH AND HEIGHT IS INCORRECT.(REPEAT
 COMMENT, NOT ADDRESSED).
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561) 805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-04-16 Cont ID  
Sent By jgomez Date 2007-04-16 Time 18:39 Rev Time 0.00
Received By jgomez Date 2007-04-16 Time 18:39 Sent To  
Notes
2007-04-17 15:44:52BUILDING REVIEWW CHECKLIST:
 1- PROVIDE ARCHITECT'S FIRM LICENSE NUMBER IN THE TITLE
 BLOCK AS REQUIRED BY SEC. 61G1-16.004 OF FLORIDA
 ADMINISTRATIVE CODE.
 ***NOTE: ARCHITECT'S TITLE BLOCK IS PEELING OFF FROM
 SHEET AND IS REVEALING ANOTHER ARCHITECT'S FIRM.
 UPDATE/REVISE ORIGINALSHEETS TO INCLUDE CORRECT AND
 CURRENT ARCHITECT'S FIRM NAME.
  
 2- AFTER ALL DRAWINGS ARE REVISED BRING THEMTO PALM
 BEACH COUNTY (2300 N. JOG RD. (561)233-5115) TO PAY
 IMPACT FEES. BRING BACK STAMPED PLANS AND COPY OF PAID
 RECEIPT IF ADDITIONAL FEES ARE DUE.
  
 3- PROVIDE COMPLETE INFORMATIONSHOWING COMPLIANCE
 WITH CRAWL SPACE VENTILATION SIZE AND LOCATION AND
 ACCESS. SEE SEC. R408OF 2004 FLORIDA RESIDENTIAL CODE
 AND PROVIDE INFORMATION AS REQUIRED.
 ***NOTE: KEEP IN MIND THAT THERE IS AN INTERIOR STEM
 WALL FOR INTERIOR BEARING WALL. SHOW CROSS VENTILATION
 AND ACCESS TO BOTH SIDES OF CRAWL SPACE.
  
 4- PROVIDE COMPLETE INFORMATION SHOWING COMPLIANCE WITH
 SEC. R319.1 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 5- PROVIDE COMPLETE SPECS SHOWING COMPLIANCE WITH SEC.
 R320 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 6- ENGINEERING FIRM CERTIFICATE OF AUTHORIZATION NUMBER
 27190 IS UNDER A DELINQUENT STATUS ACCORDING TO THE
 DBPR WEBSITE.ENGINEER NEEDS TO CONTACT DBPR AND
 REVISE STATUS AS REQUIRED TO COMPLY WITH SEC.
 61G15-23.002 OF FLORIDA ADMINISTRATIVE CODE.
  
 7- SPECIFY ROOF TILE FASTENING AS REQUIRED BY SEC.
 106.1.1.2 CITY AMENDMENTS TO FBC 2004TO VERIFY THAT
 PRODUCT APPROVAL MEETS THE CALCULATED UPLIFT LOADS.
  
 8-PROVIDE COMPLETE SPECS AND DETAILS SHOWING
 COMPLIANCE WITH SEC. R806 OF 2004 FLORIDA RESIDENTIAL
 CODE.
  
 9- SHEET SP-1: CLARIFY NOTE ON PROPOSED SITE PLAN
 REGARDING LOT GRADING. WHERE IS SEC. R104.3 TAKEN
 FROM?. ALSO, SPECIFY GRADING SO WATER IS NOT DRAINED
 INTONEIGHBOR'S PROPERTY.SEC. R401.3 2004 FLORIDA
 RESIDENTIAL CODE.
  
 10- SHEET A-1:
 A) FOOTING AND VENTILATION OPENINGS DON'T MATCH
 STRUCTURAL PLANS. REVISE AS REQUIRED.
 *NOTE: COORDINATE WITH ITEM #3 ABOVE.
 ***NOTE: REVISE INFORMATION ON EXTERIOR ELEVATIONS
 ALSO.
 B) REVISE CODE SECTION REFERENCED FOR WINDOW EGRESS.
 CORRECT CODE IS THE 2004 FLORIDA RESIDENTIAL CODE AND
 CORRECT SEC. IS SEC. R310. REVISE AS REQUIRED.
  
 11- SHEET A2:
 A) FLOOR AND ROOF JOIST SIZE AND SPACING TO MATCH
 STRUCTURAL DRAWINGS. REVISE AS REQUIRED.
 B) REVISE DESIGN CRITERIA. SEE 2004 FLORIDA
 RESIDENTIAL CODE AND 2004 FBC FOR CORRECT CODE
 SECTIONS.
 C) CLARIFY WHAT'S BWS 190MPH?
  
 12- SHEET A6 AND A7: COORDINATE SIZE AND SPACING OF
 FLOOR AND ROOF JOISTS WITH-STRUCTURAL DRAWINGS.
  
 13- SHEET S1:
 A) COORDINATE WITH ARCHITECT FOR CRAWL SPACE SIZE,
 LOCATION AND ACCESS. SEE ITEM #3 ABOVE.
 B) CLARIFY WHY 4" DROP SHOWN ON GROUND FLOOR PLAN.
 SEE ARCHITECTURAL PLANS.
 C) ENERGY CALCULATIONS CALL FOR R30 INSULATION ON
 ROOF.R30 INSULATION DOESN'T FEET ON 2X8 ROOF JOIST.
 REVISE AS REQUIRED.
  
 14- SHEET S2:
 A) TYPICAL INTERIOR WALL SECTION 06/S2: PROVIDE
 COMPLETE FASTENING SPECS OF FRAMED WALL TO STEM WALL.
 SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 15- SHEET S3:
 A) CLARIFY WHY ROOFS ABOVE FRENCH DOORS IN REAR
 ELEVATIONARE CONSIDERED TO BE ON ZONE 2 FOR
 COMPONENTS AND CLADDING UPLIFT LOAD SKETCH. SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004. ALSO, REVISE ROOF
 FASTENING SPECS FOR THESE ROOFS AS REQUIRED. SEE DETAIL
 09/S2.
 B) REVISE DETAILS 01/S3,02/S3 AND 03/S3TO MATCH
 ACTUAL CONDITIONS ON THIS PROJECT. SHOW THE STEM WALL
 AND COORDINATECONNECTORS AS SHOWN ON FRAMING PLANS
 AND OTHER DETAILS. SEC. 106.1.2 CITY AMENDMENTS TO FBC
 2004.
 C) THERE IS SOME OVERLAPPING INFORMATION SHOWN ON
 STRUCTURAL NOTES RIGHT BELOW THE WATERPROOF MEMBRANES
 NOTE. REVISE AS REQUIRED.
 D) REVISE MASONRY NOTE #2. SEE SEC. R606.4 OF 2004
 FLORIDA RESIDENTIAL CODE FOR MIN. COMPRESSIVE STRENGTH
 REQUIRED.
  
 16- PROVIDE SOIL TEST REPORT.
  
 17- DESIGNER OF RECORD TO SPECIFYSOIL BEARING
 CAPACITYASSUMED FOR THE DESIGN OF THIS STRUCTURE.
 SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 18- PROVIDE COMPLETE SPECS FOR CONSTRUCTION OF NEW
 PATIO SLAB. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 19- AFTER ALL PLANS ARE REVISED,PLEASE BRING THEM TO
 THE FIFTH FLOOR TO THE HISTORIC DISTRICT DEPARTMENT FOR
 APPROVAL AND STAMPING. THEN, RE-SUBMIT THEMTO THIS
 OFFICE.
  
 20- PROVIDE PRODUCT APPROVAL AS REQUIRED BY RULE 9B-72
 FOR:
 A) FLAT ROOF SYSTEM:
 * NEED LEGIBLE NOA.
 ** NEED TO SPECIFY SPECIFIC FASTENING OPTION. SEE
 SHEET 28 OF 32.
 *** NEED RAS 117 CALCULATIONS FOR NAIL ENHANCING AT
 PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL
 LIMITATION #7. SEE SHEET 32 OF 32.
  
 B) FIXED WINDOW WITH FROSTED GLASS. PICTURE WINDOW
 701 SUBMITTED IS FOR SINGLE HUNG WINDOWS AND IS
 EXPIRED.
 C) CLAY TILE.
  
 21- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 22- ENERGY CALCULATIONS:
 A) PROVIDE COMPLETE INFORMATION ON TOP OF FORM.
 B) THERE IS NOT SLAB ON GRADE. SEE PLANS.
 C) NEED TO HAVE R19 ON EXTERIOR 2X6 FRAMED WALLS.
  
 D) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM.
 E) ENGINEER WHO PREPARED CALCULATIONS NEEDS TO SIGN
 AND SEAL THEM AND PROVIDE ALL HIS INFORMATION AS
 REQUIRED BY CHAPTER 471 FLORIDA STATUTES AND FLORIDA
 ADMINISTRATIVE CODE.
 F) OVERHANG LENGTH AND HEIGHT IS INCORRECT.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-09-18 Cont ID  
Sent By btrobaug Date 2007-09-18 Time 08:29 Rev Time 0.00
Received By btrobaug Date 2007-09-18 Time 06:47 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-03-22 Cont ID  
Sent By btrobaug Date 2007-03-22 Time 14:11 Rev Time 0.75
Received By btrobaug Date 2007-03-22 Time 12:25 Sent To M
Notes
2007-03-22 13:03:51 
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THE RISER DIAGRAM INDICATES A NEW 150 AMP PANEL AND
 A PANEL INSIDE THE HOUSE. THE PLAN INDICATES EXISTING
 METER AND MAIN PANEL "A" ON THE OUTSIDE OF THE HOUSE.
 PLEASE CORRELATE AND IF THE PANEL IS INSIDE SHOW THE
 LOCATION ON THE PLAN.
  
 2} PER 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT.
  
 3} 250.50 GROUNDING ELECTRODE SYSTEM
 ALL GROUNDING ELECTRODES AS DESCRIBED IN 250.52(A)(1)
 THROUGH (A)(6) THAT ARE PRESENT AT EACH BUILDING OR
 STRUCTURE SERVED SHALL BE BONDED TOGETHER TO FORM THE
 GROUNDING ELECTRODE SYSTEM.SEE 250.52(A)(3) FOR
 FOOTER STEEL, AS IT WILL BE PRESENT AT THE NEW
 ADDITION. THIS IS THE BEST GROUNDING ELECTRODE THAT CAN
 BE USED.
  
 4} PROVIDE LOAD CALCULATIONS PER ARTICLE 220 PART III,
 STANDARD OR PART IV OPTIONAL, INDICATE METHOD USED.
 THERE ARE 5 NEW CIRCUITS IN THE "SCOPE OF WORK" NOTES,
 ONLY 3 IN THE "LOAD SUMMARY. THERE MUST BE A MINIMUM OF
 3 FOR LIGHTING, 1 FOR THE BATH PER 210.11(C)(3), 3 FOR
 THE TANKLESS @ 100 AMPS (24000 WATTS/240), 1 FOR THE
 NEW MICROWAVE, AND THE NAMEPLATE ON THE NEW OVEN SHOULD
 BE VERIFIED @ 7500W.
  
 5} PROVIDE A PANEL SCHEDULE PER 408.4. PLEASE SEE NEW
 VERBAGE FOR 2005 NEC: "THE IDENTIFICATION SHALL INCLUDE
 SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE
 DISTINGUISHED FROM ALL OTHERS."
  
 6} THE NOTE ABOUT SMOKE DETECTORS AND PALM BEACH COUNTY
 DO NOT APPLY TO WEST PALM BEACH OR THEIS PROJECT. SEE
 R313.1.1 RESIDENTIAL BUILDING CODE. ALSO LOCATE ON
 PLANS.ALSO SEE THE DEFINITION OF "SMOKE DETECTORS"
 11.8.2.1 NFPA-72, CLARIFY IF USING DETECTORS OR ALARMS,
 TO AVOID CONFUSION IN THE FIELD.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2008-04-09 Cont ID  
Sent By adarroug Date 2008-04-09 Time 16:57 Rev Time 0.00
Received By adarroug Date 2008-04-09 Time 16:57 Sent To M
Notes
2008-04-09 16:57:33TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2008-04-01 Cont ID  
Sent By adarroug Date 2008-04-01 Time 13:09 Rev Time 0.00
Received By adarroug Date 2008-04-01 Time 13:09 Sent To  
Notes
2008-04-01 13:10:02TO "JGOMEZ" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-03-13 Cont ID  
Sent By adarroug Date 2008-03-13 Time 16:15 Rev Time 0.00
Received By adarroug Date 2008-03-13 Time 16:15 Sent To M
Notes
2008-03-13 16:18:01TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-11-27 Cont ID  
Sent By adarroug Date 2007-11-27 Time 16:22 Rev Time 0.00
Received By adarroug Date 2007-11-27 Time 16:21 Sent To P
Notes
2007-11-27 16:22:31TO "P" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-09-17 Cont ID  
Sent By adarroug Date 2007-09-17 Time 14:36 Rev Time 0.00
Received By adarroug Date 2007-09-17 Time 14:36 Sent To E
Notes
2007-09-17 14:36:55TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-09-11 Cont ID  
Sent By adarroug Date 2007-09-11 Time 10:40 Rev Time 0.00
Received By adarroug Date 2007-09-11 Time 10:40 Sent To Z
Notes
2007-09-11 10:40:35TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-03-20 Cont ID  
Sent By adarroug Date 2007-03-20 Time 09:12 Rev Time 0.00
Received By adarroug Date 2007-03-20 Time 09:12 Sent To E
Notes
2007-03-20 09:12:36TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-04-16 Cont ID  
Sent By jgomez Date 2007-04-16 Time 18:39 Rev Time 0.00
Received By jgomez Date 2007-03-16 Time 09:42 Sent To  
Notes
2007-03-16 09:42:44TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2008-04-10 Cont ID  
Sent By tgordon Date 2008-04-10 Time 10:40 Rev Time 0.20
Received By tgordon Date 2008-04-10 Time 10:40 Sent To B
Notes
2008-04-10 10:40:40REVISION TO ENERGY CAL'S.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2008-04-02 Cont ID  
Sent By tgordon Date 2008-04-02 Time 15:41 Rev Time 0.30
Received By tgordon Date 2008-04-02 Time 15:41 Sent To  
Notes
2008-04-02 15:49:41PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) REVISED ENERGY CALCULATIONS LINE 13A SHOWS AN
 ELECTRIC HEAT PUMP SYSTEM, MECHANICAL PLAN ON FILE
 SHOWS A STRAIGHT COOLING SYSTEM BEING INSTALLED, PLEASE
 CORRECT ENERGY CALCULATIONS.
  
 2) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-103.3.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-03-14 Cont ID  
Sent By tgordon Date 2008-03-14 Time 11:33 Rev Time 0.30
Received By tgordon Date 2008-03-14 Time 11:33 Sent To  
Notes
2008-03-14 11:33:39REVISION TO MECH. PLANS.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-09-18 Cont ID  
Sent By tgordon Date 2007-09-18 Time 09:15 Rev Time 0.30
Received By tgordon Date 2007-09-18 Time 09:15 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-03-27 Cont ID  
Sent By tgordon Date 2007-03-27 Time 14:51 Rev Time 0.30
Received By tgordon Date 2007-03-27 Time 14:51 Sent To P
Notes
2007-03-27 15:02:00*** DENIED ***
 1) MAIN RETURN AIR GRILL MAY NOT BE LOCATED IN THE
 KITCHEN, SEE 2004 FBC/R M1602.2 (4).
  
 2) THE CLOTHES DRYER VENT MAY NOT TERMINATE NEAR THE
 A/C CONDENSER UNIT, SEE2004 FBC/M 501.2 .
  
 3) THE JOB ADDRESS NEEDS TO APPEAR IN THE TITLE BLOCK
 ON THE PLANS, SEE 2004 FBC 106.1.3 CITY WPB AMEND.
  
 4) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-600.3.ABC.2.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-12-07 Cont ID  
Sent By mperson Date 2007-12-07 Time 09:41 Rev Time 0.00
Received By mperson Date 2007-12-07 Time 09:41 Sent To B
Notes
2007-12-07 10:55:24****************PROVISO**************
 NOTE: IF TUB ACCESS PANEL IS REMOVED THE TUB SHALL NOT
 HAVE SLIP JOINT CONNECTIONS. PER *405.8, SLIP JOINT
 CONNECTIONS.
  
 NOTE: ROOF DOWNSPOUTS SHALL DISCHARGE AT LEAST 1 FOOT
 AWAY FROM THE STRUCTURE SIDEWALL ON SPLASH BLOCKS. PER
 *1503.6 PROTECTION AGAINST DECAY AND TERMITES.
  
 NOTE: PER *604.9 WATER HAMMER. A WATER-HAMMER
 ARRESTOR SHALL BE INSTALLED WHERE
 QUICK-CLOSING VALVES ARE UTILIZED. WATER-HAMMER
 ARRESTORS SHALL BE INSTALLED IN ACCORDANCE WITH THE
 MANUFACTURER'S SPECIFICATIONS.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-09-27 Cont ID  
Sent By mperson Date 2007-09-27 Time 08:36 Rev Time 0.00
Received By mperson Date 2007-09-27 Time 08:36 Sent To B
Notes
2007-09-27 09:31:43DENIED 2ND TIME
 REFERENCE:
 ** FBC-2004 WITH 05 & 06 REVISIONS, PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE (FAC).
 ** FLORIDA STATUTES (FS).
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS,
 SOME BASED ON PLANS NOW SUBMITTED, NEW DOCUMENTS BEING
 REVIEWED FOR THE FIRST TIME AND SOME NEW COMMENTS NOT
 MADE ON PREVIOUS REVIEWS.
  
 ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM
 PREVIOUS REVIEW WITH A NO, OK OR A NO/OK.
 THESE WILL BE FOR THE EXACT NUMERICAL NOTATION OF THE
 PREVIOUS REVIEW NOTES.
  
 A NO IS IF THE COMMENT WAS NOT FULLY ADDRESSED AND/OR
 FURTHER EXPLANATION OR CHANGES IN PLANS OR DOCUMENTS
 ARE STILL NEEDED. THIS REVIEWER WILL TRY TO BETTER
 EXPLAIN NOTE ABOVE PREVIOUS REVIEW COMMENT.
  
 AN OK WILL BE LABELED AS SUCH ON THE SAME NUMERICAL
 COMMENT AND WILL HAVE OLD NOTE REMOVED FROM COMMENTS.
  
 A NO/OK MEANS PART OF THE COMMENT MAY HAVE BEEN
 ADDRESSED, HOWEVER NOT ALL OF THE PREVIOUS REVIEW
 COMMENT MAY HAVE BEEN FULLY ADDRESSED.
  
 ** PLEASE SEE ANY NEW NOTES WILL BE ADDED TO THE END OF
 THE PREVIOUS REVIEW COMMENTS AND NOTED AS SUCH.
  
 1. **NO** SHEET D-1 INDICATES REMOVAL OF THE ACCESS
 DOOR TO THE BATH TUB WASTE AND OVERFLOW. PER FBC-2004
 W/-5 7 06 REV. PLUMBING SECTION 405.8 SLIP JOINT
 CONNECTIONS: FIXTURES WITH CONCEALED SLIP JOINT
 CONNECTIONS SHALL BE PROVIDED WITH AN ACCESS PANEL OR
 UTILITY SPACE AT LEAST 12 INCHES IN ITS SMALLEST
 DEMINSION OR OTHER APPROVED ARRANGEMENT SO AS TO
 PROVIDE ACCESS TO THE SLIP JOINT CONNECTIONS FOR
 INSPECTION AND REPAIR.
 NOTE: PLEASE ADD TO SHEET D-1 THAT THIS TUB WILL NOT
 HAVE ANY SLIP JOINT CONNECTIONS ON THE RESUBMITTAL.
  
 2. **OK**
  
 3. SHEET P-1 SANITARY ISOMETRIC RISER DIAGRAM THE
 FOLLOWING IS STILL REQUIRED FOR THE WASHING MACHINE.
 (A) **OK**
 (B) **OK**
 (C) **NO** 708.9 ACCESS SHALL BE PROVIDED TO ALL
 CLEANOUTS. PLEASE CLEARLY INDICATE ON THE RESUBMITTAL
 THAT THE CLEANOUT FOR THE WASHING MACHINE IS LOCATED AT
 THE BASE OF THE DRAINAGE STACK TO THE OUTSIDE OF THE
 BUILDING OR AT 4 FEET ABOVE FINNISH FLOOR TO THE INSIDE
 OF THE BUILDING ON THE RESUBMITTAL.
  
 4. **OK**
  
 5. **NO/OK** SHEET P-1 ISOMETRIC WATER RISER DIAGRAM:
 PER FBC-2004 W/05 & 06 REV., PLUMBING SECTION 604.9
 WATER HAMMER ARRESTORS ARE REQUIRED FOR QUICK CLOSING
 VALVES.
 NOTE: A WATER HAMMER ARRESTOR IS ALSO REQUIRED ON THE
 HOT WATER TO THE WASHING MACHINE. PLEASE ADD THE
 FOLLOWING NOTE TO THE WATER RISER DIAGRAM "WATER HAMMER
 ARRESTORS ARE TO BE INSTALLED PER FBC-2004 W/05 & 06
 REV. SECTION 604.9".
  
 6. **OK**
  
 7. **OK**
  
 8. **OK**
  
 9. **OK**
  
 ******THE FOLLOWING ARE NEW COMMENTS.
  
 10. SHEET P-1 SANITARY ISOMETRIC RISER DIAGRAM: THE
 ADDED DOUBLE COMPARTMENT SINK AND DISHWASHER DRAINAGE
 PIPING TO THE DRAWINGS IS WRONG PER FBC-2004 W/05 & 06
 REV. SECTION 909.1
 WET VENT PERMITTED: ONLY THE FIXTURES
 WITHIN THE BATHROOM GROUPS SHALL CONNECT
 TO THE WET-VENTED HORIZONTAL BRANCH
 DRAIN. ANY ADDITIONAL FIXTURES SHALL
 DISCHARGE DOWNSTREAM OF THE WET VENT.
 ALSO THIS PIPING NEEDS TO BE SIZED PER FBC-2004 CHAPTER
 1, SECTION 106.3.5.4.
  
 11. SHEET P-1 SANITARY RISER DIAGRAM AND PLUMBING
 FLOOR PLAN THE NEW SHOWER IN THE NEW MASTER BATH IS
 MISLABELED AS A TUB.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING IN RED INK
 ON THE INDICATED PLAN SHEETS BY THIS PLANS EXAMINER FOR
 REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-04-02 Cont ID  
Sent By mperson Date 2007-04-02 Time 11:26 Rev Time 1.25
Received By mperson Date 2007-04-02 Time 11:26 Sent To B
Notes
2007-04-02 13:27:58DENIED
 REFERENCE:
 ** FBC-2004 PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1.SHEET D-1 INDICATES REMOVAL OF THE ACCESS DOOR TO
 THE BATH TUB PLUMBING. PER FBC-2004 PLUMBING, SECTION
 405.8 SLIP JOINT CONNECTIONS: FIXTURES WITH CONCEALED
 SLIP JOINT CONNECTIONS SHALL BE PROVIDED WITH AN ACCESS
 PANEL OR UTILITY SPACE AT LEAST 12 INCHES IN ITS
 SMALLEST DEMINSION OR OTHER APPROVED ARRANGEMENT SO AS
 TO PROVIDE ACCESS TO THE SLIP JOINT CONNECTIONS FOR
 INSPECTION AND REPAIR.
  
 2. SHEETS A-3 AND A-6 INDICATEPARAPET WALLS ON THE
 PROPOSED NEW ADDITION.
 PLEASE PROVIDE A ROOF PLAN THAT INDICATES HOW THE ROOF
 WILL BE PITCHED TO PROPERLY DRAIN, AND INDICATE THE
 FOLLOWING INFORMATION PER THE FOLLOWING CODE
 REFERENCES.
 A} DETAIL OF ROOF INDICATING SQUARE FOOTAGE OF ROOF
 AND VERTICAL WALLS (PARAPET) DRAINING TO DOWNSPOUTS AND
 SCUPPERS TO VERIFY COMPLIANCE WITH FBC-2004 PLUMBING,
 SECTION 1106.
 B} VERTICAL CONDUCTORS AND LEADERS, PER FBC-2004
 PLUMBING, SECTION 1106.2
 C} VERTICAL WALLS, PER FBC-2004 PLUMBING, SECTION
 1106.4
 D} SCUPPERS, (PROVIDE DETAIL PER FBC-2004 BUILDING,
 SECTIONS 1503.4.2 AND 1503.4.3) SIZE PER FBC-2004
 PLUMBING, TABLE 1106.7.
 E} SECONDARY (EMERGENCY) ROOF DRAINS, PER FBC-2004
 PLUMBING, SECTION 1107.
 A) SECONDARY DRAINAGE REQUIRED, PER FBC-2004 PLUMBING,
 SECTION 1107.1.
 B) SEPERATE SYSTEMS REQUIRED PER FBC-2004 PLUMBING,
 SECTION 1107.2.
  
 3. SHEET P-1 SANITARY ISOMETRIC RISER DIAGRAM THE
 FOLLOWING INFORMATION IS REQUIRED FOR THE WASHING
 MACHINE:
  
 (A)802.4 STANDPIPES.STANDPIPES SHALL BE INDIVIDUALLY
 TRAPPED. STANDPIPES SHALL
 EXTEND A MINIMUM OF 18 INCHES (457MM)
 AND A MAXIMUM OF 42 INCHES (1066MM)
 ABOVE THE TRAP WEIR. ACCESS SHALL BE
 PROVIDED TO ALL STANDPIPES AND DRAINS
 FOR RODDING. PLEASE INDICATE THE STANDPIPE ON THE
 RESUBMITTAL
 (B)406.3 WASTE CONNECTION. THE TRAP AND FIXTURE
 DRAIN FOR AN AUTOMATIC CLOTHES WASHER STANDPIPE SHALL
 BE A MINIMUM OF 2 INCHES IN DIAMETER. PLEASE INDICATE
 THIS ON THE RESUBMITTAL.
 (C) 708.9ACCESS SHALL BE PROVIDED TO ALL CLEANOUTS.
 PLEASE CLEARLY INDICATE ON THE RESUBMITTAL THAT THE
 CLEANOUT IS TO THE OUTSIDE OF THE BUILDING DUE TO SHEET
 A-1 INDICATING "NEW STACK WASH/DRY".
  
 4. SHEET P-1 SANITARY ISOMETRIC RISER DIAGRAM: PLEASE
 SIZE ALL PIPING AND TRAPS PER FBC-2004 CHAPTER 1,
 SECTION 106.3.5.4 ON THE RESUBMITTAL.
  
 5. SHEET P-1 ISOMETRIC WATER RISER DIAGRAM: PER
 FBC-2004 PLUMBING, SECTION 604.9 WATER HAMMER ARRESTORS
 REQUIRED FOR QUICK CLOSING VALVES.
 NOTE: WASHING MACHINE AND NEW DISHWASHER INDICATED ON
 (SHEET A-1) REQUIRE WATER HAMMER ARRESTORS. PLEASE NOTE
 THIS ON THE RESUBMITTAL. PLEASE CLEARIFY IF THE NEW
 REF. FRZ. INDICATED ON (SHEET A-1) HAS AN ICE MAKER OR
 WATER DIS. ON THE RESUBMITTAL. IF ITS DOES WATER HAMMER
 ARRESTORS ARE REQUIRED AND NEED TO BE NOTED ON THE
 RESUBMITTAL.
  
 6. SHEET P-1 ISOMETRIC WATER DIAGRAM: PLEASE INDICATE
 EXPANSION CONTROL FOR WATER HEATER PER FBC-2004
 PLUMBING, SECTION 607.3.
  
 7. SHEET P-1 ISOMETRIC WATER RISER DIAGRAM: PLEASE
 INDICATE FOR NEW HOSE BIBB "REFERENCE GENERAL PLUMBING
 NOTE #14 FOR VACUUM BREAKER" ON THE RESUBMITTAL.
  
 8. PER FBC-2004 CHAPTER 1, SECTION 106.3 THE JOB
 ADDRESS NEEDS TO APPEAR ON ALL TITLE BLOCKS.
  
 9. SHEET P-2 PLEASE DELETE THE FLOOR/HUB DRAIN DETAIL,
 PLUMBING LEGEND AND TRAP PRIMER DIAGRAM ON THE
 RESUBMITTAL DUE TO THE FACT THAT THERE ARE NIETHER
 INDICATED ON THE PLANS.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop Z ZONING
Rev No 2 Status P Date 2007-09-16 Cont ID  
Sent By jroach Date 2007-09-16 Time 16:50 Rev Time 0.00
Received By jroach Date 2007-09-16 Time 16:50 Sent To I
Notes
2007-09-16 16:52:09***PROVISO***
  
 NEW ADDITIONAL SHALL BE A MINIMUM OF SIX (6) FROM THE
 EXISTING GARAGE...NOT A MAXIMUM (AS NOTED ON THE
 PLANS).
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2007-03-19 Cont ID  
Sent By jroach Date 2007-03-19 Time 17:36 Rev Time 0.00
Received By jroach Date 2007-03-19 Time 17:36 Sent To I
Notes
2007-03-19 17:49:19***FAILED***
  
 1) TWO (2) COPIES OF A RECENT SURVEY (WITHIN THE LAST
 YEAR) SHALL BE PROVIDED SHOWING THE LOCATION OF THE
 PROPOSED ADDITION AND THE SETBACKS.
  
 2) DIMENSIONS/SETBACKS SHALL BE PROVIDED ON THE SITE
 PLAN AND THE SURVEY INDICATING THE DISTANCE FROM THE
 PROPERTY LINE TO THE A/C UNIT.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.