Plan Review Stops For Permit 07030569 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
6 |
Status |
P |
Date |
2008-04-17 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2008-04-17 |
Time |
13:16 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2008-04-17 |
Time |
12:38 |
Sent To |
PC |
|
Notes |
2008-04-17 13:16:40 | REVISED ENERGY CALCULATIONS. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
5 |
Status |
F |
Date |
2008-04-02 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2008-04-02 |
Time |
14:37 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2008-04-02 |
Time |
14:30 |
Sent To |
M |
|
Notes |
2008-04-02 14:55:10 | ENERGY CALCULATIONS BUILDING REVIEW CHECKLIST: | | | | 1- ENGINEER WHO PREPARED,SIGNED AND SEALEDTHE | | ENERGY CALCULATIONS NEEDS TO PROVIDE HIS INFORMATION AS | | REQUIRED BY CHAPTER 471 AND SEC. 61G15-23.002 FLORIDA | | ADMINISTRATIVE CODE. | | | | 2-COORDINATE UNDER ATTIC AREA ITEM # 10A WITH | | ARCHITECTURAL PLANS.SEE ARCHITECTURAL PLANS FOR | | SPECIFIED INSULATION R VALUE. | | | | 3- CEILING FAN CREDIT WAS TAKEN ON ITEM #15.THEN, | | NEED TO REVISE ELECTRICAL PLAN SHOWINGCEILING FAN | | SIZES TO BE INSTALLED IN ALL ROOMS AS REQUIRED BY TABLE | | 13-607.1.A.1 FBC 2004. | | | | 4- OWNER AGENT TO SIGN AND DATE BOTTOM OF FORM. | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2008-01-28 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2008-01-28 |
Time |
14:19 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2008-01-28 |
Time |
14:19 |
Sent To |
|
|
Notes |
2008-01-28 14:22:07 | MET WITH MR.POPP.LEGACY REPORT FOR ICYNENE WAS NOT | | USED.ONLY USING THE MANUFACTURER SPECIFICATIONS WHICH | | DOESN'T HAVE THE THICKNESS LIMITATIONS. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2007-12-07 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2007-12-07 |
Time |
17:12 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2007-12-07 |
Time |
16:58 |
Sent To |
PC |
|
Notes |
2007-12-07 17:24:36 | BUILDING REVIEW APPROVED WITH PROVISO: | | 1- REVISE ICYNENE R-VALUE INSULATION ON CEILING. SEE | | SEC. 7.4 OF LEGACY REPORT NER-420 SUBMITTEDFOR | | MAXIMUMALLOWED THICKNESS. REVISE ARCHITECTURAL | | DRAWINGS AS REQUIRED. | | 2- REVISE ENERGY CALCULATIONS TO MATCHARCHITECTURAL | | DRAWINGS. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2007-10-03 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2007-10-03 |
Time |
07:39 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2007-10-02 |
Time |
18:32 |
Sent To |
PC |
|
Notes |
2007-10-03 09:53:25 | RESIDENTIAL ADDITION BUILDING REVIEW SECOND CHECKLIST. | | REVIEW DONE UNDER 2004 FLORIDA RESIDENTIAL CODE AND | | 2004 FBC. | | | | 1- ONLY ONE SET OF PLANS WAS SIGNED AND SEALED.BOTH | | SETS NEED TO BE SIGNED AND SEALED BY THE ARCHITECT. | | | | 2- OLD TITLE BLOCK WITH AA0002284 NUMBER WAS | | RESUBMITTED WITH REVISED DRAWINGS.REVISE TITLE BLOCK | | SHOWING ONLY THE NAME OF THE ARCHITECT AND HISFLORIDA | | LICENSE NUMBER AS REQUIRED BY SEC. 61G1-16.004 OF | | FLORIDA ADMINISTRATIVE CODE. | | | | 3- AFTER ALL DRAWINGS ARE REVISED, BRING THEM TO PALM | | BEACH COUNTY (2300 N. JOG RD (561)233-5115.BRING | | BACK STAMPED PLANS AND COPY OF PAID RECEIPT. | | NOTE: THIS MIGHT BE DONE LATER ON TIME OF PERMIT PICK | | UP. | | | | 4- PROVIDE COMPLETE INFORMATION SHOWING COMPLIANCE WITH | | CRAWL SPACESEC. R408 OF 2004 FLORIDA RESIDENTIAL | | CODE.PLANS DON'T COMPLY WITH VENTILATION LOCATION | | SEC. R408.1 AND SEC. R408.2 OF 2004 FLORIDA RESIDENTIAL | | CODE.ALSO,NEED TO PROVIDE ACCESS AS REQUIRED BY | | SEC. R408.3 OF 2004 FLORIDA RESIDENTIAL CODE. | | ***NOTE: PLEASE MAKE SURE THIS INFORMATION IS | | COORDINATED WITH ALL ARCHITECTURAL AND STRUCTURAL PLANS | | AND ELEVATIONS TO AVOID CONFLICTS AND DELAYS IN THE | | REVIEW PROCESS. | | | | 5- PROVIDE COMPLETE SPECS SHOWING HOW COMPLYING WITH | | SEC. R319.1 OF 2004 FLORIDA RESIDENTIAL CODE REGARDING | | PROTECTION OF WOOD AGAINST DECAY.COPYING THIS CODE | | SECTION IN THE PLANS DOESN'T ANSWER THE QUESTION. | | CLEARLY SPECIFY HOW PROTECTING THE WOOD TO COMPLY WITH | | THIS SECTION.SEC. 106.1.2 CITY AMENDMENTS TO FBC | | 2004. | | | | 6- SPECIFY ROOF TILE FASTENING AS REQUIRED BY SEC. | | 106.1.1.2 CITY AMENDMENTS TO FBC 2004.DESIGNER OF | | RECORD NEEDS TO SPECIFY FASTENING. PRODUCT APPROVAL IS | | JUST TO DEMONSTRATE THAT IT MEETS THE DESIGNER OF | | RECORD SPECIFICATIONS.REPEAT COMMENT. THIS COMMENT | | WAS NOT ADDRESSED AT ALL. | | | | 7- A) PLANS WERE REVISED TO HAVE ICYNENE INSULATION. | | NEED TO PROVIDE COMPLETE SPECS FOR YCENENE INSULATION | | INSTALLATION TO VERIFY THAT INSULATION VALUES SHOWN ON | | THE ENERGY CALCULATIONS ARE MET. SEC. 106.1.2 CITY | | AMENDMENTS TO FBC 2004. | | | | B) SPECIFY ICYNENE R VALUE IN ALL PLANS AND BUILDING | | SECTIONS TO SHOW COMPLIANCE WITH ENERGY CALCULATIONS. | | SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. | | | | 8- SHEETS A-6 AND A-7: | | A) PLEASE MAKE SURE THAT FLOOR JOIST SIZE AND | | SPACINGSHOWN ON ALL ARCHITECTURAL SECTIONSMATCH | | STRUCTURAL DRAWINGS. | | | | B) CLARIFY IF EXTERIOR WALLS ARE GOING TO BE 2X4'S | | OR 2X6'S TO VERIFY COMPLIANCE WITH INSULATION VALUES | | SPECIFIED ON ENERGY CALCULATIONS. SEC. 106.1.2 CITY | | AMENDMENTS TO FBC 2004. | | | | C) SPECIFY CLEARANCE FROMGRADE TO BOTTOM OF FLOOR | | JOIST TO VERIFY COMPLIANCE WITH SEC. R319 OF 2004 | | FLORIDA RESIDENTIAL CODE. | | | | 9- SOIL TEST REPORT: | | A) BOTH COPIES NEED TO HAVE ENGINEER'S ORIGINAL | | SEAL, SIGNATURE AND DATE AS REQUIRED BY SEC. | | 61G15-23.002FLORIDA ADMINISTRATIVE CODE. | | | | B) ENGINEERING FIRM NEEDS TO WRITE IN ALL SHEETS THE | | FIRM'S CERTIFICATE OF AUTHORIZATIONNUMBER AS REQUIRED | | BY SEC. 61G15-23.002(2) OF FLORIDA STATUTE. | | | | C) THERE IS A TYPO ON THE ADDRESS. REVISE HOUSE | | NUMBER ASREQUIRED. | | | | 10- PROPERTY IS LOCATED ON HISTORICAL SITE.PLEASE | | BRING ALL PLANS FOR HISTORICAL APPROVAL PRIOR TO | | SUBMITTAL TO THIS OFFICE. | | | | 11- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCARULE | | 9B-72 FOR: | | A) CLAY TILE.NOA #02-1115.02 SUBMITTED WAS | | SUPERSEDED. SEE ATTACHED COPY OF MIAMI DADE PRODUCT | | APPROVAL DIVISION. NEED TO PROVIDE CURRENT PRODUCT | | APPROVAL. | | | | 12- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING | | (NOT SIGNING AND SEALING)ALL PRODUCT APPROVALS AS | | REQUIRED BY SEC. 106.3.3CITY AMENDMENTS TO FBC 2004. | | REPEAT COMMENT. NOT ADDRESSED ON PREVIOUS CHECKLIST. | | | | 13- ENERGY CALCULATIONS: | | A) PROVIDE COMPLETE INFORMATION ON TOP OF FORM | | (REPEAT COMMENT, NOT ADDRESSED). | | | | B) THERE IS NOT SLAB ON GRADE.SEE PLANS AND REVISE | | AS REQUIRED. (REPEAT COMMENT, NOT ADDRESSED). | | | | C) COORDINATE R VALUE WITH YCENENE INSULATION. | | | | D) ENGINEER WHO PREPARED CALCULATIONS NEEDS TO | | PROVIDE ALL HIS INFORMATION AS REQUIRED BY CHAPTER 471 | | FLORIDA STATUTE AND FLORIDA ADMINISTRATIVE CODE. | | (REPEAT COMMENT, NOT ADDRESSED). | | | | E) OVERHANG LENGTH AND HEIGHT IS INCORRECT.(REPEAT | | COMMENT, NOT ADDRESSED). | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561) 805-6712 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2007-04-16 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2007-04-16 |
Time |
18:39 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2007-04-16 |
Time |
18:39 |
Sent To |
|
|
Notes |
2007-04-17 15:44:52 | BUILDING REVIEWW CHECKLIST: | | 1- PROVIDE ARCHITECT'S FIRM LICENSE NUMBER IN THE TITLE | | BLOCK AS REQUIRED BY SEC. 61G1-16.004 OF FLORIDA | | ADMINISTRATIVE CODE. | | ***NOTE: ARCHITECT'S TITLE BLOCK IS PEELING OFF FROM | | SHEET AND IS REVEALING ANOTHER ARCHITECT'S FIRM. | | UPDATE/REVISE ORIGINALSHEETS TO INCLUDE CORRECT AND | | CURRENT ARCHITECT'S FIRM NAME. | | | | 2- AFTER ALL DRAWINGS ARE REVISED BRING THEMTO PALM | | BEACH COUNTY (2300 N. JOG RD. (561)233-5115) TO PAY | | IMPACT FEES. BRING BACK STAMPED PLANS AND COPY OF PAID | | RECEIPT IF ADDITIONAL FEES ARE DUE. | | | | 3- PROVIDE COMPLETE INFORMATIONSHOWING COMPLIANCE | | WITH CRAWL SPACE VENTILATION SIZE AND LOCATION AND | | ACCESS. SEE SEC. R408OF 2004 FLORIDA RESIDENTIAL CODE | | AND PROVIDE INFORMATION AS REQUIRED. | | ***NOTE: KEEP IN MIND THAT THERE IS AN INTERIOR STEM | | WALL FOR INTERIOR BEARING WALL. SHOW CROSS VENTILATION | | AND ACCESS TO BOTH SIDES OF CRAWL SPACE. | | | | 4- PROVIDE COMPLETE INFORMATION SHOWING COMPLIANCE WITH | | SEC. R319.1 OF 2004 FLORIDA RESIDENTIAL CODE. | | | | 5- PROVIDE COMPLETE SPECS SHOWING COMPLIANCE WITH SEC. | | R320 OF 2004 FLORIDA RESIDENTIAL CODE. | | | | 6- ENGINEERING FIRM CERTIFICATE OF AUTHORIZATION NUMBER | | 27190 IS UNDER A DELINQUENT STATUS ACCORDING TO THE | | DBPR WEBSITE.ENGINEER NEEDS TO CONTACT DBPR AND | | REVISE STATUS AS REQUIRED TO COMPLY WITH SEC. | | 61G15-23.002 OF FLORIDA ADMINISTRATIVE CODE. | | | | 7- SPECIFY ROOF TILE FASTENING AS REQUIRED BY SEC. | | 106.1.1.2 CITY AMENDMENTS TO FBC 2004TO VERIFY THAT | | PRODUCT APPROVAL MEETS THE CALCULATED UPLIFT LOADS. | | | | 8-PROVIDE COMPLETE SPECS AND DETAILS SHOWING | | COMPLIANCE WITH SEC. R806 OF 2004 FLORIDA RESIDENTIAL | | CODE. | | | | 9- SHEET SP-1: CLARIFY NOTE ON PROPOSED SITE PLAN | | REGARDING LOT GRADING. WHERE IS SEC. R104.3 TAKEN | | FROM?. ALSO, SPECIFY GRADING SO WATER IS NOT DRAINED | | INTONEIGHBOR'S PROPERTY.SEC. R401.3 2004 FLORIDA | | RESIDENTIAL CODE. | | | | 10- SHEET A-1: | | A) FOOTING AND VENTILATION OPENINGS DON'T MATCH | | STRUCTURAL PLANS. REVISE AS REQUIRED. | | *NOTE: COORDINATE WITH ITEM #3 ABOVE. | | ***NOTE: REVISE INFORMATION ON EXTERIOR ELEVATIONS | | ALSO. | | B) REVISE CODE SECTION REFERENCED FOR WINDOW EGRESS. | | CORRECT CODE IS THE 2004 FLORIDA RESIDENTIAL CODE AND | | CORRECT SEC. IS SEC. R310. REVISE AS REQUIRED. | | | | 11- SHEET A2: | | A) FLOOR AND ROOF JOIST SIZE AND SPACING TO MATCH | | STRUCTURAL DRAWINGS. REVISE AS REQUIRED. | | B) REVISE DESIGN CRITERIA. SEE 2004 FLORIDA | | RESIDENTIAL CODE AND 2004 FBC FOR CORRECT CODE | | SECTIONS. | | C) CLARIFY WHAT'S BWS 190MPH? | | | | 12- SHEET A6 AND A7: COORDINATE SIZE AND SPACING OF | | FLOOR AND ROOF JOISTS WITH-STRUCTURAL DRAWINGS. | | | | 13- SHEET S1: | | A) COORDINATE WITH ARCHITECT FOR CRAWL SPACE SIZE, | | LOCATION AND ACCESS. SEE ITEM #3 ABOVE. | | B) CLARIFY WHY 4" DROP SHOWN ON GROUND FLOOR PLAN. | | SEE ARCHITECTURAL PLANS. | | C) ENERGY CALCULATIONS CALL FOR R30 INSULATION ON | | ROOF.R30 INSULATION DOESN'T FEET ON 2X8 ROOF JOIST. | | REVISE AS REQUIRED. | | | | 14- SHEET S2: | | A) TYPICAL INTERIOR WALL SECTION 06/S2: PROVIDE | | COMPLETE FASTENING SPECS OF FRAMED WALL TO STEM WALL. | | SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. | | | | 15- SHEET S3: | | A) CLARIFY WHY ROOFS ABOVE FRENCH DOORS IN REAR | | ELEVATIONARE CONSIDERED TO BE ON ZONE 2 FOR | | COMPONENTS AND CLADDING UPLIFT LOAD SKETCH. SEC. | | 106.1.2 CITY AMENDMENTS TO FBC 2004. ALSO, REVISE ROOF | | FASTENING SPECS FOR THESE ROOFS AS REQUIRED. SEE DETAIL | | 09/S2. | | B) REVISE DETAILS 01/S3,02/S3 AND 03/S3TO MATCH | | ACTUAL CONDITIONS ON THIS PROJECT. SHOW THE STEM WALL | | AND COORDINATECONNECTORS AS SHOWN ON FRAMING PLANS | | AND OTHER DETAILS. SEC. 106.1.2 CITY AMENDMENTS TO FBC | | 2004. | | C) THERE IS SOME OVERLAPPING INFORMATION SHOWN ON | | STRUCTURAL NOTES RIGHT BELOW THE WATERPROOF MEMBRANES | | NOTE. REVISE AS REQUIRED. | | D) REVISE MASONRY NOTE #2. SEE SEC. R606.4 OF 2004 | | FLORIDA RESIDENTIAL CODE FOR MIN. COMPRESSIVE STRENGTH | | REQUIRED. | | | | 16- PROVIDE SOIL TEST REPORT. | | | | 17- DESIGNER OF RECORD TO SPECIFYSOIL BEARING | | CAPACITYASSUMED FOR THE DESIGN OF THIS STRUCTURE. | | SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. | | | | 18- PROVIDE COMPLETE SPECS FOR CONSTRUCTION OF NEW | | PATIO SLAB. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. | | | | 19- AFTER ALL PLANS ARE REVISED,PLEASE BRING THEM TO | | THE FIFTH FLOOR TO THE HISTORIC DISTRICT DEPARTMENT FOR | | APPROVAL AND STAMPING. THEN, RE-SUBMIT THEMTO THIS | | OFFICE. | | | | 20- PROVIDE PRODUCT APPROVAL AS REQUIRED BY RULE 9B-72 | | FOR: | | A) FLAT ROOF SYSTEM: | | * NEED LEGIBLE NOA. | | ** NEED TO SPECIFY SPECIFIC FASTENING OPTION. SEE | | SHEET 28 OF 32. | | *** NEED RAS 117 CALCULATIONS FOR NAIL ENHANCING AT | | PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL | | LIMITATION #7. SEE SHEET 32 OF 32. | | | | B) FIXED WINDOW WITH FROSTED GLASS. PICTURE WINDOW | | 701 SUBMITTED IS FOR SINGLE HUNG WINDOWS AND IS | | EXPIRED. | | C) CLAY TILE. | | | | 21- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING | | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS | | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. | | | | 22- ENERGY CALCULATIONS: | | A) PROVIDE COMPLETE INFORMATION ON TOP OF FORM. | | B) THERE IS NOT SLAB ON GRADE. SEE PLANS. | | C) NEED TO HAVE R19 ON EXTERIOR 2X6 FRAMED WALLS. | | | | D) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM. | | E) ENGINEER WHO PREPARED CALCULATIONS NEEDS TO SIGN | | AND SEAL THEM AND PROVIDE ALL HIS INFORMATION AS | | REQUIRED BY CHAPTER 471 FLORIDA STATUTES AND FLORIDA | | ADMINISTRATIVE CODE. | | F) OVERHANG LENGTH AND HEIGHT IS INCORRECT. | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2007-09-18 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2007-09-18 |
Time |
08:29 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2007-09-18 |
Time |
06:47 |
Sent To |
M |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2007-03-22 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2007-03-22 |
Time |
14:11 |
Rev Time |
0.75 |
Received By |
btrobaug |
Date |
2007-03-22 |
Time |
12:25 |
Sent To |
M |
|
Notes |
2007-03-22 13:03:51 | | | | | | | NONCOMPLIANT | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | 1} THE RISER DIAGRAM INDICATES A NEW 150 AMP PANEL AND | | A PANEL INSIDE THE HOUSE. THE PLAN INDICATES EXISTING | | METER AND MAIN PANEL "A" ON THE OUTSIDE OF THE HOUSE. | | PLEASE CORRELATE AND IF THE PANEL IS INSIDE SHOW THE | | LOCATION ON THE PLAN. | | | | 2} PER 110.9 AND 110.10: OBTAIN THE | | AVAILABLE FAULT CURRENT AT THE UTILITY | | AND CALCULATE THE SAME AT THE EQUIPMENT. | | INDICATE THE AIC RATING FOR THE | | EQUIPMENT IS EQUAL TO OR GREATER THAN | | THE AVAILABLE FAULT. | | | | 3} 250.50 GROUNDING ELECTRODE SYSTEM | | ALL GROUNDING ELECTRODES AS DESCRIBED IN 250.52(A)(1) | | THROUGH (A)(6) THAT ARE PRESENT AT EACH BUILDING OR | | STRUCTURE SERVED SHALL BE BONDED TOGETHER TO FORM THE | | GROUNDING ELECTRODE SYSTEM.SEE 250.52(A)(3) FOR | | FOOTER STEEL, AS IT WILL BE PRESENT AT THE NEW | | ADDITION. THIS IS THE BEST GROUNDING ELECTRODE THAT CAN | | BE USED. | | | | 4} PROVIDE LOAD CALCULATIONS PER ARTICLE 220 PART III, | | STANDARD OR PART IV OPTIONAL, INDICATE METHOD USED. | | THERE ARE 5 NEW CIRCUITS IN THE "SCOPE OF WORK" NOTES, | | ONLY 3 IN THE "LOAD SUMMARY. THERE MUST BE A MINIMUM OF | | 3 FOR LIGHTING, 1 FOR THE BATH PER 210.11(C)(3), 3 FOR | | THE TANKLESS @ 100 AMPS (24000 WATTS/240), 1 FOR THE | | NEW MICROWAVE, AND THE NAMEPLATE ON THE NEW OVEN SHOULD | | BE VERIFIED @ 7500W. | | | | 5} PROVIDE A PANEL SCHEDULE PER 408.4. PLEASE SEE NEW | | VERBAGE FOR 2005 NEC: "THE IDENTIFICATION SHALL INCLUDE | | SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE | | DISTINGUISHED FROM ALL OTHERS." | | | | 6} THE NOTE ABOUT SMOKE DETECTORS AND PALM BEACH COUNTY | | DO NOT APPLY TO WEST PALM BEACH OR THEIS PROJECT. SEE | | R313.1.1 RESIDENTIAL BUILDING CODE. ALSO LOCATE ON | | PLANS.ALSO SEE THE DEFINITION OF "SMOKE DETECTORS" | | 11.8.2.1 NFPA-72, CLARIFY IF USING DETECTORS OR ALARMS, | | TO AVOID CONFUSION IN THE FIELD. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 | | [email protected] | | | | | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
8 |
Status |
N |
Date |
2008-04-09 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-04-09 |
Time |
16:57 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-04-09 |
Time |
16:57 |
Sent To |
M |
|
Notes |
2008-04-09 16:57:33 | TO "M" BOX/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
7 |
Status |
N |
Date |
2008-04-01 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-04-01 |
Time |
13:09 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-04-01 |
Time |
13:09 |
Sent To |
|
|
Notes |
2008-04-01 13:10:02 | TO "JGOMEZ" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
6 |
Status |
N |
Date |
2008-03-13 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-03-13 |
Time |
16:15 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-03-13 |
Time |
16:15 |
Sent To |
M |
|
Notes |
2008-03-13 16:18:01 | TO "M" BOX/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2007-11-27 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-11-27 |
Time |
16:22 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-11-27 |
Time |
16:21 |
Sent To |
P |
|
Notes |
2007-11-27 16:22:31 | TO "P" BOX/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2007-09-17 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-09-17 |
Time |
14:36 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-09-17 |
Time |
14:36 |
Sent To |
E |
|
Notes |
2007-09-17 14:36:55 | TO "BTROBAUG" DESK/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2007-09-11 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-09-11 |
Time |
10:40 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-09-11 |
Time |
10:40 |
Sent To |
Z |
|
Notes |
2007-09-11 10:40:35 | TO "Z" BOX/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2007-03-20 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-03-20 |
Time |
09:12 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-03-20 |
Time |
09:12 |
Sent To |
E |
|
Notes |
2007-03-20 09:12:36 | TO "E" BOX |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2007-04-16 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2007-04-16 |
Time |
18:39 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2007-03-16 |
Time |
09:42 |
Sent To |
|
|
Notes |
2007-03-16 09:42:44 | TO "Z" BOX |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
5 |
Status |
P |
Date |
2008-04-10 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2008-04-10 |
Time |
10:40 |
Rev Time |
0.20 |
Received By |
tgordon |
Date |
2008-04-10 |
Time |
10:40 |
Sent To |
B |
|
Notes |
2008-04-10 10:40:40 | REVISION TO ENERGY CAL'S. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
4 |
Status |
F |
Date |
2008-04-02 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2008-04-02 |
Time |
15:41 |
Rev Time |
0.30 |
Received By |
tgordon |
Date |
2008-04-02 |
Time |
15:41 |
Sent To |
|
|
Notes |
2008-04-02 15:49:41 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | (F.S.). | | | | *** DENIED *** | | 1) REVISED ENERGY CALCULATIONS LINE 13A SHOWS AN | | ELECTRIC HEAT PUMP SYSTEM, MECHANICAL PLAN ON FILE | | SHOWS A STRAIGHT COOLING SYSTEM BEING INSTALLED, PLEASE | | CORRECT ENERGY CALCULATIONS. | | | | 2) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT | | ALSO, PER 2004 FBC 13-103.3. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729 | | E-MAIL; [email protected] |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2008-03-14 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2008-03-14 |
Time |
11:33 |
Rev Time |
0.30 |
Received By |
tgordon |
Date |
2008-03-14 |
Time |
11:33 |
Sent To |
|
|
Notes |
2008-03-14 11:33:39 | REVISION TO MECH. PLANS. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2007-09-18 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2007-09-18 |
Time |
09:15 |
Rev Time |
0.30 |
Received By |
tgordon |
Date |
2007-09-18 |
Time |
09:15 |
Sent To |
P |
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2007-03-27 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2007-03-27 |
Time |
14:51 |
Rev Time |
0.30 |
Received By |
tgordon |
Date |
2007-03-27 |
Time |
14:51 |
Sent To |
P |
|
Notes |
2007-03-27 15:02:00 | *** DENIED *** | | 1) MAIN RETURN AIR GRILL MAY NOT BE LOCATED IN THE | | KITCHEN, SEE 2004 FBC/R M1602.2 (4). | | | | 2) THE CLOTHES DRYER VENT MAY NOT TERMINATE NEAR THE | | A/C CONDENSER UNIT, SEE2004 FBC/M 501.2 . | | | | 3) THE JOB ADDRESS NEEDS TO APPEAR IN THE TITLE BLOCK | | ON THE PLANS, SEE 2004 FBC 106.1.3 CITY WPB AMEND. | | | | 4) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT | | ALSO, PER 2004 FBC 13-600.3.ABC.2. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2007-12-07 |
|
|
Cont ID |
|
Sent By |
mperson |
Date |
2007-12-07 |
Time |
09:41 |
Rev Time |
0.00 |
Received By |
mperson |
Date |
2007-12-07 |
Time |
09:41 |
Sent To |
B |
|
Notes |
2007-12-07 10:55:24 | ****************PROVISO************** | | NOTE: IF TUB ACCESS PANEL IS REMOVED THE TUB SHALL NOT | | HAVE SLIP JOINT CONNECTIONS. PER *405.8, SLIP JOINT | | CONNECTIONS. | | | | NOTE: ROOF DOWNSPOUTS SHALL DISCHARGE AT LEAST 1 FOOT | | AWAY FROM THE STRUCTURE SIDEWALL ON SPLASH BLOCKS. PER | | *1503.6 PROTECTION AGAINST DECAY AND TERMITES. | | | | NOTE: PER *604.9 WATER HAMMER. A WATER-HAMMER | | ARRESTOR SHALL BE INSTALLED WHERE | | QUICK-CLOSING VALVES ARE UTILIZED. WATER-HAMMER | | ARRESTORS SHALL BE INSTALLED IN ACCORDANCE WITH THE | | MANUFACTURER'S SPECIFICATIONS. | | | | REVIEW BY: MIKE PERSON | | PLUMBING PLANS EXAMINER | | (561) 805-6730 | | FAX (561) 805-6731 | | E-MAIL: [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2007-09-27 |
|
|
Cont ID |
|
Sent By |
mperson |
Date |
2007-09-27 |
Time |
08:36 |
Rev Time |
0.00 |
Received By |
mperson |
Date |
2007-09-27 |
Time |
08:36 |
Sent To |
B |
|
Notes |
2007-09-27 09:31:43 | DENIED 2ND TIME | | REFERENCE: | | ** FBC-2004 WITH 05 & 06 REVISIONS, PLUMBING. | | ** FBC-2004 CHAPTER 1, THE CITY OF | | WEST PALM BEACH AMENDMENTS. | | ** FLORIDA ADMINISTRATIVE CODE (FAC). | | ** FLORIDA STATUTES (FS). | | | | ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL | | IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS, | | SOME BASED ON PLANS NOW SUBMITTED, NEW DOCUMENTS BEING | | REVIEWED FOR THE FIRST TIME AND SOME NEW COMMENTS NOT | | MADE ON PREVIOUS REVIEWS. | | | | ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM | | PREVIOUS REVIEW WITH A NO, OK OR A NO/OK. | | THESE WILL BE FOR THE EXACT NUMERICAL NOTATION OF THE | | PREVIOUS REVIEW NOTES. | | | | A NO IS IF THE COMMENT WAS NOT FULLY ADDRESSED AND/OR | | FURTHER EXPLANATION OR CHANGES IN PLANS OR DOCUMENTS | | ARE STILL NEEDED. THIS REVIEWER WILL TRY TO BETTER | | EXPLAIN NOTE ABOVE PREVIOUS REVIEW COMMENT. | | | | AN OK WILL BE LABELED AS SUCH ON THE SAME NUMERICAL | | COMMENT AND WILL HAVE OLD NOTE REMOVED FROM COMMENTS. | | | | A NO/OK MEANS PART OF THE COMMENT MAY HAVE BEEN | | ADDRESSED, HOWEVER NOT ALL OF THE PREVIOUS REVIEW | | COMMENT MAY HAVE BEEN FULLY ADDRESSED. | | | | ** PLEASE SEE ANY NEW NOTES WILL BE ADDED TO THE END OF | | THE PREVIOUS REVIEW COMMENTS AND NOTED AS SUCH. | | | | 1. **NO** SHEET D-1 INDICATES REMOVAL OF THE ACCESS | | DOOR TO THE BATH TUB WASTE AND OVERFLOW. PER FBC-2004 | | W/-5 7 06 REV. PLUMBING SECTION 405.8 SLIP JOINT | | CONNECTIONS: FIXTURES WITH CONCEALED SLIP JOINT | | CONNECTIONS SHALL BE PROVIDED WITH AN ACCESS PANEL OR | | UTILITY SPACE AT LEAST 12 INCHES IN ITS SMALLEST | | DEMINSION OR OTHER APPROVED ARRANGEMENT SO AS TO | | PROVIDE ACCESS TO THE SLIP JOINT CONNECTIONS FOR | | INSPECTION AND REPAIR. | | NOTE: PLEASE ADD TO SHEET D-1 THAT THIS TUB WILL NOT | | HAVE ANY SLIP JOINT CONNECTIONS ON THE RESUBMITTAL. | | | | 2. **OK** | | | | 3. SHEET P-1 SANITARY ISOMETRIC RISER DIAGRAM THE | | FOLLOWING IS STILL REQUIRED FOR THE WASHING MACHINE. | | (A) **OK** | | (B) **OK** | | (C) **NO** 708.9 ACCESS SHALL BE PROVIDED TO ALL | | CLEANOUTS. PLEASE CLEARLY INDICATE ON THE RESUBMITTAL | | THAT THE CLEANOUT FOR THE WASHING MACHINE IS LOCATED AT | | THE BASE OF THE DRAINAGE STACK TO THE OUTSIDE OF THE | | BUILDING OR AT 4 FEET ABOVE FINNISH FLOOR TO THE INSIDE | | OF THE BUILDING ON THE RESUBMITTAL. | | | | 4. **OK** | | | | 5. **NO/OK** SHEET P-1 ISOMETRIC WATER RISER DIAGRAM: | | PER FBC-2004 W/05 & 06 REV., PLUMBING SECTION 604.9 | | WATER HAMMER ARRESTORS ARE REQUIRED FOR QUICK CLOSING | | VALVES. | | NOTE: A WATER HAMMER ARRESTOR IS ALSO REQUIRED ON THE | | HOT WATER TO THE WASHING MACHINE. PLEASE ADD THE | | FOLLOWING NOTE TO THE WATER RISER DIAGRAM "WATER HAMMER | | ARRESTORS ARE TO BE INSTALLED PER FBC-2004 W/05 & 06 | | REV. SECTION 604.9". | | | | 6. **OK** | | | | 7. **OK** | | | | 8. **OK** | | | | 9. **OK** | | | | ******THE FOLLOWING ARE NEW COMMENTS. | | | | 10. SHEET P-1 SANITARY ISOMETRIC RISER DIAGRAM: THE | | ADDED DOUBLE COMPARTMENT SINK AND DISHWASHER DRAINAGE | | PIPING TO THE DRAWINGS IS WRONG PER FBC-2004 W/05 & 06 | | REV. SECTION 909.1 | | WET VENT PERMITTED: ONLY THE FIXTURES | | WITHIN THE BATHROOM GROUPS SHALL CONNECT | | TO THE WET-VENTED HORIZONTAL BRANCH | | DRAIN. ANY ADDITIONAL FIXTURES SHALL | | DISCHARGE DOWNSTREAM OF THE WET VENT. | | ALSO THIS PIPING NEEDS TO BE SIZED PER FBC-2004 CHAPTER | | 1, SECTION 106.3.5.4. | | | | 11. SHEET P-1 SANITARY RISER DIAGRAM AND PLUMBING | | FLOOR PLAN THE NEW SHOWER IN THE NEW MASTER BATH IS | | MISLABELED AS A TUB. | | | | ********IMPORTANT INFORMATION******** | | IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, | | PLEASE REPLACE ONLY SHEETS | | WHICH HAVE CHANGED, PLEASE INCLUDE A | | TRANSMITTAL LETTER INDICATING HOW EACH | | ITEM WAS ADDRESSED AND PROVIDE ONE COPY | | OF ALL OLD/VOIDED SHEETS FOR REFERENCE | | ONLY. | | NOTE: THERE IS ONLY ONE CORRECTED DRAWING IN RED INK | | ON THE INDICATED PLAN SHEETS BY THIS PLANS EXAMINER FOR | | REFERENCE FOR THE | | RESUBMITTAL. | | | | END OF COMMENTS: | | | | REVIEW BY: MIKE PERSON | | PLUMBING PLANS EXAMINER | | (561) 805-6730 | | FAX (561) 805-6731 | | E-MAIL: [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2007-04-02 |
|
|
Cont ID |
|
Sent By |
mperson |
Date |
2007-04-02 |
Time |
11:26 |
Rev Time |
1.25 |
Received By |
mperson |
Date |
2007-04-02 |
Time |
11:26 |
Sent To |
B |
|
Notes |
2007-04-02 13:27:58 | DENIED | | REFERENCE: | | ** FBC-2004 PLUMBING. | | ** FBC-2004 CHAPTER 1, THE CITY OF | | WEST PALM BEACH AMENDMENTS. | | ** FLORIDA ADMINISTRATIVE CODE. | | ** FLORIDA STATUTES. | | | | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR | | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE: | | | | 1.SHEET D-1 INDICATES REMOVAL OF THE ACCESS DOOR TO | | THE BATH TUB PLUMBING. PER FBC-2004 PLUMBING, SECTION | | 405.8 SLIP JOINT CONNECTIONS: FIXTURES WITH CONCEALED | | SLIP JOINT CONNECTIONS SHALL BE PROVIDED WITH AN ACCESS | | PANEL OR UTILITY SPACE AT LEAST 12 INCHES IN ITS | | SMALLEST DEMINSION OR OTHER APPROVED ARRANGEMENT SO AS | | TO PROVIDE ACCESS TO THE SLIP JOINT CONNECTIONS FOR | | INSPECTION AND REPAIR. | | | | 2. SHEETS A-3 AND A-6 INDICATEPARAPET WALLS ON THE | | PROPOSED NEW ADDITION. | | PLEASE PROVIDE A ROOF PLAN THAT INDICATES HOW THE ROOF | | WILL BE PITCHED TO PROPERLY DRAIN, AND INDICATE THE | | FOLLOWING INFORMATION PER THE FOLLOWING CODE | | REFERENCES. | | A} DETAIL OF ROOF INDICATING SQUARE FOOTAGE OF ROOF | | AND VERTICAL WALLS (PARAPET) DRAINING TO DOWNSPOUTS AND | | SCUPPERS TO VERIFY COMPLIANCE WITH FBC-2004 PLUMBING, | | SECTION 1106. | | B} VERTICAL CONDUCTORS AND LEADERS, PER FBC-2004 | | PLUMBING, SECTION 1106.2 | | C} VERTICAL WALLS, PER FBC-2004 PLUMBING, SECTION | | 1106.4 | | D} SCUPPERS, (PROVIDE DETAIL PER FBC-2004 BUILDING, | | SECTIONS 1503.4.2 AND 1503.4.3) SIZE PER FBC-2004 | | PLUMBING, TABLE 1106.7. | | E} SECONDARY (EMERGENCY) ROOF DRAINS, PER FBC-2004 | | PLUMBING, SECTION 1107. | | A) SECONDARY DRAINAGE REQUIRED, PER FBC-2004 PLUMBING, | | SECTION 1107.1. | | B) SEPERATE SYSTEMS REQUIRED PER FBC-2004 PLUMBING, | | SECTION 1107.2. | | | | 3. SHEET P-1 SANITARY ISOMETRIC RISER DIAGRAM THE | | FOLLOWING INFORMATION IS REQUIRED FOR THE WASHING | | MACHINE: | | | | (A)802.4 STANDPIPES.STANDPIPES SHALL BE INDIVIDUALLY | | TRAPPED. STANDPIPES SHALL | | EXTEND A MINIMUM OF 18 INCHES (457MM) | | AND A MAXIMUM OF 42 INCHES (1066MM) | | ABOVE THE TRAP WEIR. ACCESS SHALL BE | | PROVIDED TO ALL STANDPIPES AND DRAINS | | FOR RODDING. PLEASE INDICATE THE STANDPIPE ON THE | | RESUBMITTAL | | (B)406.3 WASTE CONNECTION. THE TRAP AND FIXTURE | | DRAIN FOR AN AUTOMATIC CLOTHES WASHER STANDPIPE SHALL | | BE A MINIMUM OF 2 INCHES IN DIAMETER. PLEASE INDICATE | | THIS ON THE RESUBMITTAL. | | (C) 708.9ACCESS SHALL BE PROVIDED TO ALL CLEANOUTS. | | PLEASE CLEARLY INDICATE ON THE RESUBMITTAL THAT THE | | CLEANOUT IS TO THE OUTSIDE OF THE BUILDING DUE TO SHEET | | A-1 INDICATING "NEW STACK WASH/DRY". | | | | 4. SHEET P-1 SANITARY ISOMETRIC RISER DIAGRAM: PLEASE | | SIZE ALL PIPING AND TRAPS PER FBC-2004 CHAPTER 1, | | SECTION 106.3.5.4 ON THE RESUBMITTAL. | | | | 5. SHEET P-1 ISOMETRIC WATER RISER DIAGRAM: PER | | FBC-2004 PLUMBING, SECTION 604.9 WATER HAMMER ARRESTORS | | REQUIRED FOR QUICK CLOSING VALVES. | | NOTE: WASHING MACHINE AND NEW DISHWASHER INDICATED ON | | (SHEET A-1) REQUIRE WATER HAMMER ARRESTORS. PLEASE NOTE | | THIS ON THE RESUBMITTAL. PLEASE CLEARIFY IF THE NEW | | REF. FRZ. INDICATED ON (SHEET A-1) HAS AN ICE MAKER OR | | WATER DIS. ON THE RESUBMITTAL. IF ITS DOES WATER HAMMER | | ARRESTORS ARE REQUIRED AND NEED TO BE NOTED ON THE | | RESUBMITTAL. | | | | 6. SHEET P-1 ISOMETRIC WATER DIAGRAM: PLEASE INDICATE | | EXPANSION CONTROL FOR WATER HEATER PER FBC-2004 | | PLUMBING, SECTION 607.3. | | | | 7. SHEET P-1 ISOMETRIC WATER RISER DIAGRAM: PLEASE | | INDICATE FOR NEW HOSE BIBB "REFERENCE GENERAL PLUMBING | | NOTE #14 FOR VACUUM BREAKER" ON THE RESUBMITTAL. | | | | 8. PER FBC-2004 CHAPTER 1, SECTION 106.3 THE JOB | | ADDRESS NEEDS TO APPEAR ON ALL TITLE BLOCKS. | | | | 9. SHEET P-2 PLEASE DELETE THE FLOOR/HUB DRAIN DETAIL, | | PLUMBING LEGEND AND TRAP PRIMER DIAGRAM ON THE | | RESUBMITTAL DUE TO THE FACT THAT THERE ARE NIETHER | | INDICATED ON THE PLANS. | | | | ********IMPORTANT INFORMATION******** | | IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, | | PLEASE REPLACE ONLY SHEETS | | WHICH HAVE CHANGED, PLEASE INCLUDE A | | TRANSMITTAL LETTER INDICATING HOW EACH | | ITEM WAS ADDRESSED AND PROVIDE ONE COPY | | OF ALL OLD/VOIDED SHEETS FOR REFERENCE | | ONLY. NOTE: ONLY ONE CORRECTED DRAWING | | IN RED INK FOR REFERENCE FOR | | RESUBMITTAL. | | | | END OF COMMENTS: | | | | REVIEW BY MIKE PERSON | | (561) 805-6730 | | FAX (561) 805-6731 | | E-MAIL [email protected] | | UNDER SUPERVISION OF K.STEVENS | | (561) 805-6721 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2007-09-16 |
|
|
Cont ID |
|
Sent By |
jroach |
Date |
2007-09-16 |
Time |
16:50 |
Rev Time |
0.00 |
Received By |
jroach |
Date |
2007-09-16 |
Time |
16:50 |
Sent To |
I |
|
Notes |
2007-09-16 16:52:09 | ***PROVISO*** | | | | NEW ADDITIONAL SHALL BE A MINIMUM OF SIX (6) FROM THE | | EXISTING GARAGE...NOT A MAXIMUM (AS NOTED ON THE | | PLANS). | | | | QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER, | | AT (561) 822-1435. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2007-03-19 |
|
|
Cont ID |
|
Sent By |
jroach |
Date |
2007-03-19 |
Time |
17:36 |
Rev Time |
0.00 |
Received By |
jroach |
Date |
2007-03-19 |
Time |
17:36 |
Sent To |
I |
|
Notes |
2007-03-19 17:49:19 | ***FAILED*** | | | | 1) TWO (2) COPIES OF A RECENT SURVEY (WITHIN THE LAST | | YEAR) SHALL BE PROVIDED SHOWING THE LOCATION OF THE | | PROPOSED ADDITION AND THE SETBACKS. | | | | 2) DIMENSIONS/SETBACKS SHALL BE PROVIDED ON THE SITE | | PLAN AND THE SURVEY INDICATING THE DISTANCE FROM THE | | PROPERTY LINE TO THE A/C UNIT. | | | | QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER, | | AT (561) 822-1435. |
|
|