Plan Review Details - Permit 07030543
Plan Review Stops For Permit 07030543
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-12-21 Cont ID  
Sent By rmcdouga Date 2007-12-21 Time 14:38 Rev Time 0.00
Received By rmcdouga Date 2007-12-21 Time 14:38 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-09-28 Cont ID  
Sent By rmcdouga Date 2007-09-28 Time 10:01 Rev Time 0.00
Received By rmcdouga Date 2007-09-28 Time 10:01 Sent To  
Notes
2007-09-28 11:11:252007 FBC W/2006 REVISIONS
  
 DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE DECORATIVE CHIMNEY THAT HAS BEEN DELETED IS
 STILL SHOWN ON THE ELEVATIONS ON SHEET A9. PLEASE
 CORRECT.
  
 3) SUBMIT PRODUCT APPROVALS FOR THE STRUCTURAL MULLIONS
 AND THE FIXED GLASS TRANSOM WINDOW ABOVE THE FRONT
 WINDOWS (MARK A).
  
 4) THE 32" X 68" (MARK A) WINDOWS EXCEED THE MAXIMUM
 SIZE LISTED IN THE PRODUCT APPROVAL NOA FOR THE SINGLE
 OPERABLE CASEMENT WINDOWS. PLEASE SUBMIT A PRODUCT
 APPROVAL FOR THESE WINDOWS OR REVISE THE SIZE. SEE THE
 DESIGN LOAD CAPACITY TABLES ON SHEET 7 OF NOA NO.
 02-1113.04.
  
 5) NOTE: THE PRODUCT APPROVALS SUBMITTED FOR THE
 WINDOWS HAVE BEEN TESTED FOR LARGE MISSILE IMPACT AND
 STORM PANELS ARE NOT REQUIRED. ALSO THE WINDOWS ARE
 REQUIRED TO MEET THE WINDLOAD PRESSURES REGARDLESS OF
 BEING SHUTTERED.
  
 - ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-04-23 Cont ID  
Sent By rmcdouga Date 2007-04-23 Time 10:29 Rev Time 0.00
Received By rmcdouga Date 2007-04-23 Time 07:01 Sent To  
Notes
2007-04-23 07:16:20DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) THE LICENSE NUMBER FOR THE ARCHITECTURAL FIRM IS
 MISSING FROM THE TITLE BLOCK. SEE FAC 61G1-16.004.
  
 4) FBC TABLE R301.5 REQUIRES EXTERIOR BALCONIES TO HAVE
 A LIVE LOAD OF 60 PSF. PLEASE CORRECT THE STRUCTURAL
 NOTE ON SHEET A2.
  
 5) ON SHEET A2 COLUMNS C8 ARE INCORRECTLY SPECIFIED AT
 THE FRONT ENTRY.
  
 6) SPECIFY THE SIZES OF THE ATTIC ACCESSES ON THE
 PLANS.
  
 7) SUBMIT THE MANUFACTURER'S SPECIFICATIONS,
 INSTALLATION INSTRUCTIONS AND LISTING INFORMATION FOR
 THE ISOKERN FLUELESS FIREPLACE.
  
 8) SUBMIT THE MANUFACTURER'S SPECIFICATIONS,
 INSTALLATION INSTRUCTIONS AND LISTING INFORMATION FOR
 THE GAS BBQ ON THE LOGGIA. NOTE: THE CEILING OF THE
 LOGGIA IS COVERED WITH FLAMMABLE MATERIAL.
  
 9) SUBMIT THE MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION INSTRUCTIONS FOR THE SPRAY FOAM INSULATION
 THAT WILL BE INSTALLED IN THE VENTLESS ATTIC.
  
 10) PROVIDE ADDITIONAL INFORMATION FOR THE CHIMNEY. IS
 THIS A DECORATIVE ASSEMBLY OR WILL IT BE FUNCTIONING?
 PROVIDE DETAILS FOR THE CHIMNEY CAP SHOWN ON THE
 ELEVATIONS ON A8. THE ELEVATION SHOWS A STUCCO BAND
 WHICH IS NOT SHOWN ON THE STRUCTURAL DETAILS. THE
 TRUSSES WILL BE REQUIRED TO BE DESIGNED FOR THE CHIMNEY
 ATTACHMENT.
  
 11) SHOW COMPLIANCE WITH R502.12 DRAFTSTOPPING
 REQUIRED.
 WHEN THERE IS USABLE SPACE BOTH ABOVE AND BELOW THE
 CONCEALED SPACE OF A FLOOR/CEILING ASSEMBLY, DRAFTSTOPS
 SHALL BE INSTALLED SO THAT THE AREA OF THE CONCEALED
 SPACE DOES NOT EXCEED 1,000 SQUARE FEET (92.9 M 2 ).
 DRAFTSTOPPING SHALL DIVIDE THE CONCEALED SPACE INTO
 APPROXIMATELY EQUAL AREAS. WHERE THE ASSEMBLY IS
 ENCLOSED BY A FLOOR MEMBRANE ABOVE AND A CEILING
 MEMBRANE BELOW DRAFTSTOPPING SHALL BE PROVIDED IN
 FLOOR/CEILING ASSEMBLIES UNDER THE FOLLOWING
 CIRCUMSTANCES:
 1.CEILING IS SUSPENDED UNDER THE FLOOR FRAMING. 2.
 FLOOR FRAMING IS CONSTRUCTED OF TRUSS-TYPE OPEN-WEB OR
 PERFORATED MEMBERS.
 SPECIFY THE LOCATION OF DRAFTSTOPPING AND MATERIAL THAT
 WILL BE USED. SEE R502.12.1.
  
 12) PLEASE REVISE ROOF SHEATHING FASTENING NOTES ON A7.
 THE 2006 REVISIONS TO THE 2004 FBC REQUIRES RING SHANK
 NAILS TO BE USED IN ALL ROOF ZONES. FBC R803.2.3.1
  
 13) SPECIFY THE TREAD DEPTH OF THE STAIRS ON SHEET A11.
 SEE R311.5.3.2.
  
 14) SPECIFY THE ATTACHMENT THAT WILL BE USED FOR THE
 MONIER CONCRETE ROOF TILES. CIRCLE THE APPROPRIATE
 FASTENER OR ADHESIVE ON THE PRODUCT APPROVAL.
  
 15) SUBMIT PRODUCT APPROVALS FOR THE TRUSS CONNECTORS.
  
 16) SUBMIT DRAWING #IRC-5316-175-45 WHICH IS REQUIRED
 TO ACCOMPANY THE PRODUCT APPROVAL FOR THE OVERHEAD
 GARAGE DOOR.
  
 17) SUBMIT PRODUCT APPROVALS FOR THE STRUCTURAL
 MULLIONS, RAISED PANEL/HALF GLASS DOORS AT THE GARAGE
 AND LAUNDRY ROOM, THE 4' X 8' MAHOGANY ENTRY DOOR AND
 THE FIXED GLASS TRANSOM WINDOW ABOVE WINDOW A.
  
 18) THE FLORIDA COVERSHEET SUBMITTED FOR THE MARVIN
 IMPACT CASEMENT WINDOW IS NOT THE CORRECT ONE FOR NOA
 02-1113.04. IF THERE IS NO FL# THAT CORRESPONDS TO IT,
 THE NOA IS ACCEPTABLE WITHOUT THE FL COVERSHEET.
 HOWEVER, IT IS STILL REQUIRED TO BE APPROVED IN WRITING
 BY THE DESIGNER OF RECORD.
  
 19) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE
 CASEMENT WINDOWS DO NOT HAVE DESIGN PRESSURES ON PAGE 7
 OF THE NOA THAT ARE ACCEPTABLE FOR WINDOWS A & K AS
 SPECIFIED IN THE SCHEDULE ON A5.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2009-06-22 Cont ID  
Sent By btrobaug Date 2009-06-22 Time 11:09 Rev Time 0.00
Received By btrobaug Date 2009-06-22 Time 10:41 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-09-11 Cont ID  
Sent By btrobaug Date 2007-09-11 Time 11:04 Rev Time 0.00
Received By btrobaug Date 2007-09-11 Time 10:45 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-03-16 Cont ID  
Sent By btrobaug Date 2007-03-16 Time 08:47 Rev Time 1.50
Received By btrobaug Date 2007-03-15 Time 17:44 Sent To Z
Notes
2007-03-16 08:47:09 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} 210.52(B)(2) ISLAND COUNTER SPACES AT LEAST ONE
 RECEPTACLE SHALL BE INSTALLED AT EACH ISLAND COUNTER
 SPACE WITH A LONG DIMENSION OF 600 MM (24 IN.) OR
 GREATER AND A SHORT DIMENSION OF 300 MM (12 IN.) OR
 GREATER. WHERE A RANGETOP OR SINK IS INSTALLED IN AN
 ISLAND COUNTER AND THE WIDTH OF THE COUNTER BEHIND THE
 RANGETOP OR SINK IS LESS THAN 300 MM (12 IN.), THE
 RANGETOP OR SINK IS CONSIDERED TO DIVIDE THE ISLAND
 INTO TWO SEPARATE COUNTERTOP SPACES AS DEFINED IN
 210.52(C)(4).
  
 2} 210.52(C)(1) WALL COUNTER SPACES A RECEPTACLE OUTLET
 SHALL BE INSTALLED AT EACH WALL COUNTER SPACE THAT IS
 300 MM (12 IN.) OR WIDER. RECEPTACLE OUTLETS SHALL BE
 INSTALLED SO THAT NO POINT ALONG THE WALL LINE IS MORE
 THAN 600 MM (24 IN.) MEASURED HORIZONTALLY FROM A
 RECEPTACLE OUTLET IN THAT SPACE.
  
 2} THE CONDENSER DISCONNECTS DO NOT MEET 110.26
 CLEARANCE REQUIREMENTS.
  
 3} THE 2005 NEC WAS ADOPTED BY THE FLORIDA LEGISLATURE
 EFFECTIVE 8 DECEMBER 2006. THE APPLICATION FOR THIS
 PROJECT WAS AFTER THAT DATE AND THE PLANS ARE SUBJECT
 TO THAT CODE. PLEASE CHANGE ALL NOTES TO REFLECT THIS
 CHANGE.
  
 4} NOTE #20 INCORRECTLY REFERENCES 2204 FBC AND 907
 NFPA-72. THE CORRECT REFERENCE STANDARDS PER 2004 FBC
 ARE R313 RESIDENTIAL AND CHAPTER 11NFPA-72, 2002
 EDITION. PLEASE CORRECT FOR CLARITY IN THE FIELD.
  
 5} A RECEPTACLE, AS WELL AS THE LIGHT INDICATED ON
 SHEET E-2, IS REQUIRED IN THE ATTIC FOR SERVICING THE
 AIR HANDLER PER 210.63 NEC AND M1305.1.3.1 FBC.
  
 6} A RECEPTACLE PER 210.52(D) IS REQUIRED IN BATH #1
 SHEET E-2.
  
 NOTE: THE #2 EQUIPMENT GROUND RAN WITH THE PANEL
 FEEDERS, ALTHOUGH NOT A VIOLATION, IS ONLY REQUIRED TO
 BE #6CU. IF IT REMAINS #2 ON THE PLAN IT MUST BE
 INSTALLED OR A REVISION WILL BE REQUIRED TO MAKE THE
 CHANGE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2009-06-02 Cont ID  
Sent By kstevens Date 2009-06-02 Time 09:53 Rev Time 0.00
Received By kstevens Date 2009-06-02 Time 09:53 Sent To  
Notes
2009-06-02 09:54:32REVISION OK -- SHT M-3 CHANGED O 2 PSI SYSTEM, ADDED
 REGULATORS, CHANGED LENGTHS AND MATERIAL.

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2007-12-17 Cont ID  
Sent By mperson Date 2007-12-17 Time 08:27 Rev Time 0.00
Received By mperson Date 2007-12-17 Time 08:27 Sent To B
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2007-09-25 Cont ID  
Sent By mperson Date 2007-09-25 Time 14:06 Rev Time 0.00
Received By mperson Date 2007-09-25 Time 14:06 Sent To B
Notes
2007-09-25 14:39:37DENIED 2ND TIME
 REFERENCE:
 ** FBC-2004 WITH 2006 REVISIONS FUEL GAS.
 ** NFPA-2002 CHAPTER 54.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS,
 SOME BASED ON PLANS NOW SUBMITTED, NEW DOCUMENTS BEING
 REVIEWED FOR THE FIRST TIME AND SOME NEW COMMENTS NOT
 MADE ON PREVIOUS REVIEWS.
  
 ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM
 PREVIOUS REVIEW WITH A NO, OK OR A NO/OK.
 THESE WILL BE FOR THE EXACT NUMERICAL NOTATION OF THE
 PREVIOUS REVIEW NOTES.
  
 A NO IS IF THE COMMENT WAS NOT FULLY ADDRESSED AND/OR
 FURTHER EXPLANATION OR CHANGES IN PLANS OR DOCUMENTS
 ARE STILL NEEDED. THIS REVIEWER WILL TRY TO BETTER
 EXPLAIN NOTE ABOVE PREVIOUS REVIEW COMMENT.
  
 AN OK WILL BE LABELED AS SUCH ON THE SAME NUMERICAL
 COMMENT AND WILL HAVE OLD NOTE REMOVED FROM COMMENTS.
  
 A NO/OK MEANS PART OF THE COMMENT MAY HAVE BEEN
 ADDRESSED, HOWEVER NOT ALL OF THE PREVIOUS REVIEW
 COMMENT MAY HAVE BEEN FULLY ADDRESSED.
  
 ** PLEASE SEE ANY NEW NOTES WILL BE ADDED TO THE END OF
 THE PREVIOUS REVIEW COMMENTS AND NOTED AS SUCH.
  
 1. **OK**
  
 2. **OK**
  
 3. **NO/OK** SHEET M-3
 SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 NOTE: THE RESUBMITTED ISOMETRIC IS NOT INDICATING ALL
 CORRESPONDING LENGTHS OF THE CUT SECTIONS.
  
 4. **OK**
  
 5. **OK**
  
 6. **OK**
  
 7. **NO/OK** SHEET M-3
 SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 NOTE: THE INDICATED LONGEST LENGTH IS BEING INDICATED
 AS 145', THE TOTAL SUM OF THE INDICATED CUT SECTION
 CORRESPONDING LENGTHS IS 105'. PLEASE CORRELATE THE
 LONGEST LENGTHS ON THE RESUBMITTAL BY INDICATING ALL
 CORRESPONDING LENGTHS OF ALL CUT SECTIONS OF
 PIPE.(REFERENCE COMMENT #3)
  
 8. **OK**
  
 9. **OK**
  
 10. **OK**
  
 **THE FOLLOWING IS A NEW COMMENT
  
 11. SHEET M-3 THE RESUBMITTED GAS ISOMETRIC IS
 INDICATING THE GAS METER AS BEING UNDERGROUND. PER
 NFPA-2002 CHAPTER 54 SECTION 5.7.2.1 GAS METERS SHALL
 BE LOCATED IN VENTILATED SPACES READILY ACCESSIBLE FOR
 EXAMINATION, READING, REPACEMENT OR NECESSARY
 MAINTENANCE AND SECTION 5.7.2.2 GAS METERS SHALL NOT BE
 PLACED WHERE THEY WILL BE SUBJECT TO EXCESSIVE
 CORROSION. PLEASE INDICATE THE GAS METER AS BEING ABOVE
 GROUND AND INDICATE THE REQUIRED CORRESPONDING LENGTHS
 TO THE CUT SECTIONS TO CORRECT THIS ON THE
 RESUBMITTAL.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING IN RED INK ON
 THE INDICATED PLAN SHEETS BY THIS PLAN EXAMINER FOR FOR
 REFERENCE FOR THE RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-03-30 Cont ID  
Sent By mperson Date 2007-03-30 Time 16:07 Rev Time 0.45
Received By mperson Date 2007-03-30 Time 16:07 Sent To B
Notes
2007-03-30 16:59:10DENIED
 REFERENCE:
  
 ** FBC-2004 FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. PLEASE REFERENCE PLUMBING COMMENT #1 IN RELATION TO
 FIRM LICENSE NUMBER REQUIRED IN TITLE BLOCK.
  
 2. 106.1.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL
 BE OF SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE
 AND RELAVENT LAWS, ORDINANCES, RULES AND REGULATIONS,
 AS DETERMINED BY THE
 BUILDING OFFICIAL.
 NOTE: THE SUBMITTED GAS ISOMETRIC ON SHEET M-3 DOES NOT
 REFLECT THE FLOOR PLANS ON SHEETS A-3 AND A-4. GAS
 ISOMETRIC INDICATES TWO RANGES IN DIFFERENT LOCATIONS
 BUT THE FLOOR PLANS ONLY INDICATE ONE RANGE IN THE
 KITCHEN. PLEASE CLARIFY ON THE RESUBMITTAL.
  
 3. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 NOTE: CORRESPONDING LENGTHS OF CUT SECTIONS ARE NOT
 INDICATED.
  
 4. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 NOTE: NOT ALL PIPE SIZES ARE INDICATED AND IF BLACK
 STEEL PIPE IS BEING INSTALLED UNDERGROUND PLEASE ADD
 THE FOLLOWING TO "GAS NOTES" ON SHEET M-3.
  
 A} PER FBC-2004 FUEL GAS SECTION 404.8.2 PROTECTIVE
 COATINGS AND WRAPPING. PIPE PROTECTIVE COATINGS AND
 WRAPPINGS SHALL BE APPROVED FOR THE APPLICATION AND
 SHALL BE FACTORY APPLIED.
  
  
 5. PLEASE INDICATE THE TYPE OF GAS, (LP OR NATURAL)
 BEING USED ON THE RESUBMITTAL.
  
 6. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 7. CLEARLY SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM ON THE ISOMETRIC
 PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 8. PLEASE SUBMIT MANUFACTURER SPECIFICATIONS OF
 APPLIANCES (CUT SHEETS) VARIFYING BTU LOADS AND SHOWING
 LISTINGS FROM A NATIONALLY RECOGNIZED TESTING
 LABORATORY (NRTL).
  
 9. PLEASE CLARIFY WHAT THE NIPPLE AND HARD CAP ON THE
 RUN OF THE TEE FOR THE POOL HEATER IS. IS THIS SUPPOST
 TO BE A SEDIMENT TRAP? IF SO ITS IN THE WRONG LOCATION.
 PLEASE CLARIFY ON THE RESUBMITTAL.
  
 10. PLEASE DELETE THE SEDIMENT TRAP BEING INDICATED
 UNDERGROUND ON THE RESUBMITTAL.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2010-07-12 Cont ID  
Sent By vmolina Date 2010-07-12 Time 10:32 Rev Time 0.00
Received By vmolina Date 2010-07-12 Time 10:31 Sent To  
Notes
2010-07-12 10:32:14IN ZONING BOX

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2009-03-09 Cont ID  
Sent By adarroug Date 2009-03-09 Time 11:37 Rev Time 0.00
Received By adarroug Date 2009-03-09 Time 11:37 Sent To M
Notes
2009-03-09 11:38:38TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-12-10 Cont ID  
Sent By adarroug Date 2007-12-10 Time 16:31 Rev Time 0.00
Received By adarroug Date 2007-12-10 Time 16:31 Sent To P
Notes
2007-12-10 16:32:00TO "P" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-09-06 Cont ID  
Sent By adarroug Date 2007-09-06 Time 10:23 Rev Time 0.00
Received By adarroug Date 2007-09-06 Time 10:23 Sent To E
Notes
2007-09-06 10:24:01TO "BTROBAUG" DESK/ RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-04-23 Cont ID  
Sent By rmcdouga Date 2007-04-23 Time 10:29 Rev Time 0.00
Received By rmcdouga Date 2007-03-15 Time 16:35 Sent To  
Notes
2007-03-15 16:35:17TO "SFR""Z"

Review Stop L LANDSCAPING
Rev No 1 Status P Date 2010-07-13 Cont ID  
Sent By rkussner Date 2010-07-13 Time 11:57 Rev Time 0.00
Received By rkussner Date 2010-07-13 Time 11:57 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2009-07-01 Cont ID  
Sent By hmoser Date 2009-07-01 Time 13:54 Rev Time 0.00
Received By hmoser Date 2009-07-01 Time 13:54 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2009-06-16 Cont ID  
Sent By rregueir Date 2009-06-16 Time 08:51 Rev Time 0.00
Received By rregueir Date 2009-06-15 Time 16:45 Sent To  
Notes
2009-06-16 08:51:10REVISED M1 AND M2 DELTA 2

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2009-04-03 Cont ID  
Sent By rregueir Date 2009-04-03 Time 16:55 Rev Time 0.00
Received By rregueir Date 2009-04-03 Time 16:53 Sent To  
Notes
2009-04-03 16:54:50REVISED ENERGY AND COOLING LOAD CALCS. NEED REVISED
 PLANS TO MATCH EQUIPMENT SCHEDULE WITH CALCS.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-09-11 Cont ID  
Sent By tgordon Date 2007-09-11 Time 14:19 Rev Time 0.45
Received By tgordon Date 2007-09-11 Time 14:19 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-03-27 Cont ID  
Sent By tgordon Date 2007-03-27 Time 13:44 Rev Time 0.45
Received By tgordon Date 2007-03-27 Time 13:44 Sent To P
Notes
2007-03-27 13:55:24*** DENIED ***
 1) MANUAL J CALCULATIONS ARE CALLING FOR THREE A/C
 SYSTEMS, SYSTEM #1 26,518 SENSIBLE BTU'S, SYSTEM #2
 10,694 SENSIBLE BTU'S, AND SYSTEM #3 11,351 SENSIBLE
 BTU'S. MECHANICAL PLANS ARE CALLING FOR A/C SYSTEM #1
 44,600 SENSIBLE BTU'S, SYSTEM #2 25,000 SENSIBLE BTU'S,
 AND SYSTEM #3 25,000 SENSIBLE BTU'S. THE PLANS A/C
 SYSTEMS ARE TO LARGE. THE PLANS CAN ONLY CALL FOR 15%
 MORE THAN THE MANUAL J CALCULATIONS, SEE 2004 FBC
 13-607.1.ABC.1.1 (12-8-07 REVISION). PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 4 Status F Date 2009-06-02 Cont ID  
Sent By kstevens Date 2009-06-02 Time 08:13 Rev Time 0.00
Received By kstevens Date 2009-06-01 Time 16:55 Sent To  
Notes
2009-06-02 09:53:19REVISION OK ADDED -- SHT M-3 CHANGED TWO COMP. SINK TO
 SINGLE BOWL SINK AND ADDED A THREE COMPARTMENT SINK &
 ADDITIONAL D.W. & DISPOSAL.

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-12-17 Cont ID  
Sent By mperson Date 2007-12-17 Time 07:49 Rev Time 0.00
Received By mperson Date 2007-12-17 Time 07:49 Sent To  
Notes
2007-12-17 08:23:43****************PROVISO****************
 604.9 WATER HAMMER. A WATER-HAMMER
 ARRESTOR SHALL BE INSTALLED WHERE
 QUICK-CLOSING VALVES ARE UTILIZED.
 WATER-HAMMER ARRESTORS SHALL BE INSTALLED IN ACCORDANCE
 WITH THE MANUFACTURER'S SPECIFICATIONS.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-09-25 Cont ID  
Sent By mperson Date 2007-09-25 Time 14:05 Rev Time 0.00
Received By mperson Date 2007-09-25 Time 14:05 Sent To G
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-03-30 Cont ID  
Sent By mperson Date 2007-03-30 Time 13:24 Rev Time 0.55
Received By mperson Date 2007-03-30 Time 13:24 Sent To G
Notes
2007-03-30 13:44:31DENIED
 REFERENCE:
 ** FBC-2004 PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. FAC-61G1-16.004 TITLE BLOCK:
 A TITLE BLOCK MUST APPEAR ON ALL
 ARCHITECTURAL OR INTERIOR DESIGN
 DRAWINGS AND SPECIFICATION
 IDENTIFICATION SHEETS. THE TITLE BLOCK
 MUST, AT A MINIMUM, CONTAIN THE
 FOLLOWING INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE
 NUMBER.
 (2) FIRM LICENSE NUMBER.
 (3) NAME OR IDENTIFICATION OF PROJECT.
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED
 SEAL.
 (6) A SPACE FOR THE PRINTED NAME OF THE
 PERSON SEALING THE DOCUMENT.
 NOTE: IF "SMITH AND MOORE ARCHITECTS, INC." IS A FIRM
 THEN THE FIRMS LICENSE NUMBER IS MISSING FROM THE TITLE
 BLOCK ON ALL SHEETS. PLEASE CORRECT ON THE
 RESUBMITTAL.
  
 2. SHEET M-3 SANITARY ISOMETRIC RISER DIAGRAM:
  
 A} SECOND FLOOR "BATH #2 ROOM # 206", THE SANITARY
 STACK MUST DRAIN DOWNSTREAM OF FIRST FLOOR "HIS BATH
 ROOM # 113" PER FBC-2004 PLUMBING, SECTIONS 909.1 AND
 908.3. PLEASE CORRECT ON THE RESUBMITTAL.
  
 B} "HIS BATH ROOM # 113" FLOOR PLAN ON SHEET A-3
 INDICATES A SHOWER BUT ON THE RISER DIAGRAM A B.T. IS
 INDICATED. PLEASE CORRELATE ON THE RESUBMITTAL.
  
 C} THE FOLLOWING CORRECTIONS ARE REQUIRED FOR THE
 WASHING MACHINE ON THE RESUBMITTAL.
 (A) 406.3 WASTE CONNECTIONS.THE TRAP AND
 FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES
 WASHER SHALL BE A MINIMUM OF 2 INCHES
 (51MM) IN DIAMETER. THE AUTOMATIC
 CLOTHES WASHER FIXTURE DRAIN SHALL
 CONNECT TO A BRANCH DRAIN OR DRAINAGE
 STACK A MINIMUM OF 3 INCHES (76MM) IN
 DIAMETER. PLEASE CORRECT ON THE RESUBMITTAL.
 (B) 802.4 STANDPIPES.STANDPIPES SHALL BE INDIVIDUALLY
 TRAPPED. STANDPIPES SHALL
 EXTEND A MINIMUM OF 18 INCHES (457MM)
 AND A MAXIMUM OF 42 INCHES (1066MM)
 ABOVE THE TRAP WEIR. ACCESS SHALL BE
 PROVIDED TO ALL STANDPIPES AND DRAINS
 FOR RODDING. PLEASE INDICATE THE STANPIPE FOR THE
 WASHING MACHINE ON THE RESUBMITTAL.
  
 3.PER FBC-2004 CHAPTER 1, SECTION 106.3.5.4
 RESIDENTIAL (ONE AND TWO-FAMILY) PLEASE SUBMIT A
 PLUMBING SANITARY ISOMETRIC RISER DIAGRAM INDICATING
 ALL WASTE, VENTS, TRAPS AND SIZES WITH CLEANOUT
 LOCATIONS.
 NOTE: NOT ALL PIPES OR TRAPS ARE SIZED AND NOT ALL
 CLEANOUTS ARE INDICATED ON THE SANITARY RISER DIAGRAM
 ON SHEET M-3.
 (A) 708.3.4 BASE OF STACK. A CLEANOUT
 SHALL BE PROVIDED AT THE BASE OF EACH
 WASTE OR SOIL STACK
 (B) 708.3.5 BUILDING DRAIN AND BUILDING
 SEWER JUNCTION. THERE SHALL BE A TWO-WAY
 CLEANOUT NEAR THE JUNCTION OF THE
 BUILDING DRAIN AND THE BUILDING SEWER.
 (C) 708.7 MINIMUM SIZE. CLEANOUTS SHALL
 BE THE SAME NOMINAL SIZE AS THE PIPE
 THEY SERVE UP TO 4 INCHES (102MM)
 (D) 708.9 ACCESS. ACCESS SHALL BE
 PROVIDED TO ALL CLEANOUTS.
 NOTE: CLEANOUT FOR THE WASHING MACHINE TO BE LOCATED AT
 FOUR FEET ABOVE FINNISH FLOOR (4' A.F.F.)
  
 4. SHEET M-3 PLUMBING NOTES: PLEASE DELETE "AIR
 CHAMBER" FROM NOTE #11 ON THE RESUBMITTAL.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop Z ZONING
Rev No 1 Status P Date 2007-03-22 Cont ID  
Sent By jroach Date 2007-03-22 Time 14:19 Rev Time 0.00
Received By jroach Date 2007-03-22 Time 14:19 Sent To I
Notes
2007-03-22 14:19:57PASSED, PER A. JONES-VANN.