Plan Review Details - Permit 07030530
Plan Review Stops For Permit 07030530
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-12-05 Cont ID  
Sent By jgomez Date 2007-12-05 Time 10:59 Rev Time 0.00
Received By jgomez Date 2007-12-05 Time 07:58 Sent To PC
Notes
2007-12-05 11:29:58BUILDING REVIEW SECOND CHECKLIST:
 1- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713.13 FLORIDA STATUTE. (REPEAT COMMENT).
  
 2- AFTER DRAWINGS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY TO PAY IMPACT FEES. BRING BACK STAMPED PLANS AND
 COPY OF PAID RECEIPT. (REPEAT COMMENT).
  
 3- A)REVISE GENERAL CONSTRUCTION NOTE REGARDING
 CONCRETE BLOCK COMPRESSIVE STRENGTH. SEE SEC. R606.4
 2004 FLORIDA RESIDENTIAL CODE AND REVISE AS REQUIRED.
 ***IT WAS CHANGED TO 100PSI. THIS IS INCORRECT. REVISE
 AS REQUIRED.
  
 B)WIND LOAD AFFIDAVIT CHART: * CLARIFY WHY
 INTERNAL PRESSURE COEFFICIENT IS 0.
 ***REVISED AFFIDAVIT STATES THAT USING SHUTTERS TO
 PROTECT AGAINST WIND-BORNE DEBRIS.BUILDING WAS
 DESIGNED AS ENCLOSED,THAT'S WHY SHUTTERS OR IMPACT
 GLAZING IS USED TO CONSIDERED THE BUILDING AS ENCLOSED.
 THERE ARE STILL INTERNAL PRESSURES TO BE CONSIDERED.
 SEE FIGURE 6-5 OF ASCE 7-02 AND REVISED AS REQUIRED.
  
 C) PROVIDE COMPLETE INFORMATION FOR GUARDRAIL AT
 REAR AREASHOWING COMPLIANCE WITH TABLE R301.5AND
 SEC. R312 OF 2004 FLORIDA RESIDENTIALCODE.
 INFORMATION SUBMITTED DOESN'T PROVIDE ALL THIS
 INFORMATION.MISSING INFORMATION COMPLYING WITH TABLE
 R301.5 AND PICKETS SPACING SO A 4" SPHERE CAN'T PASS
 THRU.
  
 D) PROVIDE FINISH REAR PORCH ELEVATION AND GRADE
 ELEVATION TO VERIFY IF GUARDRAIL ISREQUIRED. SEC.
 R312OF 2004 FLORIDA RESIDENTIAL CODE. SEE SURVEY FOR
 FINISH ELEVATIONS SHOWN.
  
 E) NUMBER OF TREADS SHOWN ON REAR PORCH PLAN DON'T
 MATCH NUMBER OF RISERS SPECIFIED ON PLAN. REVISE AS
 REQUIRED. PLAN SHOWS FOUR RISERS.
  
 4- SHEET A3:
 A) PROVIDE CRAWL SPACE VENTILATION AND ACCESS.SEE
 SEC. R4082004 FLORIDA RESIDENTIAL CODE FOR MIN. SIZES
 AND LOCATION.
 ***INFORMATION SUBMITTED IS INCOMPLETE. PROVIDE CRAWL
 SPACE VENTILATION CALCULATIONS TO VERIFY THAT THE TWO
 PROPOSED 16"X16" OPENINGS ARE ADEQUATE. ALSO, PROVIDE
 ACCESS AS REQUIRED BY SEC. R408.3.SPECIFY SIZE OF
 OPENING TO GO FROM ONE SIDE OF THE CRAWL SPACE TO THE
 OTHER.INFORMATION SUBMITTED ONLY SHOWS A 16" DEEP
 LINTEL, BUT IT DOESN'T SPECIFY SIZE OF OPENING.IN
 ADDITION, STILL NEED TO PROVIDE ACCESS TO THE CRAWL
 SPACE FROM THE OUTSIDE OR INSIDE. SEE SEC. R312 AND
 REVISE AS REQUIRED.
  
 B) TYPICAL WALL SECTION:CLARIFY NOTE REGARDING
 FOOTING REINFORCEMENT CONCRETE COVER.3" & 2" COVER AT
 BOTTOM?. SEE SEC. R403 OF 2004 FLORIDA RESIDENTIAL CODE
 FOR MIN. COVERING REQUIRED.
 *** MINIMUM 3" COVERING REQUIRED IS AT BOTTOM AND SIDE
 ALSO. REVISE AS REQUIRED OR SPECIFY WHICH CODE SECTION
 STATES THAT 2" SIDE COVER IS REQUIRED.
  
  
 5- SHEET A4:
 A) R4412IS NOT AN STANDARDTEST METHOD FOR WIND
 RESISTANCE OF ASPHALT SHINGLES WITH A WIND VELOCITY OF
 140MPH (MINIMUM).REVISE NOTE AS REQUIRED. WHERE IS
 THIS INFORMATION TAKEN FROM?.
  
 6- SHEET A5:REVISE ROOF SHEATHING NAILING SCHEDULE.
 SEE SEC. R803.2.3.1 2004 FLORIDA RESIDENTIAL CODE AND
 REVISEFASTENER SPACING AS REQUIRED FOR ROOF ZONE 3.
  
 7- REVISEENERGY CALCULATIONS:
 A) THERE IS NOT CONCRETE SLAB ON GRADE. SEE PLANS
 AND REVISE AS REQUIRED.
  
 B)FILL IN ALLTHE INFORMATION ON TOP OF FORM.
  
 8- ENGINEERING FIRM TO PROVIDE THE CERTIFICATE OF
 AUTHORIZATION NUMBER IN ALL DRAWINGS AS REQUIRED BY
 SEC. 61G15-23..002 OF FLORIDA ADMINISTRATIVE CODE.
 *** PROVIDE THE CERTIFICATE OF AUTHORIZATION NUMBER
 OR REMOVE THE SAGE NAME FROM THE TITLE BLOCK.OR GET
 FLORIDA BOARD OF PROFESSIONAL ENGINEERSAPPROVAL TO
 USE THE SAGE NAME.
  
 9- SPECIFY ALL LOADS INCLUDING LIVE AND DEAD LOADS AS
 REQUIRED BY SEC. R301 AND TABLE R301.5OF 2004 FLORIDA
 RESIDENTIAL CODE.
 *** MISSING THE ATTIC LIVE LOAD AS REQUIRED BY TABLE
 R301.5
  
 10- PROVIDE SOIL TEST REPORT. (REPEAT COMMENT).
  
 11- SURVEYSUBMITTED:
 A) MISSING REAR DECK.
  
 B) NOTE #6 DOESN'T ALLOW THIS DRAWING TO BE USED FOR
 CONSTRUCTION.
  
 12- BRING DRAWINGS FOR HISTORIC APPROVAL AND STAMPING
 PRIOR TO SUBMITTING THEM TO THIS OFFICE. (REPEAT
 COMMENT).
  
 13- PROVIDE PRODUCT APPROVAL AS REQUIRED BY RULE 9B-72
 FOR:
 A) ALL TRUSS CONNECTORS SPECIFIED ON PLANS. (REPEAT
 COMMENT).
  
 B) ROOF SHINGLES. NOA 04-0820.01 SUBMITTED WAS
 SUPERSEDED BY DADE COUNTY. SEE ATTACHED COPY. (REPEAT
 COMMENT).
 NEED TO PROVIDE NOA THAT SUPERSEDED ABOVE ONE.
  
 14- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
 *** ENGINEER RESPONSE LETTER SAID THAT NOTE WAS
 ADDED. NO INFORMATION WAS FOUND IN THIS PACKAGE.
 IF SEPARATE LETTER IS PROVIDED TO SHOW REVIEW OF
 PRODUCT APPROVALS, THEN, PLEASEMAKE SURE CORRECT NOA
 NUMBERS,COMPANY NAME, SPECIFIC PRODUCT, MODEL, ETC.
 IS LISTED AND MATCHING PRODUCT APPROVALS SUBMITTED TO
 AVOID CONFLICTS OR UNNECESSARY DELAYS.
  
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-04-16 Cont ID  
Sent By jgomez Date 2007-04-16 Time 17:56 Rev Time 0.00
Received By jgomez Date 2007-04-16 Time 17:56 Sent To  
Notes
2007-04-16 18:02:43BUILDING REVIEW CHECKLIST:
 1- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713.13 FLORIDA STATUTE.
  
 2- AFTER DRAWINGS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY TO PAY IMPACT FEES. BRING BACK STAMPED PLANS AND
 COPY OF PAID RECEIPT.
  
 3- SHEET A1:
 A) BUILDING DIMENSIONS AND SETBACKS DON'T MATCH
 THOSE DIMENSIONS SHOWN ON SURVEY. REVISE AS REQUIRED.
 B) REVISE INFORMATION GIVEN:* THIS IS NOT A
 MULTIFAMILY DWELLING.** THERE IS NOT NEW PORCH. SEE
 PLANS.
 C) REVISE DESIGN DATA: * DESIGN CONSIDERATION IS FOR
 IS FOR INTERIOR ZONES AND END ZONES, NOT INTERIOR AND
 EXTERIOR ZONES. REVISE AS REQUIRED.** UPDATE BUILDING
 CODE. SEE FBC 2004.
 D) THIS IS PENN STREET, NOT AVENUE. REVISE AS
 REQUIRED.
  
 4- SHEET A2:
 A) BUILDING DIMENSIONS DON'T MATCH SURVEY. REVISE AS
 REQUIRED.
 B) SPECIFY SAFETY GLASS FOR NEW BATHROOM WINDOW.
 SEC. R308.42004 FLORIDA RESIDENTIAL CODE.
 C) SPECIFY ATTIC ACCESS LOCATION AND SIZE. SEC. R807
 2004 FLORIDA RESIDENTIAL CODE.
 D) REVISE DESIGN DATA INFORMATION. SEE ITEM 3(C)
 ABOVE.
 E) WALL LEGEND CALLS FOR 2X4 BEARING WALL, WHILE
 FLOOR PLAN SHOWS 2X6 BEARING WALL. REVISE AS REQUIRED.
  
 F) REVISE GENERAL CONSTRUCTION NOTE REGARDING
 CONCRETE BLOCK COMPRESSIVE STRENGTH. SEE SEC. R606.4
 2004 FLORIDA RESIDENTIAL CODE AND REVISE AS REQUIRED.
  
 G) WIND LOAD AFFIDAVIT CHART: * CLARIFY WHY INTERNAL
 PRESSURE COEFFICIENT IS 0.SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.** AND, REVISE WIND PRESSURES
 ZONES, THEY ARE INTERIOR AND END ZONES, NOT INTERIOR
 AND EXTERIOR ZONES.
 F) PROVIDE COMPLETE INFORMATION FOR STEPS, LANDING,
 HANDRAIL AND GUARDRAIL AT REAR AREA BY SLIDING GLASS
 DOORS. SEE SEC. R311.5 AND R3122004 FLORIDA
 RESIDENTIAL CODE.
  
 5- SHEET A3:
 A) PROVIDE CRAWL SPACE VENTILATION AND ACCESS.SEE
 SEC. R4082004 FLORIDA RESIDENTIAL CODE FOR MIN. SIZES
 AND LOCATION.
 B) TYPICAL WALL FRAMING DETAIL/SECTION DOESN'T APPLY
 TO THIS PROJECT. SEE TYPICAL WALL SECTION AND REVISE AS
 REQUIRED TO MATCH.
 C) TYPICAL WALL SECTION:
 * SPECIFY HOW COMPLYING WITH SEC. R3192004 FLORIDA
 RESIDENTIAL CODE.
 ** SPECIFY HOW COMPLYING WITH SEC. R3202004
 FLORIDA RESIDENTIAL CODE.
 *** SPECIFY DESIGN CRITERIAFOR SOIL BEARING
 CAPACITY.
 **** IT'S NOT CLEAR IF USING PRE-ENGINEERED ROOF
 TRUSSES OR CONVENTIONAL ROOF FRAMING. INFORMATION IS
 MISLEADING AND DOESN'T MATCH ROOF FRAMING PLAN.
 ***** SIMPSON MAS CONNECTOR SPECIFIED TO FASTEN 2X6
 STUD AT BOTTOM DOESN'T WORK FOR THIS APPLICATION.
 REVISE AS REQUIRED. SEC. 106.1.2 CITY AMENDMENTS TO FBC
 2004.
 ****** CLARIFY NOTE REGARDING FOOTING REINFORCEMENT
 CONCRETE COVER.3" & 2" COVER AT BOTTOM?. SEE SEC.
 R403 OF 2004 FLORIDA RESIDENTIAL CODE FOR MIN. COVERING
 REQUIRED.
 ******* PROVIDE COMPLETE SPECS FOR FASTENING OF STUD
 WALL TO STEM WALL. SEC. 106.1.2 CITY AMENDMENTS TO FBC
 2004.
 D)PROVIDE INFORMATION FOR STEPS AT SLIDING GLASS
 DOORS FROM FAMILY ROOM.
 E)PROVIDE SECTION/DETAIL AT 16" DEEP LINTEL THAT
 PROVIDE ACCESS FROM ONE SIDE OF HOUSE TO THE OTHER. SEE
 FOUNDATION PLAN. SEC. 106.1.2 CITY AMENDMENTS TO FBC
 2004.
 F)REVISE SIZE OF CRAWL SPACE VENTILATION.
 COORDINATE WITH ITEM 3(A) ABOVE.
 G)REVISE ATTIC VENTING CALCULATIONS. INCLUDE SIZE
 SHOWN ON TYP. WALL SECTION AND SPECIFY NET CLEAR
 OPENING.
  
 6- SHEET A4:
 A) REVISE DESIGN DATA FOR WIND LOADS. SPECIFY
 CURRENT CODE AND THERE IS NOT EXTERIOR ZONE.
 B) ASTM D-3161 IS NOT A TEST METHOD FOR 140MPH.
 REVIEWSUCH STANDARD AND REVISE NOTE AS REQUIRED.
  
 7- SHEET A5:
 A) REVISE ROOF SHEATHING NAILING SCHEDULE. SEE SEC.
 R803.2.3.1 2004 FLORIDA RESIDENTIAL CODE AND REVISE
 TYPE OF FASTENER ASREQUIRED.
 B) REVISE STRAP TYPE NAILING TABLE.NEED TO SPECIFY
 WOOD TO WOOD CONNECTORS OR WOOD TO MASONRY CONNECTORS
 AS REQUIRED.EG: CONNECTOR A DOESN'T WORK. NEED WOOD
 TO WOOD CONNECTOR.REVISE ALL SCHEDULE AS REQUIRED.
 C) PROVIDE COMPLETE DETAIL AND SPECS SHOWING COMPLIANCE
 WITH SEC. 2304.3.4 FBC 2004 AND SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004. DETAIL FOR TYP. GABLE END WALL
 IS INCOMPLETE (THERE ARE DETAILS THAT ARE NOT PROVIDED)
 AND DOESN'T COMPLY WITH THIS SECTION.
  
 8- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 13-600 FBC 2004.
  
 9- ENGINEERING FIRM TO PROVIDE THE CERTIFICATE OF
 AUTHORIZATION NUMBER IN ALL DRAWINGS AS REQUIRED BY
 SEC. 61G15-23..002 OF FLORIDA ADMINISTRATIVE CODE.
  
 10- SPECIFY ALL LOADS INCLUDING LIVE AND DEAD LOADS AS
 REQUIRED BY SEC. R301 AND TABLE R301.5OF 2004 FLORIDA
 RESIDENTIAL CODE.
  
 11- PROVIDE SOIL TEST REPORT.
  
 12- PROVIDE SURVEYWITH ORIGINAL SIGNATURE AS REQUIRED
 BY CHAPTER 472FLORIDA STATUTE.
  
 13- BRING DRAWINGS FOR HISTORIC APPROVAL AND STAMPING
 PRIOR TO SUBMITTING THEM TO THIS OFFICE.
  
 14- PROVIDE PRODUCT APPROVAL AS REQUIRED BY RULE 9B-72
 FOR:
 A) ALL TRUSS CONNECTORS SPECIFIED ON PLANS.
 B) ROOF SHINGLES. NOA 04-0820.01 SUBMITTED WAS
 SUPERSEDED BY DADE COUNTY. SEE ATTACHED COPY.
  
 15- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 16- VALUE DECLARED ON THE PERMIT APPLICATION IS TOO
 LOW.OWES $856.50 FOR UPDATED VALUATION AND RADON
 FEES. SEC. 108.3 CITY AMENDMENTS TO FBC 2004.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-12-03 Cont ID  
Sent By btrobaug Date 2007-12-03 Time 07:47 Rev Time 0.00
Received By btrobaug Date 2007-12-03 Time 07:26 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-03-20 Cont ID  
Sent By btrobaug Date 2007-03-20 Time 17:45 Rev Time 0.50
Received By btrobaug Date 2007-03-20 Time 17:06 Sent To M
Notes
2007-03-20 17:45:10 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} PLEASE CORRECT THE ELECTRICAL NOTES AS FOLLOWS:
 #2 REFERENCES THE "SOUTH FLORIDA BUILDING CODE",
 WHICH IS NO LONGER IN USE. THE STATE OF FLORIDA PER 553
 FS HAS ADOPTED THE 2004 FBC AND ALL REFERENCED
 MATERIAL.
 #3 PER 210.8(A)(6) ALL COUNTER TOP RECEPTACLES
 SHALL BE GFCI PROTECTED.
 #4 SMOKE ALARMS MUST BE AFCI PROTECTED. THE NOTE
 REFERENCES "SMOKE DETECTORS, NOT SMOKE ALARMS. SEE THE
 DEFINITION OF "SMOKE DETECTORS" 11.8.2.1 NFPA-72,
 CLARIFY IF USING DETECTORS OR
 ALARMS, TO AVOID CONFUSION IN THE FIELD.
 #7 REFERENCES A CODE ARTICLE FROM 1996.THE 2005 NEC
 WAS ADOPTED BY THE FLORIDA LEGISLATURE EFFECTIVE 8
 DECEMBER 2006.
  
 2} THE "EXISTING" SERVICE IS IN VIOLATION OF 250.66,
 MUST HAVE A #6 EQUIPMENT GROUND RAN WITH THE FEEDERS
 FROM THE DISCONNECT SHOWN ON THE RISER (BUT NOT ON THE
 FLOOR PLAN) TO THE PANEL. THE EXISTING #6 GEC IS
 REQUIRED TO BE #4 PER 250.66. ALSO VERIFY IT BEING RAN
 IN A 2" CONDUIT.
  
 3} THE REQUIRED BATH CIRCUITS PER 210.11(C)(3) ARE NOT
 LISTED ON THE PANEL SCHEDULE.
  
 4} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
 IF AN ARCHITECT OR ENGINEER, COMPLY WITH 418 AND 417
 FS, RESPECTIVELY. THE CONTRACTOR OF RECORD MAY BE THE
 DESIGN PROFESSIONAL IF EXEMPTIONS UNDER THOSE STATUTES
 ARE APPLICABLE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-11-16 Cont ID  
Sent By adarroug Date 2007-11-16 Time 11:00 Rev Time 0.00
Received By adarroug Date 2007-11-16 Time 11:00 Sent To Z
Notes
2007-11-16 11:00:38TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-03-20 Cont ID  
Sent By adarroug Date 2007-03-20 Time 09:06 Rev Time 0.00
Received By adarroug Date 2007-03-20 Time 09:06 Sent To E
Notes
2007-03-20 09:07:28TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-04-16 Cont ID  
Sent By jgomez Date 2007-04-16 Time 17:57 Rev Time 0.00
Received By jgomez Date 2007-03-15 Time 14:23 Sent To  
Notes
2007-03-15 14:23:40TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-12-03 Cont ID  
Sent By tgordon Date 2007-12-03 Time 09:33 Rev Time 0.30
Received By tgordon Date 2007-12-03 Time 09:33 Sent To P
Notes
2007-12-03 09:45:57PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) MECHANICAL PLAN EQUIPMENT LISTING SHOWS THE A/C
 SYSTEM AS A 12 SEER, SEE 2004 FBC 13-607.1.ABC.3.2.1
 MINIMUM SEER IS 13. PLEASE CORRECT.
  
 2) COULD NOT FIND THE MODEL NUMBERS LISTED ON THE
 MECHANICAL PLAN FOR THE A/C SYSTEM ON THE ARI DIRECTORY
 WEB SITE. PLEASE CORRECT MODEL NUMBERS OR SUBMIT ARI
 REFERENCE NUMBER.
  
 3) THE SUPPLY AIR DUCT (FLEX) FROM THE MIXING BOX TO
 THE BATHROOM NEEDS TO BE SIZED, SEE YELLOW HIGH LIGHT
 ON MECHANICAL PLAN.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-03-27 Cont ID  
Sent By tgordon Date 2007-03-27 Time 15:34 Rev Time 0.30
Received By tgordon Date 2007-03-27 Time 15:34 Sent To P
Notes
2007-03-27 15:41:38*** DENIED ***
 1) PLEASE SUBMIT ENERGY CALCULATIONS,SEE 2004 FBC
 13-101.2.2.
  
 2) MECHANICAL PERMIT NUMBER 07030532 APPLIED FOR BUT NO
 MECHANICAL PLANS WERE SUBMITTED FOR REVIEW. PLEASE
 SUBMIT MECHANICAL PLANS FOR REVIEW, SEE 2004 FBC CITY
 WPB AMEND. 106.3.5.4 (10).
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-12-03 Cont ID  
Sent By mperson Date 2007-12-03 Time 13:29 Rev Time 0.00
Received By mperson Date 2007-12-03 Time 13:29 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-03-29 Cont ID  
Sent By mperson Date 2007-03-29 Time 13:56 Rev Time 0.55
Received By mperson Date 2007-03-29 Time 13:56 Sent To B
Notes
2007-03-29 14:46:13DENIED
 REFERENCE:
 ** FBC-2004 PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION IS REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. FAC-61G15-23.002 SEAL SIGNATURE AND DATE
 SHALL BE AFFIXED:
 EACH SHEET OF PLANS AND PRINTS WHICH
 MUST BE SEALED UNDER PROVISIONS OF
 CHAPTER 471 SHALL BE SEALED, SIGNED AND
 DATED BY THE PROFESSIONAL ENGINEER IN
 RESPONSIBLE CHARGE. ENGINEERS SHALL
 LEGIBLY INDICATE THEIR NAME, ADDRESS,
 AND LICENSE NUMBER ON EACH SHEET. IF
 PRACTICING THROUGH A DULY AUTHORIZED
 ENGINEERING BUSINESS, ENGINEERS SHALL
 LEGIBLY INDICATE THEIR NAME LICENSE NUM-
 BER, AS WELL AS, THE NAME, ADDRESS, AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF
 THE ENGNEERING BUSINESS ON EACH SHEET.
  
 NOTE: CERTIFICATE OF AUTHORIZATION NUMBER OF THE
 ENGINEERING BUSINESS IS MISSING FROM SHEETS. PLEASE
 CORRECT AND RESUBMIT.
  
 2. SHEET P-1 SANITARY ISOMETRIC RISER DIAGRAM: PER
 FBC-2004 CHAPTER 1, SECTION 106.1.1
 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL
 BE OF SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE
 AND RELAVENT LAWS, ORDINANCES, RULES AND REGULATIONS,
 AS DETERMINED BY THE
 BUILDING OFFICIAL.
  
 NOTE: THE SUBMITTED SANITARY ISOMETRIC RISER DIAGRAM
 DOES NOT REFLECT THE FLOOR PLAN AND IS NOT CODE
 COMPLIANT. PLEASE REFERENCE THE CORRECTED SANITARY
 ISOMETRIC RISER DIAGRAM ATTACHED TO THE PLUMBING
 COMMENTS THAT REFLECT THE FLOOR PLAN AND ARE CODE
 COMPLIANT FOR THE RESUBMITTAL.
  
 3. SHEET P-1 SANITARY ISOMETRIC RISER DIAGRAM THE
 FOLLOWING IS REQUIRED FOR THE WASHING MACHINE:
  
 (A) 406.3 WASTE CONNECTIONS.THE TRAP AND
 FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES
 WASHER SHALL BE A MINIMUM OF 2 INCHES
 (51MM) IN DIAMETER. THE AUTOMATIC
 CLOTHES WASHER FIXTURE DRAIN SHALL
 CONNECT TO A BRANCH DRAIN OR DRAINAGE
 STACK A MINIMUM OF 3 INCHES (76MM) IN
 DIAMETER.
  
 (B) 802.4 STANDPIPES.STANDPIPES SHALL BE INDIVIDUALLY
 TRAPPED. STANDPIPES SHALL
 EXTEND A MINIMUM OF 18 INCHES (457MM)
 AND A MAXIMUM OF 42 INCHES (1066MM)
 ABOVE THE TRAP WEIR. ACCESS SHALL BE
 PROVIDED TO ALL STANDPIPES AND DRAINS
 FOR RODDING. PLEASE INDICATE THE STANDPIPE FOR THE
 WASHING MACHINE ON THE RESUBMITTAL.
  
 4. SHEET P-1 SANITARY ISOMETRIC RISER DIAGRAM THE
 FOLLOWING IS REQUIRED FOR THE WASHING MACHINE
 CLEANOUT:
  
 (A) 708.7 MINIMUM SIZE. CLEANOUTS SHALL
 BE THE SAME NOMINAL SIZE AS THE PIPE
 THEY SERVE UP TO 4 INCHES (102MM)
  
 NOTE: CLEANOUT FOR WASHING MACHINE SHALL BE THREE INCH
 (3"). PLEASE INDICATE THIS ON THE RESUBMITTAL.
  
 (B) 708.9 ACCESS. ACCESS SHALL BE
 PROVIDED TO ALL CLEANOUTS.
 NOTE: CLEANOUT FOR THE WASHING MACHINE TO BE LOCATED
 FOUR FEET ABOVE FINNISH FLOOR (4' A.F.F.). PLEASE
 INDICATE THIS ON THE RESUBMITTAL.
  
 5. SHEET P-1 GENERAL PLUMBING NOTES: NOTE (4) PLEASE
 DELETE THE FOLLOWING "WASTE LINES TO SLOPE 1/8" TO A
 FOOT, UNLESS OTHERWISE NOTED." AND ADD IN ITS PLACE
 "SLOPE OF HORIZONTAL DRAINAGE PIPE PER FBC-2004
 PLUMBING TABLE 704.1" ON THE RESUBMITTAL.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop Z ZONING
Rev No 2 Status F Date 2007-11-29 Cont ID  
Sent By jroach Date 2007-11-29 Time 18:21 Rev Time 0.00
Received By jroach Date 2007-11-29 Time 18:21 Sent To E
Notes
2007-11-29 18:24:50***FAILED***
  
 1) THE REAR SETBACK SHALL BE A MINIMUM OF 10.4 FEET
 (10% OF THE LOT DEPTH).THE ORIGINAL SITE PLAN WAS
 OK....IT WAS THE SURVEY THAT WAS INCORRECT.
  
 2) PORCHES/PATIOS IN EXCESS OF THREE (3) FEET IN HEIGHT
 (INCLUDING THE RAILING) SHALL CONFORM TO THE MINIMUM
 REAR SETBACK REQUIREMENTS.THIS PORCH WAS NOT SHOWN ON
 THE ORIGINAL SUBMITTAL.
  
 3) REPEAT COMMENT - THE LOCATION OF THE A/C EQUIPMENT
 (WITH SETBACK DIMENSIONS) SHALL BE SHOWN ON THE
 SURVEY.
  
 4) THE SURVEY DOES NOT SHOW THE LOCATION OF THE
 NEWLY-PROPOSED PORCH.
  
 5) HISTORIC PRESERVATION DIVISION SHALL REVIEW,
 APPROVE, AND STAMP ALL REVISED PLANS PRIOR TO
 RESUBMITTAL.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2007-03-19 Cont ID  
Sent By jroach Date 2007-03-19 Time 17:23 Rev Time 0.00
Received By jroach Date 2007-03-19 Time 17:23 Sent To I
Notes
2007-03-19 17:26:52***FAILED***
  
 1) THE SETBACKS ON THE SITE PLAN ARE DIFFERENT THAN
 THOSE SHOWN ON THE SURVEY.ENSURE THAT ALL PLANS ARE
 CONSISTENT.
  
 2) THE LOCATION OF THE A/C EQUIPMENT SHALL BE SHOWN ON
 THE SURVEY WITH THE DIMENSION/SETBACK FROM THE PROPERTY
 LINE PROVIDED.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.