Plan Review Details - Permit 07030499
Plan Review Stops For Permit 07030499
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-04-11 Cont ID  
Sent By mjacobs Date 2007-04-11 Time 08:38 Rev Time 0.00
Received By mjacobs Date 2007-04-10 Time 09:59 Sent To PC
Notes
2007-04-10 12:56:17BUILDING PLAN REVIEW
 PERMIT: 07030499
 ADD: 1039 18TH STREET
 CONT: DREAMALITIES CONSTRUCTION
 TEL: (561)842-5500
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3)FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE
 RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE:
 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT
 THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 4)WPB AMENDMENTS 108.3*THE VALUE IS LOW. IF IN THE
 OPINION OF THE BUILDING OFFICIAL THE CLAIMED VALUATION
 IS UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL
 BE DENIED. FOR PERMITTING PURPOSES, THE VALUE SHALL
 INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL,
 INTERIOR FINISH NORMAL SITE WORK, ARCHITECTURAL AND
 DESIGN FEES. OUR VALUATION REFERENCE IS ICC (BVD),
 MARSHALL-SWIFT AND MEANS COST ANALYSIS.
  
 5)R802.1.6TRUSS DESIGN DRAWINGS, PREPARED IN
 CONFORMANCE WITH SEC. R802.1.6.1, SHALL BE PROVIDED TO
 THE BUILDING OFFICIAL AND APPROVED PRIOR TO
 INSTALLATION. TRUSS DESIGN DRAWINGS SHALL INCLUDE, AT A
 MINIMUM, (1) DESIGN WIND SPEED AND EXPOSURE CATETORY
 (2) SLOPE OR DEPTH, SPAN AND SPACING, (3) LOCATION OF
 ALL JOINTS (4)REQUIRED BEARING WIDTHS. (5) DESIGN
 LOADS AS APPLICABLE. (5.1) TOP CHORD LIVE LOAD (5.2)
 TOP CHORD DEAD LOAD (5.3) BOTTON CHORD LIVE LOAD (5.4)
 BOTTOM CHORD DEAD LOAD. ETC.
  
 6)R319.1 LOCATION REQUIRED.
 IN AREAS SUBJECT TO DECAY DAMAGE AS ESTABLISHED BY
 TABLE R301.2(1) , THE FOLLOWING LOCATIONS SHALL REQUIRE
 THE USE OF AN APPROVED SPECIES AND GRADE OF LUMBER,
 PRESSURE TREATED IN ACCORDANCE WITH AWPA C1, C2, C3,
 C4, C9, C15, C18, C22, C23, C24, C28, C31, C33, P1, P2
 AND P3, OR DECAY -RESISTANT HEARTWOOD OF REDWOOD, BLACK
 LOCUST, OR CEDARS. (1)WOOD JOISTS OR THE BOTTOM OF A
 WOOD STRUCTURAL FLOOR WHEN CLOSER THAN 18 INCHES (457
 MM) OR WOOD GIRDERS WHEN CLOSER THAN 12 INCHES (305 MM)
 TO THE EXPOSED GROUND IN CRAWL SPACES OR UNEXCAVATED
 AREA LOCATED WITHIN THE PERIPHERY OF THE BUILDING
 FOUNDATION.
 (2)ALL WOOD FRAMING MEMBERS THAT REST ON CONCRETE OR
 MASONRY EXTERIOR FOUNDATION WALLS AND ARE LESS THAN 8
 INCHES (203 MM) FROM THE EXPOSED GROUND. (5)WOOD
 SIDING, SHEATHING AND WALL FRAMING ON THE EXTERIOR OF A
 BUILDING HAVING A CLEARANCE OF LESS THAN 6 INCHES (152
 MM) FROM THE GROUND.
  
 7)106.3.3* PRODUCT APPROVALS- 2004
 THOSE PRODUCTS THAT ARE RGULATED BY DCA
 RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITTING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. PROVIDE THE STATE COVER SHEET
 FOR THE PRODUCT APPROVALS.
  
 8)THE ENERGY CALCULATION SHEETS ARE NOT LEGIBLE.
 PROVIDE CLEAR AND LEGIBLE INFORMATION. SEE NEW FORMS IN
 PACKAGE.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-03-26 Cont ID  
Sent By btrobaug Date 2007-03-26 Time 10:40 Rev Time 0.50
Received By btrobaug Date 2007-03-26 Time 10:00 Sent To M
Notes
2007-03-26 10:40:20 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THE 2005 NEC WAS ADOPTED BY THE FLORIDA LEGISLATURE
 EFFECTIVE 8 DECEMBER 2006. THE APPLICATION FOR THIS
 PROJECT WAS AFTER THAT DATE AND THE PLANS ARE SUBJECT
 TO THAT CODE. PLEASE CHANGE ALL NOTES TO REFLECT THIS
 CHANGE.
  
 2} SMOKE DETECTORS ARE REQUIRED TO BE INSTALLED PER
 R313.1 FBC, (OUTSID EACH SLEEPING ROOM), & 11.8.3.5
 NFPA-72.ALSO SEE THE DEFINITION OF "SMOKE DETECTORS"
 11.8.2.1 NFPA-72, CLARIFY IF USING DETECTORS OR ALARMS,
 TO AVOID CONFUSION IN THE FIELD. ALSO SMOKE ALARMS TO
 BE AFCI PROTECTED PER 210.12.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-03-22 Cont ID  
Sent By adarroug Date 2007-03-22 Time 08:12 Rev Time 0.00
Received By adarroug Date 2007-03-22 Time 08:12 Sent To E
Notes
2007-03-22 08:13:10TO "SFR" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2007-04-11 Time   Rev Time 0.00
Received By adarroug Date 2007-03-14 Time 14:38 Sent To  
Notes
2007-03-14 14:39:16TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-03-27 Cont ID  
Sent By tgordon Date 2007-03-27 Time 11:21 Rev Time 0.30
Received By tgordon Date 2007-03-27 Time 11:21 Sent To P
Notes
2007-03-27 11:35:10*** DENIED ***
 1) PLEASE SHOW THE SIZE OFF THE RETURN AIR GRILL TO THE
 AIR HANDLER UNIT.
  
 2) ELECTRICAL PLANS ARE CALLING FOR A 7.5 KW
 ELECT.HEATER, AND THE MECHANICAL PLANS ARE CALLING FOR
 A 10 KW HEATER THE TWO MUST COINCIDE, PLEASE CORRECT.
  
 3) THE MECHANICAL PLANS ARE CALLING FOR A 5 TON A/C
 SYSTEM WHICH IS TO LARGE. MANUAL J CALCULATIONS ARE
 CALLING FOR 18,235 SENSIBLE BTU'S, AND THE MECHANICAL
 PLANS ARE CALLING FOR 38,500 SENSIBLE BTU'S, THE PLANS
 CAN ONLY CALL FOR 15% MORE THAN THE MANUAL J
 CALCULATIONS, SEE 2004 FBC 13-607.1.ABC.1.1 (12-8-06
 REVISION). PLEASE CORRECT.
  
 4) THE ENERGY CALCULATIONS ARE CALLING FOR A 30 SEER
 A/C SYSTEM, AND THE MECHANICAL PLANS ARE CALLING FOR A
 13 SEER, THE TWO MUST COINCIDE, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-03-28 Cont ID  
Sent By mperson Date 2007-03-28 Time 15:31 Rev Time 0.50
Received By mperson Date 2007-03-28 Time 15:31 Sent To B
Notes
2007-03-28 15:56:49DENIED
 REFERENCE:
 ** FBC-2004 PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION IS REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.4
 RESIDENTIAL (ONE AND TWO-FAMILY) PLEASE SUBMIT A
 PLUMBING SANITARY ISOMETRIC RISER DIAGRAM INDICATING
 ALL WASTE, VENTS, TRAPS AND SIZES WITH CLEANOUT
 LOCATIONS OF THE PROPOSED PLUMBING.
  
 2. SHEET 4 FOUNDATION PLAN:
 PER FBC-2004, PLUMBING, SECTION 909.1
 WET VENT PERMITTED: ONLY THE FIXTURES
 WITHIN THE BATHROOM GROUPS SHALL CONNECT
 TO THE WET-VENTED HORIZONTAL BRANCH
 DRAIN. ANY ADDITIONAL FIXTURES SHALL
 DISCHARGE DOWNSTREAM OF THE WET VENT.
  
 3. SHEET 4 FOUNDATION PLAN:
 (A) 406.3 WASTE CONNECTIONS.THE TRAP AND
 FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES
 WASHER SHALL BE A MINIMUM OF 2 INCHES
 (51MM) IN DIAMETER. THE AUTOMATIC
 CLOTHES WASHER FIXTURE DRAIN SHALL
 CONNECT TO A BRANCH DRAIN OR DRAINAGE
 STACK A MINIMUM OF 3 INCHES (76MM) IN
 DIAMETER.
 (B) 802.4 STANDPIPES.STANDPIPES SHALL BE INDIVIDUALLY
 TRAPPED. STANDPIPES SHALL
 EXTEND A MINIMUM OF 18 INCHES (457MM)
 AND A MAXIMUM OF 42 INCHES (1066MM)
 ABOVE THE TRAP WEIR. ACCESS SHALL BE
 PROVIDED TO ALL STANDPIPES AND DRAINS
 FOR RODDING
  
 4. SHEET 4 FOUNDATION PLAN:
 (A) 708.3.4 BASE OF STACK. A CLEANOUT
 SHALL BE PROVIDED AT THE BASE OF EACH
 WASTE OR SOIL STACK
 (B) 708.3.5 BUILDING DRAIN AND BUILDING
 SEWER JUNCTION. THERE SHALL BE A
 CLEANOUT NEAR THE JUNCTION OF THE
 BUILDING DRAIN AND THE BUILDING SEWER.
 (C) 708.7 MINIMUM SIZE. CLEANOUTS SHALL
 BE THE SAME NOMINAL SIZE AS THE PIPE
 THEY SERVE UP TO 4 INCHES (102MM)
 NOTE: CLEANOUT FOR WASHING MACHINE SHALL BE THREE INCH
 (3")
 (D) 708.9 ACCESS. ACCESS SHALL BE
 PROVIDED TO ALL CLEANOUTS.
 NOTE: CLEANOUT FOR WASHING MACHINE TO BE LOCATED AT
 FOUR FEET ABOVE FINNISH FLOOR (4' A.F.F.) PLEASE
 INDICATE THIS ON THE RESUBMITTAL.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop Z ZONING
Rev No 1 Status F Date 2007-03-21 Cont ID  
Sent By adavila Date 2007-03-21 Time 17:16 Rev Time 0.00
Received By adavila Date 2007-03-21 Time 13:08 Sent To I
Notes
2007-03-21 17:22:49PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 1.ONLY ONE SIGNED AND SEALED SURVEY WAS PROVIDED WITH
 THE APPLICATION PACKET.NEED TO PROVIDE AN ADDITIONAL
 SIGNED AND SEALED COPY.
  
 2.PROPOSED ADDITION WITH SETBACK DIMENSIONS SHALL BE
 SHOWN ON BOTH COPIES OF SURVEY.
  
 3.SIDE SETBACK DIMENSIONS NEED TO BE CORRECTED ON THE
 SITE PLAN TO REFLECT THE SIDE SETBACK DIMENSIONS ON
 SURVEY.
  
 4.PROVIDE BUILDING HEIGHT DIMENSIONS FROM GRADE.
  
 COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA Q. OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.