Plan Review Details - Permit 07030479
Plan Review Stops For Permit 07030479
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-07-30 Cont ID  
Sent By lmartine Date 2007-07-30 Time 09:50 Rev Time 0.00
Received By lmartine Date 2007-07-30 Time 09:50 Sent To G
Notes
2007-07-30 09:52:35GAVE TO MICHAEL

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-07-09 Cont ID  
Sent By lmartine Date 2007-07-09 Time 15:10 Rev Time 0.00
Received By lmartine Date 2007-07-09 Time 15:10 Sent To  
Notes
2007-07-09 15:14:44BUILDING REVIEW COMMENTS
  
  
  
 PROVIDE 2 COMPLETE SETS OF CONSTRUCTION DOCUMENTS.
  
 SEE REVISED MANUFACTURE'S SPECIFICATIONS, SYSTEM SHALL
 BE MOUNTED A MINIMUM OF 5' FROM ANY STRUCTURE.
  
  
  
  
  
  
 L.MARTINEZ
 561-805-6710

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-04-23 Cont ID  
Sent By lmartine Date 2007-04-23 Time 10:50 Rev Time 0.00
Received By lmartine Date 2007-04-23 Time 10:50 Sent To  
Notes
2007-04-23 13:06:17 
 BUILDING REVIEW COMMENTS
  
  
  
 PROVIDE 2 COPIES OF COMPLETE CONSTRUCTION DOCUMENTS.
  
 THE GENERATOR MOUNTING DETAIL IS COPIED ON PROFESSIONAL
 ENGINEER, THOMAS TWOMEY'S TITLE BLOCK, PLEASE PROVIDE
 MR. TWOMEY'S EMBOSED SEAL AND WET SIGNATURE AS REQUIRED
 BY FLORIDA STATUE 471, OR SUBMIT DETAIL ON DIFFERENT
 FORMAT.
  
  
  
  
  
 L.MARTINEZ
 561-805-6710
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-07-26 Cont ID  
Sent By btrobaug Date 2007-07-26 Time 14:30 Rev Time 0.00
Received By btrobaug Date 2007-07-26 Time 13:54 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-06-25 Cont ID  
Sent By btrobaug Date 2007-06-25 Time 10:02 Rev Time 0.00
Received By btrobaug Date 2007-06-25 Time 07:11 Sent To G
Notes
2007-06-25 10:02:25 
  
  
 DENIED/INCOMPLETE INFORMATION
  
 1} THE MANUFACTURERS RECOMMENDED SETBACK IS 5' PER PAGE
 #5 OF THE INSTALLATION MANUAL. THERE IS NOT THE
 RECOMMENDED CLEARANCE BETWEEN THE GENERATOR AND THE
 RESIDENCE.
  
 NOTE: NO FURTHER ACTION CAN BE TAKEN REGARDING ISSUING
 THIS PERMIT AS LONG AS THERE IS A PREVIOUS APPLICATION
 STILL OPEN (#06060449) FOR THIS INSTALLATION. THE OWNER
 MUST CONTACT ADRIANNA MCKENZIE, SUPERVISOR (805-6681)
 LICENSES/PERMITS, CONSTRUCTION SERVICES DEPARTMENT, TO
 CLEAR THIS MATTER UP.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-04-12 Cont ID  
Sent By btrobaug Date 2007-04-12 Time 11:34 Rev Time 0.33
Received By btrobaug Date 2007-04-12 Time 11:25 Sent To G
Notes
2007-04-12 11:34:44 
  
 DENIED/INCOMPLETE INFORMATION
  
 1} PROVIDE MANUFACTURERS SPECIFICATIONS
 INDICATING RECOMMENDED SETBACKS FOR THE GENERATOR.
  
 2} PROVIDE A PANEL SCHEDULE FOR THE
 GENERATOR PANEL. 106.3.5.4 FBC AS
 AMENDED.
  
 3} PLEASE LOCATE ALL SERVICE AND GENERATOR EQUIPMENT ON
 A SITE PLAN, NOT THE SURVEY, METER ENCLOSURE,
 DISCONNECTS, ATS AND PANELS, SO THAT COMPLIANCE WITH
 ARTICLES 225 AND 230 CAN BE REVIEWED.
  
 4} TWO SETS OF ALL DOCUMENTS MUST BE SUBMITTED FOR
 REVIEW PER 106.1 FBC AS AMENDED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2007-07-30 Cont ID  
Sent By mperson Date 2007-07-30 Time 13:32 Rev Time 0.45
Received By mperson Date 2007-07-30 Time 13:32 Sent To B
Notes
2007-07-30 13:33:56NOTE: SENT TO LUIS MARTINEZ.

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2007-06-29 Cont ID  
Sent By mperson Date 2007-06-29 Time 10:45 Rev Time 0.33
Received By mperson Date 2007-06-29 Time 10:45 Sent To M
Notes
2007-06-29 11:31:16DENIED 2ND TIME
 REFERENCE:
 ** FBC-2004 PLUMBING.
 ** FBC-2004 FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 1. THE MANUFACTURER'S RECOMMENDED SETBACK IN THE
 INSTALLATIOM MANUAL ON PAGE #5, 1.3 GENERATOR LOCATION,
 STATES "A GOOD RULE IS TO ALLOW FIVE FEET OF SPACE ON
 ALL SIDES". THERE IS NOT THE RECOMMENDED CLEARANCE
 BETWEEN THE GENERATOR AND THE RESIDENCE.
  
 NOTE: NO FUTHER ACTION CAN BE TAKEN REGARDING ISSUING
 THIS PERMIT AS LONG AS THERE IS A PREVIOUS APPLICATION
 OPEN (#06060449) FOR THIS INSTALLATION. THE OWNER MUST
 CONTACT ADRIANNA MCKENZIE, SUPERVISER, LICENSE/PERMITS,
 CONTRUCTION SERVICES DEPARTMENT(561-805-6681) TO CLEAR
 THIS MATTER UP.
  
 2.NOTE: THE RESUBMITTED DRAWING IS INDICATING THE
 EXISTING AS WELL AS THE PROPOSED GENERATOR BTU LOAD.
 BUT IT IS FAILING TO INDICATE THE LONGEST LENGTH OF THE
 SYSTEM OR THE LOCATION OF THE MP REGULATORS TO THE
 EXISTING APPLIANCES. PLEASE CLARIFY THIS AND PLEASE
 KNOW THAT THE GENERATOR LOCATION MAY CHANGE DUE TO
 CLEARENCES. (SEE COMMENT #1).
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-04-16 Cont ID  
Sent By mperson Date 2007-04-16 Time 09:10 Rev Time 0.45
Received By mperson Date 2007-04-16 Time 09:10 Sent To B
Notes
2007-04-16 09:50:51DENIED
 REFERENCE:
 ** FBC-2004 FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. NOTE: THERE ARE TWO GEN/RES PERMIT APPLICATIONS FOR
 THIS RESIDENCE. HOME OWNER MUST SUBMIT A NOTARIZED
 LETTER FIRING THE CONTRACTOR AND VOIDING PERMIT NUMBERS
 WITH MASTER #0606449 IN ORDER TO PROCESS THIS GEN/RES
 PERMIT APPLICATION.
  
 2. NOTE: SAID RESIDENCE HAS EXISTING GAS TO A DRYER,
 W/HTR, BBQ, COOKTOP, AND POOL HEATERPLEASE REFERENCE
 CLOSED PERMIT #05030382 PERMIT DISPLAY ATTACHED TO GAS
 COMMENTS INDICATING THIS. BTU LOAD OF EACH APPLIANCE
 AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33). PLEASE INCLUDE THE EXISTING GAS SYSTEM BTU
 LOAD ON THE RESUBMITTAL..
  
 3.SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 NOTE: PLEASE INCLUDE THE EXISTING SYSTEM ON THE
 RESUBMITTED ISOMETRIC INDICATING THE LONGEST LENGTH
 FROM THE METER AND THE LOCATION OF THE MP REGULATORS.
  
 4. PLEASE SUBMIT MANUFACTURER SPECIFICATIONS
 INDICATING RECOMMENDED SET BACKS TO STRUCTURES.
  
 5. A GAS PERMIT CAN NOT BE ISSUED UNTIL
 A GEN/RES PERMIT APPLICATION HAS BEEN
 APPROVED BY ZONING FOR THE GENERATOR LOCATION.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-06-22 Cont ID  
Sent By adarroug Date 2007-06-22 Time 16:31 Rev Time 0.00
Received By adarroug Date 2007-06-22 Time 16:31 Sent To E
Notes
2007-06-22 16:31:40TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-06-01 Cont ID  
Sent By adarroug Date 2007-06-01 Time 10:11 Rev Time 0.00
Received By adarroug Date 2007-06-01 Time 10:11 Sent To Z
Notes
2007-06-01 10:11:24TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-03-29 Cont ID  
Sent By dpalmer Date 2007-03-29 Time 08:40 Rev Time 0.00
Received By dpalmer Date 2007-03-29 Time 08:39 Sent To  
Notes
2007-03-29 08:41:16TO RESIDENTIAL GEN RACK. ELEC

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-04-23 Cont ID  
Sent By lmartine Date 2007-04-23 Time 10:49 Rev Time 0.00
Received By lmartine Date 2007-04-23 Time 10:50 Sent To  
Notes
2007-03-14 09:19:22TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-07-26 Cont ID  
Sent By tgordon Date 2007-07-26 Time 14:53 Rev Time 0.20
Received By tgordon Date 2007-07-26 Time 14:53 Sent To  
Notes
2007-07-26 14:58:33GAVE FILE TO LUIS M.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-06-29 Cont ID  
Sent By tgordon Date 2007-06-29 Time 12:24 Rev Time 0.20
Received By tgordon Date 2007-06-29 Time 12:24 Sent To B
Notes
2007-06-29 12:26:05*** DENIED ***
 1) SEE ELECTRICAL REVIEW, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-03-30 Cont ID  
Sent By tgordon Date 2007-03-30 Time 12:02 Rev Time 0.20
Received By tgordon Date 2007-03-30 Time 12:02 Sent To E
Notes
2007-03-30 12:04:17*** DENIED ***
 1) SEE ZONING REVIEW NOTES, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 1 Status N Date 2007-04-23 Cont ID  
Sent By btrobaug Date 2007-04-12 Time 11:49 Rev Time 0.00
Received By lmartine Date 2007-04-23 Time 10:49 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2007-06-22 Cont ID  
Sent By jbabcock Date 2007-06-22 Time 16:17 Rev Time 0.00
Received By jbabcock Date 2007-06-22 Time 16:16 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2007-03-27 Cont ID  
Sent By jbabcock Date 2007-03-27 Time 17:20 Rev Time 0.00
Received By jbabcock Date 2007-03-27 Time 17:20 Sent To  
Notes
2007-03-27 17:19:10PLANNING AND ZONING-FAILED
  
 1. PROVIDE RESPONSE TO COMMENTS IN WRITING.
  
 2. PURSUANT TO NOTES 1 SHEET 2 OF 2, PROVIDE A SIGNED
 AND SEALED SURVEY.
  
 3.PROVIDE DIMENSIONS FROM PROPOSED GENERATOR
 TO THE SOUTH PROPERTY LINE ON PLANS.
  
 FOR ANY ADDITIONAL INFORMATION OR QUESTIONS YOU MAY
 CONTACT:
  
 JULIA BABCOCK
 PLANNER
 OFFICE: (561) 822-1442
 EMAIL: [email protected]