Plan Review Details - Permit 07030449
Plan Review Stops For Permit 07030449
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-06-21 Cont ID  
Sent By rmcdouga Date 2007-06-21 Time 16:26 Rev Time 0.00
Received By rmcdouga Date 2007-06-21 Time 16:26 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-04-03 Cont ID  
Sent By rmcdouga Date 2007-04-03 Time 09:03 Rev Time 0.00
Received By rmcdouga Date 2007-04-03 Time 09:03 Sent To  
Notes
2007-04-03 09:15:53DENIED BY BUILDING
  
 1) SUBMIT 2 SETS OF DRAFTSMAN QUALITY PLANS DRAWN TO A
 MINIMUM 1/8 INCH SCALE SHOWING THE EXISTING AND NEW
 LOCATIONS OF THE KITCHEN SINK. FBC 106.1.1* INFORMATION
 ON CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL
 BE DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 ELECTRONIC MEDIA DOCUMENTS ARE PERMITTED TO BE
 SUBMITTED WHEN APPROVED BY THE BUILDING OFFICIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL (SEE ALSO SECTION 106.3.5 ).
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-06-05 Cont ID  
Sent By btrobaug Date 2007-06-05 Time 07:42 Rev Time 0.33
Received By btrobaug Date 2007-06-05 Time 07:35 Sent To P
Notes
2007-06-05 07:43:20 
  
 WIRING WATER HEATER AND REPLACING RECEPTACLES. NOTED
 313.1 FBC.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-03-28 Cont ID  
Sent By btrobaug Date 2007-03-28 Time 09:15 Rev Time 0.33
Received By btrobaug Date 2007-03-28 Time 09:11 Sent To B
Notes
2007-03-28 09:15:09 
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW
  
 TWO SETS OF ALL DOCUMENTS MUST BE SUBMITTED FOR REVIEW
 PER 106.1 FBC AS AMENDED. DRAWINGS ARE REQUIRED SHOWING
 THE SCOPE OF THE WORK TO BE PERMITTED.
  
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-05-31 Cont ID  
Sent By adarroug Date 2007-05-31 Time 15:56 Rev Time 0.00
Received By adarroug Date 2007-05-31 Time 15:56 Sent To E
Notes
2007-05-31 15:57:08TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-04-03 Cont ID  
Sent By rmcdouga Date 2007-04-03 Time 09:03 Rev Time 0.00
Received By rmcdouga Date 2007-03-13 Time 14:30 Sent To  
Notes
2007-03-13 14:31:49TO "P" BOX

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-06-21 Cont ID  
Sent By mperson Date 2007-06-21 Time 13:03 Rev Time 0.33
Received By mperson Date 2007-06-21 Time 13:03 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-03-26 Cont ID  
Sent By mperson Date 2007-03-26 Time 10:35 Rev Time 0.33
Received By mperson Date 2007-03-26 Time 10:35 Sent To E
Notes
2007-03-26 10:41:54DENIED
 REFERENCE:
 ** FBC-2004 PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
  
 THE FOLLOWING CORRECTIONS/INFORMATION IS REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. MORE INFORMATION IS REQUIRED. THE PERMIT
 APPLICATION STATES "MOVE AND CHANGE THE KITCHEN SINK.
 PLEASE INDICATE ON THE RESUBMITTAL WHERE THE PROPOSED
 LOCATION OF THEKITCHEN SINK IS.
 INDICATE ON A DRAWING THE EXISTING PLUMBING LAYOUT, AND
 ON A SEPERATE DRAWING PLEASE INDICATE THE NEW PROPOSED
 PLUMBING LAYOUT.
 A} IF PLUMBING LAYOUT IS THE SAME
 WITH NO CHANGES, PLEASE INDICATE THIS ON
 THE DRAWING.
 B} IF PLUMBING LAYOUT IS THE
 SAME AND THE PLUMBING FIXTURES ARE TO BE
 CHANGED, PLEASE INDCATE ON THE DRAWING.
 "EXACT FIXTURE CHANGE OUT ONLY."
 C} IF THE NEW PROPOSED PLUMBING LAYOUT IS DIFFERENT
 FROM THE EXISTING PLEASE SUBMIT THE FOLLOWING
 INFORMATION REQUIRED IN COMMENT #2
  
 2. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.4
 RESIDENTIAL (ONE AND TWOFAMILY) PLEASE SUBMIT A
 PLUMBING SANITARY ISOMETRIC RISER DIAGRAM INDICATING
 ALL WASTE, VENTS, TRAPS AND SIZES WITH CLEANOUT
 LOCATIONS.
  
 3. PERMIT APPLICATION STATES "REPLACE A WATER HEATER"
 . WHAT KIND OF A WATER HEATER IS BEING REPLACED, IS IT
 A GAS OR AN ELECTRIC WATER HEATER? PLEASE CLARIFY ON
 THE RESUBMITTAL.
  
 4. FBC-2004 CHAPTER 1,SECTION 106.3.4.2:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME, AND ALSO DATE DRAWING. PLEASE DO
 THIS PRIOR TO RESUBMITTING.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721