Plan Review Details - Permit 07030437
Plan Review Stops For Permit 07030437
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-08-30 Cont ID  
Sent By amorse Date 2007-08-30 Time 16:49 Rev Time 0.00
Received By amorse Date 2007-08-30 Time 16:49 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-07-02 Cont ID  
Sent By amorse Date 2007-07-02 Time 18:14 Rev Time 0.00
Received By amorse Date 2007-07-02 Time 18:14 Sent To PC
Notes
2007-07-02 18:21:32 
  
 DENIED
  
 1)PROVIDE THE CORRECT DRAWINGS THAT BELONG TO THE
 FLORIDA STATEWIDE PRODUCT APPROVALS FOR THE ALUMINUM
 SHUTTERS, SEE LINK FOR DRAWING 05-514
  
 2)PROVIDE PRODUCT APPROVALS FOR THE GLASS BLOCK
  
 3)THE ROOF SHEATHING NOTE REQUIRED IS FOR THE NAILING
 PATTERN AND SHALL COMPLY WITH R803.2.3.1 FBC RES.
  
 4)PER 713.13(2) F.S. IF THE IMPROVEMENT DESCRIBED IN
 THE NOC HAS NOT COMMENCED WITHIN 90 DAYS OF RECORDING,
 THE NOTICE IS VOID. PLEASE HAVE THE NOC RERECORDED
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-04-17 Cont ID  
Sent By amorse Date 2007-04-17 Time 15:49 Rev Time 0.00
Received By amorse Date 2007-04-17 Time 15:49 Sent To PC
Notes
2007-04-17 16:54:51 
  
 DENIED
  
 1)PLANS SHALL REFLECT THE CURRENT 2004 FBC WITH 2006
 REVISIONS AND THE CORRECT CONSTRUCTION TYPE. PLEASE SEE
 THAT GENERAL NOTE #1 REFLECTS THE 2001 FBC AND TYPE VI
 UNPROTECTED AS CONSTRUCTION TYPE.
  
 2)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SETS OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561) 233-5025 FOR MOREINFORMATION.
  
 3)DRAWINGS SHALL SHOW THE MINIMUM DEPTH OF FOUNDATION
 ON THE WALL SECTIONS PER R403.1.4 FBC RES.
  
 4)RESIDENTIAL BUILDINGS SHALL COMPLY WITHR311.4.1
 FBC RES. PROVIDE AT MINIMUM NOT LESS THAN ONE DOOR THAT
 MEET THE REQUIREMENTS OF R311.4.2 DOOR SHALL BE 3"-0"
 WIDE AND 6"-8" IN HEIGHT
  
 5)THE SH24 ( 37"X 49") WINDOWS DO NOT MEET THE MIN
 FOR EMERGENCY EGRESS FROM THE BEDROOMS. KINCO WINDOWS
 HAVE DESIGNATIONS THAT DIFFER FROM PGT AND OTHER
 MANUFACTURERS IF USING THEIR WINDOW PLEASE USE THEIR
 DESIGNATION. MOST SH UNITS REQUIRE 5-6" SUBTRACTED FROM
 THE HEIGHT THEN DIVIDE IN HALF TO GET CLEAR OPENING
 HEIGHT.
  
 6)WINDOWS ARE NOT IMPACT RESISTANT THEREFORE PRODUCT
 APPROVALS ARE REQUIRED FOR OPENING
 PROTECTIVES/SHUTTERS
  
 7)PROVIDE ROOF PITCH AND MEAN ROOF HEIGHT ON THE
 ELEVATIONS AS REQUIRED FOR ROOF PRODUCT APPROVAL DESIGN
 PRESSURE CALCULATIONS.
  
 8)SUBMIT ENGINEERED TRUSS DRAWINGS THAT
 COMPLY WITH R802.10.1 FBC WITH PERMIT APPLICATION OR
 BEFORE INSTALLATION THAT HAVE BEEN REVIEWED AND
 APPROVED BY THE DESIGNER OF RECORD
  
 9)PLAN NOTE # 10 ON SHEET 3 OF 4 IS INCORRECT. PER
 1609.1.4 FBC PROTECTION OF OPENINGS IS REQUIRED TO MEET
 LARGE MISSILE IMPACT TESTS WHEN WITHIN 30 FEET OF
 GRADE
  
 10)PROVIDE MINIMUM ROOF SHEATHING ATTACHMENT NOTE OR
 DETAIL ON DRAWINGS
  
 11)SUBMIT ENERGY CALC'S PER 13-101.2.2
 FBC. BE SURE THAT THEY ARE SIGNED AND
 DATED BY PREPARER AND OWNER/AGENT PRIOR
 TO SUBMITTAL. PLEASE SEE MECHANICAL PLAN REVIEW NOTES
 AS TO CORRECT FORM TO BE USED
  
 12)THE FLORIDA COVER SHEET FOR THE JELD-WEN EXTERIOR
 DOOR IS INCORRECT, PLEASE SEE THE NOA'S THAT ARE
 COVERED BY FL #498-R1 ARE NOT THE MIAMI-DADE NOA THAT
 YOU ARE SUBMITTING. THE CORRECT FL# FOR THIS NOA IS FL#
 539-R1
  
 13)THE FLORIDA COVER SHEET FOR THE ENTERGRA "S" ROOF
 TILES IS INCORRECT FL# 7804 USES A TEST LAB REPORT NOT
 A MIAMI-DADE NOA. IT REQUIRES FL# 282-R1
  
 14)THE KINCO WINDOWS THAT WERE SUBMITTED ON YOUR NOA
 ARE NOT IN THE FLORIDA PRODUCT APPROVAL SYSTEM BUT ARE
 IN OUR LOCAL PRODUCT APPROVAL LISTINGS AND THE
 MIAMI-DADE NOA IS ALL THAT IS REQUIRED. PLEASE SEE NOTE
 5 TO CONFIRM THEIR USE.
  
 15)PROVIDE PRODUCT APPROVALS FOR THE CAST-CRETE
 LINTELS OR SUPPLY THERE FL# ON THE LINTEL SCHEDULE AS
 WITH THE TRUSS ANCHORS. (CAN BE FOUND UNDER FL# 158 AND
 CLICK LINK NOA03-0605.05 FOR 8" WIDE LINTELS)
  
 16)THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE
 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL PER 106.3.3 FBC*. ( ALL SHOP
 DRAWINGS AND PRODUCT APPROVALS ARE TO BE REVIEWED AND
 APPROVED BY ARCHITECT)
  
 17)PROVIDE CORRECTED SURVEY PLEASE SEE THE RIGHT SIDE
 OF BUILDING HAS A 2'-0" OFFSET YET BOTH ENDS OF THE
 BUILDING STATE 5'-0" FROM PROPERTY LINE
  
 18)PROVIDE A SITE PLAN THAT SHOWS DRAINAGE IN
 COMPLIANCE WITH THE REQUIREMENTS OF R401.3 FBC RES.
 SITE SHALL NOT DRAIN ON ADJACENT PROPERTY
  
 19)REMOVE ALL OLD PAGES AND RESUBMIT 2 COMPLETE SETS
 OF NEW DRAWINGS AND INCLUDE 1 COPY OF THE OLD PAGES
 ONLY FOR REFERENCE
  
  
 NOTE: FBC = FLORIDA BUILDING CODE 2004
 FBC* = WEST PALM BEACH ADMINISTRATIVE
 AMENDMENTS TO FBC
 FAC = FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-08-27 Cont ID  
Sent By btrobaug Date 2007-08-27 Time 11:52 Rev Time 0.00
Received By btrobaug Date 2007-08-27 Time 11:13 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-07-02 Cont ID  
Sent By btrobaug Date 2007-07-02 Time 13:19 Rev Time 0.00
Received By btrobaug Date 2007-07-02 Time 12:58 Sent To  
Notes
2007-07-02 13:08:24 
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THE RISER INDICATES A METER AND A PANEL, THE PLAN
 INDICATES A DISCONNECT AT THE METER AND THE PANEL
 INSIDE THE UNIT. PLEASE CORRELATE.
  
 2} CIRCUIT #27 MUST BE #12 WIRE ON A 20 AMP CIRCUIT TO
 COMPLY WITH 210.11(C)(1).
  
 3} INDICATE IF THE PROPOSED SERVICE IS OVERHEAD OR
 UNDERGROUND ON THE RISER. 215.5
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2007-04-03 Cont ID  
Sent By btrobaug Date 2007-04-03 Time 07:44 Rev Time 0.25
Received By btrobaug Date 2007-04-03 Time 07:44 Sent To M
Notes
2007-04-03 07:46:26ROUTED TO ELECTRICAL IN ERROR, SEE 3/14/07 REVIEW SENT
 TO MECH, RES RACK./WRT.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-03-14 Cont ID  
Sent By btrobaug Date 2007-03-14 Time 13:34 Rev Time 0.50
Received By btrobaug Date 2007-03-14 Time 12:02 Sent To Z
Notes
2007-03-14 12:38:26 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN,
 METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT
 COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE REVIEWED.
  
 2} CIRCUIT #19 DOES NOT COMPLY WITH210.52(B)(1) FOR
 KITCHEN (SMALL APPLIANCE) CIRCUITS.
  
 3} IF CIRCUIT #27 IS MEANT FOR THE DINNING ROOM
 RECEPTALES, IT ALSO VIOLATES 210.52(B)(1). SEPERATE THE
 LIGHTING FROM THE RECEPTACLES IN THIS AREA. SEE 408.4,
 2005 NEC FOR CLARIFICATION.
  
 4} INDICATE IF THE PROPOSED SERVICE IS OVERHEAD OR
 UNDERGROUND. 215.5.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
  
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2007-03-12 Cont ID  
Sent By swurafti Date 2007-03-12 Time 14:44 Rev Time 0.00
Received By swurafti Date 2007-03-12 Time 14:44 Sent To  
Notes
2007-03-12 14:45:08HISTORIC APPROVED BY GJUDGE

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-08-13 Cont ID  
Sent By adarroug Date 2007-08-13 Time 16:13 Rev Time 0.00
Received By adarroug Date 2007-08-13 Time 16:13 Sent To Z
Notes
2007-08-13 16:13:58TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-06-19 Cont ID  
Sent By adarroug Date 2007-06-19 Time 11:12 Rev Time 0.00
Received By adarroug Date 2007-06-19 Time 11:12 Sent To M
Notes
2007-06-19 11:13:02TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-06-07 Cont ID  
Sent By adarroug Date 2007-06-07 Time 16:12 Rev Time 0.00
Received By adarroug Date 2007-06-07 Time 16:12 Sent To Z
Notes
2007-06-07 16:13:15TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-04-02 Cont ID  
Sent By spalmer Date 2007-04-02 Time 18:06 Rev Time 0.00
Received By spalmer Date 2007-04-02 Time 18:06 Sent To E
Notes
2007-04-02 18:06:44TO ELEC SFR RACK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2007-04-17 Time   Rev Time 0.00
Received By adarroug Date 2007-03-13 Time 15:22 Sent To  
Notes
2007-03-13 15:22:31TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-08-29 Cont ID  
Sent By tgordon Date 2007-08-29 Time 09:45 Rev Time 0.25
Received By tgordon Date 2007-08-29 Time 09:45 Sent To B
Notes
2007-08-29 09:46:32APPROVED PLANS WERE REVIEWED ON 6-19-07.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-06-19 Cont ID  
Sent By tgordon Date 2007-06-19 Time 14:23 Rev Time 0.30
Received By tgordon Date 2007-06-19 Time 14:23 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-04-03 Cont ID  
Sent By tgordon Date 2007-04-03 Time 10:55 Rev Time 0.45
Received By tgordon Date 2007-04-03 Time 10:55 Sent To P
Notes
2007-04-03 11:16:16*** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE ON FORM600B-04R (OR
 600A-04R), SEE 2004 FBC 13-600.3.B (12-8-06 REVISION).
  
 2)ENERGY CALCULATIONS NEED TO BE SIGNED BY
 OWNER/AGENT ALSO, PER 2004 FBC 13-600.3.ABC.2.
  
 3) PLEASE SUBMITCOOLING LOAD CALCULATIONS, PER 2004
 FBC 13-607.1.ABC.1 .
  
 4) THE A/C EQUIPMENT SCHEDULE ON THE MECHANICAL PLANS
 PAGE 4 OF 4 NEEDS TO SHOW THE SENSIBLE BTU'S. ALSO.
  
 5) MOST OF THE SUPPLY AIR DUCTS ARE NOT SIZED, SEE THE
 YELLOW HIGH LIGHTS ON THE MECHANICAL PLANS, PLEASE
 CORRECT.
  
 6) THE RETURN AIR TRANSFER DUCTS FROM BEDROOM #1 TO
 BEDROOM #2 AND FROM BEDROOM #2 TO BEDROOM #3 NEEDS TO
 BE SIZED.
  
 7) THE 9" RETURN AIR TRANSFER DUCT FROM BEDROOM #3 TO
 THE HALLWAY MAY BE TO SMALL AS IT IS RETURNING AIR FROM
 THE THREE BEDROOMS, SEE 2004 FBC/R M1602.4.
  
 ** 2004 FBC/R M1602.4 BALANCED RETURN AIR MAY BE
 ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING THE
 RETURN TRANSFER ONE AND ONE HALF TIMES THE CROSS
 SECTIONAL AREA (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING AND THE DOOR
 HAVING AT LEAST AN UNRESTRICTED 1 INCHUNDERCUT TO
 ACHIEVE PROPER RETURN AIR BALANCE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-08-29 Cont ID  
Sent By mperson Date 2007-08-29 Time 08:48 Rev Time 0.00
Received By mperson Date 2007-08-29 Time 08:48 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-06-29 Cont ID  
Sent By mperson Date 2007-06-29 Time 11:56 Rev Time 0.33
Received By mperson Date 2007-06-29 Time 11:56 Sent To E
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-04-09 Cont ID  
Sent By mperson Date 2007-04-09 Time 14:23 Rev Time 0.55
Received By mperson Date 2007-04-09 Time 14:22 Sent To B
Notes
2007-04-09 14:51:20DENIED
 REFERENCE:
 ** FBC-2004 PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. SHEET 2 SANITARY ISOMETRIC RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN AND IS NOT CODE COMPLIANT, PER
 FBC-2004 CHAPTER 1, SECTION 106.1.1.
 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL
 BE OF SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE
 AND RELAVENT LAWS, ORDINANCES, RULES AND REGULATIONS,
 AS DETERMINED BY THE
 BUILDING OFFICIAL.
  
 2.PER FBC-2004 CHAPTER 1, SECTION 106.3.5.4
 RESIDENTIAL (ONE AND TWO-FAMILY) PLEASE SUBMIT A
 PLUMBING SANITARY ISOMETRIC RISER DIAGRAM INDICATING
 ALL WASTE, VENTS, TRAPS AND SIZES WITH CLEANOUT
 LOCATIONS.
 NOTE: NOT ALL WASTE ,TRAPS AND SIZES WITH CLEANOT
 LOCATIONS ARE INDICATED ON SHEET 2 SANITARY ISOMETRIC
 RISER DIAGRAM. PLEASE REFERENCE THE ATTACHED SANITARY
 ISOMETRIC RISER DIAGRAM TO THE PLUMBING COMMENTS THAT
 REFLECTS THE FLOOR PLAN AND IS CODE COMPLIANT.
  
 (A) 406.3 WASTE CONNECTIONS.THE TRAP AND
 FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES
 WASHER SHALL BE A MINIMUM OF 2 INCHES
 (51MM) IN DIAMETER. THE AUTOMATIC
 CLOTHES WASHER FIXTURE DRAIN SHALL
 CONNECT TO A BRANCH DRAIN OR DRAINAGE
 STACK A MINIMUM OF 3 INCHES (76MM) IN
 DIAMETER.
  
 (B) 802.4 STANDPIPES.STANDPIPES SHALL BE INDIVIDUALLY
 TRAPPED. STANDPIPES SHALL
 EXTEND A MINIMUM OF 18 INCHES (457MM)
 AND A MAXIMUM OF 42 INCHES (1066MM)
 ABOVE THE TRAP WEIR. ACCESS SHALL BE
 PROVIDED TO ALL STANDPIPES AND DRAINS
 FOR RODDING
  
 (C) 708.7 MINIMUM SIZE. CLEANOUTS SHALL
 BE THE SAME NOMINAL SIZE AS THE PIPE.
 NOTE: CLEANOUT FOR THE WASHING MACHINE SHALL BE THREE
 INCH (3").
 THEY SERVE UP TO 4 INCHES (102MM)
  
 (D) 708.9 ACCESS. ACCESS SHALL BE
 PROVIDED TO ALL CLEANOUTS.
 NOTE: CLEANOUT FOR THE WASHING MACHINE SHALL BE LOCATED
 FOUR FEET ABOVE FINNISH FLOOR (4' A.F.F.).
  
 (E) 917 AIR ADMITTANCE VALVE (A.A.V.) REQUIRED FOR THE
 KITCHEN SINK DUE TO THE FACT A KNEE WALL IS LOCATED
 WHERE A VENT THROUGH ROOF IS LOCATED ON SHEET 2.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop Z ZONING
Rev No 3 Status P Date 2007-08-22 Cont ID  
Sent By bpowell Date 2007-08-22 Time 16:54 Rev Time 0.00
Received By bpowell Date 2007-08-22 Time 16:54 Sent To I
Notes
2007-08-22 16:59:26PROVISO
 1.THE AIR CONDITIONER SHALL BE LOCATED SIX (6) FEET
 AWAY FROM THE SIDE PROPERTY LINE AS SHOWN ON THE
 SURVEY.
  
 FOR QUESTIONS OR COMMENTS CONTACT: BOBBY POWELL JR.,
 (561) 822-1435, [email protected].

Review Stop Z ZONING
Rev No 2 Status F Date 2007-06-18 Cont ID  
Sent By bpowell Date 2007-06-18 Time 17:15 Rev Time 0.00
Received By bpowell Date 2007-06-18 Time 17:15 Sent To I
Notes
2007-06-18 17:27:101.THE RESUBMITTAL OF THIS PROJECT HAS TO BE APPROVED
 BY THE HISTORIC PRESERVATION DIVISION.
  
 2.PLEASE SHOW THE DIMENSIONS OF THE AIR CONDITIONER,
 AND HOW FAR IT IS SETBACK FROM THE PROPERTY LINE.
  
 3.THE SITE PLAN AND THE SURVEY SHOULD BE CONSISTENT
 (THE AIR CONDITIONER IS IN DIFFERENT PLACES ON EACH).
  
 FOR ANY QUESTIONS OR COMMENTS PLEASE CONTACT:BOBBY
 POWELL, JR., PLANNER, [email protected], (561) 822-1435

Review Stop Z ZONING
Rev No 1 Status F Date 2007-06-18 Cont ID  
Sent By bpowell Date 2007-03-29 Time   Rev Time 0.00
Received By bpowell Date 2007-03-29 Time 16:06 Sent To  
Notes
2007-03-29 16:25:461.THE SIDE SETBACKS MEASURING FROM THE PROPERTY LINE
 TO THE HOME SHALL DEPICT THE CORRECT NUMBERS.
  
 2.THE LESSER OF 1,000 SQUARE FEET OR 75 PERCENT OF
 THE FRONT YARD AREA MUST BE LANDSCAPED, PER SEC. 94-482
 OF THE CITY'S ZONING AND LAND DEVELOPMENT REGULATIONS.
  
 * FOR SINGLE FAMILY DWELLING UNITS AT LEAST ONE SHADE,
 FLOWERING OR FRUIT TREE, SHALL BE PLANTED EACH 1,200
 SQUARE FEET OF OPEN SPACE.