Plan Review Details - Permit 07030364
Plan Review Stops For Permit 07030364
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-03-23 Cont ID  
Sent By jgomez Date 2007-03-23 Time 08:52 Rev Time 0.00
Received By jgomez Date 2007-03-23 Time 08:41 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-03-20 Cont ID  
Sent By kconrad Date 2007-03-20 Time 17:35 Rev Time 0.00
Received By kconrad Date 2007-03-20 Time 17:35 Sent To I
Notes
2007-03-20 18:36:42A PRELIMINARY ROOF INSPECTION WAS PERFORMED AT 1638
 EMBASSY DRIVE IN ORDER TO DETERMINE IF A ROOF RECOVER
 COULD BE WARRANTED. I MET WITH MIKE, A REPRESENTATIVE
 FOR CENTIMARK AND PERFORMED A ROOF INSPECTION OF THE
 EXISTING ROOF MEMBRANE AND UNDERLYING SUBSTRATE/ROOF
 APPLICATIONS. THE FOLLOWING WAS NOTED:
  
 1) THE EXISTING ROOF MEMBRANE APPEARS TO BE A POLYESTER
 FABRIC ENCAPSULATED BETWEEN LAYERS OF POLYVINYLCHLORIDE
 WITH A THICKNESS OF .040 TO .060". THERE WERE NUMEROUS
 AREAS OF THE ROOF WHERE THERE APPEARS TO BE VAST
 AMOUNTS OF WATER PONDING. IN THESE AREAS THE ROOF
 MEMBRANE APPEARED TO BE DELAMINATED AND ONLY THE SINGLE
 PLY BACKING REMAINED.
  
 2) THE SUBSTRATE AND EXISTING ROOF LAYERS WERE
 VERIFIED: A CORE SAMPLE WAS TAKEN. IT APPEARS THAT
 THERE ARE TWO LAYERS OF ROOF COVERINGS. THE SUBSTRATE
 APPEARS TO BE WOOD STRUCTURAL PANELS WITH A MODIFIED
 BITUMEN/BALLAST ROOF COVERING. A SINGLE PLY OVER
 POLYSTYRENE BOARD EXISTS OVER THE FORMER. THE
 INSULATION BOARD THAT WAS RECOVERED FROM THE ROOF CORE
 SAMPLE WAS WATER SOAKED AND WHILE WALKING ON MOST OF
 THE ROOF, THE INSULATION BOARD APEARED TO BE SPONGY AND
 WATER SOAKED THEREBY CONFIRMING THE SAME.
  
 3) WITH THE AMOUNT OF PONDING WATER THAT WAS EVIDENT ON
 THE ROOF, THERE MAY BE DAMAGE TO THE STRUCTURAL PANEL
 SUBSTRATE AT NUMEROUS LOCATIONS.
  
 IN SUMMARY, A ROOF RECOVER PERMIT MAY NOT BE ISSUED DUE
 TO THE AFOREMENTIONED CONDITIONS AND THE FLORIDA
 EXISTING BUILDING CODE SECTIONS 511.2 AND 511.3 (1) AND
 (6).
  
 FEBC 511.2- THE STRUCTURAL ROOF COMPONENTS SHALL BE
 CAPABLE OF SUPPORTING THE ROOF COVERING SYSTEM AND THE
 MATERIAL AND EQUIPMENT LOADS THAT WILL BE ENCOUNTERED
 DURING THE INSTALLATION OF THE ROOF COVERING SYSTEM.
  
 FEBC 511.3 RECOVERING VERSUS REPLACEMENT. NEW ROOF
 COVERINGS SHALL NOT BE INSTALLED WITHOUT FIRST REMOVING
 EXISTING ROOF COVERINGS WHER ANY OF THE FOLLOWING
 OCCUR:
  
 1) WHEN THE OLD ROOFING IS WATER SOAKED OR DETERIORATED
 TO THE POINT THAT IT IS NOT SUITABLE AS A BASE FOR
 ADDITIONAL ROOFING.
  
 6) WHEN EXISTING ROOF HAS TWO OR MORE APPLICATIONS OF
 ANY TYPE ROOFING MATERIAL. CONFORMANCE WITH THIS ITEM
 SHALL MAKE REPLACEMENT MANDATORY.
  
 YOU MAY REVISE THE PERMIT APPLICATION TO INDICATE A
 REROOFAND RESUBMIT THE APPLICABLE PRODUCT APPROVALS
 FOR PLAN REVIEW.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-03-12 Cont ID  
Sent By jgomez Date 2007-03-12 Time 18:10 Rev Time 1.00
Received By jgomez Date 2007-03-12 Time 18:07 Sent To  
Notes
2007-03-12 18:36:48BUILDING REVIEW CHECKLIST:
 1-RECOVER ROOFING PERMITSREQUIRES PRE-INSPECTION BY
 BUILDING INSPECTOR.APPLICATION SENT TO KEN CONRAD,
 CHIEF BUILDING INSPECTOR, FOR PRE-INSPECTION.
  
 2- NOA #05-0613.05 FILE IS CLOSED. SEE ATTACHED COPY
 FROM MIAMI DADE COUNTY WEBSITE. NEED TO PROVIDE CURRENT
 PRODUCT APPROVAL.
  
 3- ENGINEER CALCULATIONS:
 A) FASTENER SPACING OF 2.67 AT CORNER AREAS IS NOT
 ALLOWED. FASTENER SPACING CAN'T BE LESS THAN 4"O.C..
 SEE RAS 117SEC. 8.1.
  
 B) ENGINEER TO PROVIDE RAS 117 CALCULATIONSTO
 DETERMINE FASTENER SPACING AS REQUIRED BY GENERAL
 LIMITATION #7 ON LAST PAGE OF NOA SUBMITTED.
  
 B) ENGINEER TO HAVE THE CERTIFICATE OF AUTHORIZATION
 NUMBER ON ALL SHEETS AS REQUIRED BY SEC. 61G15-23.002
 OF FLORIDA ADMINISTRATIVE CODE.
  
 4- WITHDRAWAL RESISTANCE TEST:
 A) ARCHITECT NEEDS TO PROVIDE ALL HIS INFORMATION IN
 THE TITLE BLOCK AS REQUIRED BY SEC. 61G1-16.004 OF
 FLORIDA ADMINISTRATIVE CODE AND SEC. 481 FLORIDA
 STATUTE.
  
 B) ARCHITECT TO PROVIDE ORIGINAL SIGNATURE, NOT
 RUBBER STAMP AS REQUIRED BY SEC. 61G1-16.003 FLORIDA
 ADMINISTRATIVE CODE AND SEC. 481 FLORIDA STATUTE.
  
 C) TEST WAS DONE ON FEBRUARY OF 2006 OR 2007.IF
 TYPO, THEN REVISE AS REQUIRED.
  
 D) THERE ARE NOT TESTS DONE IN CORNER AREAS. NEED TO
 DO TESTSAT CORNER AREAS AS REQUIRED BY SEC. 8.1 AND
 8.2 OF TAS 105-98.
  
  
 5- ROOF MOISTURE TEST:
 A) ARCHITECT TO PROVIDE ALL HIS INFORMATION AND
 ORIGINAL SIGNATURE. SEE COMMENTS ON ITEM 4 A AND B
 ABOVE.
  
 B) ACCORDING TO THE ROOF MOISTURE TESTS HIGH
 MOISTURE LEVELS ARE FOUND IN THE BOTTOM LAYER OF BUILT
 UP ROOF MATERIAL. PERCENT OF MOISTURE EXCEEDS THE MAX.
 PERCENTAGE ALLOWED BY SEC. 1521.12 FBC 2004. SPECIFY
 HOW IS THIS ISSUED ADDRESSED TO COMPLYWITH THIS
 SECTION.
  
 C) PROVIDE ALL INFORMATION REQUESTED BY SEC. 14 OF
 TAS 126-95.
  
  
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2007-03-29 Cont ID  
Sent By rregueir Date 2007-03-29 Time 11:48 Rev Time 0.00
Received By rregueir Date 2007-03-29 Time 11:47 Sent To  
Notes
2007-03-29 11:48:26ROOF STANDS OK