Plan Review Stops For Permit 07030345 |
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2007-03-12 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2007-03-12 |
Time |
15:43 |
Rev Time |
0.00 |
Received By |
tgordon |
Date |
2007-03-12 |
Time |
09:04 |
Sent To |
|
|
Notes |
2007-03-12 09:04:53 | TO "M" BOX |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2007-03-12 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2007-03-12 |
Time |
15:27 |
Rev Time |
0.30 |
Received By |
tgordon |
Date |
2007-03-12 |
Time |
15:27 |
Sent To |
|
|
Notes |
2007-03-12 15:41:47 | *** DENIED *** | | 1) PLEASE SHOW ON PLANS, SUPPLY AIR GRILLS AS SQUARES | | OR RECTANGLES WITH AN X IN THEM, AND SHOW RETURN GRILLS | | WITH AN / IN THEM. | | | | 2) PLEASE SHOW ON PLANS THE MAIN RETURN AIR GRILL AND | | SIZE. | | | | 3) PLEASE PROVIDE RETURN AIR FOR THE FAMILY ROOM, SEE | | 2004 FBC/R M1602.4. | | | | 4) PLEASE SHOW THE CFM'S AT ALL SUPPLY AIR GRILLS. | | | | 5)ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND | | ACCOMPANYING DATA SHALL BEAR THE PRINTED NAME AND | | SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN. PER | | FBC 104.2.1 . | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. | | | | | | |
|
|
|