Plan Review Details - Permit 07030319
Plan Review Stops For Permit 07030319
Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2007-10-09 Cont ID  
Sent By mawillia Date 2007-10-09 Time 10:15 Rev Time 0.00
Received By mawillia Date 2007-10-09 Time 09:46 Sent To  
Notes
2007-10-09 10:07:09*****APPROVED*****
  
  
 REVISED PLAN SHEETS WERE STAMPED, INITIALED, AND DATED;
 READY FOR PERMIT ISSUANCE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-04-26 Cont ID  
Sent By mawillia Date 2007-04-26 Time 16:20 Rev Time 0.00
Received By mawillia Date 2007-04-26 Time 15:50 Sent To  
Notes
2007-04-26 15:56:17*****APPROVED*****
  
  
 ALL PRIOR COMMENTS HAVE BEEN ADDRESSED. PLAN SHEETS
 WERE STAMPED, INITIALED, AND DATED;READY FOR PERMIT
 ISSUANCE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-03-27 Cont ID  
Sent By mawillia Date 2007-03-27 Time 12:43 Rev Time 0.00
Received By mawillia Date 2007-03-27 Time 12:10 Sent To  
Notes
2007-03-27 12:16:50*****UNSAT*****
  
  
 PLEASE BE ADVISED,AS PER THE FLORIDA BOARD OF
 ENGINEERS, CONTRACTORS CANNOT MAKE CHANGES TO THE
 ENGINEER'S SIGNED AND SEALED PLANS.
  
  
  
 1.THE ADDRESS OF WHERE THE SCOPE OF WORK WILL BE DONE
 SHALL BE IN THE TITLE BLOCK OF EACH SUBMITTED PLAN
 SHEET.
  
 2.AS PER WPB FIRE PREVENTION BUREAU, DUCT SMOKE
 DETECTORS SHALL INITIATE A GENERAL FIRE ALARM.
 THEREFORE IN REFERENCE TO FIRE ALARM NOTE #3, DELETE
 "SUPERVISORY SIGNAL" AND INSERT "GENERAL FIRE ALARM".
  
 NEW COMMENT:
  
 A.RECTIFY FIRE ALARM NOTES TO INDICATE THAT NFPA 72 -
 2002 EDITION IS REFERENCED INSTEAD OF THE 1999
 EDITION.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-03-12 Cont ID  
Sent By mawillia Date 2007-03-12 Time 17:18 Rev Time 0.00
Received By mawillia Date 2007-03-12 Time 17:08 Sent To  
Notes
2007-03-12 17:18:32*****DENIED*****
  
  
 1.THE ADDRESS OF WHERE THE SCOPE OF WORK WILL BE DONE
 SHALL BE IN THE TITLE BLOCK OF EACH SUBMITTED PLAN
 SHEET.
  
 2.AS PER WPB FIRE PREVENTION BUREAU, DUCT SMOKE
 DETECTORS SHALL INITIATE A GENERAL FIRE ALARM.
 THEREFORE IN REFERENCE TO FIRE ALARM NOTE #3, DELETE
 "SUPERVISORY SIGNAL" AND INSERT "GENERAL FIRE ALARM".
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-09-19 Cont ID  
Sent By adarroug Date 2007-09-19 Time 16:44 Rev Time 0.00
Received By adarroug Date 2007-09-19 Time 16:44 Sent To FIRE
Notes
2007-09-19 16:44:57TO "F" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-04-23 Cont ID  
Sent By adarroug Date 2007-04-23 Time 14:34 Rev Time 0.00
Received By adarroug Date 2007-04-23 Time 14:34 Sent To FIRE
Notes
2007-04-23 14:34:28TO "F" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-03-15 Cont ID  
Sent By adarroug Date 2007-03-15 Time 11:50 Rev Time 0.00
Received By adarroug Date 2007-03-15 Time 11:50 Sent To FIRE
Notes
2007-03-15 11:51:03TO "F" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-03-12 Cont ID  
Sent By mawillia Date 2007-03-12 Time 17:08 Rev Time 0.00
Received By mawillia Date 2007-03-10 Time 12:45 Sent To  
Notes
2007-03-10 12:45:49TO "F" BOX


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved