Plan Review Details - Permit 07030274
Plan Review Stops For Permit 07030274
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-03-23 Cont ID  
Sent By shill Date 2007-03-23 Time 17:18 Rev Time 0.00
Received By shill Date 2007-03-23 Time 17:18 Sent To  
Notes
2007-03-23 17:20:03****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 1.)PROVIDE ANCHORING INFORMATION TO
 COMPLY WITH FBC1609.1.3; STRUCTURAL
 MEMBERS AND SYSTEMS, AND COMPONENTS AND CLADDING IN A
 BUILDING OR STRUCTURE SHALL BE ANCHORED TO RESIST
 WIND-INDUCED OVERTURNING, UPLIFT AND SLIDING AND TO
 PROVIDE CONTINUOUS LOAD PATHS FOR THESE FORCES TO THE
 FOUNDATION.WHERE A PORTION OF THE RESISTANCE TO THESE
 FORCES IS PROVIDED BY DEAD LOAD, THE MINIMUM DEAD LOAD
 LIKELY TO BE IN PLACE DURING A DESIGN WIND EVENT SHALL
 BE USED.
  
 2.)THE VALUE IS TOO LOW.PROVIDE A REASONABLE VALUE
 OR AN ESTIMATED VALUE WILL BE DONE FOR YOU USING
 MARSHALL & SWIFT.
  
 3.)A NOTICE OF COMMENCEMENT MUST BE FILED WITH THE
 CLERK OF COURTS BEFORE A PERMIT CAN BE ISSUED.
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-03-20 Cont ID  
Sent By btrobaug Date 2007-03-14 Time 10:58 Rev Time 0.50
Received By btrobaug Date 2007-03-14 Time 10:50 Sent To Z
Notes
2007-03-14 10:58:30 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE VALUE ON THE APPLICATION MUST
 INCLUDE THE TOTAL COST OF LABOR AND
 MATERIAL FOR THE GENERATOR, EQUIPMENT
 (TRANSFER SWITCHES, PANELS ETC.)
 AND PAD PER 108.3 FBC AS AMENDED.
 INCREASE THE VALUE AT THE COUNTER WHEN
 RESUBMITTING, AND GET A RECEIPT FROM THE
 PERMIT CLERK.
  
 2} PROVIDE MANUFACTURERS SPECIFICATIONS
 INDICATING RECOMMENDED SETBACKS AND
 ELECTRICAL SPEC'S FOR THE GENERATOR AND
 TRANSFER SWITCH.
  
 3} PROVIDE A PANEL SCHEDULE FOR THE
 GENERATOR PANEL. 106.3.5.4 FBC AS
 AMENDED.
  
 4} PLEASE LOCATE ALL SERVICE AND GENERATOR EQUIPMENT ON
 A SITE PLAN, NOT THE SURVEY, METER ENCLOSURE,
 DISCONNECTS, ATS AND PANELS, SO THAT COMPLIANCE WITH
 ARTICLES 225 AND 230 CAN BE REVIEWED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
  

Review Stop FUEL DIESEL GENERATOR
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status   Date   Cont ID  
Sent By mperson Date   Time 15:02 Rev Time 0.00
Received By mperson Date 2007-10-16 Time 15:02 Sent To  
Notes
2007-10-16 15:19:35 

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-03-20 Cont ID  
Sent By mperson Date 2007-03-20 Time 10:16 Rev Time 0.55
Received By mperson Date 2007-03-20 Time 10:16 Sent To B
Notes
2007-03-20 10:46:18DENIED
 REFERENCE: FBC-2004 FUEL GAS; FBC-2004 CHAPTER 1, THE
 CITY OF WEST PALM BEACH AMENDMENTS; THE CITY OF WEST
 PALM BEACH GAS PERMIT APPLICATION REQUIREMENTS;
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 CONTRACTOR INFORMATION
 NOTE: GAS PERMIT REQUIRED. GAS CONTRAC-
 TOR TO SUBMIT PLANS WITH PERMIT APPLICA-
 TION. ALL GAS INSPECTIONS TO BE COMPLETE
 BEFORE FINAL GEN/RES INSPECTION.
  
 ******IMPORTANT INFORMATION******
 AS OF 8/25/06 GENERATOR (GEN/RES AND
 GEN/COM) PERMIT APPLICATIONS SHALL NOT
 BE ACCEPTED UNLESS THE ELECTRICAL INFOR-
 MATION AND GAS (OR DIESEL) INFORMATION
 IS ALL SUBMITTED AT THE SAME TIME. THE
 GENERATOR, ELECTRICAL AND GAS/DIESEL IN-
 FORMATION WILL BE ROUTED TOGETHER. THIS
 WILL ENSURE THAT ALL OF THE INFORMATION (PARTICULARLY
 THE MANUFACTURER'S SPECI-
 FICATIONS AND INSTALLATION INSTRUCTIONS)
 ARE AVAILABLE TO ALL PLAN REVIEWERS.
  
 1. A GAS PERMIT CAN NOT BE ISSUED UNTIL
 A GEN/RES PERMIT APPLICATION HAS BEEN
 APPROVED BY ZONING FOR THE GENERATOR LOCATION.
  
 2. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 NOTE: THIS INCLUDES THE EXISTING GAS SYSTEM AS WELL AS
 THE PROPOSED GENERATOR. PLEASE CLEARLY INDICATE THE
 EXISTING GAS SYSTEM AS WELL AS THE PROPOSED.
  
 3. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 NOTE: THIS INCLUDES THE EXISTING AS WELL AS THE
 PROPOSED.
  
 4. PLEASE INDICATE THE TYPE OF GAS, (LP OR NATURAL) ON
 THE DRAWING.
  
 5. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 6. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 7. PLEASE INDICATE THE DELIVERY PRESSURE (PSI) PER
 FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 8. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 A} GENERATOR.
 B} MP REGULATOR IF DELIVERY PRESSURE IS 2 PSI.
  
 9. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 10. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 11. FBC-2004 CHAPTER 1,SECTION 106.3.4.2:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME, AND ALSO DATE DRAWING. PLEASE DO
 THIS PRIOR TO RESUBMITTING.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-03-23 Cont ID  
Sent By shill Date 2007-03-23 Time 17:20 Rev Time 0.00
Received By shill Date 2007-03-19 Time 08:29 Sent To  
Notes
2007-03-19 08:30:31TO "GEN-RES" "MECH"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-03-19 Cont ID  
Sent By tgordon Date 2007-03-19 Time 10:18 Rev Time 0.15
Received By tgordon Date 2007-03-19 Time 10:18 Sent To G
Notes
2007-03-19 10:21:53*** DENIED ***
 1) SEE ZONING REVIEW NOTES, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop Z ZONING
Rev No 1 Status F Date 2007-03-15 Cont ID  
Sent By btrobaug Date 2007-03-20 Time 11:04 Rev Time 0.00
Received By adavila Date 2007-03-15 Time 16:04 Sent To I
Notes
2007-03-15 17:06:16PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 1.PROVIDE TWO (2) SIGNED AND SEALED SURVEYS.THE
 SURVEY SHALL BE LESS THAN A YEAR OLD.
  
 2.PROVIDE SETBACK DIMENSIONS FROM PROPERTY LINE TO
 GENERATOR.
  
 COMMENTS/QUESTIONS CONTACT ANDREINA DAVILA Q., OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.
  