Plan Review Details - Permit 07030203
Plan Review Stops For Permit 07030203
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2007-03-23 Cont ID  
Sent By shill Date 2007-03-23 Time 16:09 Rev Time 0.00
Received By shill Date 2007-03-23 Time 16:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-05-03 Cont ID  
Sent By btrobaug Date 2007-05-03 Time 13:35 Rev Time 0.33
Received By btrobaug Date 2007-05-03 Time 13:18 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-03-14 Cont ID  
Sent By btrobaug Date 2007-03-14 Time 10:41 Rev Time 0.50
Received By btrobaug Date 2007-03-14 Time 10:32 Sent To M
Notes
2007-03-14 10:40:59 
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 PLEASE SUBMIT A SITE PLAN INDICATING THE PHYSICAL
 LOCATION OF THE EQUIPMENT WITH REGARD TO THE SERVICE
 AND GENERATOR EQUIPMENT. NOTE: DISCONNECT REQUIRED TO
 BE SERVICE RATED PER 225.36. THIS INCLUDES THE TRANSFER
 SWITCH IF LOCATED AS A MAIN SERVICE DISCONNECTING
 MEANS. ALSO 110.9 FOR AIC RATING.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2007-05-04 Cont ID  
Sent By mperson Date 2007-05-04 Time 09:28 Rev Time 0.45
Received By mperson Date 2007-05-04 Time 09:28 Sent To M
Notes
2007-05-04 09:36:46****************PROVISO****************
 A} PER FBC-2004 FUEL GAS, SECTION 404.13.3AN
 INSULATED COPPER TRACER WIRE SHALL BE INSTALLED
 ADJACENT TO UNDERGROUND NONMETALLIC GAS PIPING. THE
 TRACER WIRE SIZE SHALL NOT BE LESS THAN 18 AWG AND THE
 INSULATION TYPE SHALL BE SUITABLE FOR DIRECT BURIAL.
  
 B} PER FBC-2004 FUEL GAS SECTION 408.4 A SEDIMENT
 TRAP SHALL BE INSTALLED DOWNSTREAM OF THE EQUIPMENT
 SHUTOFF VALVE AS CLOSE TO THE INLET OF THE EQUIPMENT AS
 PRACTICAL.
  
 C} PER FBC-2004 FUEL GAS, SECTION 409.1 SHUTOFF VALVE
 FOR GENERATOR IS PART OF THE PIPING SYSTEM AND SHALL BE
 FULL SIZE. REDUCE PIPING SIZE AT GENERATOR DUE TO BTU
 LOAD.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-03-16 Cont ID  
Sent By mperson Date 2007-03-16 Time 09:15 Rev Time 0.50
Received By mperson Date 2007-03-16 Time 09:15 Sent To B
Notes
2007-03-16 10:22:57DENIED
 REFERENCE: FBC-2004 FUEL GAS; FBC-2004 CHAPTER 1, THE
 CITY OF WEST PALM BEACH AMENDMENTS;
  
 THE FOLLOWING CORRECTIONS ARE REQUIRED FOR GAS PLAN
 REVIEW TO MEET CODE COMPLIANCE:
  
 1. A GAS PERMIT CAN NOT BE ISSUED UNTIL THE ZONING
 ISSUES HAVE BEEN RESOLVED. ON THE RESUBMITTED SURVEY
 PLEASE CLEARLY MARK THE PROPOSED LOCATION OF THE
 GENERATOR. INDICATION OF ALL DIMENSIONS FROM PROPERTY
 LINES AND DISTANCES FROM ADJACENT DWELLING STRUCTURES.
 INDICATION THAT THE GENERATOR EXHAUST IS NOT INSTALLED
 ANY CLOSER THAN TEN FEET FROM ANY OPENING INTO THE
 DWELLING STRUCTURE. THIS INCLUDES DOORS, WINDOWS AND
 ATTIC VENTILATION OPENINGS.
  
 2. PLEASE SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY
 SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. CLEARLY INDICATE ON THE RESUBMITTAL THE
 EXISTING GAS PIPE AND NEW GAS PIPE.
  
 3. PLEASE SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED ON THE RESUBMITTED
 ISOMETRIC.
 NOTE: THE PIPING TO THE GENERATOR NEEDS TO BE INCREASED
 TO 1-1/4" PE DUE TO THE BTU LOAD OF 560,000 TO THE
 GENERATOR. PLEASE REFERENCE THE SUBMITTED
 MANUFACTURER'S SPECIFICATIONS INDICATING THE BTU LOAD
 TO THE GENERATOR.
  
 4. PLEASE INDICATE THE TYPE OF GAS, (LP OR NATURAL) ON
 THE RESUBMITTED ISOMETRIC.
  
 5. PLEASE INDICATE THE BTU LOAD OF EACH APPLIANCE AND
 THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33) ON THE RESUBMITTED ISOMETRIC.
 NOTE: PLEASE INDICATE THE BTU LOAD TO THE GENERATOR ON
 THE RESUBMITTED ISOMETRIC.
  
 6. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 7. PLEASE INDICATE THE DELIVERY PRESSURE (PSI) PER
 FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI ON THE RESUBMITTED
 ISOMETRIC.
 NOTE: ON THE SUBMITTED DRAWING THE GAS PRESSURE WAS
 INDICATED AS 0.5 PSI. PLEASE NOTE THE RED LINE
 CORRECTIONS TO THE PE PIPING TO THE GENERATOR. PLEASE
 REFERENCE THE ATTACHED SIZING TABLES TO THE GAS
 COMMENTS INDICATING THE NEED TO INCREASE THE GAS PIPE
 TO THE GENERATOR.
  
 8. FBC-2004 CHAPTER 1,SECTION 106.3.4.2:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME, AND ALSO DATE DRAWING. PLEASE DO
 THIS PRIOR TO RESUBMITTING.
  
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-05-01 Cont ID  
Sent By adarroug Date 2007-05-01 Time 10:20 Rev Time 0.00
Received By adarroug Date 2007-05-01 Time 10:20 Sent To E
Notes
2007-05-01 10:20:34TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-04-26 Cont ID  
Sent By adarroug Date 2007-04-26 Time 15:40 Rev Time 0.00
Received By adarroug Date 2007-04-26 Time 15:40 Sent To Z
Notes
2007-04-26 15:40:21TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-03-13 Cont ID  
Sent By adarroug Date 2007-03-13 Time 10:51 Rev Time 0.00
Received By adarroug Date 2007-03-13 Time 10:51 Sent To E
Notes
2007-03-13 10:52:42TO "GEN-RES" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-05-04 Cont ID  
Sent By tgordon Date 2007-03-23 Time 11:50 Rev Time 0.00
Received By tgordon Date 2007-03-07 Time 10:06 Sent To  
Notes
2007-03-07 10:06:58TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-05-04 Cont ID  
Sent By tgordon Date 2007-05-04 Time 12:11 Rev Time 0.25
Received By tgordon Date 2007-05-04 Time 12:11 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-03-15 Cont ID  
Sent By tgordon Date 2007-03-15 Time 10:44 Rev Time 0.20
Received By tgordon Date 2007-03-15 Time 10:44 Sent To G
Notes
2007-03-15 10:46:19*** DENIED ***
 1) SEE NOTES FROM OTHER REVIEWERS, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop Z ZONING
Rev No 2 Status P Date 2007-04-30 Cont ID  
Sent By kdfreema Date 2007-04-30 Time 11:02 Rev Time 0.00
Received By kdfreema Date 2007-04-30 Time 11:02 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2007-03-09 Cont ID  
Sent By kdfreema Date 2007-03-09 Time 10:51 Rev Time 0.00
Received By kdfreema Date 2007-03-09 Time 10:51 Sent To I
Notes
2007-03-09 10:54:37SURVEY SHALL BE SIGNED AND SEALED BY A REGISTERED
 SURVEYOR, SIGNATURES MUST BE ORGINAL. SURVEY SHALL BE
 LESS THAN ONE YEAR OLD.
  
 PLEASE CONTACT KELLY FREEMAN, PLANNER, AT 561-822-1435
 WITH ANY QUESTIONS.