2007-03-20 19:54:44 | |
| PLANS EXAMINER: KEN CONRAD |
| PROJECT: 529 SOUTH FLAGLER |
| SCOPE: INTERIOR ALTERATIONS/REPAIR |
| |
| 1) REQUIRE SEPARATE ELECTRICAL/PLUMBING PERMITS WITH |
| PLANS. |
| |
| 2) THE PROJECT VALUATION APPEARS TO BE LOW AND SHOULD |
| BE VERIFIED WITH THE CONTRACT VALUE. |
| |
| 3) THE PROPOSED WORK MUST CONFORM TO THE FOLLOWING |
| APPLICABLE FLORIDA EXISTING BUILDING CODE SECTIONS: |
| |
| |
| |
| SECTION 303 |
| ALTERATION LEVEL 1 |
| 303.1SCOPE. |
| LEVEL 1 ALTERATIONS INCLUDE THE REMOVAL AND REPLACEMENT |
| OR THE COVERING OF EXISTING MATERIALS, ELEMENTS, |
| EQUIPMENT, OR FIXTURES USING NEW MATERIALS, ELEMENTS, |
| EQUIPMENT, OR FIXTURES THAT SERVE THE SAME PURPOSE. |
| LEVEL 1 ALTERATIONS SHALL NOT INCLUDE ANY REMOVAL, |
| REPLACEMENT OR COVERING OF EXISTING MATERIALS, |
| ELEMENTS, EQUIPMENT OR FIXTURES UNDERTAKEN FOR PURPOSE |
| OF REPAIR AS DEFINED IN CHAPTER 2 AND DESCRIBED IN |
| SECTION 302. |
| 303.2APPLICATION. |
| LEVEL 1 ALTERATIONS SHALL COMPLY WITH THE PROVISIONS OF |
| CHAPTER 5. |
| |
| CHAPTER 5 |
| ALTERATIONS LEVEL 1 |
| SECTION 501 |
| GENERAL |
| 501.1SCOPE. |
| LEVEL 1 ALTERATIONS AS DESCRIBED IN SECTION 303 SHALL |
| COMPLY WITH THE REQUIREMENTS OF THIS CHAPTER. LEVEL 1 |
| ALTERATIONS TO HISTORIC BUILDINGS SHALL COMPLY WITH |
| THIS CHAPTER, EXCEPT AS MODIFIED IN CHAPTER 10. 501.2 |
| CONFORMANCE. |
| AN EXISTING BUILDING OR PORTION THEREOF SHALL NOT BE |
| ALTERED SUCH THAT THE BUILDING BECOMES LESS SAFE OR |
| ENERGY EFFICIENT THAN ITS EXISTING CONDITION. IF IN THE |
| ALTERATION THE CURRENT LEVEL OF SAFETY OR SANITATION IS |
| TO BE REDUCED, THE PORTION ALTERED SHALL CONFORM TO THE |
| REQUIREMENTS OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| SECTION 504 |
| FIRE PROTECTION |
| 504.1 |
| LEVEL 1 ALTERATIONS SHALL BE DONE IN A MANNER THAT |
| MAINTAINS THE LEVEL OF FIRE PROTECTION PROVIDED. |
| |
| SECTION 506 |
| ACCESSIBILITY |
| 506.1 |
| ACCESSIBILITY SHALL BE IN ACCORDANCE WITH CHAPTER 11 OF |
| THE FLORIDA BUILDING CODE, BUILDING. |