Plan Review Details - Permit 07030188
Plan Review Stops For Permit 07030188
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-04-14 Cont ID  
Sent By mjacobs Date 2007-04-14 Time 07:01 Rev Time 0.00
Received By mjacobs Date 2007-04-14 Time 06:58 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-03-15 Cont ID  
Sent By mjacobs Date 2007-03-15 Time 06:20 Rev Time 0.00
Received By mjacobs Date 2007-03-14 Time 17:37 Sent To PC
Notes
2007-03-14 18:59:44BUILDING PLAN REVIEW
 PERMIT:
 ADD:
 CONT:
 TEL: (561)###-####
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)FBC 106.1.1 CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS. SO PROVIDE AN EXISTING FLOOR PLAN AND A
 PROPOSED FLOOR PLAN. THE PROPOSED FLOOR PLAN SHALL SHOW
 ONLY THE NEW WALLS AND AREA OF THE RECONFIGURED SPACE.
  
 3)FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE
 RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE:
 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT
 THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 4)THE SCOPE OF WORK APPLIED FOR IS IN SPACE 110A
 HOWEVER, THE PLANS SHOWS WORK IN 110A AND 110B. THE
 PLANS SHALL REFLECT THE DESCRIPTION ON THE
 APPLICATION.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-04-13 Cont ID  
Sent By dpalmer Date 2007-04-13 Time 15:55 Rev Time 0.00
Received By dpalmer Date 2007-04-13 Time 15:48 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-03-08 Cont ID  
Sent By dpalmer Date 2007-03-08 Time 11:44 Rev Time 0.00
Received By dpalmer Date 2007-03-08 Time 10:54 Sent To  
Notes
2007-03-08 11:45:12** UNSAT **
  
  
 1) NOTE: PLEASE SEE SCOPE OF WORK AS APPLIED STATES
 WORK IN SPACE 110A , YET PLANS INDICATE WORK IN BOTH
 110A AND 110B
  
 2) NOTE: PLEASE SEE PLANS SHALL INDICATE THE MINIMUM
 CODES UNDER THE DESIGN.
 2004 FBC W/ 2006 REVISIONS.
 2005 NFPA-70
  
 3) NOTE: PLEASE SEE NEW LIGHTING CONTROL DEVICES BEING
 INSTALLED AS NEW SHALL COMPLY W/ 13-415.1.ABC.1.1 FOR
 AUTOMATE SHUT OFF. IF NOT PART OF A LIGHTING CONTROL
 SYSTEM, THEN THIS MUST BE 30MINS MAXIMUM FOR OC TYPE
 DEVICES.
  
 4) NOTE: PLEASE CLARIFY NEW LIGHTING FIXTURES BEING
 ADDED AND WHETHER OR NOT THEY COMPLY WITH CHAPTER 13.
 MUST STATE TYPE.
 2004 FBC CHAPTER 13.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-04-13 Cont ID  
Sent By mwennerg Date 2007-04-13 Time 14:47 Rev Time 0.00
Received By mwennerg Date 2007-04-13 Time 14:47 Sent To  
Notes
2007-04-13 14:58:58***APPROVED***
  
 1) FIRE EXTINGUISHER IS SHOWN IN SUITE #110 B. AN
 EXTINGUISHER SHALL ALSO BE PROVIDED IN SUITE #110 A.
  
 2) AS INDICATED ON DRAWINGS, SEPARATE SHOP DRAWINGS AND
 PERMITS REQUIRED FOR FIRE SPRINKLER AND FIRE ALARM
 REMODEL.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-03-15 Cont ID  
Sent By mawillia Date 2007-03-15 Time 23:28 Rev Time 0.00
Received By mawillia Date 2007-03-15 Time 23:11 Sent To  
Notes
2007-03-15 23:27:20*****DENIED*****
  
  
 1.THE COMPLETE ADDRESS, INCLUDING THE APPROPIATE
 SUITE NUMBER OR CHARACTER, SHALL BE IN THE TITLE BLOCK
 OF EACH SUBMITTED PLAN SHEET.
  
 2.ON THE COVER SHEET, GENERAL NOTE #15 REFERS TO NFPA
 75.PLEASE EXPLAIN WHAT NFPA 75 IS AND HOW IT RELATES
 TO FIRE SPRINKLER SYSTEMS.
  
 3.DOES THIS BUILDING HAVE A FIRE ALARM SYSTEM?IF
 SO, PLEASE EXPLAIN HOW THE FIRE ALARM SYSTEM WILL
 DIFFERENTIATE THE ACTIVATION OF FIRE ALARM DEVICE IN
 SUITE 110-A FROM 110-B?
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-04-10 Cont ID  
Sent By adarroug Date 2007-04-10 Time 16:15 Rev Time 0.00
Received By adarroug Date 2007-04-10 Time 16:14 Sent To  
Notes
2007-04-10 16:15:15TO "BOB"#12

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-03-15 Cont ID  
Sent By mawillia Date 2007-03-15 Time 23:25 Rev Time 0.00
Received By mawillia Date 2007-03-07 Time 11:21 Sent To  
Notes
2007-03-07 11:28:46TO "BOB"#7

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-04-11 Cont ID  
Sent By tgordon Date 2007-04-11 Time 11:30 Rev Time 0.30
Received By tgordon Date 2007-04-11 Time 11:30 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-03-13 Cont ID  
Sent By tgordon Date 2007-03-13 Time 13:30 Rev Time 0.25
Received By tgordon Date 2007-03-13 Time 13:30 Sent To  
Notes
2007-03-13 13:35:01*** DENIED ***
 1) JOB ADDRESS MUST APPEAR IN TITLE BLOCK, SEE 2004 FBC
 106.1.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
 .

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-04-16 Cont ID  
Sent By jleech Date 2007-04-16 Time 09:05 Rev Time 0.00
Received By jleech Date 2007-04-16 Time 09:05 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-03-10 Cont ID  
Sent By jleech Date 2007-03-10 Time 12:39 Rev Time 0.00
Received By jleech Date 2007-03-10 Time 12:39 Sent To  
Notes
2007-03-10 12:53:41DENIED;
 1. WATER HAMMER ARRESTOR SHOULD BE NEXT TO SUPPLY LINE
 AT SINK NOTIN CEILING PLUMBING CODE SECTION 604.9
 MANUFACTURES SPECIFICATIONS, AS CLOSE TO SOURCE AS
 POSSIBLE.
 2. PAGE A-1 ELEVATIONS FOR BREAK SINK; NO DOORS
 PERMITED IN THE CLEAR FLOOR SPACE OF THE FRONTAL
 APPROACH. PER NEIL MELICK BUILDING OFFICIAL.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695