Plan Review Details - Permit 07030127
Plan Review Stops For Permit 07030127
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-08-15 Cont ID  
Sent By jwitmer Date 2007-08-15 Time 16:46 Rev Time 0.77
Received By jwitmer Date 2007-08-15 Time 16:46 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-07-07 Cont ID  
Sent By jwitmer Date 2007-07-07 Time 11:36 Rev Time 1.33
Received By jwitmer Date 2007-07-07 Time 11:36 Sent To PC
Notes
2007-07-07 11:37:16 
  
  
  
 BUILDING PLAN REVIEW
 PERMIT: 07030127
 ADD: 1400 CENTREPARK BLVD
 CONT: PASS INTERNATIONAL, INC
 TEL: (561)954-9000
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2 ) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLY
 COMMENCED WITHIN 90 DAYS AFTER THE RECORDING THEREOF,
 SUCH NOTICE IS
 NULL & VOID. NOTE: 713.13(6)THE POSTING OF THE NOTICE
 OF COMMENCEMENT
 AT THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) NEW COMMENT, THE NEW SHEETS ADDED TO THE PLANS WERE
 NOT SIGNED AND SEALED.
 PLANS, SPECIFICATIONS, REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND
 BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-04-02 Cont ID  
Sent By jwitmer Date 2007-04-02 Time 08:54 Rev Time 1.33
Received By jwitmer Date 2007-04-02 Time 08:54 Sent To  
Notes
2007-04-02 09:17:23BUILDING PLAN REVIEW
 PERMIT: 07030127
 ADD: 1400 CENTREPARK BLVD
 CONT: PASS INTERNATIONAL, INC
 TEL: (561)954-9000
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2 ) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLY
 COMMENCED WITHIN 90 DAYS AFTER THE RECORDING THEREOF,
 SUCH NOTICE IS
 NULL & VOID. NOTE: 713.13(6)THE POSTING OF THE NOTICE
 OF COMMENCEMENT
 AT THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) COVERSHEET PROJECT DATA: THE PLANS INDICATE THIS IS
 A TYPE IABUILDING.THIS BUILDING BY THE MINIMUM
 STANDARDS OF THE 2006 FBC IS CONSIDERED A TYPE IB
 BUILDING .
 THE OTHER ISSUE WITH THE BUILDING RATING OF
 "UNPROTECTED" SEE TABLE 601 FOR A TYPE IB BUILDING
 COLUMNS AND FLOORS ARE A MINIMUM OF 2 HR FIRE
 RATINGALSO SEE FOOTNOTE "B".
  
 4)PLANS SUBMITTED AFTER DEC. 8TH, 2006 WILL BE
 REVIEWED UNDER THE 2006 FBC NOT THE 2004 FBC.
  
 5)SHEET A-2 DETAIL "A" BREAK ROOM SINK: INDICATES
 DOORS/ FLOOR WITHIN THE BASE CABINET:
 DOORS AND SHELVING AND FLOOR OF THE SINK BASE CABINET
 TO BE REMOVED FOR FRONTAL APPROACH.
 SINKS:
 11-4.24.2 SINKS, HEIGHT. SINKS SHALL
 BE MOUNTED WITH THE COUNTER NO HIGHER
 THAN 34" ABOVE THE FINISH FLOOR.
 11-4.24.3 KNEE CLEARANCE THAT IS AT
 LEAST 27" HIGH 30" WIDE, AND 19" DEEP
 SHALL BE PROVIDED UNDERNEATH SINKS.
 11-4.24.5 CLEAR FLOOR SPACE.
 A CLEAR FLOOR SPACE AT LEAST 30 INCHES BY 48 INCHES
 (760 MM BY 1219 MM) COMPLYING WITH SECTION 11-4.2.4
 SHALL BE PROVIDED IN FRONT OF A SINK TO ALLOW FORWARD
 APPROACH. THE CLEAR FLOOR SPACE SHALL BE ON AN
 ACCESSIBLE ROUTE AND SHALL EXTEND A MAXIMUM OF 19
 INCHES (485 MM) UNDERNEATH THE SINK.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2007-08-29 Cont ID  
Sent By dpalmer Date 2007-08-29 Time 10:14 Rev Time 0.00
Received By dpalmer Date 2007-08-29 Time 10:14 Sent To PC
Notes
2007-08-29 10:17:19** NEW PLANS AND CALCULATIONS SENT VIA FED EX.
 NEW SHEET E-2 WAS INSERTED INOT THE TWO SETS BY THIS
 REVIEWER.
 STAMPED AND ISSUED FOR PERMIT.

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2007-08-28 Cont ID  
Sent By dpalmer Date 2007-08-28 Time 15:14 Rev Time 0.00
Received By dpalmer Date 2007-08-28 Time 15:14 Sent To PC
Notes
2007-08-28 15:25:59*** DENIED 5TH TIME**
  
 1) NOTE: REVISED SHEET E-2 AND ENERGY CALCULATIONS WERE
 SENT VIA FED EX TO THIS OFFICE. THIS REVIEWER IN ORDER
 TO PROCESS PERMITTING REMOVED OLD SHEETS AND INSERTED
 NEW SHEETS INTO THE SETS OF PLANS.
 THE SHEET E-2 WAS STILL MISSING ONE EM LT HOWEVER THIS
 IS BEING REDLINED ON PLANS AND NO CHANGES ARE NEEDED.
 ** PLEASE SEE HOWEVER ALL THREE COPIES OF THE ENERGY
 CALCULATIONS WERE NOT SIGNED, DATED AND SEALED AS
 REQUIRED UNDER FAC 61G15-23.002 AND FS471.025. PLEASE
 KNOW IN-FACT THESE ACTUALLY CONTAINED A RAISED SEAL
 OVER *PHOTO-COPIED* SIGNATURE AND DATE.
 THESE SUBMITTED WERE NOT ORIGINAL. THIS REVIEWER HAS
 CALLED OCI AND SPOKE TO MR. RICHARD CREAVELLE WHO IS
 THE ELECTRICAL ENGINEER. HE IS GOING TO GET WITH THE
 MECHANICAL ENGINEER AND FED-EX ONCE AGAIN NEW ENERGY
 CALCULATIONS TO THIS OFFICE FOR AM DELIVERY ON 8/29.
 THIS OFFICE CAN ONLY REQUEST FOR ITEMS TO BE DONE PER
 CODE AND REGULATED STATUTES AND ADMINISTRATIVE CODES.
 UNDER FLORIDA STATUTES, THIS OFFICE AND SPECIFICALLY
 THIS REVIEWER IS BOUND BY THE LAWS AND RULES OF THE
 STATE NOT TO ISSUE PERMIT UNTIL FOUND COMPLIANT WITH
 THE ADOPTED CODES AND ALL OTHER RULES AND ORDINANCES
 ADOPTED BY THE STATE.
 PERMIT IS READY TO ISSUE ONCE THESE ARE IN THIS OFFICE
 AND FOUND TO BE CORRECT.
 PLANS WILL BE OUT-FRONT ONCE AGAIN ON HOLD WAITING FOR
 NEW CALCULATIONS.
  
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2007-08-24 Cont ID  
Sent By dpalmer Date 2007-08-24 Time 17:24 Rev Time 0.00
Received By dpalmer Date 2007-08-24 Time 17:21 Sent To PC
Notes
2007-08-27 10:48:35*** NOTES ADDED
  
 SPOKE TO ENGINEER 10:40AM, NEW ENERGY CALCULATIONS AND
 SHEET E-2 IS BEING FED-EX .
2007-08-24 17:29:02*** PLANS ARE IN A FAILED STATUS AT THIS TIME.
 CALLED ENGINEER'S OFFICE AT 4:55PM 8/24/07 FOR ITEMS ON
 PLANS AND ENERGY CALCULATIONS TO BE GONE OVER. THERE
 ARE AREAS FOR CONTROL OF DECORATIVE/ACCENT LIGHTING AND
 OTHER SWITCHES SHOWN AS *EMERGENCY SWITCHES* WHICH ARE
 UNCLEAR TO THIS REVIEWER.
 LEFT MESSAGE FOR THE ENGINEER TO CALL BACK.
 PLANS WILL BE PLACED UPFRONT UNDER "P" FOR THE GC ON
 HOLD.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 561-805-6717

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-08-01 Cont ID  
Sent By dpalmer Date 2007-08-01 Time 15:06 Rev Time 0.00
Received By dpalmer Date 2007-08-01 Time 12:43 Sent To  
Notes
2007-08-01 15:06:18** UNSAT 3RD REVIEW **
  
  
 1) NOTE: PLEASE SEE SOME AREAS OF PLANS WHERE APPEARS
 ONLY STANDARD ELECTRICAL SWITCHES ARE BEING SHOWN.
 PLEASE SEE REDLINED PLANS.
 13-415.1.ABC.1.1, .1.2 AND .1.3 FOR ACCENT
 LIGHTING/DECRETIVE LIGHTING.
 PLEASE SEE 13-415.2ABC.1.2 (3) FOR TRACK LIGHTING.
 PLEASE CLARIFY AS THE LOADS ARE BASED ON VA OF THE
 AMOUNT OF FIXTURES OR LINEAR FT OF TRACK PER MIN VA IN
 THE CODE WHICH EVER IS GREATER.
 PLEASE SEE THERE ARE A FEW *SEPARATE SPACES* AND WHAT
 APPEARS AS ACCENT LIGHTING IN ONE ROOM.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-06-19 Cont ID  
Sent By dpalmer Date 2007-06-19 Time 19:43 Rev Time 0.00
Received By dpalmer Date 2007-06-19 Time 18:54 Sent To  
Notes
2007-06-19 19:43:55*** UNSAT 2ND REVIEW **
  
  
 ** PLEASE SEE THERE ARE ITEMS FROM PREVIOUS REVIEW
 WHICH ARE STILL NOT ADDRESSED.
 ** PLEASE SEE AS NOTED AND STATED ON PREVIOUS REVIEW AS
 INFORMATION IS ONLY JUST NOW BEING SUBMITTED FOR REVIEW
 THERE ARE NEW COMMENTS.
  
  
  
 1) NOTE: PLEASE SEE COMPLIANCE WITH THE 2004 FBC
 CHAPTER 13HAS NOT BEEN ACHIEVED ON PLANS FOR CODE
 COMPLIANCE. PLEASE SEE PLANS NOW INDICATE A LIGHTING
 CONTROL PANEL/SYSTEM IS NOW GOING TO BE INSTALLED WHICH
 IS OK, HOWEVER NOT TIME OF SCHEDULING, NO DEVICES FOR
 OVER RIDE OF SYSTEM AT SEPARATE SPACES CONTAINING FLOOR
 TO CEILING HEIGHT PARTITIONS.
 NO TIMES ON OVER RIDES.(MAXIMUM AS STATED PER CODE)
 NO LOCATIONS ON PLANS FOR THESE TYPE(S) OF DEVICES.
 PLEASE SEE THE DEVICES ON LEGEND DO NOT COORDINATE WITH
 PLANS. PLEASE SEE SOME DEVICES ARE SHOWN ON PLANS FOR
 OS TYPE DEVICES YET RESPONSE LETTER MENTIONS THESE ARE
 ALL TO BE REMOVED. IF REMOVED, PLEASE MEET CODE FOR
 DEVICES WHICH ARE REQUIRED.
 PLEASE SEE 13-415.1ABC.1.1, .1.2 AND .1.3.
 ** PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED ARE NOT
 CODE COMPLIANT. PLEASE KNOW AS THE WAS APPLIED FOR
 PERMIT AFTER DECEMBER 8TH, 2006 THE FLA-COM PROGRAMS
 RELEASED FROM THE STATE CONTAINS THE VERSION 3.0 WHICH
 STATES AT THE TOP OF THE SHEET *EFFECTIVE DATE OF
 DECEMBER 8TH, 2006*.
 PLEASE SEE THE NUMBER OF FIXTURES DO NOT CORRELATE WITH
 PLANS.
 PLEASE SEE THE TYPE OF FIXTURES DO NOT CORRELATE WITH
 PLANS.
 PLEASE SEE THE WATTAGE OF FIXTURES DOES NOT CORRELATE
 WITH PLANS.
 PLEASE SEE THE METHOD OF CONTROLS FOR LIGHTING DOES NOT
 CORRELATE.
 PLEASE SEE THE OWNER AGENT IS NOT SIGNED.
 *PLEASE SEE THE FOLLOWING COMMENT #2 WITH RESPECT TO
 SIGNATURE.
 PLEASE SEE AS MOST THE REQUIRED SYSTEM, DEVICES AND
 ENERGY CALCULATIONS ARE NOT COMPLETE OR COMPLIANT A
 REVIEW CAN ONLY BE DONE ON PLANS SUBMITTED.
 13-415.1.AB.1.1, 13.415.2
  
 2) NOTE: AS STATED ON PREVIOUS REVIEW TO PLEASE BE SURE
 TO HAVE THE DESIGNER OF RECORD FOR THE ENERGY
 CALCULATIONS SIGN, DATE AND SEAL THESE AS REQUIRED PER
 13-103.1.1.1
 PLEASE SEE THE ENERGY CALCULATIONS AS SUBMITTED IN FACT
 CONTAIN A RAISED SEAL OVER A PHOTO-COPIED SIGNATURE ON
 BOTH SETS SUBMITTED. ONE SET IS BEING RETAINED BY THIS
 OFFICE.
 PLEASE SEE FS 471.025, FAC 61G15-23.002
  
 3) NOTE: PLEASE SEE FS 471.025 AS NO SHEETS IN EITHER
 SET OF ELECTRICAL PLANS CONTAINS ANY SIGNATURE, DATE OR
 RAISED SEAL.
 PLEASE SEE FAC 61G15-23.002
  
 4) NOTE: PLEASE SEE PLANS DO NOT INDICATE SUFFICIENT
 LIGHTING FIXTURES WITH BATTERY BACK UP FOR MINIMUM
 LIGHTING LEVELS PER LS 7.8, 7.9.
 PLEASE SEE PLANS APPEARS TO SHOW SOME 2X4 LAY-IN
 FIXTURES WITH A LINE WHICH ARE TYPICALLY THE BATTERY
 BACK UP TYPE FIXTURE HOWEVER THE SYMBOL AND FIXTURE
 LEGEND DOES NOT SHOW A DIFFERENCE BETWEEN THE TWO.
 PLEASE SEE OTHER AREAS WHICH SHOW THE WALL MOUNTED
 BATTERY BACK UP FIXTURES WHICH ARE OK.
 PLEASE SEE COMMENTS FROM THE FIRE MARSHAL.
  
 5) NOTE: PLEASE CLARIFY WHY CONTINUOUS LOADS ARE NOT
 SHOWN ON TRANSFORMER/SERVICE LOADS?
 215.3, 230.42, 220.
  
 6) NOTE: PLEASE CLARIFY ANY METERING DEVICES ARE
 LOCATED ON RISER/SERVICE.
  
 7) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE. SETS OF PLANS HAVE
 BEEN RETAINED.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-03-10 Cont ID  
Sent By dpalmer Date 2007-03-10 Time 17:07 Rev Time 0.00
Received By dpalmer Date 2007-03-10 Time 16:03 Sent To  
Notes
2007-03-10 17:08:43** UNSAT **
  
  
 1)NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH
 ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS
 UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS.
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 2) NOTE: PLEASE SEE FBC 2004 11-4.28.1, .2 AND .3(4)
 AND STATE THE MINIMUM HORN, STROBE LEVELS ON PLANS FOR
 ADA REQUIRED AREAS. DEVICES ARE BEING SHOWN ON
 PLANS/LEGEND.
  
 3) NOTE: PLEASE SEE COMPLIANCE WITH THE 2004 FBC
 CHAPTER 13 FOR CONTROL OF LIGHTING PER 13-415.1ABC.1.1,
 .1.2 AND .1.3. SOME IS SHOWN, HOWEVER NOT ALL AREAS FOR
 CONTROL ARE CLEAR OR SHOWN MEETING THESE SECTIONS.
 PLEASE SUBMIT LIGHTING POWER DENSITIES PER THE 2004 FBC
 W/ 2006 REVISION. PLEASE SEE 13-415.1.AB.1.1, 13-415.2
 FOR LIGHTING PERFORMANCE CALCULATIONS ALONG WITH ENERGY
 CALCULATIONS.
 PLEASE SEE THAT THE FIXTURE SCHEDULE SHALL BE SPECIFIC
 FOR FIXTURES TO BE INSTALLED AND COORDINATION WITH THE
 LPD/CALCULATIONS IS REVIEWED FOR COMPLIANCE. PLEASE BE
 SURE TO HAVE THE DESIGNER OF RECORD FOR THE ENERGY
 CALCULATIONS SIGN, DATE AND SEAL THESE AS REQUIRED PER
 13-103.1.1.1
  
 4) NOTE: PLEASE CORRELATE RISER AND PANEL LP-5, ONE
 SHOWS MCB AND THE MLO.
  
 5) NOTE: PLEASE SEE BOTH BATHROOMS MEN'S AND WOMEN'S
 WILL REQUIRE BATTERY BACK UP FIXTURES OF SOME TYPE.
 PLEASE SEE THE FIXTURE *D*, AS TWO SYMBOLS ARE SHOWN
 FOR THE SAME TYPE OF FIXTURE ON PLANS THEFIXTURE
 LEGEND DOES INDICATE BUT ONLY ONE TYPE.
 PLEASE INDICATE A BATTERY BACK UP FIXTURE.
 LS 101 7.8 AND 7.9.
 PLEASE SEE 700.12E FOR CIRCUITING TO LOCAL LIGHTING
 CIRCUIT IN EACH ROOM.
  
 6) NOTE: PLEASE ADJUST NOTED FOR * LOCK-ON/OFF* DEVICE
 AS NOTED ON PANEL SCHEDULE.
 PLEASE STATE/NOTE THAT THE *LOCK OFF/ON DEVICE SHALL BE
 AN INTEGRAL PART OF THE BREAKER* THIS DEVICE MAY NOT BE
 OF THE TYPE WHICH *SNAPS/CLIPS* ON THE BREAKER. (OR
 WORDS TO THE AFFECT).
 110.3.
 FBC 106.1.2 ADMIN SECTION FOR ADDITIONAL INFORMATION.
  
 ** PLEASE KNOW AS ENERGY CALCULATIONS/LIGHTING
 PERFORMANCE CALCULATIONS AND INFORMATION FOR LIGHTING
 CONTROL SYSTEM/CONTROLS ARE NOT COMPLETE AT THIS TIME
 FOR REVIEW, THERE MAY BE NEW COMMENTS ON THE FOLLOWING
 REVIEW WHICH HAVE NOT YET BEEN MADE
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-08-15 Cont ID  
Sent By mawillia Date 2007-08-15 Time 14:36 Rev Time 0.00
Received By mawillia Date 2007-08-15 Time 13:58 Sent To  
Notes
2007-08-15 14:36:30*****APPROVED*****
  
  
 PLAN SHEET A-1, E-2, AND E-3 WERE STAMPED, INITIALED,
 AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-08-14 Cont ID  
Sent By mawillia Date 2007-06-28 Time 16:20 Rev Time 0.00
Received By mawillia Date 2007-06-28 Time 15:23 Sent To  
Notes
2007-06-28 15:24:18*****APPROVED*****
  
  
  
 THE APPROPIATE PLAN SHEETS WILL BE STAMPED WHEN OTHER
 PLAN REVIEWS HAVE BEEN SATISFIED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2007-04-10 Cont ID  
Sent By mawillia Date 2007-04-10 Time 17:58 Rev Time 0.00
Received By mawillia Date 2007-04-10 Time 15:25 Sent To  
Notes
2007-04-10 17:58:18*****APPROVED*****
  
  
  
 THE APPROPIATE PLAN SHEETS WILL BE STAMPED WHEN OTHER
 PLAN REVIEWS HAVE BEEN SATISFIED.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-08-23 Cont ID  
Sent By adarroug Date 2007-08-23 Time 10:49 Rev Time 0.00
Received By adarroug Date 2007-08-23 Time 10:49 Sent To E
Notes
2007-08-23 10:50:37TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-07-18 Cont ID  
Sent By adarroug Date 2007-07-18 Time 11:28 Rev Time 0.00
Received By adarroug Date 2007-07-18 Time 11:28 Sent To  
Notes
2007-07-27 12:00:57TO "COMM" BD#64
2007-07-18 11:29:02WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-05-23 Cont ID  
Sent By adarroug Date 2007-05-23 Time 15:04 Rev Time 0.00
Received By adarroug Date 2007-05-23 Time 15:04 Sent To  
Notes
2007-06-14 13:23:48TO "COMM" BD#58
2007-05-23 15:05:12WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-04-10 Cont ID  
Sent By mawillia Date 2007-04-10 Time 15:25 Rev Time 0.00
Received By mawillia Date 2007-03-06 Time 14:48 Sent To  
Notes
2007-03-08 13:52:58TO "COMM" BD#12
2007-03-06 14:48:41WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-06-16 Cont ID  
Sent By rregueir Date 2007-06-16 Time 09:30 Rev Time 0.00
Received By rregueir Date 2007-06-16 Time 08:46 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-03-30 Cont ID  
Sent By rregueir Date 2007-03-30 Time 08:30 Rev Time 0.00
Received By rregueir Date 2007-03-30 Time 07:35 Sent To  
Notes
2007-03-30 08:30:53----------------DENIED-----------------
  
 1. PLEASE SHOW DUCTWORK CHANGES RELATED TO THE DELETION
 OF HP-L AND THE ADDITION OF HP-NEW. FBC 106.1.1.
  
 2. PLEASE SHOW DUCTWORK CHANGES RELATED TO THE
 REDISTRIBUTION OF AIR FROM HP-5 ALONG WITH NEW AIR
 BALANCES TO BE ACHIEVED RELATED TO NOTE 9. FBC
 106.1.1.
  
 3. PLEASE SHOW DETAILS RELATED TO NOTE 4 SUCH AS DUCT
 SIZES, LOCATION AND CFM. FBC 106.1.1.
  
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-08-14 Cont ID  
Sent By mperson Date 2007-08-14 Time 16:39 Rev Time 0.00
Received By mperson Date 2007-08-14 Time 16:38 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-07-06 Cont ID  
Sent By kstevens Date 2007-07-06 Time 08:36 Rev Time 0.00
Received By kstevens Date 2007-07-06 Time 08:36 Sent To  
Notes
2007-07-06 08:39:25DENIED
 REFERENCE: FBC-2204 CHAPTER 1
  
 1. SHT P-1 THE DESIGN PROFESSIONAL SHALL SIGN, SEAL AND
 DATE ON THE PLUMBING SHEET. SECTION 106.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-03-20 Cont ID  
Sent By kstevens Date 2007-03-20 Time 06:46 Rev Time 0.00
Received By kstevens Date 2007-03-20 Time 06:46 Sent To  
Notes
2007-03-20 06:57:05DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL SHEETS. THE ARCHITECT ADDRESS IN THE TITLE
 BLOCKS DO NOT REFLECT THE ADDRESS INDICATED ON THE
 FLORIDA DBPR WEBSITE. (SEE ATTACHED SHEET). PLEASE
 UPDATE THE WEBSITE INFORMATION OR THE TITLE BLOCKS SO
 THEY CORRELATE. FAC 61G1-16.004(1) & FS 481.2055.
  
 2. SHT A-1 PLAN SHOWS REMOVAL OF THE DRINKING FOUNTAIN.
 PER TABLE 403.1 A DRINKING FOUNTAIN IS REQUIRED. PLEASE
 PROVIDE A DRINKING FOUNTAIN AND INDICATE THE LOCATION.
  
 3. SHT A-1 PLEASE SHOW THE CLEAR FLOOR SPACE FOR THE
 BREAK ROOM SINK. SECTION 11-4.24.5.
  
 4. SHT A-2 ELEVATION A. CABINET DOORS ARE NOT ALLOWED
 IN THE CLEAR FLOOR SPACE. PLEASE DELETE. (PER BLDG
 OFFICIAL).
  
 5. SHT A-3 DETAIL #1 INDICATE CLEARANCE AS REQUIRED IN
 SECTION 11-4.19.2. (29").
  
 6. SHT P-1 DOMESTIC WATER RISER DIAGRAM. WATER HAMMER
 ARRESTORS SHALL BE LOCATED NEAR THE FIXTURE IN AN
 "EFFECTIVE RANGE" NOT IN THE CEILING AS SHOWN. PDI-WH
 201 AND MANUF. INSTALLATION INSTRUCTIONS.
  
 7. SHT P-1. SUBMIT THE MANUF. SPECIFICATIONS FOR THE
 IWH-1. MUST SHOW LISTING. SECTION 106.1.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]