Plan Review Details - Permit 07030100
Plan Review Stops For Permit 07030100
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-03-30 Cont ID  
Sent By shill Date 2007-03-30 Time 13:09 Rev Time 0.00
Received By shill Date 2007-03-30 Time 13:09 Sent To Z
Notes
2007-03-30 13:14:28****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC*CITY OF WEST PALM BEACH AMENDMENTS TO THE
 FBC2004
 FACFLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)DOCUMENTS PREPARED BY AN ARCHITECT AND SUBMITTED
 FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED
 ORIGINALS.
  
 2.)FBC11-3, EGRESS, MEANS OF. A CONTINUOUS AND
 UNOBSTRUCTED WAY OF EXIT TRAVEL FROM ANY POINT IN A
 BUILDING OR FACILITY TO A PUBLIC WAY.HOW DOES THIS
 AFFECT ACCESSIBLE EXITS?
  
 3.)THIS STRUCTURE IS TO COMPLY WITH THE WIND DESIGN
 CRITERIA OF FBC1609.
  
 4.)YOU HAVE PROVIDED A SITE PLAN, BUT THE PROPOSED
 GATE LOCATION IS NOT SHOWN.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-03-15 Cont ID  
Sent By btrobaug Date 2007-03-09 Time 13:01 Rev Time 0.33
Received By btrobaug Date 2007-03-09 Time 12:26 Sent To B
Notes
2007-03-15 07:02:05 
  
 DENIED/INCOMPLETE INFORMATION
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 THE LOCATION(S) OF THE GATES IS NOT CLEAR. PLEASE
 SUMBIT A DIFFERENT SITE PLAN OR HIGHLTE AND DESCRIBE
 LOCATIONS ON THIS ONE, AND RESUBMIT. 106.1.1 FBC AS
 AMENDED.
  
 1} INDICATE THE PANEL DESIGNATION AND CIRCUIT
 NUMBER(S)USED FOR POWER. 106.3.5.1.2 FBC AS AMENDED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-03-14 Cont ID  
Sent By btrobaug Date 2007-03-15 Time 07:02 Rev Time 0.00
Received By mawillia Date 2007-03-14 Time 12:02 Sent To E
Notes
2007-03-14 12:23:51*****DENIED*****
  
  
 1.CLARIFY ON THE CIVIL DRAWING AS TO WHERE THE SWING
 GATES ARE TO BE LOCATED.
  
 2.HOW WILL THE INSTALLATION OF THE GATES IMPACT FIRE
 DEPARTMENT ACCESS TO THE SAID BUILDING OR VICINITY
 THEREOF?PLLEASE BE ADVISED THAT A KNOX GATE ENTRY
 SYSTEM MAY BE REQUIRED.
  
 3.HOW WILL THE INSTALLATION OF THE GATES IMPACT
 EXITING FROM THE BUILDING AND/OR PARKING GARAGE?
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-04-04 Cont ID  
Sent By shill Date 2007-03-30 Time 17:04 Rev Time  
Received By shill Date 2007-03-05 Time 15:17 Sent To  
Notes
2007-03-30 13:15:23NEEDS ZONING
2007-03-05 15:17:48TO "E" BOX

Review Stop Z ZONING
Rev No 1 Status P Date 2007-04-03 Cont ID  
Sent By aaponte Date 2007-04-03 Time 15:29 Rev Time 0.00
Received By aaponte Date 2007-04-03 Time 15:29 Sent To  
Notes
***NONE***