2007-03-05 12:26:40 | *** DENIED *** |
| 1) SHOW SEER OF A/C SYSTEMS ON PLANS. |
| |
| 2) SHOW HOW RETURN AIR IS REACHING SECOND FLOOR AIR |
| HANDLER UNIT. |
| |
| 3) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND |
| ACCOMPANYING DATA SHALL BEAR THE PRINTED NAME AND |
| SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN. PER |
| FBC 104.2.1. |
| |
| 4)ALL OF THE RETURN AIR TRANSFER DUCTS ARE TO SMALL, |
| SEE 2004 FBC/R M1602.4 (A) AND (C) EXCEPT. |
| |
| *** 2004 FBC/R M1602.4. |
| BALANCED RETURN AIR MAY BE ACHIEVED BY. |
| (A)TRANSFER DUCTS MAY ACHIEVE THIS BY |
| INCREASING THE RETURN TRANSFER ONE AND |
| ONE HALF TIMES THE CROSS SECTIONAL AREA |
| (SQUARE INCHES) OF THE SUPPLY DUCT |
| ENTERING THE ROOM OR SPACE IT'S SERVING |
| AND THE DOOR HAVING AT LEAST AN |
| UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE |
| PROPER RETURN AIR BALANCE. |
| (C)HABITABLE ROOMS ONLY SHALL BE |
| REQUIRED TO MEET THESE REQUIREMENTS FOR |
| PROPER BALANCED RETURN AIR EXCLUDING |
| BATHROOMS, CLOSETS, STORAGE ROOMS AND |
| LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY |
| AIR INTO THE MASTER SUITE SHALL BE |
| INCLUDED. PER 2004 FBC/R M1602.4 . |
| |
| MECHANICAL PLAN REVIEW BY; |